Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Ls Catalog

Download as pdf or txt
Download as pdf or txt
You are on page 1of 126

Meta Solution

Low voltage circuit breakers


CÔNG TY TNHH THƯƠNG MẠI KỸ THUẬT ASTER
Số 7/31 KDC Thương Mại Sóng Thần, Kp. Nhị Đồng 1, P. Dĩ An, Tx. Dĩ An, Bình Dương
Tel: (0650) 3617 012
Fax: (0650) 3617 011

Nhà cung cấp thiết bị điện chuyên nghiệp


Email: contact@beeteco.com
Hotline: 0909 41 61 43

DỊCH VỤ CHĂM SÓC KHÁCH HÀNG TOÀN DIỆN

Tư vấn chọn sản phẩm

Giao hàng tận nơi

Hỗ trợ kỹ thuật

Chính sách hậu mãi đa dạng


Leader in Electrics & Automation

Upgraded for the global


best worth!

Molded case circuit breaker / Earth leakage circuit breaker

Marking and configuration 16


External configuration 18
Quick selection table (Molded Case Circuit Breakers) 20
Quick selection table (Earth Leakage Circuit Breakers) 28
Ratings 32
Accessories 72
Type numbering system 86
Characteristics curves 87
Dimensions 92
Technical Information 109
Meta solution

MCCB = ELCB

4I
Metasol
Molded case circuit breaker / Earth leakage circuit breaker

Upgrade of Meta-MEC series


… Low voltage circuit breaker
�Ics = 100%×Icu
�Ui = 750V
�Uimp = 8kV

�Compatible and differentiated design �Upgrade breaking capacity


- Compatible with the Meta-MEC - N100AF : 10 � 18kA
- Outlook differentiated design - S125AF : 25 � 37kA
- S250AF : 25 � 37kA
�Same External dimension with - H250AF : 35 � 50kA
MCCB and ELCB - N400AF : 25 � 37kA
�Upgrade the coordination - S400AF : 35 � 50kA
- S800AF : 50 � 65kA
- Upgrade the coordination with Susol /
Meta-MEC mass capacity
�Ics = 100% Icu
I5
MCCB/ELCB

Metasol MCCB
Upgrade breaking capacity
460V
85kA
ABL400c ABL800c
85kA 85kA
75kA

65kA
ABH400c ABS800c
50� 65kA 50� 65kA
50kA
ABH50c ABH125c ABH250c ABS400c
25� 50kA 35� 50kA 35� 50kA 35� 50kA
37kA
ABS125c ABS250c ABN400c ABN800c
25� 37kA 25� 37kA 25� 37kA 35� 37kA
26kA
ABN250c
18� 26kA
18kA
ABS50c ABS60c ABN100c
10�18kA 10�18kA 10�18kA
14kA
ABS30c ABN50c ABN60c
5�14kA 5�14kA 5�14kA

30AF 50AF 60AF 100AF 125AF 250AF 400AF 800AF


6I
Short-circuit breaking capacity

Upgrade breaking capacity


● N100AF : ● S125AF : ● S250AF : ● H250AF :
10 � 18kA 25 � 37kA 25 � 37kA 35 � 50kA
● N400AF : ● S400AF : ● S630AF : ● S800AF :
25 � 37kA 35 � 50kA 50 � 65kA 50 � 65kA

Metasol ELCB
Upgrade breaking capacity
460V
85kA
EBL400c EBL800c
85kA 85kA
75kA

65kA
EBH400c EBS800c
50� 65kA 50� 65kA
50kA
EBH50c EBH125c EBH250c EBS400c
25� 50kA 35� 50kA 35� 50kA 35� 50kA
37kA
EBS125c EBS250c EBN400c EBN800c
25� 37kA 25� 37kA 25� 37kA 35� 37kA
26kA
EBN250c
18� 26kA
18kA
EBS50c EBS60c EBN100c
10�18kA 10�18kA 10�18kA
14kA
EBS30c EBN50c EBN60c
5�14kA 5�14kA 5�14kA

30AF 50AF 60AF 100AF 125AF 250AF 400AF 800AF

I7
MCCB/ELCB Compatible and Standard
● 100% compatible with Meta-MEC Series.

● Standardized dimension (Depth, Cutout) when the panel is made.

yz
e.x
ath
nh
die

105×165×60mm 90×155×60mm 75×130×60mm


w.

Metasol MCCB

AF
ww

30AF 50AF 60AF 100AF 125AF 250AF 400AF 800AF


Type
ABN50c ABN60c ABN100c ABN250c ABN400c ABN800c
ABN 14kA 14kA 18kA 26kA 37kA 37kA

ABS30c ABS50c ABS60c ABS125c ABS250c ABS400c ABS800c


ABS 14kA 18kA 18kA 37kA 37kA 50kA 65kA

ABH50c ABH125c ABH250c ABH400c


ABH 50kA 50kA 50kA 65kA

ABL400c ABL800c
ABL 85kA 85kA

Note) Dimension is for 3 pole and breaking capacity is for AC460V.


8I
● Same external dimension with MCCB and ELCB.

yz
60 mm

e.x
ath
50 mm
nh
die

75×130×60mm 90×155×60mm 105×165×60mm


w.

Metasol ELCB

AF
ww

30AF 50AF 60AF 100AF 125AF 250AF 400AF 800AF


Type
EBN50c EBN60c EBN100c EBN250c EBN400c EBN800c
EBN 14kA 14kA 18kA 26kA 37kA 37kA

EBS30c EBS50c EBS60c EBS125c EBS250c EBS400c EBS800c


EBS 14kA 18kA 18kA 37kA 37kA 50kA 65kA

EBH50c EBH125c EBH250c EBH400c


EBH 50kA 50kA 50kA 65kA

EBL400c EBL800c
EBL 85kA 85kA

Note) Dimension is for 3 pole and breaking capacity is for AC460V.

I9
MCCB/ELCB System overview

Various installable Accessories


● Wider range of installable accessories compared to Meta MEC series.
● Composed of User Friendly Method.
System overview

� Breaker
� Internal auxiliaries
� Plug-in kit

� Rotary handle (direct)
� Rotary handle (direct, key lock)
� Rotary handle (extended)
� Rear terminal
� Terminal cover (Short, Long)
� � Insulation barrier





I 11
MCCB/ELCB Internal accessories

● ●


Internal Accessories
Internal Accessories can be commonly used in all Metasol MCCB and ELCB
(Notice: Exception of SHT, UVT in ELCB)
Internal accessories

Common use to all Metasol MCCBs and ELCBs

Alarm Switch (AL)


Alarm switches offer provisions for immediate audio or visual indication of a tripped
breaker due to overload, short-circuit, operation of shunt trip, or undervoltage trip
conditions, operation of push button.
They are particularly useful in automated plants where operators must be signaled
about changes in the electrical distribution system. This switch features a closed
contact when the circuit breaker is tripped automatically. In other words, this switch
does not function when the breaker is operated manually. Its contact is open when
the circuit breaker is reset.

Auxiliary Switch (AX)


Auxiliary switch is for applications requiring remote“ON”and“OFF”indication.
Each switch contains two contacts having a common connection. One is open and
the other closed when the circuit breaker is open, and vice-versa.

Undervoltage trip (UVT)


The undervoltage trip automatically opens a circuit breaker when voltage drops to a
value ranging between 35% to 70% of the line voltage. The operation is
instantaneous, and the circuit breaker cannot be reclosed until the voltage returns
to 85% of line voltage.
Continuously energized, the undervoltage trip must be operating be fore the circuit
breaker can be closed.

Shunt Trip (SHT)


The shunt trip opens the mechanism in response to an externally applied voltage
signal. LS shunt trips include coil clearing contacts that automatically clear the
signal circuit when the mechanism has tripped.contact with live parts and thereby
guarantee protection against direct contacts.

AX AL AL AX AX AL AL AX

SHT/UVT SHT/UVT
AX AL AL AX

SHT/UVT

I 13
MCCB/ELCB External accessories

External Accessories
Designed for various mount and user safety.
External accessories

Front and rear connection


Several kinds of terminals can be equipped with ELCBs as well as MCCBs.
- Terminals for front connection
- Rear connection terminals

Plug-in base
It makes to extract and/or rapidly replace the circuit breaker without having to touch
connections.(Easy replacement and maintenance)

Direct & Extended Rotary Handle


There are two types of rotary handles.
- Direct rotary handle(with or w/o key lock device)
- Extended rotary handle

Locking device
- Fixed padlock
- Removable padlock
- Key lock device on direct handle

Insulation barrier
These allow the insulation characteristics between the phases at the connections
to be increased.

Insulation terminal cover


The terminal covers are applied to the circuit-breaker to prevent accidental contact
with live parts and thereby guarantee protection against direct contacts.

I 15
Marking and configuration

MCCB

MCCB model
�ABN: Economic type
�ABS: Standard type
�ABH: High capacity type

Standardized characteristics
Ui: Rated insulation voltage
Uimp: Impulse withstand
voltage
Ue: Rated operational voltage
Icu: Ultimate breaking
capacity
Ics: Service breaking capacity

Rated frequency Utilization Manufacturer Standard


category

Symbol indicating
suitability for isolation
as defined by IEC 947-2

MCCB
Upstream connections
Fixing hole

Product name

Brand name

Operating handle

Indication of closed (I/ON) position


Indication of open (O/OFF) position

Certification mark

Company logo

"push to trip" button

Fixing hole
Downstream connections

16
ELCB

ELCB model
�EBN: Economic type
�EBS: Standard type
�EBH: High capacity type

Rated frequency Standard Manufacturer Utilization category

Symbol indicating
suitability for isolation
as defined by IEC 947-2

ELCB
Upstream connections

Fixing hole
Brand name

Indication of closed (I/ON) position


Indication of open (O/OFF) position

Product name

Trip indication by earth fault

Operating handle
Residual current(I△n) setting

"push to trip" button for earth fault

"push to trip" button for overcurrent trip

Company logo

Certification mark

Fixing hole

Downstream connections

17
External configuration

MCCB
① Handle
�Function of indications
- “ON” “OFF” “TRIP”
�Resetting Handle

When the handle indicates "tripped" position


it must first be reset by moving the handle to
the “OFF” position and then closing is
possible
Terminal
�Trip-Free even if the handle is held at “ON”,
the breaker will trip if an over current flows
�Suitable for Verification of the main contact
position under abnormal conditions because Arc-Extinguishing
unit
the handle doesn’t indicate open position

② Arc-Extinguishing unit
LS patent technique PASQ Contact
Arc-Extinguishing unit
PASQ : Puffer Assisted Self-Quenching
�Reduction of arc voltage for a short time Mechanism

Hybrid Grid
chamber Ass’y

Trip

③ Trip button (push to trip)


Trip button
�Enables tripping mechanically from outside,
for confirming the operation of the accessory
switches and the manual resetting function.

A Application of PASQ Arc Extinguishing A Application of Current limiting structure

�The reduction of breaking �Current limiting repulsion structure


time by applying PASQ (U fixed structure)
arc extinguishing for �Toggle structure
inhibition of arc voltage for - When the operating unit repulses by short circuit
a short time. current, repulsion structure at bigger angle.

18
ELCB

① Residual
indication LED

① Residual indication LED


�Normal situation is yellow , trio situation
is red

② Residual test Button


�Special design for Upgrade to prohibit
resistance accident

③ Residual detection unit


② Residual test (ZCT + Main board)
Button
�For upgrade the design is selected the 3
phase input power method and in case
of Voltage problem, it can break residual
current safely.
③ Residual
detection unit
(ZCT + Main board)

Upgrade coil operation by special design 3 phase power supply method

�Sliding structure application �In case of 1 phase loss


of Trip lever residual operation upgrade
�Trip special design by �New IEC standard
applying design Button
method.
�Upgrade the testing unit

19
Quick selection table
Molded Case Circuit Breakers

MCCBs
AF 30AF 50AF 60AF

Type E-Type S-Type N-Type S-Type H-Type N-Type S-Type


Type and Pole 2-pole ABE32b ABS32c ABN52c ABS52c ABH52c ABN62c ABS62c
3-pole ABE33b ABS33c ABN53c ABS53c ABH53c ABN63c ABS63c
4-pole - ABS34c ABN54c ABS54c ABH54c ABN64c ABS64c
Rated current, In A 15, 20, 30,
(3, 5, 10), 15, 20, 30 15, 20, 30, 40, 50 15, 20, 30, 40, 50, 60
40, 50
Rated operational AC(V) 460 690 690 690 690 690 690
voltage, Ue DC(V) - 500 500 500 500 500 500
Rated insulation voltage, Ui V 460 750 750 750 750 750 750
Rated impulse withstand
voltage, Uimp kV 6 8 8 8 8 8 8

Rated short-circuit breaking capacity(Icu) kA (Sym), KSC8321, IEC 60947-2


AC 690V - 2.5 2.5 5 10 2.5 5
480/500V - 7.5 7.5 10 35 7.5 10
415/460V 2.5 14 (10) 14 18 50 14 18
380V 2.5 18 (14) 18 22 50 18 22
220/250V 5 30 (25) 30 35 100 30 35
DC 500V(3P) - 5 5 10 30 5 10
250V(2P) - 5 5 10 30 5 10
Ics=%×Icu 50 100 100 100 100 100 100
Dimensions (mm) W×H×D 75×96×60mm 75×130×60mm 75×130×60mm 90×155×60mm 75×130×60mm
(3-pole) (Fig. 1) (Fig. 1) (Fig. 2) (Fig. 1)
More info. Ratings 32 page 34 page 36 page 36 page 38 page
Curves 87 page 87 page 87 page 88 page 87 page
Drawings 92 page 93 page 93 page 94 page 93 page
Note) The short-circuit breaking capacities in ( ) are applied to the rated current in (3, 5, 10A)

AF 50
∅4.5

Type 30AF 50AF 60AF 100AF 125AF 250AF


130
115
84
50

ABN50c ABN60c ABN100c ABN250c


ABN 14kA 14kA 18kA 26kA

ABS30c ABS50c ABS60c ABS125c ABS250c


ABS 14kA 18kA 18kA 37kA 37kA
22 58
60
50
ABH
ABH50c ABH125c ABH250c 64
50kA 50kA 50kA 75
68
82
(Fig. 1)
20
100AF 125AF 250AF

N-Type S-Type H-Type N-Type S-Type H-Type


ABN102c ABS102c ABH102c ABN202c ABS202c ABH202c
ABN103c ABS103c ABH103c ABN203c ABS203c ABH203c
ABN104c ABS104c ABH104c ABN204c ABS204c ABH204c
15, 20, 30, 40,
15, 20, 30, 40, 50, 60, 75, 100, 125 100, 125, 150, 175, 200, 225, 250
50, 60, 75, 100
690 690 690 690 690 690
500 500 500 500 500 500
750 750 750 750 750 750

8 8 8 8 8 8

5 8 10 8 8 10
10 26 35 18 26 35
18 37 50 26 37 50
22 42 50 30 42 50
35 85 100 65 85 100
10 20 30 10 20 30
10 20 30 10 20 30
100 100 100 100 100 100
75×130×60mm 90×155×60mm 105×165×60mm
(Fig. 1) (Fig. 2) (Fig. 3)
40 page 42 page 44 page
87 page 88 page 89 page
93 page 94 page 95 page
∅8.2
5

50
47
100
50

155
135

59.4

102
126
144
165

CL
50

60 58
8 60 60
90 35
82 70 64
105 68.5
(Fig. 2) (Fig. 3) 86.85
21
Quick selection table
Molded Case Circuit Breakers

MCCBs
AF 400AF

Type N-Type S-Type H-Type L-Type

Type and Pole 2-pole ABN402c ABS402c ABH402c ABL402c


3-pole ABN403c ABS403c ABH403c ABL403c
4-pole ABN404c ABS404c ABH404c ABL404c
Rated current, In A 250, 300, 350, 400
Rated operational AC(V) 690 690 690 690
voltage, Ue DC(V) 500 500 500 500
Rated insulation voltage, Ui V 750 750 750 750
Rated impulse withstand
voltage, Uimp kV 8 8 8 8

Rated short-circuit breaking capacity(Icu) kA (Sym), KSC8321, IEC 60947-2


AC 690V 5 8 10 14
480/500V 18 35 50 65
415/460V 37 50 65 85
380V 42 65 70 100
220/250V 50 75 85 125
DC 500V(3P) 10 20 40 40
250V(2P) 10 20 40 40
Ics=%×Icu 100 100 100 75
Dimensions (mm) W×H×D 140×257×109mm
(3-pole) (Fig. 4)
More info. Ratings 46 page
Curves 90 page
Drawings 96 page

AF
Type 400AF 800AF 1000AF 1200AF

ABN400c ABN800c
ABN 37kA 37kA
257
225
215
150

ABS400c ABS800c ABS1000b ABS1200b


ABS 50kA 65kA 65kA 65kA

ABH400c
ABH 65kA

95

ABL400c ABL800c ABL1000b ABL1200b


109
ABL 85kA 85kA 85kA 85kA 113
145

(Fig. 4)
22
800 AF 1000 AF 1200 AF
N-Type S-Type L-Type S-Type L-Type S-Type L-Type

ABN802c ABS802c ABL802c - - - - -


ABN803c ABS803c ABL803c ABS1003b ABL1003b ABS1203b ABS1203bE ABL1203b
ABN804c ABS804c ABL804c ABS1004b ABL1004b ABS1204b - ABL1204b
500, 630, 700, 800 1000 1200
690 690 690
500 500 500
750 750 750

8 8 8

8 10 14
25 45 65 50 75 50 50 75
37 65 85 65 85 65 65 85
45 75 100 65 85 65 65 85
50 85 125 100 125 100 100 125
10 20 40
10 20 40
100 100 75
210×280×109mm 220×400×105mm 220×400×105mm
(Fig. 5) (Fig. 6) (Fig. 6)
48 page 50 page 50 page 51 page 50 page
90 page 91 page 91 page 92 page 91 page
97 page 98 page 98 page 99 page 98 page
93
48.5
17
116
90

21.4
280
243
150
96

25

400
110

98.5

95
90
40

109 17
44 48.5
20

113 70 70 102.5
145 220 105
122.5
159
(Fig. 5) (Fig. 6) 230
23
Quick selection table
ZCT Molded Case Circuit Breakers

MCCBs
AF 30AF 50AF 60AF

Type S-Type N-Type S-Type H-Type N-Type S-Type


Type and Pole 2-pole - - - ABH52cZ - -
3-pole ABS33cZ ABN53cZ ABS53cZ ABH53cZ ABN63cZ ABS63cZ
4-pole ABS34cZ ABN54cZ ABS54cZ ABH54cZ ABN64cZ ABS64cZ
Rated current, In A
15, 20, 30 15, 20, 30, 40, 50 15, 20, 30, 40, 50, 60

Rated operational
AC(V) 690 690 690 690 690 690
voltage, Ue
Rated insulation voltage, Ui V 750 750 750 750 750 750
Rated impulse withstand
voltage, Uimp kV 8 8 8 8 8 8

Rated short-circuit breaking capacity(Icu) kA (Sym), KSC8321, IEC 60947-2


AC 690V 2.5 2.5 5 10 2.5 5
480/500V 7.5 7.5 10 35 7.5 10
415/460V 14 14 18 50 14 18
380V 18 18 22 50 18 22
220/250V 30 30 35 100 30 35
Ics=%×Icu 100 100 100 100 100 100
Dimensions (mm) W×H×D 75×130×60mm 75×130×60mm 90×155×60mm 75×130×60mm
(3-pole) (Fig. 1) (Fig. 1) (Fig. 2) (Fig. 1)
More info. Ratings 32 page 36 page 36 page 38 page
Curves 87 page 87 page 88 page 87 page
Drawings 92 page 92 page 94 page 92 page
Note) 1. MCCB와 동일 사양임(Size 동일).
2. ACCE : MCCB와 동일하게 취부 가능.

50
AF
∅4.5

Type 30AF 50AF 60AF 100AF 125AF 250AF


130
115
84
50

ABN50c ABN60c ABN100c ABN250c


ABN 14kA 14kA 18kA 26kA

ABS30c ABS50c ABS60c ABS125c ABS250c


ABS 14kA 18kA 18kA 37kA 37kA
22 58
60
50
64
ABH
ABH50c ABH125c ABH250c 75
50kA 50kA 50kA 68
82
(Fig. 1)

24
100AF 125AF 250AF

N-Type S-Type H-Type N-Type S-Type H-Type


- ABS102cZ ABH102cZ - - -
ABN103cZ ABS103cZ ABH103cZ ABN203cZ ABS203cZ ABH203cZ
ABN104cZ ABS104cZ ABH104cZ ABN204cZ ABS204cZ ABH204cZ
15, 20, 30, 40, 50
15, 20, 30, 40, 50, 60, 75, 100, 125 100, 125, 150, 175, 200, 225, 250
60, 75, 100, 125

690 690 690 690 690 690

750 750 750 750 750 750

8 8 8 8 8 8

5 8 10 8 8 10
10 26 35 18 26 35
18 37 50 26 37 50
22 42 50 30 42 50
35 85 100 65 85 100
100 100 100 100 100 100
75×130×60mm 90×155×60mm 105×165×60mm
(Fig. 1) (Fig. 2) (Fig. 3)
40 page 42 page 44 page
87 page 88 page 89 page
92 page 94 page 95 page
∅8.2
5

50
47
100
50

155
135

59.4

102
126
144
165

CL
50

60 58
8 60 60
90 35
82 70 64
105 68.5
(Fig. 2) (Fig. 3) 86.85

25
Quick selection table
ZCT Molded Case Circuit Breakers

MCCBs
AF 400AF

Type N-Type S-Type H-Type L-Type

Type and Pole 2-pole - -


3-pole ABN403cZ ABS403cZ ABH403cZ ABL403cZ
4-pole ABN404cZ ABS404cZ ABH404cZ ABL404cZ
Rated current, In A 250, 300, 350, 400
Rated operational
AC(V) 690 690 690 690
voltage, Ue
Rated insulation voltage, Ui V 750 750 750 750
Rated impulse withstand
voltage, Uimp kV 8 8 8 8

Rated short-circuit breaking capacity(Icu) kA (Sym), KSC8321, IEC 60947-2


AC 690V 5 8 10 14
480/500V 18 35 50 65
415/460V 37 50 65 85
380V 42 65 70 100
220/250V 50 75 85 125
Ics=%×Icu 100 100 100 75
Dimensions (mm) W×H×D 140×257×109mm
(3-pole) (Fig. 4)
More info. Ratings 46 page
Curves 90 page
Drawings 96 page
Note) 1. MCCB와 동일 사양임(Size 동일).
2. ACCE : MCCB와 동일하게 취부 가능.

AF
Type 400AF 800AF

ABN400c ABN800c
ABN 37kA 37kA

ABS400c ABS800c
ABS 50kA 65kA

ABH400c
ABH 65kA

ABL400c ABL800c
ABL 85kA 85kA

26
800 AF
N-Type S-Type L-Type

- - -
ABN803cZ ABS803cZ ABL803cZ
- - -
500, 630, 700, 800

690 690 690

750 750 750

8 8 8

8 10 14
25 45 65
37 65 85
45 75 100
50 85 125
100 100 75
210×280×109mm
(Fig. 5)
48 page
90 page
97 page
280
243
150
96
257
225
215
150

95
95
109
109
113 113
145
145
(Fig. 4) (Fig. 5)

27
Quick selection table
Earth Leakage Circuit Breakers

ELCBs
AF 30AF 50AF 60AF

Type S-Type N-Type S-Type H-Type N-Type S-Type


Type and Pole 2-pole - EBN52c - - - -
3-pole EBS33c EBN53c EBS53c EBH53c EBN63c EBS63c
4-pole EBS34c - EBS54c EBH54c - EBS64c
Protective function Overload, Short-circuit Overload, Short-circuit Overload, Short-circuit Overload, Short-circuit
and Ground fault and Ground fault and Ground fault and Ground fault
Rated current, In A 15, 20, 30 15, 20, 30, 40, 50 15, 20, 30, 40, 50 60
Rated residual current, I△n mA 30, 100/200/500mA 30, 100/200/500mA 30, 100/200/500mA 30,100/200/500mA
Rated operational voltage,Ue AC(V) 220/460 220/460 220/460 220/460
Rated impulse withstand
kV 6 6 6 6
voltage, Uimp
Residual current off-time at I△n sec ≤0.1 sec ≤0.1 sec ≤0.1 sec ≤0.1 sec

Rated short-circuit breaking capacity (Icu) kA (Sym), KSC8321, IEC 60947-2


AC 415/460V 14 14 18 50 14 18
220/250V 30 30 35 100 30 35
Dimensions (mm) W×H×D 75×130×60mm 75×130×60mm 90×155×60mm 75×130×60mm
(3-pole) (Fig. 1) (Fig. 1) (Fig. 2) (Fig. 1)
More info. Ratings 54 page 56 page 56 page 58 page
Curves 87 page 87 page 88 page 87 page
Drawings 100 page 100 page 101 page 100 page

AF
Type 30AF 50AF 60AF 100AF 125AF 250AF

EBN50c EBN60c EBN100c EBN250c


EBN 14kA 14kA 18kA 26kA

EBS30c EBS50c EBS60c EBS125c EBS250c


EBS 37kA
14kA 18kA 18kA 37kA

EBH50c EBH125c EBH250c


EBH 50kA 50kA 50kA

(Fig. 1)

28
100AF 125AF 250AF

N-Type S-Type H-Type N-Type S-Type H-Type


EBN102c - - EBN202c - -
EBN103c EBS103c EBH103c EBN203c EBS203c EBH203c
EBN104c EBS104c EBH104c - EBS204c EBH204c
Overload, Short-circuit Overload, Short-circuit Overload, Short-circuit
and Ground fault and Ground fault and Ground fault
60, 75, 100 15, 20, 30, 40, 50, 60, 75, 100, 125 100, 125, 150, 175, 200, 225, 250
30, 100/200/500mA 30,100/200/500mA 30,100/200/500mA
220/460 220/460 220/460

6 6 6

≤0.1 sec ≤0.1 sec ≤0.1 sec

18 37 50 26 37 50
35 85 100 65 85 100
75×130×60mm 90×155×60mm 105×165×60mm
(Fig. 1) (Fig. 2) (Fig. 3)
60 page 62 page 64 page
87 page 88 page 89 page
100 page 101 page 102 page
∅5

50
∅4.5

47
100
135
155
50

102

144

165

CL
50
7
4.7

60 58
60
90 8 60 35
64
70
82 66.5
105
68.5
86.85
(Fig. 2) (Fig. 3)

29
Quick selection table
Earth Leakage Circuit Breakers

ELCBs
AF 400AF

Type N-Type S-Type H-Type L-Type


Type and Pole 3-pole EBN403c EBS403c EBH403c EBL403c
4-pole EBN404c EBS404c EBH404c EBL404c
Protective function Overload, Short-circuit and Ground fault
Rated current, In A 250, 300, 350, 400
Rated residual current, I△n mA 30, 100/200/500mA
Rated operational voltage,Ue AC(V) 220/460 220/460 220/460 220/460
Rated impulse withstand
kV 6 6 6 6
voltage, Uimp
Residual current off-time at I△n sec 0.1 sec 0.1 sec 0.1 sec 0.1 sec

Rated short-circuit breaking capacity (Icu) kA (Sym), KSC8321, IEC 60947-2


AC 415/460V 37 50 65 85
220/250V 50 75 85 125
Ics=%×Icu 100 100 100 75
Dimensions (mm) W×H×D 140×257×109mm
(3-pole) (Fig. 4)
More info. Ratings 66 page
Curves 90 page
Drawings 103 page

AF
Type 400AF 800AF 1000AF 1200AF

EBN400c EBN800c
EBN 37kA 37kA
257
225

215

150

EBS400c EBS800c EBS1000b EBS1200b


EBS 50kA 65kA 65kA 65kA

EBH400c
EBH 65kA

95
EBL400c EBL800c 109
EBL 85kA 85kA
113
145

(Fig. 4)

30
800 AF 1000 AF 1200 AF

N-Type S-Type L-Type S-Type S-Type


EBN803c EBS803c EBL803c EBS1003b EBS1203b
- - - - -
Overload, Short-circuit and Ground fault Overload, Short-circuit and Ground fault

500, 630, 700, 800 1000 1200


30, 100/200/500mA 100/200/500mA 100/200/500mA
220/460 220/460 220/460 220/460 220/460

6 6 6

0.1 sec 0.1 sec 0.1 sec 0.1 sec 0.1 sec

37 65 85 85 85
50 85 125 125 125
100 100 75
210×280×109mm 220×565×105mm
(Fig. 5) (Fig. 6)
68 page 70 page
90 page 91 page
104 page 105 page
93
48.5
17
116
90
∅8

21.4
∅13.5

206
25

400
360
110
280
243

98.5
150
96

525
165
165

95
109
90
40

113 17
44
20

48.5
145 70 70 102.5
220 105
122.5
159
(Fig. 5) (Fig. 5) 231

31
30AF MCCB
ABE30b

Ratings

Frame size 30AF


Type and Pole E-Type
2-pole ABE32b
3-pole ABE33b
4-pole -
Rated current, In 3-5-10-15-20-30A
Rated operational voltage, Ue AC : 460V
-
Rated insulation voltage, Ui AC : 460V
ABE32b
Rated impulse withstand voltage, Uimp 6kV

Rated short-circuit breaking E-Type


capacity, Icu AC 690V -
IEC 60947-2 (lcu) 480/500V -
460V 2.5kA
415V 2.5kA
380V 2.5kA
220/250V 5kA
DC 500V (3P) -
ABE33b
250V (2P) -

Protective function Overload, Short-circuit


Type of trip unit Hydraulic-Magnetic
Magnetic trip range 12In
Endurance Mechanical 8500 operations
Electrical 1500 operations
Connection Standard Front connection
Optional -
-
Mounting Standard Screw fixing

Dimensions (mm) Pole 2p 3p


d
c2
a 50 75
a c1
b 96 96
c1 Note) 60 60
b

c2 Note) - -
For more information d 80 80
�Drawings ▶ 92 page Weight, kg Standard 0.5 0.7
�Trip curves ▶ 87 page
Certification Pole 2p 3p
�Accessories ▶ 72 page
�Connection and mounting ▶ 100 page CE marking ○ ○
Note) Depth by door cut size : c1 for large cut, c2 for small cut

32
Ordering types

Breaker types Accessories


ABE type (2.5kA/460V)

Rated current, In 2-pole 3-pole


3A ABE32b/3 ABE33b/3
5A ABE32b/5 ABE33b/5
10 A ABE32b/10 ABE33b/10
15 A ABE32b/15 ABE33b/15
20 A ABE32b/20 ABE33b/20
Electrical auxiliaries
30 A ABE32b/30 ABE33b/30
AX Auxiliary Switch
AL Alarm Switch
SHT Shunt Trip R T

Maximum possibilities
T-position One of above auxiliaries
R-position Option of AX or AL
Note) For more detail see 72 page

External accessories
ABE30b Name

IB13 Insulation barrier


TBS23 Short type
Note) For more detail see 80 page

33
30AF MCCB
ABS30c

Ratings

Frame size 30AF


Type and Pole S-Type
2-pole ABS32c
3-pole ABS33c
4-pole ABS34c
Rated current, In (3-5-10)-15-20-30A
Rated operational voltage, Ue AC: 690V
DC: 500V
ABS52c Rated insulation voltage, Ui AC: 750V
Rated impulse withstand voltage, Uimp 8kV

Rated short-circuit breaking S-Type


capacity, Icu AC 690V 2.5 kA
480/500V 7.5 kA
IEC 60947-2 (lcu) 460V 14 (10)kA
415V 14 (10)kA
380V 18 (14)kA
220/250V 30 (25)kA
DC 500V(3P) 5 kA
ABS53c
250V(2P) 5 kA

Protective function Overload, Short-circuit


Type of trip unit Thermal-Magnetic
Magnetic trip range 400A
Endurance Mechanical 25000 operations
Electrical 10000 operations
Connection Standard Front connection
Optional Rear connection
Plug-in

ABS54c Mounting Standard Screw fixing

Dimensions (mm) Pole 2p 3p 4p


d
c2
a 50 75 100
a c1
b 130 130 130
c1 Note) 60 60 60
b

c2 Note) 64 64 64
For more information d 82 82 82
�Drawings ▶ 93 page Weight, kg Standard 0.5 0.7 0.9
�Trip curves ▶ 87 page
Certification Pole 2p 3p 4p
�Accessories ▶ 72 page
�Connection and mounting ▶ 110 page CE marking ○ ○ ○
Note) Depth by door cut size : c1 for large cut, c2 for small cut

34
Ordering types

Breaker types Accessories


ABS type (10kA/460V)
Rated current, In 2-pole 3-pole 4-pole
3A ABS32c/3 ABS33c/3 ABS34c/3
5A ABS32c/5 ABS33c/5 ABS34c/5
10 A ABS32c/10 ABS33c/10 ABS34c/10

Electrical auxiliaries

ABS type (14kA/460V) AX Auxiliary Switch


AL Alarm Switch
Rated current, In 2-pole 3-pole 4-pole
AX+AL Combination switch R T
15 A ABS32c/15 ABS33c/15 ABS34c/15
SHT Shunt Trip
20 A ABS32c/20 ABS33c/20 ABS34c/20
UVT Undervoltage trip
30 A ABS32c/30 ABS33c/30 ABS34c/30

Maximum possibilities
T-position One of above auxiliaries
R-position Option of AX or AL or AX+AL
Note) For more detail see 72 page

External accessories
ABS30c Name

IB13 Insulation barrier


TCL13 Terminal cover (Long)
TCS13 Terminal cover (Short)
DH100 Rotary handle (Direct)
DHK100 Rotary handle (Direct, Key lock)
EH100 Rotary handle (Extended)
RTR1 Rear terminal (Round)
PB-A3 Plug-in kit
PHL100C Pad handle lock
Note) For more detail see 80 page

35
50AF MCCB
ABN50c, ABS50c, ABH50c

Ratings

Frame size 50AF


Type and Pole N-Type S-Type H-Type
2-pole ABN52c ABS52c ABH52c
3-pole ABN53c ABS53c ABH53c
4-pole ABN54c ABS54c ABH54c
Rated current, In 15-20-30-40-50A
Rated operational voltage, Ue AC: 690V
DC: 500V
Rated insulation voltage, Ui AC: 750V
ABS52c
Rated impulse withstand voltage, Uimp 8kV

Rated short-circuit breaking N-Type S-Type H-Type


capacity, Icu AC 690V 2.5kA 5kA 10kA
480/500V 7.5kA 10kA 35kA
IEC 60947-2 (lcu) 460V 14kA 18kA 50kA
lcs=100%Icu 415V 14kA 18kA 50kA
380V 18kA 22kA 50kA
220/250V 30kA 35kA 100kA
DC 500V(3P) 5kA 10kA 30kA
ABS53c 250V(2P) 5kA 10kA 30kA

Protective function Overload, Short-circuit


Type of trip unit Thermal-Magnetic
Magnetic trip range 12×In (30A and under: 400A)
Endurance Mechanical 25000 operations
Electrical 10000 operations
Connection Standard Front connection
Optional Rear connection
Plug-in
Mounting Standard Screw fixing

Dimensions (mm) Pole 2p 3p 4p 2p 3p 4p 2p 3p 4p


d
c2
a 50 75 100 50 75 100 60 90 120
a c1
b 130 130 155
c1 Note) 60 60 60
b

c2 Note) 64 64 64
For more information d 82 82 82
�Drawings ▶ 93 page Weight, kg Standard 0.5 0.7 0.9 0.5 0.7 0.9 0.7 1 1.2
�Trip curves ▶ 87, 88 page
Certification Pole 2p 3p 4p 2p 3p 4p 2p 3p 4p
�Accessories ▶ 72 page
�Connection and mounting ▶ 110 page CE marking ○ ○ ○
Note) Depth by door cut size : c1 for large cut, c2 for small cut

36
Ordering types

Breaker types Accessories


ABN type (14kA/460V)
Rated current, In 2-pole 3-pole 4-pole
15 A ABN52c/15 ABN53c/15 ABN54c/15
20 A ABN52c/20 ABN53c/20 ABN54c/20
30 A ABN52c/30 ABN53c/30 ABN54c/30
40 A ABN52c/40 ABN53c/40 ABN54c/40
50 A ABN52c/50 ABN53c/50 ABN54c/50
Electrical auxiliaries
ABS type (18kA/460V) AX Auxiliary Switch
Rated current, In 2-pole 3-pole 4-pole AL Alarm Switch
15 A ABS52c/15 ABS53c/15 ABS54c/15 AX+AL Combination switch R T
20 A ABS52c/20 ABS53c/20 ABS54c/20 SHT Shunt Trip
30 A ABS52c/30 ABS53c/30 ABS54c/30 UVT Undervoltage trip
40 A ABS52c/40 ABS53c/40 ABS54c/40
50 A ABS52c/50 ABS53c/50 ABS54c/50 Maximum possibilities
T-position One of above auxiliaries
ABH type (50kA/460V) R-position Option of AX or AL or AX+AL
Note) For more detail see 72 page
Rated current, In 2-pole 3-pole 4-pole
15 A ABH52c/15 ABH53c/15 ABH54c/15
20 A ABH52c/20 ABH53c/20 ABH54c/20
30 A ABH52c/30 ABH53c/30 ABH54c/30
40 A ABH52c/40 ABH53c/40 ABH54c/40
50 A ABH52c/50 ABH53c/50 ABH54c/50

External accessories
ABN50c
ABH50c Name
ABS50c

IB13 IB23 Insulation barrier


TCL13 TCL23 Terminal cover (Long)
TCS13 TCS23 Terminal cover (Short)
DH100 DH125 Rotary handle (Direct)
DHK100 DHK125 Rotary handle (Direct, Key lock)
EH100 EH125 Rotary handle (Extended)
- RTB2 Rear terminal (Bar)
RTR1 RTR2 Rear terminal (Round)
PB-A3 PB-C3 Plug-in kit
PHL100 PHL125 Pad handle lock
Note) For more detail see 80 page

37
60AF MCCB
ABN60c, ABS60c

Ratings

Frame size 60AF


Type and Pole N-Type S-Type
2-pole ABN62c ABS62c
3-pole ABN63c ABS63c
4-pole ABN64c ABS64c
Rated current, In 15-20-30-40-50-60A
Rated operational voltage, Ue AC: 690V
DC: 500V

ABS62c
Rated insulation voltage, Ui AC: 750V
Rated impulse withstand voltage, Uimp 8kV

Rated short-circuit breaking N-Type S-Type


capacity, Icu AC 690V 2.5kA 5kA
480/500V 7.5kA 10kA
IEC 60947-2 (lcu) 460V 14kA 18kA
lcs=100%Icu 415V 14kA 18kA
380V 18kA 22kA
220/250V 30kA 35kA
DC 500V(3P) 5kA 10kA
ABS63c
250V(2P) 5kA 10kA

Protective function Overload, Short-circuit


Type of trip unit Thermal-Magnetic
Magnetic trip range 12×In (30A and under: 400A)
Endurance Mechanical 25000 operations
Electrical 10000 operations
Connection Standard Front connection
Optional Rear connection
Plug-in
Mounting Standard Screw fixing
ABS64c
Dimensions (mm) Pole 2p 3p 4p 2p 3p 4p
d
c2
a 50 75 100 50 75 100
a c1
b 130 130
c1 Note) 60 60
b

c2 Note) 64 64
For more information d 82 82
�Drawings ▶ 93 page Weight, kg Standard 0.5 0.7 0.9 0.5 0.7 0.9
�Trip curves ▶ 87 page
Certification Pole 2p 3p 4p 2p 3p 4p
�Accessories ▶ 72 page
�Connection and mounting ▶ 110 page CE marking ○ ○
Note) Depth by door cut size : c1 for large cut, c2 for small cut

38
Ordering types

Breaker types Accessories


ABN type (14kA/460V)
Rated current, In 2-pole 3-pole 4-pole
15 A ABN62c/15 ABN63c/15 ABN64c/15
20 A ABN62c/20 ABN63c/20 ABN64c/20
30 A ABN62c/30 ABN63c/30 ABN64c/30
40 A ABN62c/40 ABN63c/40 ABN64c/40
50 A ABN62c/50 ABN63c/50 ABN64c/50
Electrical auxiliaries
60 A ABN62c/60 ABN63c/60 ABN64c/60
AX Auxiliary Switch
ABS type (18kA/460V) AL Alarm Switch
Rated current, In 2-pole 3-pole 4-pole AX+AL Combination switch R T
15 A ABS62c/15 ABS63c/15 ABS64c/15 SHT Shunt Trip
20 A ABS62c/20 ABS63c/20 ABS64c/20 UVT Undervoltage trip
30 A ABS62c/30 ABS63c/30 ABS64c/30
40 A ABS62c/40 ABS63c/40 ABS64c/40 Maximum possibilities
50 A ABS62c/50 ABS63c/50 ABS64c/50 T-position One of above auxiliaries
60 A ABS62c/60 ABS63c/60 ABS64c/60 R-position Option of AX or AL or AX+AL
Note) For more detail see 72 page

External accessories
ABS60c
Name
ABN60c
IB13 Insulation barrier
TCL13 Terminal cover (Long)
TCS13 Terminal cover (Short)
DH100 Rotary handle (Direct)
DHK100 Rotary handle (Direct, Key lock)
EH100 Rotary handle (Extended)
RTB1 Rear terminal (Bar)
RTR1 Rear terminal (Round)
PB-A3 Plug-in kit
PHL100 Pad handle lock
Note) For more detail see 80 page

39
100AF MCCB
ABN100c

Ratings

Frame size 100AF


Type and Pole N-Type
2-pole ABN102c
3-pole ABN103c
4-pole ABN104c
Rated current, In 15-20-30-40-50-60-75-100A
Rated operational voltage, Ue AC: 690V
DC: 500V
Rated insulation voltage, Ui AC: 750V
ABN102c
Rated impulse withstand voltage, Uimp 8kV

Rated short-circuit breaking N-Type


capacity, Icu AC 690V 5kA
480/500V 10kA
IEC 60947-2 (lcu) 460V 18kA
lcs=100%Icu 415V 18kA
380V 22kA
220/250V 35kA
DC 500V(3P) 10kA
ABN103c
250V(2P) 10kA

Protective function Overload, Short-circuit


Type of trip unit Thermal-Magnetic
Magnetic trip range 400A
Endurance Mechanical 25000 operations
Electrical 10000 operations
Connection Standard Front connection
Optional Rear connection
Plug-in
Mounting Standard Screw fixing
ABN104c
Dimensions (mm) Pole 2p 3p 4p
d
c2
a 50 75 100
a c1
b 130 130 130
c1 Note) 60 60 60
b

c2 Note) 64 64 64
For more information d 82 82 82
�Drawings ▶ 93 page Weight, kg Standard 0.5 0.7 0.9
�Trip curves ▶ 87 page
Certification Pole 2p 3p 4p
�Accessories ▶ 72 page
�Connection and mounting ▶ 110 page CE marking ○ ○ ○
Note) Depth by door cut size : c1 for large cut, c2 for small cut

40
Ordering types

Breaker types Accessories


ABN type (14kA/460V)

Rated current, In 2-pole 3-pole 4-pole


15 A ABN102c/15 ABN103c/15 ABN104c/15
20 A ABN102c/20 ABN103c/20 ABN104c/20
30 A ABN102c/30 ABN103c/30 ABN104c/30
40 A ABN102c/40 ABN103c/40 ABN104c/40
50 A ABN102c/50 ABN103c/50 ABN104c/50
Electrical auxiliaries
60 A ABN102c/60 ABN103c/60 ABN104c/60
75 A ABN102c/75 ABN103c/75 ABN104c/75 AX Auxiliary Switch
100 A ABN102c/100 ABN103c/100 ABN104c/100 AL Alarm Switch
AX+AL Combination switch R T
SHT Shunt Trip
UVT Undervoltage trip

Maximum possibilities
T-position One of above auxiliaries
R-position Option of AX or AL or AX+AL
Note) For more detail see 72 page

External accessories
ABN100c Name

IB13 Insulation barrier


TCL13 Terminal cover (Long)
TCS13 Terminal cover (Short)
DH100 Rotary handle (Direct)
DHK100 Rotary handle (Direct, Key lock)
EH100 Rotary handle (Extended)
RTB1 Rear terminal (Bar)
RTR1 Rear terminal (Round)
PB-A3 Plug-in kit
PHL100 Pad handle lock
Note) For more detail see 80 page

41
125AF MCCB
ABS125c, ABH125c

Ratings

Frame size 125AF


Type and Pole S-Type H-Type
2-pole ABS102c ABH102c
3-pole ABS103c ABH103c
4-pole ABS104c ABH104c
Rated current, In 15-20-30-40-50-60-75-100-125A
Rated operational voltage, Ue AC: 690V
DC: 500V
Rated insulation voltage, Ui AC: 750V
ABS102c Rated impulse withstand voltage, Uimp 8kV

Rated short-circuit breaking S-Type H-Type


capacity, Icu AC 690V 8kA 10kA
480/500V 26kA 35kA
IEC 60947-2 (lcu) 460V 37kA 50kA
lcs=100%Icu 415V 37kA 50kA
380V 42kA 50kA
220/250V 85kA 100kA
DC 500V(3P) 20kA 30kA
250V(2P) 20kA 30kA

Protective function Overload, Short-circuit


ABS103c
Type of trip unit Thermal-Magnetic
Magnetic trip range 12×In (30A and under: 400A)
Endurance Mechanical 25000 operations
Electrical 10000 operations
Connection Standard Front connection
Optional Rear connection
Plug-in
Mounting Standard Screw fixing

Dimensions (mm) Pole 2p 3p 4p 2p 3p 4p


d
c2
a 60 90 120 60 90 120
ABS104c a c1
b 155 155
c1 Note) 60 60
b

c2 Note) 64 64
For more information d 82 82
�Drawings ▶ 94 page Weight, kg Standard 0.7 1 1.2 0.7 1 1.2
�Trip curves ▶ 88 page
Certification Pole 2p 3p 4p 2p 3p 4p
�Accessories ▶ 72 page
�Connection and mounting ▶ 110 page CE marking ○ ○
Note) Depth by door cut size : c1 for large cut, c2 for small cut

42
Ordering types

Breaker types Accessories


ABS type (37kA/460V)
Rated current, In 2-pole 3-pole 4-pole
15 A ABS102c/15 ABS103c/15 ABS104c/15
20 A ABS102c/20 ABS103c/20 ABS104c/20
30 A ABS102c/30 ABS103c/30 ABS104c/30
40 A ABS102c/40 ABS103c/40 ABS104c/40
50 A ABS102c/50 ABS103c/50 ABS104c/50
Electrical auxiliaries
60 A ABS102c/60 ABS103c/60 ABS104c/60
75 A ABS102c/75 ABS103c/75 ABS104c/75 AX Auxiliary Switch
100 A ABS102c/100 ABS103c/100 ABS104c/100 AL Alarm Switch
125 A ABS102c/125 ABS103c/125 ABS104c/125 AX+AL Combination switch R T
SHT Shunt Trip
ABH type (50kA/460V) UVT Undervoltage trip
Rated current, In 2-pole 3-pole 4-pole
15 A ABH102c/15 ABH103c/15 ABH104c/15 Maximum possibilities
20 A ABH102c/20 ABH103c/20 ABH104c/20 T-position One of above auxiliaries
30 A ABH102c/30 ABH103c/30 ABH104c/30 R-position Option of AX or AL or AX+AL
40 A ABH102c/40 ABH103c/40 ABH104c/40 Note) For more detail see 72 page

50 A ABH102c/50 ABH103c/50 ABH104c/50


60 A ABH102c/60 ABH103c/60 ABH104c/60
75 A ABH102c/75 ABH103c/75 ABH104c/75
100 A ABH102c/100 ABH103c/100 ABH104c/100
125 A ABH102c/125 ABH103c/125 ABH104c/125

External accessories
ABS125c
Name
ABH125c
IB23 Insulation barrier
TCL23 Terminal cover (Long)
TCS23 Terminal cover (Short)
DH125 Rotary handle (Direct)
DHK125 Rotary handle (Direct, Key lock)
EH125 Rotary handle (Extended)
RTB2 Rear terminal (Bar)
RTR2 Rear terminal (Round)
PB-C3 Plug-in kit
PHL125 Pad handle lock
Note) For more detail see 80 page

43
250AF MCCB
ABN250c, ABS250c, ABH250c

Ratings

Frame size 250AF


Type and Pole N-Type S-Type H-Type
2-pole ABN202c ABS202c ABH202c
3-pole ABN203c ABS203c ABH203c
4-pole ABN204c ABS204c ABH204c
Rated current, In 100-125-150-175-200-225-250A
Rated operational voltage, Ue AC: 690V
DC: 500V
Rated insulation voltage, Ui AC: 750V
ABS202c
Rated impulse withstand voltage, Uimp 8kV

Rated short-circuit breaking N-Type S-Type H-Type


capacity, Icu AC 690V 8kA 8kA 10kA
480/500V 18kA 26kA 35kA
IEC 60947-2 (lcu) 460V 26kA 37kA 50kA
lcs=100%Icu 415V 26kA 37kA 50kA
380V 30kA 42kA 50kA
220/250V 65kA 85kA 100kA
DC 500V(3P) 10kA 20kA 30kA
250V(2P) 10kA 20kA 30kA
ABS203c
Protective function Overload, Short-circuit
Type of trip unit Thermal-Magnetic
Magnetic trip range 12×In
Endurance Mechanical 25000 operations
Electrical 10000 operations
Connection Standard Front connection
Optional Rear connection
Plug-in
Mounting Standard Screw fixing

Dimensions (mm) Pole 2p 3p 4p 2p 3p 4p 2p 3p 4p

ABS204c
d
c2
a 105 105 140 105 105 140 105 105 140
a c1
b 165 165 165
c1 Note) 60 60 60
b

c2 Note) 64 64 64
For more information d 87 87 87
�Drawings ▶ 95 page Weight, kg Standard 1.1 1.2 1.6 1.1 1.2 1.6 1.1 1.2 1.6
�Trip curves ▶ 89 page
Certification Pole 2p 3p 4p 2p 3p 4p 2p 3p 4p
�Accessories ▶ 72 page
�Connection and mounting ▶ 110 page CE marking ○ ○ ○
Note) Depth by door cut size : c1 for large cut, c2 for small cut

44
Ordering types

Breaker types Accessories


ABN type (25kA/460V)
Rated current, In 2-pole 3-pole 4-pole
100 A ABN202c/100 ABN203c/100 ABN204c/100
125 A ABN202c/125 ABN203c/125 ABN204c/125
150 A ABN202c/150 ABN203c/150 ABN204c/150
175 A ABN202c/175 ABN203c/175 ABN204c/175
200 A ABN202c/200 ABN203c/200 ABN204c/200
225 A ABN202c/225 ABN203c/225 ABN204c/225
Electrical auxiliaries
250 A ABN202c/250 ABN203c/250 ABN204c/250 AX Auxiliary Switch
AL Alarm Switch
ABS type (37kA/460V)
AX+AL Combination switch R T
Rated current, In 2-pole 3-pole 4-pole SHT Shunt Trip
100 A ABS202c/100 ABS203c/100 ABS204c/100 UVT Undervoltage trip
125 A ABS202c/125 ABS203c/125 ABS204c/125
150 A ABS202c/150 ABS203c/150 ABS204c/150 Maximum possibilities
175 A ABS202c/175 ABS203c/175 ABS204c/175 T-position One of above auxiliaries
200 A ABS202c/200 ABS203c/200 ABS204c/200 R-position Option of AX or AL or AX+AL
225 A ABS202c/225 ABS203c/225 ABS204c/225 Note) For more detail see 72 page
250 A ABS202c/250 ABS203c/250 ABS204c/250

ABH type (50kA/460V)


Rated current, In 2-pole 3-pole 4-pole
100 A ABH202c/100 ABH203c/100 ABH204c/100
125 A ABH202c/125 ABH203c/125 ABH204c/125
150 A ABH202c/150 ABH203c/150 ABH204c/150
175 A ABH202c/175 ABH203c/175 ABH204c/175
200 A ABH202c/200 ABH203c/200 ABH204c/200
225 A ABH202c/225 ABH203c/225 ABH204c/225
250 A ABH202c/250 ABH203c/250 ABH204c/250

External accessories
ABH250c Name

B33 Insulation barrier


TCL33 Terminal cover (Long)
TCS33 Terminal cover (Short)
DH250 Rotary handle (Direct)
DHK250 Rotary handle (Direct, Key lock)
EH250 Rotary handle (Extended)
RTB3 Rear terminal (Bar)
RTR3 Rear terminal (Round)
PBA250C Plug-in kit
PHL250 Pad handle lock
Note) For more detail see 80 page

45
400AF MCCB
ABN400c, ABS400c, ABH400c, ABL400c

Ratings

Frame size 400AF


Type and Pole N-Type S-Type H-Type L-Type
2-pole ABN402c ABS402c ABH402c ABL402c
3-pole ABN403c ABS403c ABH403c ABL403c
4-pole ABN404c ABS404c ABH404c ABL404c
Rated current, In 250-300-350-400A
Rated operational voltage, Ue AC: 690V
DC: 500V
Rated insulation voltage, Ui AC: 750V
Rated impulse withstand voltage, Uimp 8kV
ABS403c
Rated short-circuit breaking N-Type S-Type H-Type L-Type
capacity, Icu AC 690V 5kA 8kA 10kA 14kA
480/500V 18kA 35kA 50kA 65kA
IEC 60947-2 (lcu) 415/460V 37kA 50kA 65kA 85kA
380V 42kA 65kA 70kA 100kA
220/250V 50kA 75kA 85kA 125kA
DC 500V(3P) 10kA 20kA 40kA 40kA
250V(3P) 10kA 20kA 40kA 40kA
lcs=100%Icu 125V 100% 100% 100% 75%
ABL404c Protective function Overload, Short-circuit
Type of trip unit Thermal-Magnetic
Magnetic trip range 8~12In
Endurance Mechanical 4000 operations
Electrical 1000 operations
Connection Standard Front connection
Optional Rear connection
Plug-in
Mounting Standard Screw fixing

Dimensions (mm) Pole 2p 3p 4p 2p 3p 4p 2p 3p 4p 2p 3p 4p


d
c2
a 140 140 184 140 140 184 140 140 184 140 140 184
a c1
b 257 257 257 257
c1 Note) 109 109 109 109
b

c2 Note) 113 113 113 113


For more information d 145 145 145 145
�Drawings ▶ 96 page Weight, kg Standard 5.2 6.2 7.8 5.2 6.2 7.8 5.2 6.2 7.8 5.2 6.2 7.8
�Trip curves ▶ 90 page
�Accessories ▶ 72 page
Certification Pole 2p 3p 4p 2p 3p 4p 2p 3p 4p 2p 3p 4p
�Connection and mounting ▶ 111 page CE marking ○ ○ ○ ○
Note) Depth by door cut size : c1 for large cut, c2 for small cut

46
Ordering types

Breaker types Accessories


ABN type (37kA/460V)
Rated current, In 2-pole 3-pole 4-pole
250 A ABN402c/250 ABN403c/250 ABN404c/250
300 A ABN402c/300 ABN403c/300 ABN404c/300
350 A ABN402c/350 ABN403c/350 ABN404c/350
400 A ABN402c/400 ABN403c/400 ABN404c/400

ABS type (50kA/460V)


Rated current, In 2-pole 3-pole 4-pole
250 A ABS402c/250 ABS403c/250 ABS404c/250
300 A ABS402c/300 ABS403c/300 ABS404c/300
Electrical auxiliaries
350 A ABS402c/350 ABS403c/350 ABS404c/350
400 A ABS402c/400 ABS403c/400 ABS404c/400 AX Auxiliary Switch
AL Alarm Switch
R T
SHT Shunt Trip
ABH type(65kA/460V)
UVT Undervoltage trip
Rated current, In 2-pole 3-pole 4-pole
250 A ABH402c/250 ABH403c/250 ABH404c/250
Maximum possibilities
300 A ABH402c/300 ABH403c/300 ABH404c/300
T-position Option of 2AX, 2AL and SHT or UVT
350 A ABH402c/350 ABH403c/350 ABH404c/350
R-position Option of 2AX, 2AL and SHT or UVT
400 A ABH402c/400 ABH403c/400 ABH404c/400
Note) For more detail see 73 page

ABL type(85kA/460V)
Rated current, In 2-pole 3-pole 4-pole
250 A ABL402c/250 ABL403c/250 ABL404c/250
300 A ABL402c/300 ABL403c/300 ABL404c/300
350 A ABL402c/350 ABL403c/350 ABL404c/350
400 A ABL402c/400 ABL403c/400 ABL404c/400

E-70U N-70

External accessories
IBL400 Insulation barrier
T1-43A Terminal cover (Long) - 2, 3pole
T1-44A Terminal cover (Long) - 4pole
N-70 Rotary handle (Direct)
E-70U Rotary handle (Extended)
MI-43 Mechanical interlock - 2, 3pole
MI-44 Mechanical interlock - 4pole
X-402 Rear terminal - 2pole
X-403 Rear terminal - 3pole
X-404 Rear terminal - 4pole
PB-I3-FR Plug-in kit
Note) For more detail see 80 page

47
800AF MCCB
ABN800c, ABS800c, ABL800c

Ratings

Frame size 800AF


Type and Pole N-Type S-Type L-Type
2-pole ABN802c ABS802c ABL802c
3-pole ABN803c ABS803c ABL803c
4-pole ABN804c ABS804c ABL804c
Rated current, In 500-630-700-800A
Rated operational voltage, Ue AC: 690V
DC: 500V
Rated insulation voltage, Ui AC: 750V
Rated impulse withstand voltage, Uimp 8kV
ABS803c
Rated short-circuit breaking N-Type S-Type L-Type
capacity, Icu AC 690V 8kA 10kA 14kA
480/500V 25kA 45kA 65kA
IEC 60947-2 (lcu) 415/460V 37kA 65kA 85kA
380V 45kA 75kA 100kA
220/250V 50kA 85kA 125kA
DC 500V(3P) 10kA 20kA 40kA
250V(3P) 10kA 20kA 40kA
lcs=100%Icu 125V 100% 100% 75%

ABL804c Protective function Overload, Short-circuit


Type of trip unit Thermal-Magnetic
Magnetic trip range 8~12In
Endurance Mechanical 2500 operations
Electrical 500 operations
Connection Standard Front connection
Optional Rear connection
Plug-in
Mounting Standard Screw fixing

Dimensions (mm) Pole 2p 3p 4p 2p 3p 4p 2p 3p 4p


d
c2
a 210 210 280 210 210 280 210 210 280
a c1
b 280 280 280
c1 Note) 109 109 109
b

c2 Note) 113 113 113


For more information d 145 145 145
�Drawings ▶ 97 page Weight, kg Standard 11 11.5 18.2 11 11.5 18.2 11 11.5 18.2
�Trip curves ▶ 90 page
�Accessories ▶ 72 page
Certification Pole 2p 3p 4p 2p 3p 4p 2p 3p 4p
�Connection and mounting ▶ 111 page CE marking ○ ○ ○
Note) Depth by door cut size : c1 for large cut, c2 for small cut

48
Ordering types

Breaker types Accessories


ABN type (37kA/460V)
Rated current, In 2-pole 3-pole 4-pole
500 A ABN802c/500 ABN803c/500 ABN804c/500
630 A ABN802c/630 ABN803c/630 ABN804c/630
700 A ABN802c/700 ABN803c/700 ABN804c/700
800 A ABN802c/800 ABN803c/800 ABN804c/800

ABS type (65kA/460V)


Rated current, In 2-pole 3-pole 4-pole
500 A ABS802c/500 ABS803c/500 ABS804c/500
630 A ABS802c/630 ABS803c/630 ABS804c/630 Electrical auxiliaries
700 A ABS802c/700 ABS803c/700 ABS804c/700 Auxiliary Switch
AX
800 A ABS802c/800 ABS803c/800 ABS804c/800 Alarm Switch
AL
R T
SHT Shunt Trip
ABL type(85kA/460V) UVT Undervoltage trip

Rated current, In 2-pole 3-pole 4-pole


Maximum possibilities
500 A ABL802c/500 ABL803c/500 ABL804c/500
630 A ABL802c/630 ABL803c/630 ABL804c/630 T-position Option of 2AX, 2AL and SHT or UVT
700 A ABL802c/700 ABL803c/700 ABL804c/700 R-position Option of 2AX, 2AL and SHT or UVT
800 A ABL802c/800 ABL803c/800 ABL804c/800 Note) For more detail see 73 page

E-80U N-80

External accessories

IBL800 Insulation barrier


T1-63A Terminal cover (Long) - 2, 3pole
T1-64A Terminal cover (Long) - 4pole
N-80 Rotary handle (Direct)
E-80U Rotary handle (Extended)
MI-83S Mechanical interlock - 2, 3pole
MI-84S Mechanical interlock - 4pole
X-802 Rear terminal - 2pole
X-803 Rear terminal - 3pole
X-804 Rear terminal - 4pole
PB-J3-FR Plug-in kit
Note) For more detail see 80 page

49
1000/1200AF MCCB
ABS1000b/1200b, ABL1000b/1200b

Ratings

Frame size 1000AF 1200AF


Type and Pole S-Type L-Type S-Type L-Type
2-pole - - - -
3-pole ABS1003b ABL1003b ABS1203b ABL1203b
4-pole ABS1004b ABL1004b ABS1204b ABL1204b
Rated current, In 1000A 1200A
Rated operational voltage, Ue AC: 600V
Rated insulation voltage, Ui 690V
Rated impulse withstand voltage, Uimp 6kV

Rated short-circuit breaking S-Type L-Type


capacity, Icu AC 690V 45kA 65kA
480/500V 50kA 75kA
IEC 60947-2 (lcu) 415/460V 65kA 85kA
380V 65kA 85kA
220/250V 100kA 125kA
lcs=100%Icu 125V 50kA 50kA
Protective function Overload, Short-circuit
Type of trip unit Thermal-Magnetic
Magnetic trip range 3~6×In
Endurance Mechanical 2500 operations
Electrical 500 operations
Connection Standard Front connection
Mounting Standard Screw fixing

Dimensions (mm) Pole 3p 4p


d
c2 a 220 290
a c1
b 400 400
c 105 105
b

d 159 159
Weight, kg Standard 19.6 25.7
For more information
Certification Pole 3p 4p
�Drawings ▶ 98 page
�Trip curves ▶ 91 page CE marking

50
Ordering types

Breaker types Contact operation for Auxiliary and Alarm Switches


ABS type (65kA/460V) MCCB ON OFF TRIP

Rated current, In 3-pole 4-pole


1000 A ABS1003b/1000 ABS1004b/1000
AX
1200 A ABS1203b/1200 ABS1204b/1200

ABL type (85kA/460V)


Rated current, In 3-pole 4-pole
AL
1000 A ABL1003b/1000 ABL1004b/1000
1200 A ABL1203b/1200 ABL1204b/1200

Option of below items for T-position Contact rating for Auxiliary and Alarm Switches
AX1 Auxiliary Switch (1c) AC DC
AX2 Auxiliary Switch (2c) Voltage Current (A) Voltage Current (A)
AL1 Alarm Switch (1c) R T (V) Resistive load Inductive load (V) Resistive load Inductive load
AL2 Alarm Switch (2c) 125 20 20 30 6 5
AX1+AL Auxiliary (1c) + Alarm (1c) Switch 250 20 20 125 0.4 0.05
AX2+AL Auxiliary (2c) + Alarm (1c) Switch 500 10 5 250 0.2 0.03

Option of below items for R-position


SHT Shunt Trip Rating for Shunt trip (SHT)
UVT Undervoltage trip Control voltage Time rating Operational voltage

100~110V Continuous 85~110% of control voltage


AC 200~220V
380~440V
48V 75~125% of control voltage
DC 100~110V
200~220V

Rating for Undervoltage release (UVT)

Control voltage Time rating Operational voltage Trip voltage

100~110V Continuous 85~110% of 20~70% of


AC 200~220V control voltage control voltage
380~440V
100V 85~125% of 20~70% of
DC
200V control voltage control voltage

51
1200AF 전자식 MCCB
ABS1203bE

Ratings

Frame size 1200AF


Type and Pole S-Type
2-pole -
3-pole ABS1203bE
4-pole) -
Rated current, In 1200A
Rated operational voltage, Ue AC: 600V
Rated insulation voltage, Ui AC: 600V
Rated impulse withstand voltage, Uimp 6kV

Type Long time Current, IR (0.5-0.6-0.7-0.8-0.9-1.0)×In, adjustable...①


pick-up time 5sec ± 20% at 6×Ir, fixed
Short time Current, Im (2-3-4-5-6-8-10)×ln, adjustable...②
pick-up time 0.1-0.2-0.3 sec, adjustable...③
Instantaneous Current, It 11×ln, fixed
pick-up time within 0.03 sec, fixed
⑤ LED Pre-Alarm between 70 to 110% of set current Ir: LED flickering
over 110% of set current Ir: stays on
④ Rated frequency 50-60Hz selectable by the switch of the trip unit

Rated short-circuit breaking S-Type


capacity, Icu AC 690V 45kA
480/500V 50kA
415/460V 65kA
380V 65kA
220/250V 100kA
lcs=100%Icu 50%

Protective function Overload, Short-circuit


Type of trip unit Electronic type
Endurance Mechanical 2500 operations
Electrical 500 operations
Connection Standard Front connection
Mounting Standard Screw fixing
Dimensions (mm) Pole 3p
d
c2 a 220
a c1
b 400

For more information c 105


b

d 159
�Drawings ▶ 99 page
�Trip curves ▶ 92 page Weight, kg Standard 21

52
Ordering types

Breaker types Contact operation for Auxiliary and Alarm Switches


ABS type (65kA/460V) MCCB ON OFF TRIP

Rated current, In 3P
1200 A ABS1203bE
AX

AL

Option of below items for T-position Contact rating for Auxiliary and Alarm Switches
AX1 Auxiliary Switch (1c) AC DC
AX2 Auxiliary Switch (2c) Voltage Current (A) Voltage Current (A)
AL1 Alarm Switch (1c) R T (V) Resistive load Inductive load (V) Resistive load Inductive load
AL2 Alarm Switch (2c) 125 20 20 30 6 5
AX1+AL Auxiliary (1c) + Alarm (1c) Switch 250 20 20 125 0.4 0.05
AX2+AL Auxiliary (2c) + Alarm (1c) Switch 500 10 5 250 0.2 0.03

Option of below items for R-position


SHT Shunt Trip Rating for Shunt trip (SHT)
UVT Undervoltage trip Control voltage Time rating Operational voltage

100~110V Continuous 85~110% of control voltage


AC 200~220V
380~440V
48V 75~125% of control voltage
DC 100~110V
200~220V

Rating for Undervoltage release (UVT)

Control voltage Time rating Operational voltage Trip voltage

100~110V Continuous 85~110% of 20~70% of


AC 200~220V control voltage control voltage
380~440V
100V 85~125% of 20~70% of
DC
200V control voltage control voltage

53
30AF ELCB
EBS30c

Ratings

Frame size 30AF


Type and Pole S-Type
2-pole(2-sensor) -
3-pole(3-sensor) EBS33c
4-pole(3-sensor) EBS34c
Rated current, In 15-20-30A
Rated residual current, I△n 30, 100/200/500mA (Adjustable)
Residual current off-time at I△n ≤0.1 sec
Rated operational voltage, Ue AC: 220/460V
Rated impulse withstand voltage, Uimp 6kV
EBS33c Wiring system 2-pole(2-sensor) -
3-pole(3-sensor) 1∅2W, 1∅3W, 3∅3W
4-pole(3-sensor) 1∅2W, 1∅3W, 3∅3W, 3∅4W

Rated short-circuit breaking S-Type


capacity, Icu AC 460V 14 kA
IEC 60947-2 (lcu) 415V 14 kA
lcs=100%Icu 220/250V 30 kA

Protective function Overload, Short-circuit and Ground fault


Type of trip unit Thermal-Magnetic
Magnetic trip range 400A
Endurance Mechanical 25000 operations
Electrical 10000 operations
Connection Standard Front connection
Optional Rear connection
Plug-in
Mounting Standard Screw fixing

Dimensions (mm) Pole 3p 4p


d
c2
a 75 100
a c1
b 130 130
c1 Note) 60 60
b

c2 Note) 64 64
For more information d 82 82
�Drawings ▶ 100 page Weight, kg Standard 0.7 0.9
�Trip curves ▶ 87 page
�Accessories ▶ 72 page Certification Pole 3p 4p
�Connection and mounting ▶ 110 page CE marking ○ ○
Note) Depth by door cut size : c1 for large cut, c2 for small cut

54
Ordering types

Breaker types Accessories


EBS type (14kA/460V)
△n: 30mA
Rated residual current, I△
Rated current, In
3-pole 4-pole
15 A EBS33c/15/30 EBS34c/15/30
20 A EBS33c/20/30 EBS34c/20/30
30 A EBS33c/30/30 EBS34c/30/30

Electrical auxiliaries

EBS type (14kA/460V) AX Auxiliary Switch


AL Alarm Switch R T
△n: 100/200/500mA
Rated residual current, I△
Rated current, In AX+AL Combination switch
3-pole 4-pole
15 A EBS33c/15/100 EBS34c/15/100
Maximum possibilities
20 A EBS33c/20/100 EBS34c/20/100
T-position Not available
30 A EBS33c/30/100 EBS34c/30/100
R-position Option of AX or AL or AX+AL
Note) For more detail see 72 page

External accessories
EBS30c Name

IB13 Insulation barrier


TCL13 Terminal cover (Long)
TCS13 Terminal cover (Short)
DH100 Rotary handle (Direct)
DHK100 Rotary handle (Direct, Key lock)
EH100 Rotary handle (Extended)
RTR1 Rear terminal (Round)
PB-A3 Plug-in kit
PHL100 Pad handle lock
Note) For more detail see 80 page

55
50AF ELCB
EBN50c, EBS50c, EBH50c

Ratings

Frame size 50AF


Type and Pole N-Type S-Type H-Type
2-pole(2-sensor) EBN52c - -
3-pole(3-sensor) EBN53c EBS53c EBH53c
4-pole(3-sensor) - EBS54c EBH54c
Rated current, In 15-20-30-40-50A
Rated residual current, I△n 30, 100/200/500mA (Adjustable)
Residual current off-time at I△n ≤0.1 sec
Rated operational voltage, Ue AC: 220/460V
Rated impulse withstand voltage, Uimp 6kV

EBN53c Wiring system 2-pole(2-sensor) 1∅2W


3-pole(3-sensor) 1∅2W, 1∅3W, 3∅3W
4-pole(3-sensor) 1∅2W, 1∅3W, 3∅3W, 3∅4W

Rated short-circuit breaking N-Type S-Type H-Type


capacity, Icu AC 460V 14kA 18kA 50kA
IEC 60947-2 (lcu) 415V 14kA 18kA 50kA
lcs=100%Icu 220/250V 30kA 35kA 100kA

Protective function Overload, Short-circuit and Ground fault


Type of trip unit Thermal-Magnetic
Magnetic trip range 12×In (30A and under: 400A)
Endurance Mechanical 25000 operations
Electrical 10000 operations
EBS53c Connection Standard Front connection
Optional Rear connection
Plug-in
Mounting Standard Screw fixing

Dimensions (mm) Pole 2p 3p 3p 4p 3p 4p


d
c2
a 75 75 75 100 90 120
a c1
b 130 130 155
c1 Note) 60 60 60
b

c2 Note) 64 64 64
For more information d 82 82 82
�Drawings ▶ 100 page Weight, kg Standard 0.5 0.7 0.7 0.9 1 1.2
�Trip curves ▶ 87, 88 page
Certification Pole 2p 3p 3p 4p 3p 4p
�Accessories ▶ 72 page
�Connection and mounting ▶ 110 page CE marking ○ ○ ○
Note) Depth by door cut size : C1 for large cut, C2 for small cut

56
Ordering types

Breaker types Accessories


EBN type (14kA/460V)
Rated residual current, Rated residual current,
Rated
△n: 30mA
I△ △n: 100/200/500mA
I△
current, In
2-pole 3-pole 2-pole 3-pole
15 A EBN52c/15/30 EBN53c/15/30 EBN52c/15/100 EBN53c/15/100
20 A EBN52c/20/30 EBN53c/20/30 EBN52c/20/100 EBN53c/20/100
30 A EBN52c/30/30 EBN53c/30/30 EBN52c/30/100 EBN53c/30/100
40 A
Electrical auxiliaries
EBN52c/40/30 EBN53c/40/30 EBN52c/40/100 EBN53c/40/100
50 A EBN52c/50/30 EBN53c/50/30 EBN52c/50/100 EBN53c/50/100 AX Auxiliary Switch
AL Alarm Switch R T
AX+AL Combination switch
EBS type (18kA/460V)
Rated residual current, Rated residual current, Maximum possibilities
Rated
△n: 30mA
I△ △n: 100/200/500mA
I△
current, In T-position Not available
3-pole 4-pole 3-pole 4-pole
R-position Option of AX or AL or AX+AL
15 A EBS53c/15/30 EBS54c/15/30 EBS53c/15/100 EBS54c/15/100
Note) For more detail see 72 page
20 A EBS53c/20/30 EBS54c/20/30 EBS53c/20/100 EBS54c/20/100
30 A EBS53c/30/30 EBS54c/30/30 EBS53c/30/100 EBS54c/30/100
40 A EBS53c/40/30 EBS54c/40/30 EBS53c/40/100 EBS54c/40/100
50 A EBS53c/50/30 EBS54c/50/30 EBS53c/50/100 EBS54c/50/100

EBH type (37kA/460V)


Rated residual current, Rated residual current,
Rated
△n: 30mA
I△ △n: 100/200/500mA
I△ External accessories
current, In
3-pole 4-pole 3-pole 4-pole
EBN50c
15 A EBH53c/15/30 EBH54c/15/30 EBH53c/15/100 EBH54c/15/100 EBH50c Name
EBS50c
20 A EBH53c/20/30 EBH54c/20/30 EBH53c/20/100 EBH54c/20/100
30 A EBH53c/30/30 EBH54c/30/30 EBH53c/30/100 EBH54c/30/100 IB13 IB23 Insulation barrier
40 A EBH53c/40/30 EBH54c/40/30 EBH53c/40/100 EBH54c/40/100 TCL13 TCL23 Terminal cover (Long)
50 A EBH53c/50/30 EBH54c/50/30 EBH53c/50/100 EBH54c/50/100 TCS13 TCS23 Terminal cover (Short)
DH100 DH125 Rotary handle (Direct)
DHK100 DHK125 Rotary handle (Direct, Key lock)
EH100 EH125 Rotary handle (Extended)
- RTB2 Rear terminal (Bar)
RTR1 RTR2 Rear terminal (Round)
PB-A3 PB-C3 Plug-in kit
PHL100 PHL125 Pad handle lock
Note) For more detail see 80 page

57
60AF ELCB
EBN60c, EBS60c

Ratings

Frame size 60AF


Type and Pole N-Type S-Type
2-pole(2-sensor) - -
3-pole(3-sensor) EBN63c EBS63c
4-pole(3-sensor) - EBS64c
Rated current, In 60A
Rated residual current, I△n 30, 100/200/500mA (Adjustable)
Residual current off-time at I△n ≤0.1 sec
Rated operational voltage, Ue AC: 220/460V
Rated impulse withstand voltage, Uimp 6kV
EBN63c Wiring system 2-pole(2-sensor) -
3-pole(3-sensor) 1∅2W, 1∅3W, 3∅3W
4-pole(3-sensor) 1∅2W, 1∅3W, 3∅3W, 3∅4W

Rated short-circuit breaking N-Type S-Type


capacity, Icu AC 460V 14kA 18kA
IEC 60947-2 (lcu) 415V 14kA 18kA
lcs=100%Icu 220/250V 30kA 35kA

Protective function Overload, Short-circuit and Ground fault


Type of trip unit Thermal-Magnetic
Magnetic trip range 12×In
Endurance Mechanical 25000 operations
Electrical 10000 operations
EBS63c
Connection Standard Front connection
Optional Rear connection
Plug-in
Mounting Standard Screw fixing

Dimensions (mm) Pole 3p 3p 4p


d
c2
a 75 75 100
a c1
b 130 130 130
c1 Note) 60 60 60
b

c2 Note) 64 64 64
For more information d 82 82 82
�Drawings ▶ 100 page Weight, kg Standard 0.7 0.7 0.9
�Trip curves ▶ 87 page
Certification Pole 3p 3p 4p
�Accessories ▶ 72 page
�Connection and mounting ▶ 110 page CE marking ○ ○
Note) Depth by door cut size : C1 for large cut, C2 for small cut

58
Ordering types

Breaker types Accessories


EBN type (14kA/460V)
Rated residual current, Rated residual current,
Rated
△n: 30mA
I△ △n: 100/200/500mA
I△
current, In
3-pole 3-pole
60 A EBN63c/60/30 EBN63c/60/100

EBS type (18kA/460V) Electrical auxiliaries


Rated residual current, Rated residual current, AX Auxiliary Switch
Rated
△n: 30mA
I△ △n: 100/200/500mA
I△ AL Alarm Switch R T
current, In
3-pole 4-pole 3-pole 4-pole AX+AL Combination switch
60 A EBS63c/60/30 EBS64c/60/30 EBS63c/60/100 EBS64c/60/100
Maximum possibilities
T-position Not available
R-position Option of AX or AL or AX+AL
Note) For more detail see 72 page

External accessories
EBS60c
Name
EBN60c
IB13 Insulation barrier
TCL13 Terminal cover (Long)
TCS13 Terminal cover (Short)
DH100 Rotary handle (Direct)
DHK100 Rotary handle (Direct, Key lock)
EH100 Rotary handle (Extended)
RTB1 Rear terminal (Bar)
RTR1 Rear terminal (Round)
PB-A3 Plug-in kit
PHL100 Pad handle lock
Note) For more detail see 80 page

59
100AF ELCB
EBN100c

Ratings

Frame size 100AF


Type and Pole N-Type
2-pole(2-sensor) EBN102c
3-pole(3-sensor) EBN103c
4-pole(3-sensor) EBN104c
Rated current, In 60-75-100A
Rated residual current, I△n 30, 100/200/500mA (Adjustable)
Residual current off-time at I△n ≤0.1 sec
Rated operational voltage, Ue AC: 220/460V
Rated impulse withstand voltage, Uimp 6kV
EBN103c
Wiring system 2-pole(2-sensor) 1∅2W
3-pole(3-sensor) 1∅2W, 1∅3W, 3∅3W
4-pole(3-sensor) 1∅2W, 1∅3W, 3∅3W, 3∅4W

Rated short-circuit breaking N-Type


capacity, Icu AC 460V 18kA
IEC 60947-2 (lcu) 415V 18kA
lcs=100%Icu 220/250V 35kA

Protective function Overload, Short-circuit and Ground fault


Type of trip unit Thermal-Magnetic
Magnetic trip range 12×In
Endurance Mechanical 25000 operations
Electrical 10000 operations
Connection Standard Front connection
Optional Rear connection
Plug-in
Mounting Standard Screw fixing

Dimensions (mm) Pole 2p 3p 4p


d
c2
a 75 75 100
a c1
b 130 130 130
c1 Note) 60 60 60
b

c2 Note) 64 64 64
For more information d 82 82 82
�Drawings ▶ 100 page Weight, kg Standard 0.5 0.7 0.9
�Trip curves ▶ 87 page
Certification Pole 2p 3p 4p
�Accessories ▶ 72 page
�Connection and mounting ▶ 110 page CE marking ○ ○ ○
Note) Depth by door cut size : c1 for large cut, c2 for small cut

60
Ordering types

Breaker types Accessories


EBN type (18kA/460V)
△n: 30mA
Rated residual current, I△
Rated current, In
2-pole 3-pole 4-pole
60 A EBN102c/60/30 EBN103c/60/30 EBN104c/60/30
75 A EBN102c/75/30 EBN103c/75/30 EBN104c/75/30
100 A EBN102c/100/30 EBN103c/100/30 EBN104c/100/30

Electrical auxiliaries
△n: 100/200/500mA
Rated residual current, I△
Rated current, In
2-pole 3-pole 4-pole AX Auxiliary Switch
60 A EBN102c/60/100 EBN103c/60/100 EBN104c/60/100 AL Alarm Switch R T
75 A EBN102c/75/100 EBN103c/75/100 EBN104c/75/100 AX+AL Combination switch
100 A EBN102c/100/100 EBN103c/100/100 EBN104c/100/100
Maximum possibilities
T-position Not available
R-position Option of AX or AL or AX+AL
Note) For more detail see 72 page

External accessories
EBN100c Name

IB13 Insulation barrier


TCL13 Terminal cover (Long)
TCS13 Terminal cover (Short)
DH100 Rotary handle (Direct)
DHK100 Rotary handle (Direct, Key lock)
EH100 Rotary handle (Extended)
RTB1 Rear terminal (Bar)
RTR1 Rear terminal (Round)
PB-A3 Plug-in kit
PHL100 Pad handle lock
Note) For more detail see 80 page

61
125AF ELCB
EBS125c, EBH125c

Ratings

Frame size 125AF


Type and Pole S-Type H-Type
2-pole(2-sensor) - -
3-pole(3-sensor) EBS103c EBH103c
4-pole(3-sensor) EBS104c EBH104c
Rated current, In 15-20-30-40-50-60-75-100-125A
Rated residual current, I△n 30, 100/200/500mA (Adjustable)
Residual current off-time at I△n ≤0.1 sec
Rated operational voltage, Ue AC: 220/460V
Rated impulse withstand voltage, Uimp 6kV

EBS103c Wiring system 2-pole(2-sensor) -


3-pole(3-sensor) 1∅2W, 1∅3W, 3∅3W
4-pole(3-sensor) 1∅2W, 1∅3W, 3∅3W, 3∅4W

Rated short-circuit breaking S-Type H-Type


capacity, Icu AC 460V 37kA 50kA
IEC 60947-2 (lcu) 415V 37kA 50kA
lcs=100%Icu 220/250V 85kA 100kA

Protective function Overload, Short-circuit and Ground fault


Type of trip unit Thermal-Magnetic
Magnetic trip range 12×In (30A and under: 400A)
Endurance Mechanical 25000 operations
Electrical 10000 operations
EBH103c Connection Standard Front connection
Optional Rear connection
Plug-in
Mounting Standard Screw fixing

Dimensions (mm) Pole 3p 4p 3p 4p


d
c2
a 90 120 90 120
a c1
b 155 155 155 155
c1 Note) 60 60 60 60
b

c2 Note) 64 64 64 64
For more information d 82 82 82 82
�Drawings ▶ 101 page Weight, kg Standard 1 1.2 1 1.2
�Trip curves ▶ 88 page
Certification Pole 3p 4p 3p 4p
�Accessories ▶ 72 page
�Connection and mounting ▶ 110 page CE marking ○ ○ ○ ○
Note) Depth by door cut size : c1 for large cut, c2 for small cut

62
Ordering types

Breaker types Accessories


EBS type (37kA/460V)
Rated residual current, Rated residual current,
Rated
△n: 30mA
I△ △n: 100/200/500mA
I△
current, In
3-pole 4-pole 3-pole 4-pole
15 A EBS103c/15/30 EBS104c/15/30 EBS103c/15/100 EBS104c/15/100
20 A EBS103c/20/30 EBS104c/20/30 EBS103c/20/100 EBS104c/20/100
30 A EBS103c/30/30 EBS104c/30/30 EBS103c/30/100 EBS104c/30/100
40 A
Electrical auxiliaries
EBS103c/40/30 EBS104c/40/30 EBS103c/40/100 EBS104c/40/100
50 A EBS103c/50/30 EBS104c/50/30 EBS103c/50/100 EBS104c/50/100 AX Auxiliary Switch
60 A EBS103c/60/30 EBS104c/60/30 EBS103c/60/100 EBS104c/60/100 AL Alarm Switch R T
75 A EBS103c/75/30 EBS104c/75/30 EBS103c/75/100 EBS104c/75/100 AX+AL Combination switch
100 A EBS103c/100/30 EBS104c/100/30 EBS103c/100/100 EBS104c/100/100
125 A EBS103c/125/30 EBS104c/125/30 EBS103c/125/100 EBS104c/125/100 Maximum possibilities
T-position Not available
EBH type (50kA/460V) R-position Option of AX or AL or AX+AL
Rated residual current, Rated residual current, Note) For more detail see 72 page
Rated
△n: 30mA
I△ △n: 100/200/500mA
I△
current, In
3-pole 4-pole 3-pole 4-pole
15 A EBH103c/15/30 EBH104c/15/30 EBH103c/15/100 EBH104c/15/100
20 A EBH103c/20/30 EBH104c/20/30 EBH103c/20/100 EBH104c/20/100
30 A EBH103c/30/30 EBH104c/30/30 EBH103c/30/100 EBH104c/30/100
40 A EBH103c/40/30 EBH104c/40/30 EBH103c/40/100 EBH104c/40/100
50 A EBH103c/50/30 EBH104c/50/30 EBH103c/50/100 EBH104c/50/100
60 A EBH103c/60/30 EBH104c/60/30 EBH103c/60/100 EBH104c/60/100
75 A EBH103c/75/30 EBH104c/75/30 EBH103c/75/100 EBH104c/75/100
100 A EBH103c/100/30 EBH104c/100/30 EBH103c/100/100 EBH104c/100/100
125 A EBH103c/125/30 EBH104c/125/30 EBH103c/125/100 EBH104c/125/100 External accessories
EBS125c
Name
EBH125c

IB23 Insulation barrier


TCL23 Terminal cover (Long)
TCS23 Terminal cover (Short)
DH125 Rotary handle (Direct)
DHK125 Rotary handle (Direct, Key lock)
EH125 Rotary handle (Extended)
RTB2 Rear terminal (Bar)
RTR2 Rear terminal (Round)
PB-C3 Plug-in kit
PHL125 Pad handle lock
Note) For more detail see 80 page

63
250AF ELCB
EBN250c, EBS250c, EBH250c

Ratings

Frame size 250AF


Type and Pole N-Type S-Type H-Type
2-pole(2-sensor) EBN202c - -
3-pole(3-sensor) EBN203c EBS203c EBH203c
4-pole(3-sensor) - EBS204c EBH204c
Rated current, In 100-125-150-175-200-225-250A
Rated residual current, I△n 30, 100/200/500mA (Adjustable)
Residual current off-time at I△n ≤0.1 sec
Rated operational voltage, Ue AC: 220/460V
Rated impulse withstand voltage, Uimp 6kV
EBN203c
Wiring system 2-pole(2-sensor) 1∅2W
3-pole(3-sensor) 1∅2W, 1∅3W, 3∅3W
4-pole(3-sensor) 1∅2W, 1∅3W, 3∅3W, 3∅4W

Rated short-circuit breaking N-Type S-Type H-Type


capacity, Icu AC 460V 26kA 37kA 50kA
IEC 60947-2 (lcu) 415V 26kA 37kA 50kA
lcs=100%Icu 220/250V 65kA 85kA 100kA

Protective function Overload, Short-circuit and Ground fault


Type of trip unit Thermal-Magnetic
Magnetic trip range 12×In
EBS203c
Endurance Mechanical 20000 operations
Electrical 5000 operations
Connection Standard Front connection
Optional Rear connection
Plug-in
Mounting Standard Screw fixing

Dimensions (mm) Pole 2p 3p 3p 4p 3p 4p


d
c2
a 105 105 105 140 105 140
a c1
b 165 165 165
c1 Note) 60 60 60
b

c2 Note) 64 64 64
For more information d 87 87 87
�Drawings ▶ 102 page Weight, kg Standard 1.1 1.2 1.2 1.5 1.2 1.5
�Trip curves ▶ 89 page
Certification Pole 2p 3p 3p 4p 3p 4p
�Accessories ▶ 72 page
�Connection and mounting ▶ 110 page CE marking ○ ○ ○
Note) Depth by door cut size : c1 for large cut, c2 for small cut

64
Ordering types

Breaker types Accessories


EBN type (25kA/460V)
Rated residual current, Rated residual current,
Rated
△n: 30mA
I△ △n: 100/200/500mA
I△
current, In
2-pole 3-pole 2-pole 3-pole
100 A EBN202c/100/30 EBN203c/100/30 EBN202c/100/100 EBN203c/100/100
125 A EBN202c/125/30 EBN203c/125/30 EBN202c/125/100 EBN203c/125/100
150 A EBN202c/150/30 EBN203c/150/30 EBN202c/150/100 EBN203c/150/100
Electrical auxiliaries
175 A EBN202c/175/30 EBN203c/175/30 EBN202c/175/100 EBN203c/175/100
200 A EBN202c/200/30 EBN203c/200/30 EBN202c/200/100 EBN203c/200/100 AX Auxiliary Switch
225 A EBN202c/225/30 EBN203c/225/30 EBN202c/225/100 EBN203c/225/100 AL Alarm Switch R T
250 A EBN202c/250/30 EBN203c/250/30 EBN202c/250/100 EBN203c/250/100 AX+AL Combination switch

EBS type (37kA/460V) Maximum possibilities

Rated residual current, Rated residual current, T-position Not available


Rated R-position Option of AX or AL or AX+AL
△n: 30mA
I△ △n: 100/200/500mA
I△
current, In Note) For more detail see 72 page
3-pole 4-pole 3-pole 4-pole
100 A EBS203c/100/30 EBS204c/100/30 EBS203c/100/100 EBS204c/100/100
125 A EBS203c/125/30 EBS204c/125/30 EBS203c/125/100 EBS204c/125/100
150 A EBS203c/150/30 EBS204c/150/30 EBS203c/150/100 EBS204c/150/100
175 A EBS203c/175/30 EBS204c/175/30 EBS203c/175/100 EBS204c/175/100
200 A EBS203c/200/30 EBS204c/200/30 EBS203c/200/100 EBS204c/200/100
225 A EBS203c/225/30 EBS204c/225/30 EBS203c/225/100 EBS204c/225/100
250 A EBS203c/250/30 EBS204c/250/30 EBS203c/250/100 EBS204c/250/100
External accessories
EBH type (50kA/460V) EBN250c
EBS250c Name
Rated residual current, Rated residual current, EBH250c
Rated
△n: 30mA
I△ △n: 100/200/500mA
I△
current, In IB23 Insulation barrier
3-pole 4-pole 3-pole 4-pole
TCL33 Terminal cover (Long)
100 A EBH203c/100/30 EBH204c/100/30 EBH203c/100/100 EBH204c/100/100
TCS33 Terminal cover (Short)
125 A EBH203c/125/30 EBH204c/125/30 EBH203c/125/100 EBH204c/125/100
DH250 Rotary handle (Direct)
150 A EBH203c/150/30 EBH204c/150/30 EBH203c/150/100 EBH204c/150/100
DHK250 Rotary handle (Direct, Key lock)
175 A EBH203c/175/30 EBH204c/175/30 EBH203c/175/100 EBH204c/175/100
EH250 Rotary handle (Extended)
200 A EBH203c/200/30 EBH204c/200/30 EBH203c/200/100 EBH204c/200/100
RTB3 Rear terminal (Bar)
225 A EBH203c/225/30 EBH204c/225/30 EBH203c/225/100 EBH204c/225/100
RTR3 Rear terminal (Round)
250 A EBH203c/250/30 EBH204c/250/30 EBH203c/250/100 EBH204c/250/100
PB-D3 Plug-in kit
PHL250 Pad handle lock
Note) For more detail see 80 page

65
400AF ELCB
EBN400c, EBS400c, EBH400c, EBL400c

Ratings

Frame size 400AF


Type and Pole N-Type S-Type H-Type L-Type
3-pole(3-sensor) EBN403c EBS403c EBH403c EBL403c
4-pole(3-sensor) EBN404c EBS404c EBH404c EBL404c
Rated current, In 250-300-350-400A
Rated residual current, I△n 30, 100/200/500mA (Adjustable)
Residual current off-time at I△n ≤0.1 sec
Rated operational voltage, Ue 220/460V
Rated impulse withstand voltage, Uimp 6kV

EBS403c Wiring system 3-pole(3-sensor) 1∅2W, 1∅3W, 3∅3W


4-pole(3-sensor) 1∅2W, 1∅3W, 3∅3W, 3∅4W

Rated short-circuit breaking N-Type S-Type H-Type L-Type


capacity, Icu AC 415/460V 37kA 50kA 65kA 85kA
IEC 60947-2 (lcu) 220/250V 50kA 75kA 85kA 125kA
lcs=%Icu 100% 100% 100% 75%

Protective function Overload, Short-circuit and Ground fault


Type of trip unit Thermal-Magnetic
Magnetic trip range 8~12In
Endurance Mechanical 4000 operations
EBL404c
Electrical 1000 operations
Connection Standard Front connection
Optional Rear connection
Plug-in
Mounting Standard Screw fixing

Dimensions (mm) Pole 3p 4p 3p 4p 3p 4p 3p 4p


d a 140 184 140 184 140 184 140 184
c2
a c1
b 257 257 257 257
c1 Note) 109 109 109 109
b

c2 Note) 113 113 113 113


For more information d 145 145 145 145
�Drawings ▶ 103 page Weight, kg Standard 7 8.4 7 8.4 7 7
�Trip curves ▶ 90 page
Certification Pole 3p 4p 3p 4p 3p 3p
�Accessories ▶ 72 page
�Connection and mounting ▶ 110 page CE marking - - - -
Note) Depth by door cut size : c1 for large cut, c2 for small cut

66
Ordering types

Breaker types Accessories


EBN type (25kA/460V)
Rated residual current, Rated residual current,
Rated
△n: 30mA
I△ △n: 100/200/500mA
I△
current, In
3-pole 4-pole 3-pole 4-pole
250 A EBN403c/250/30 EBN404c/250/30 EBN403c/250/100 EBN404c/250/100
300 A EBN403c/300/30 EBN404c/300/30 EBN403c/300/100 EBN404c/300/100
350 A EBN403c/350/30 EBN404c/350/30 EBN403c/350/100 EBN404c/350/100
400 A EBN403c/400/30 EBN404c/400/30 EBN403c/400/100 EBN404c/400/100

EBS type (50kA/460V)


Electrical auxiliaries
Rated residual current, Rated residual current,
Rated Auxiliary Switch
△n: 30mA
I△ △n: 100/200/500mA
I△ AX
current, In Alarm Switch
3-pole 4-pole 3-pole 4-pole AL R T
250 A EBS403c/250/30 EBS404c/250/30 EBS403c/250/100 EBS404c/250/100 SHT Shunt Trip
300 A EBS403c/300/30 EBS404c/300/30 EBS403c/300/100 EBS404c/300/100 UVT Undervoltage trip
350 A EBS403c/350/30 EBS404c/350/30 EBS403c/350/100 EBS404c/350/100
400 A EBS403c/400/30 EBS404c/400/30 EBS403c/400/100 EBS404c/400/100 Maximum possibilities
T-position Not available
EBH type(65kA/460V) R-position Option of 2AX, 2AL and SHT or UVT
Note) For more detail see 73 page
Rated residual current, Rated residual current,
Rated
△n: 30mA
I△ △n: 100/200/500mA
I△
current, In
3-pole 4-pole 3-pole 4-pole
250 A EBH403c/250/30 EBH404c/250/30 EBH403c/250/100 EBH404c/250/100
300 A EBH403c/300/30 EBH404c/300/30 EBH403c/300/100 EBH404c/300/100
350 A EBH403c/350/30 EBH404c/350/30 EBH403c/350/100 EBH404c/350/100
400 A EBH403c/400/30 EBH404c/400/30 EBH403c/400/100 EBH404c/400/100

EBL type(85kA/460V) E-70U N-70

External accessories
Rated residual current, Rated residual current,
Rated IBL400 Insulation barrier
△n: 30mA
I△ △n: 100/200/500mA
I△
current, In T1-43A Terminal cover (Long) - 2, 3pole
3-pole 4-pole 3-pole 4-pole
T1-44A Terminal cover (Long) - 4pole
250 A EBL403c/250/30 EBL404c/250/30 EBL403c/250/100 EBL404c/250/100
N-70 Rotary handle (Direct)
300 A EBL403c/300/30 EBL404c/300/30 EBL403c/300/100 EBL404c/300/100
E-70U Rotary handle (Extended)
350 A EBL403c/350/30 EBL404c/350/30 EBL403c/350/100 EBL404c/350/100
MI-43 Mechanical interlock - 2, 3pole
400 A EBL403c/400/30 EBL404c/400/30 EBL403c/400/100 EBL404c/400/100
MI-44 Mechanical interlock - 4pole
X-402 Rear terminal - 2pole
X-403 Rear terminal - 3pole
X-404 Rear terminal - 4pole
PB-I3-FR Plug-in kit
Note) For more detail see 80 page

67
800AF ELCB
EBN803c, EBS803c, EBL803c

Ratings

Frame size 800AF


Type and Pole 3-pole(3-sensor) N-Type S-Type L-Type
4-pole(3-sensor) EBN803c EBS803c EBL803c
- - -
Rated current, In 500-630-700-800A
Rated residual current, I△n 30, 100/200/500mA (Adjustable)
Residual current off-time at I△n ≤0.1 sec
Rated operational voltage, Ue 220/460V
Rated impulse withstand voltage, Uimp 6 kV
Wiring system 3-pole(3-sensor) 1∅2W, 1∅3W, 3∅3W
EBS803c 4-pole(3-sensor) -

Rated short-circuit breaking N-Type S-Type L-Type


capacity, Icu AC 415/460V 37kA 65kA 85kA
IEC 60947-2 (lcu) 220/250V 50kA 85kA 125kA
lcs=%Icu 100% 100% 75%

Protective function Overload, Short-circuit and Ground fault


Type of trip unit Thermal-Magnetic
Magnetic trip range 8~12In
Endurance Mechanical 2500 operations
Electrical 500 operations
Connection Standard Front connection
Optional Rear connection
Plug-in
Mounting Standard Screw fixing

Dimensions (mm) Pole 3p


d
c2
a 210
a c1
b 280
c1 Note) 109
b

c2 Note) 113
For more information d 145
�Drawings ▶ 104 page Weight, kg Standard 11.5
�Trip curves ▶ 90 page
Certification Pole 3p
�Accessories ▶ 72 page
�Connection and mounting ▶ 110 page CE marking -
Note) Depth by door cut size : c1 for large cut, c2 for small cut

68
Ordering types

Breaker types Accessories


EBN type (37kA/460V)

Rated residual current, △n:


Rated residual current, I△
Rated △n: 30mA
I△ 100/200/500mA
current, In
3p 3p
500 A EBN803c/500/30 EBN803c/500/100
630 A EBN803c/630/30 EBN803c/630/100
700 A EBN803c/700/30 EBN803c/700/100
800 A EBN803c/800/30 EBN803c/800/100

EBS type (65kA/460V)


Electrical auxiliaries
Rated residual current, △n:
Rated residual current, I△
Rated △n: 30mA
I△ 100/200/500mA AX Auxiliary Switch
current, In Alarm Switch
3p 3p AL R T
SHT Shunt Trip
500 A EBS803c/500/30 EBS803c/500/100
UVT Undervoltage trip
630 A EBS803c/630/30 EBS803c/630/100
700 A EBS803c/700/30 EBS803c/700/100
Maximum possibilities
800 A EBS803c/800/30 EBS803c/800/100
T-position Not available
R-position Option of 2AX, 2AL and SHT or UVT
EBL type(85kA/460V)
Note) For more detail see 73 page
Rated residual current, △n:
Rated residual current, I△
Rated △n: 30mA
I△ 100/200/500mA
current, In
3p 3p
500 A EBL803c/500/30 EBL803c/500/100
630 A EBL803c/630/30 EBL803c/630/100
700 A EBL803c/700/30 EBL803c/700/100
800 A EBL803c/800/30 EBL803c/800/100

E-80U N-80

External accessories

IBL800 Insulation barrier


T1-63A Terminal cover (Long) - 2, 3pole
T1-64A Terminal cover (Long) - 4pole
N-80 Rotary handle (Direct)
E-80U Rotary handle (Extended)
MI-83S Mechanical interlock - 2, 3pole
MI-84S Mechanical interlock - 4pole
X-802 Rear terminal - 2pole
X-803 Rear terminal - 3pole
X-804 Rear terminal - 4pole
PB-J3-FR Plug-in kit
Note) For more detail see 80 page

69
1000/1200AF ELCB
EBS1003b, EBS1203b

Ratings

Frame size 1000AF 1200AF


Type and Pole S-Type S-Type
3-pole(3-sensor) EBS1003b EBS1203b
4-pole(4-sensor) - -
Rated current, In 1000A 1200A
Rated residual current, I△n 100/200/500mA (Adjustable)
Residual current off-time at I△n ≤0.1 sec
Rated operational voltage, Ue AC: 460V
Wiring system 3-pole(3-sensor) 1∅2W, 1∅3W, 3∅3W

Rated short-circuit breaking S-Type S-Type


capacity, Icu AC 415/460V 85kA
IEC 60947-2 (lcu) 220/250V 125kA
Protective function Overload, Short-circuit and Ground fault
Type of trip unit Thermal-Magnetic
Magnetic trip range 3~6×In
Endurance Mechanical 2500operations
Electrical 500operations
Connection Standard Front connection
Mounting Standard Screw fixing

Dimensions (mm) Pole 3p


d

a
c2
c1
a 220
b 565
c 105
b

For more information


d 159
�Drawings ▶ 105 page
�Trip curves ▶ 91 page Weight, kg Standard 27.1

70
Ordering types

Breaker types Contact operation for Auxiliary and Alarm Switches


EBS type (85kA/460V ) MCCB ON OFF TRIP

Rated current, In 3p
1000 A EBS1003b/1000/100
AX
1200 A EBS1203b/1200/100

AL

Option of below items for T-position Contact rating for Auxiliary and Alarm Switches
AX1 Auxiliary Switch (1c) AC DC
AL1 Alarm Switch (1c) Voltage Current (A) Voltage Current (A)
AX1+AL1 Auxiliary (1c) + Alarm (1c) Switch R T (V) Resistive load Inductive load (V) Resistive load Inductive load
Note) R-position is not available.
125 20 20 30 6 5
250 20 20 125 0.4 0.05
500 10 5 250 0.2 0.03

71
Accessories

Electrical auxiliaries of 30~250AF

SHT

yz
Shunt Trip

e.x
AX

Auxiliary UVT
Switch
ath Undervoltage
trip

AL
Left-hand seat Right-hand seat
nh
Alarm Switch

AX
Auxiliary
Switch
die

AX+AL
AL
Alarm
Combination switch Switch

Option of connecting AX or AL or AX+AL


This seat is not available for 2-pole breakers.
w.

AX+AL Combination
switch

Option of connecting SHT or UVT


or AX or AL or AX+AL
ww

This seat is not available for ELCB.

Maximum possibilities
ABN100c ABH125c ABH250c EBN100c EBH125c EBH250c
Position Type
2p 3/4p 2p 3/4p 2/3/4p 2/3/4p 3/4p 2/3/4p

AX - 1 - 1 1 1 1 1
Left-hand
AL - 1 - 1 1 1 1 1
seat
AX+AL - 1 - 1 1 1 1 1
AX 1 1 1 1 1 - - -
Right-hand AL 1 1 1 1 1 - - -
seat AX+AL 1 1 1 1 1 - - -
SHT/UVT 1 1 1 1 1 - - -

72
Electrical auxiliaries of 400~800AF

yz
e.x
AL AL

Alarm Switch Alarm Switch

SHT ath SHT

Shunt Trip Shunt Trip


nh
UVT UVT

Undervoltage trip Undervoltage trip


die

AX AX

Auxiliary Switch Auxiliary Switch


w.

Option of connecting Option of connecting


ww

AX or AL or AX+AL SHT or UVT or AX or AL or AX+AL


This seat is not available for 2-pole breakers. This seat is not available for ELCB.

Maximum possibilities
MCCB ELCB
Position Type
(400~800AF) (400~800AF)
AX 2 2
Left-hand
AL 2 2
seat
SHT/UVT 1 1
AX 2 -
Right-hand
AL 2 -
seat
SHT/UVT 1 -

73
Accessories

Combinations of accessories
Left-hand Right-hand Auxiliary switch (AX)
seat seat
Alarm switch (AL) Shunt trip (SHT) / Undervoltage trip (UVT)
Main breaker

Series MCCB (30~250AF) MCCB (400~800AF) MCCB (1000~1200AF)


ABN 53c/54c
ABN 52c ABN 402c/403c/404c
ABN 63c/64c
N-Type ABE 32b ABE 33b ABN 62c ABN 602c/603c/604c -
ABN 103c/104c, ABN 103d/104d
ABN 102c/102d ABN 802c/803c/804c
ABN 202c/203c/204c
ABS 33c/34c ABS 1003b
ABS 32c
ABS 53c/54c ABS 402c/403c/404c ABS 1004b
- - ABS 52c
S-Type ABS 63c/64c ABS 602c/603c/604c ABS 1203b
ABS 62c
ABS 103c/104c ABS 802c/803c/804c ABS 1204b
Type ABS 102c
ABS 202c/203c/204c ABS 1203bE
ABH 53c/54c
ABH 52c
H-Type - - ABH 103c/104c ABH 402c/403c/404c -
ABH 102c
ABH202c/203c/204c
ABL 1003b
ABL 402c/403c/404c
ABL 1004b
L-Type - - - - ABL 602c/603c/604c
ABL 1203b
ABL 802c/803c/804c
ABL 1204b
Pole 2 Pole 3 Pole 2 Pole 2, 3, 4 Pole 2, 3, 4 Pole 3, 4 Pole
AX

AX2

AX3 (4)

AL

AL2

AL3(4)

SHT(UVT)

SHT(UVT)2

AX+AL

AX+AL2

AX+AL3(4)

AX2+AL

AX2+AL2

AX2+AL3(4)

AX3(4)+AL

AX3(4)+AL2

AX3(4)+AL3(4)

AX+SHT(UVT)

74
Left-hand Right-hand Auxiliary switch (AX)
seat seat
Alarm switch (AL) Shunt trip (SHT) / Undervoltage trip (UVT)
Main breaker

Series MCCB (30~250AF) MCCB (400~800AF) MCCB (1000~1200AF)


ABN 53c/54c
ABN 52c ABN 402c/403c/404c
ABN 63c/64c
N-Type ABE 32b ABE 33b ABN 62c ABN 602c/603c/604c -
ABN 103c/104c
ABN 102c ABN 802c/803c/804c
ABN 202c/203c/204c
ABS 33c/34c ABS 1003b
ABS 32c
ABS 53c/54c ABS 402c/403c/404c ABS 1004b
ABS 52c
S-Type - - ABS 63c/64c ABS 602c/603c/604c ABS 1203b
ABS 62c
ABS 103c/104c ABS 802c/803c/804c ABS 1204b
Type ABS 102c
ABS 202c/203c/204c ABS 1203bE
ABH 53c/54c
ABH 52c
H-Type - - ABH 103c/104c ABH 402c/403c/404c -
ABH 102c
ABH202c/203c/204c
ABL 1003b
ABL 402c/403c/404c
ABL 1004b
L-Type - - - - ABL 602c/603c/604c
ABL 1203b
ABL 802c/803c/804c
ABL 1204b
Pole 2 Pole 3 Pole 2 Pole 2, 3, 4 Pole 2, 3, 4 Pole 3, 4 Pole
AX+SHT(UVT)2

AX2+SHT(UVT)

AX2+SHT(UVT)2

AX3(4)+SHT(UVT)

AX3(4)+SHT(UVT)2

AL+SHT(UVT)

AL+SHT(UVT)2

AL2+SHT(UVT)

AL2+SHT(UVT)2

AL3(4)+SHT(UVT)

AL3(4)+SHT(UVT)2

AX+AL+SHT(UVT)

AX+AL+SHT(UVT)2

AX2+AL2+SHT(UVT)

AX2+AL2+SHT(UVT)2

AX3(4)+AL3(4)+SHT(UVT)

AX3(4)+AL3(4)+SHT(UVT)2

75
Combinations of accessories
Left-hand Right-hand
seat seat
Main breaker
Auxiliary switch (AX)
Alarm switch (AL) Shunt trip (SHT) / Undervoltage trip (UVT)

Series ELCB (30~250AF) ELCB (400~800AF) ELCB (1000~1200AF)


EBN 52c/53c/54c
EBN 403c/404c
EBN 63c
N-Type EBN 603c -
EBN 102c/103c/104c
EBN 803c
EBN 202c/203c
EBS 33c/34c
EBS 53c/54c EBS 403c/404c
EBS 1003b
S-Type EBS 63c/64c EBS 603c
EBS 1203b
EBS 103c/104c ABS 803c
Type EBS 203c/204c
EBH 53c/54c
H-Type EBH 53c/54c EBH 403c/404c -
EBH 103c/104c

EBL 403c/404c
L-Type - EBL 603c -
EBL 803c
Pole 3, 4 Pole 3 Pole 3 Pole
AX

AX2

AL

AL2

SHT(UVT)

AX+AL

AX+AL2

AX2+AL

AX2+AL2

Terminal block type AX+SHT(UVT)

AX2+SHT(UVT)

AL+SHT(UVT)

AL2+SHT(UVT)

AX+AL+SHT(UVT)

AX2+AL2+SHT(UVT)

76
Auxiliary and Alarm switch

Auxiliary switch (AX)


Auxiliary switch is for applications requiring remote“ON”and“OFF”indication.
Each switch contains two contacts having a common connection.
One is open and the other closed when the circuit breaker is open, and viceversa.

Alarm switch (AL)


Alarm switches offer provisions for immediate audio or visual indication of a tripped breaker due to overload,
short circuit, shunt trip, or undervoltage release conditions.
They are particularly useful in automated plants where operators must be signaled about changes in the
electrical distribution system. This switch features a closed contact when the circuit breaker is tripped
automatically. In other words, this switch does not function when the breaker is operated manually.
Its contact is open when the circuit breaker is reset.

Combination switch (AX+AL)


It consists of one auxiliary switch (AX) and one alarm switch (AL) in a body to connect into the same position of
the breaker.

Contact (AX+AL)
MCCB ON OFF TRIP

AX

AL

Rating (AX+AL)
Conventional thermal current, Ith 5A

Rated operational current, Ie Current, Ie


Voltage, Ue
Resistive load Inductive load
AC 50/60Hz 125V 5 3
250V 3 2
500V - -
DC 30V 4 3
125V 0.4 0.4
250V 0.2 0.2

77
Accessories

Shunt trip, SHT

The shunt trip opens the mechanism in response to an externally applied voltage signal. The releases include
coil clearing contacts that automatically clear the signal circuit when the breaker has tripped. This is not
available for ELCBs of 30~250AF .

Rating for 30~250AF


Power consumption
Control voltage, Ue
AC (VA) DC (W) mA

AC/DC 12V 0.35 0.36 30


AC/DC 24V 0.64 0.65 27
AC/DC 48V 1.09 1.1 23
AC/DC 60V 1.2 1.22 20
Voltage
AC/DC 100~130V 0.73 0.75 5.8
AC/DC 200~250V 1.21 1.35 5.4
AC 380~450V 1.67 - 3.8
AC 440~500V 1.68 - 3.5
Max.opening time 50ms (max.)
Tightening torque of terminal screw 12 kgf∙cm
Note:
- Range of operational voltage: 0.7 ~ 1.1Vn
- Frequency (Only AC): 45Hz ~ 65Hz

Rating for 400~800AF


Power consumption
Control voltage, Ue
V mA W

AC/DC 24~48 AC 24 14 0.3


AC 100~125/DC 100~110 DC 24 15.4 0.4
AC 200~240/DC 200~220 AC 48 14 0.7
AC 380~460 DC 48 16 0.8
AC 480~550 AC 110 6 0.7
Note: Range of operational voltage DC 110 6.6 0.7
AC: 0.85 ~ 1.1Vn
DC: 0.75 ~ 1.25Vn AC 220 6.8 1.5
DC 200 7.6 1.5
AC 440 4.3 1.9
AC 480 4.4 3.3
AC 550 4.6 2.4

78
Undervoltage release, UVT

The undervoltage release automatically opens a circuit breaker when voltage drops to a value ranging between
20% to 70% of the line voltage. The operation is instantaneous, and after tripping, the circuit breaker cannot be
re-closed again until the voltage returns to 85% of line voltage.
Continuously energized, the undervoltage release must be operating before the circuit breaker can be closed.
This is not available for ELCBs of 30~250AF .

z
- Range of tripping voltage: 0.2 ~ 0.7Vn
- Reset and closing of a breaker is possible when the control voltage is over 0.85Vn

.xy
- Frequency (Only AC): 45Hz ~ 65Hz

Rating for 30~250AF


Power consumption
Control voltage, Ue
the AC (VA) DC (W) mA

AC/DC 24V 0.64 0.65 27


AC/DC 48V 1.09 1.1 23
AC/DC 100~110V 0.73 0.75 5.8
Voltage
AC/DC 200~220V 1.21 1.35 5.4
ha

AC 380~440V 1.67 - 3.8


AC 440~480V 1.68 - 3.5
Max.opening time 50ms (max.)
Tightening torque of terminal screw 12 kgf∙cm
en

Operating Trip 20~70% Vn


voltage range Reset/Closing ≥ 0.85Vn
.di

Rating for 400~800AF


Control voltage, Ue Trip voltage Reset/closing voltage Time rating

AC/DC 48
AC/DC 100~125
∙AC: 85~1.1Vn ∙AC: 0.2~0.7Vn
ww

AC/DC 200~240 Continuous


∙DC: 85~1.25Vn ∙DC: 0.2~0.7Vn
AC 380~440
AC 440~480

Terminal numbering
Auxiliary Switch (AX) Alarm Switch (AL) Shunt Trip (SHT) Undervoltage trip (UVT)

79
Accessories

External accessories

Wide range of external accessories provides user-friendly solution for mounting, cable connection, insulation, safety lock and remote control.

Insulation barrier

Terminal cover

Rear terminal

Breaker
Rotary handle (Direct)

Rotary handle
(Direct, Key lock)

Rear terminal

Plug-in kit Rotary handle


(Extended)

Terminal cover

Insulation barrier

80
Rotary handles
Direct type

The rotary handle operating mechanism is available in either the direct version or in the extended version on the
compartment door. It is always fitted with a compartment door lock and on a request it can be supplied with a
key lock in the open position.

Type
Direct type Breaker type
Direct type Extended type
Direct type (Key lock) MCCB ELCB

ABN50c/60c/100c EBN50c/60c/100c
DH100 DHK100 EH100
ABS30c/50c/60c EBS30c/50c/60c
ABS125c EBS125c
DH125 DHK125 EH125
ABH50c/125c EBH50c/125c
ABN250c, ABS250c EBN250c, EBS250c
DH250 DHK250 EH250
ABH250c EBH250c
N-70 - E-70U ABN/S/H/L400c EBN/S/H/L400c
N-80 - E-80U ABN/S/L800c EBN/S/L800c
Key lock
(30~250AF)

Degree of protections
Type Degree of protection IP degree

Circuit breaker with cover frame The access probe of 1.0mm


IP40
and rotary direct handle diameter shall not penetrate.
Circuit breaker with cover frame and Totally protected against ingress of
IP65
rotary extended handle dust and water jets from any direction
(400~800AF)

Extended type
Type suffix according to the mounting position
S-Type L-Type R-Type
LINE
LOAD LINE LINE LOAD

Extended type
(30~250AF)
LOAD

ON ON

(400~800AF)

81
Accessories

Terminal covers

The terminal covers are applied to the circuit-breaker to prevent accidental contact with live parts and thereby
guarantee protection against direct contacts.
Two types by length are available and provide IP40 degree of protection.

�Short type covers, TCS:


For fixed circuit-breakers with rear terminals and for moving parts of plug-in.
TCS (Short type)

�Long type covers, TCL:


For fixed circuit-breakers with front, front extended, front for cables terminals.

Type Breaker
Pole
Short Type Long Type MCCB ELCB

TBS22 - 2P
ABE30b -
TBS23 - 3P
TCS12 TCL12 2P
TCS13 TCL13 3P ABN50c/60c/100c EBN50c/60c/100c
TCS14L TCL14L 4P Line ABS30c/50c/60c EBS30c/50c/60c
TCL (Long type) TCS14R TCL14R 4P Load
TCS22 TCL22 2P
TCS23 TCL23 3P ABS125c EBS125c
TCS24L TCL24L 4P Line ABH50c/125c EBH50c/125c
TCS24R TCL24R 4P Load
TCS33 TCL33 2/3P
ABN250c, ABS250c EBN250c, EBS250c
TCS34L TCL34L 4P Line
ABH250c EBH250c
TCS34R TCL34R 4P Load
- T1-43A 2, 3P
ABN/S/H/L400c EBN/S/H/L400c
- T1-44A 4P
- T1-63A 2, 3P
ABN/S/L800c EBN/S/L800c
- T1-64A 4P
Note: Terminal covers for 400AF and 800AF MCCBs are in acrylic.

Short type construction Long type construction

82
Insulation barriers

Insulation barrier allows the insulation characteristics between the phases at the connections to be increased.
They are mounted from the front, even with the circuit-breaker already installed, inserting them into the
corresponding slots.
They are incompatible with both the insulating terminal covers.
It is possible to mount the phase separating partitions between two circuit-breakers side by side.

Breaker
Type
MCCB ELCB

ABN50c/60c/100c EBN50c/60c/100c
IB-13
ABS30c/50c/60c EBS30c/50c/60c
ABS125c EBS125c
ABH50c/125c EBH50c/125c
IB-23
ABN250c, ABS250c EBN250c, EBS250c
ABH250c EBH250c

IBL400 ABN/S/H/L400c EBN/S/H/L400c

IBL800 ABN/S/L800c EBN/S/L800c

Insulation barriers for line side are provided as standard.

83
Accessories

Rear connection terminals

Rear connection terminals are used to adapt the circuit breakers to switchboards or
other applications that require rear connection.
There are two kinds of rear connection terminals.

- Flat type
- Round type

Round type terminals

Breaker For 2-pole For 3-pole For 4-pole

ABN100c 50AF RTR1-52 RTR1-53 -


ABN100c 100AF RTR1-102 RTR1-103 RTR1-104
ABH125c RTR2-102 RTR2-103 RTR2-104
ABH250c RTR3-202 RTR3-203 RTR3-204

CL

Flat type terminals

Breaker For 2-pole For 3-pole For 4-pole

ABN100c RTB1-102 RTB1-103 RTB1-104


ABH125c RTB2-102 RTB2-103 RTB2-104
ABH250c RTB3-202 RTB3-203 RTB3-204
AB�
�400c X-402 X-403 X-404
AB�
�800c X-802 X-803 X-804

CL

84
Plug-in devices

Plug-in device makes it possible to extract and/or rapidly replace the circuit breaker without having to touch
connections for ship and important installations.
The plug-in base is the fixed part of the plug-in version of the circuit-breaker.
It will be installed directly on the back plate of panel.
The circuit-breaker is racked out by unscrewing the top and bottom fixing screws.

Normal type Plug-in MCCB


Plug-in base
- MCCB current rating upto 250A
- generally used in switchgears

Double-row type Plug-in MCCB


- For 125AF MCCB
- generally used in branch circuits

Type names of blocks

Breaker Arrangement P lug-in block Remark

Normal PB-A3-FR
Single-row PB-A3-1DB
Plug-in type MCCB ABN100c
(plug-in terminal built) Double-row PB-A3-2DB
Line-only PB-A3-FRL
Normal PB-C3-FR
Single-row PB-C3-1DB
ABH125c
Double-row PB-C3-2DB
Line-only PB-C3-FRL
ABH250c Normal PB-D3-FR
400AF Normal/Line-only PB-I3-FR/PB-I3-FRL

ABH103c plug-in type


800AF Normal PB-J3-FR

Normal Double-row

ABH203c plug-in type

85
Type numbering system

MCCB

AB S 10 3 C M / 100A AX SHT=220V

MCCB Type Ampere Frame Pole Series Application Rated current Accessory Control voltage
of accessory
N N-Type 3 30AF 2 2-pole General AX Auxiliary Switch
-
S S-Type 5 50AF 3 3-pole purpose AL Alarm Switch SHT
H H-Type 6 60AF 4 4-pole Motor SHT Shunt Trip AC/DC 12V
M
L L-Type 10 100/125AF protection Undervoltage AC/DC 24V
UVT
20 225/250AF trip AC/DC 48V
40 400AF Rated current Rotary handle AC/DC 60V
DH
80 800AF (Direct) AC/DC
3A 150A
100 1000AF Rotary handle 100V~130V
5A 175A EH
120 1200AF (Extended) AC/DC
10A 200A
RTR 200V~250V
15A 225A Rear terminal
RTB AC 380V~450V
20A 250A
AC 440V~500V
30A 300A
UVT
40A 350A
AC/DC 24V
50A 400A
AC/DC 48V
60A 500A
AC/DC
75A 630A
100V~110V
100A 700A
AC/DC
125A 800A
200V~220V
150A 1200A
AC 380V~440V
AC 440V~480V

ELCB

EB S 10 3 C / 100A 30mA AX

ELCB Type Ampere Frame Pole Series Rated residual Accessory


current
N N-Type 3 30AF 2 2-pole AX Auxiliary Switch
S S-Type 5 50AF 3 3-pole 30mA AL Alarm Switch
H H-Type 6 60AF 4 4-pole 100/200/500mA Rotary handle
DH
L L-Type 10 100/125AF (Direct)
20 225/250AF Rotary handle
EH
40 400AF Rated current (Extended)
80 800AF RTR
15A 225A Rear terminal
100 1000AF RTB
20A 250A
120 1200AF
30A 300A
40A 350A
50A 400A
60A 500A
75A 630A
100A 700A
125A 800A
150A 1000A
175A 1200A
200A

86
Characteristics curves

Breaker types Compensation curves Rated current: 3~30A (ABE)


MCCB ABE30b
Rated current compensation rate (%)

ABE30b

Min.
Ambient temp. 40℃
Max.

Operational time
Min.

Breaker types Compensation curves


Sec.

MCCB ABN/S, EBN/S


Rated current compensation rate (%)

Magnetic trip range


ABN50c/60c/100c/100d
ABS30c/50c/60c
ELCB Max. breaking time

EBN50c/60c/100c
EBS30c/50c/60c
Ambient temp. 40℃ Rated current

Rated current: 3~30A (ABN/S,EBN/S) Rated current: 40~100A (ABN/S,EBN/S)


Min.
Min.

Max. Max.
Operational time
Operational time

Min. Min.
Sec.
Sec.

Magnetic trip range Magnetic trip range

Max. breaking time Max. breaking time

Rated current Rated current

87
Characteristics curves

Breaker types Rated current: 15~30A, 40~100A


MCCB
ABS125c
ABH50c/125c

Min.
ELCB
EBS125c
EBH50c/125c

Max.

Operational time

Min.
Sec.

Magnetic trip range

Max. breaking time

Rated current

Compensation curves Rated current: 125A


Rated current: 15~100A
Rated current compensation rate (%)

Min.

Max.
Operational time

Ambient temp. 40℃

Min.

Rated current: 125A


Sec.
Rated current compensation rate (%)

Magnetic trip range

Max. breaking time

Rated current
Ambient temp. 40℃

88
Breaker types Rated current: 100~225A
MCCB
ABN250c, ABS250c
ABH250c
ELCB

Min.
EBN250c, EBS250c
EBH250c

Max.

Operational time
Sec. Min.

Magnetic trip range

Max. breaking time

Rated current

Compensation curves Rated current: 250A


Rated current: 100~225A 240
Rated current compensation rate (%)

180
150
150 120
100
80
60
40
Min.

20
100
10
8
6
4

2
50
0 10 20 30 40 50 Max.
1
Operational time

Ambient temp. 40℃ 40

20

10
8
6 Min.
4

Rated current: 250A 2


Rated current compensation rate (%)

Sec.

150 1
0.8
0.6
0.4
Magnetic trip
0.2
range
(960~1440%)
100
0.1
0.08
0.06
0.04
Max. breaking time

0.02
50
0 10 20 30 40 50 0.01
1 1.5 2 3 4 5 6 7 8 9 10 15 20 30 40 50 60 80 100
Ambient temp. 40℃
Rated current

89
Characteristics curves

Breaker types Rated current: 250~400A


MCCB
ABN400c, ABS400c, ABH400c, ABL400c
ABN800c, ABS800c, ABL800c
ELCB

Min.
EBN400c, EBS400c, EBH400c, EBL400c
EBN800c, EBS800c, EBL800c
Max.

Operational time

Min.
Sec.

Magnetic trip range

Max. breaking time

Rated current

Compensation curves Rated current: 500~800A


Rated current: 250~400A
Rated current compensation rate (%)

240
180
150
120

60
40
Min.

20
100
10
8
6
4
Max.
2
50
0 10 20 30 40 50
1
Operational time

Ambient temp. 40℃ 40

20

10
8
6
Min.
4

2
Rated current: 500~800A
Rated current compensation rate (%)

150
Sec.

1
0.8
0.6
0.4

0.2
Magnetic trip range
100 0.1
0.08 (800~1200%)
0.06
0.04 Max. breaking time
0.02

50
0.01
0 10 20 30 40 50
1 1.25 2 3 4 5 6 7 8 9 10 15 20 30 40 50 70 100

Ambient temp. 40℃ Rated current

90
Breaker types Rated current: 1000~1200A
MCCB
ABS1000b, ABL1000b
ABS1200b, ABL1200b
ELCB

Min.
EBS1003b, EBS1203b
Max.

Min. Rated Ranges of instantaneous trip


current
Min Max

Operational time
Compensation curves
Rated current: 1000~1200A
Rated current compensation rate (%)

Sec.

Max. breaking time

Ambient temp. 40℃

Rated current

Breaker types Rated current: 1200A


MCCB
ABS1200bE
Hou.
Min.
Operational time
Sec.

Rated current

91
Dimensions

MCCB
ABE30b

Terminal cover
Insulation barrier Insulation
Terminal cover barrier
Terminal cover
Fixing hole

DIN-Rail

Trip test button Trip test button

2P 3P

Terminal details

Panel drilling Front panel cutting

(Screw) (Screw)

(Holder) (Holder)
3P 3극

92
MCCB ABN50c ABS30c
ABN60c ABS50c
ABN100c ABS60c

25 25 25 56

Insulation barrier Insulation barrier Insulation barrier

50
50

50

∅7.4
50

∅4.5
22 22 22
115
130

115
130

115
130
50
84

50
84

50
84
19
19

19
13.3 13.3 13.3

58
25 50 25
Trip test button Trip test button Trip test button 60
50 75 75
64
100
68
2P 3P 4P 82

Terminal details Connecting


8.2

12.5

M5×14
5

9
5.


15
7.5

18 24 7 7

(≤ 50A) (≤ 50A) (≥60A)


8.2

M8×14
7.5

18 24

(≥60A)

Panel drilling Front panel cutting


M4 or ∅5 M4 or∅5 M4 or∅5
110.5

110.5

110.5

52

52

52

25 25 52 77 102

2P 3P 4P 2P 3P 4P

93
Dimensions

MCCB ABS125c ABH50c


ABH125c

30 30 30

Insulation barrier Insulation barrier Insulation barrier

80
80

80

50
50

Fixing hole Fixing hole


50
Fixing hole

5
50

8.2
22 22 22
16.5

16.5
16.5

155

155

155
135
100
135
100

135
100
50

50
50

37 37 37

4
8
8

30 60 30 58
10

10

10

Trip test button Trip test button Trip test button 8 60


60 90 90
120 82

2P 3P 4P

Terminal details Connecting

M8×14
8

9

16

18 24 8
10

Panel drilling Front panel cutting


M4 or∅5 M4 or∅5 M4 or∅5
132
132

52

52

52
132

30 30 62 92 122

2P 3P 4P 2P 3P 4P

94
MCCB ABN250c ABS250c ABH250c

56
Insulation barrier
Insulation barrier

80
80

Fixing hole Fixing hole


CL CL

∅8.2

∅4.5
22 47
22

14.5 14.5

102
126
144
165
59.4
59.4

102
126
144
165

CL CL
50
50

19.6
19.6

44.5 44.5

Trip test button Trip test button

35 35 35
60
70 70 35
64
105 140
68.5

2,3P 4P 86.85

Terminal details Connecting


M8×20
9

21

25

28 24 10

Panel drilling Front panel cutting


M4 or∅5 M4 or∅5
CL CL CL CL

CL CL CL
126
126

52
52

53.5
35 35 35 107 142

2,3P 4P 2,3P 4P

95
Dimensions

MCCB ABN400c ABS400c ABH400c ABL400c

56.5 56.5 56.5 56.5 52.5 52.5 52.5

44 44 44 44 44
Fixing hole Fixing hole Fixing hole 45
.5

.5
12

12


41.5
41.5
26.5

26.5

52.5 52.5 52.5

48
48

48
257
225
215
150

257
225
215
150

257
225
215
150
41

41

41
48

48

48
25 95
51 Trip test button Trip test button Trip test button
51 109
140 140 184 113
145
2P 3P 4P

Terminal details Connecting

30 M10×L30 37 .5
10

29.5
13

29

12.5

112
Panel drilling 111 Front panel cutting
97
"A" (Handle only) "B" (Handle and name plate) "C" (Handle, name plate & button)
CL M6 or∅6 CL M6 or∅6 CL CL CL
Slot "A"

CL CL CL CL CL CL
215

215

100

100

152

Slot "B"

Slot "C"
44 44 53 142(3p) 142(3p)
187(4p) 187(4p)

2, 3P 4P 2, 3, 4P 3, 4P 3, 4P

96
MCCB ABN800c ABS800c ABL800c

210 210 280

70 70 70 41.5
44 44 t
15

15
32
32

13.5
70

70
8
8

56 56 56

∅8
53 53 53
25

25

25
280

280
243
150

243

280
150

243
150
96

96

96
70

70

70 70 Trip test button 70 70 Trip test button 70 70 70 Trip test button 95


109
113
2P 3P 4P 145

600AF : 7t
800AF : 10t

Connecting
Terminal details

44 M12×35 34.5 14

44
29
11

10.5

Panel drilling 112 Front panel cutting


111
97

"A" (Handle only) "B" (Handle and name plate) "C" (Handle, name plate & button)
M6 M6
CL CL CL

Slot "A"
243

243

100

152
100

Slot "B"

Slot "C"
70 70 70 59 212(3p) 212(3p)
282(4p) 282(4p)
2, 3P 4P 2, 3, 4P 3, 4P 3, 4P

97
Dimensions

MCCB ABS1000b ABL1000b


ABS1200b ABL1200b

Mounting hole Mounting hole

Auxiliary handle

3P 4P

Panel drilling Front panel cutting

or or

3P 4P 3P 4P

98
ELCB
ABS1203bE

Mounting hole

Auxiliary handle

Panel drilling Front panel cutting

or

99
Dimensions

ELCB EBN50c EBS30c


EBN60c EBS50c
EBN100c EBS60c

56
25 Insulation barrier 25 25
Insulation barrier

50
50

∅7.4
Trip indication Trip indication
by earth fault by earth fault 50

∅4.5
Residual current Residual current
2.2

(I△n) setting (I△n) setting


115
130

84
50

130
115
84
50

29.2 29.2
19

19
Trip test button Trip test button
13.3 for earth fault 13.3 for earth fault

22 Trip test button 25 Trip test button


58
50 75
75 100 60
64
2,3P 4P
66.5

68

82
Terminal details Connecting
8.2

M5×14
5

9
5.



12.5

15
7.5

18 24
7 7

(≤ 50A) (≤ 50A) (≥60A)


8.2

M8×14

18 24
7.5

(≥60A)

Panel drilling Front panel cutting

M4 or∅5 M4 or∅5
110.5

110.5

52

52

25
25 77 102
50

2, 3P 4P 2, 3P 4P

100
ELCB EBS125c EBH50c
EBH125c

30 30

Insulation barrier Insulation barrier

80
80
50

50
Fixing hole Fixing hole

5
Trip indication Trip indication 50

8.2
22 22 by earth fault
by earth fault
37.8 37.8
Residual current Residual current
(I△n) setting
16.5

(I△n) setting

16.5
100

100
50

50
155

135

155
135
4.7

4.7
37
2.5
Trip test button
Trip test button for earth fault 4
for earth fault
8

Trip test button


Trip test button
60 58
30
10

10

8 60
90 90
82
120

3P 4P

Terminal details Connecting


8

M8×14
9

16

18 24 8
10

Panel drilling Front panel cutting


M4 or∅5 M4 or∅5
52
132
132

52

30 30 92 122
60

3P 4P 3P 4P

101
Dimensions

ELCB EBN250c EBS250c EBH250c

56

Insulation barrier Insulation barrier


80

80
Fixing hole Fixing hole

Trip indication Trip indication


by earth fault by earth fault

∅4.5
22 22

∅8.2
47
Residual current Residual current
(I△n) setting (I△n) setting
14.5 14.5
CL
59.4

59.4
165
144
126
102

165
144
126
102
50

50

7
7

19.6
19.6

Trip test button Trip test button


44.5 for earth fault 44.5 for earth fault

Trip test button Trip test button

35 35 35 60
70 105 35 64
105 140 66.5

2, 3P 4P 68.5
86.85
Terminal details Connecting
10
∅9

M8×20
21

25

28 24

Panel drilling Front panel cutting


CL M4 or∅5 CL M4 or∅5 CL CL
126

126

CL CL CL CL
52

52

53.5
35 35 35 107 142

2, 3P 4P 2, 3P 4P

102
ELCB EBN400c EBS400c EBH400c EBL400c

56.5 56.5 52.5 52.5 52.5


44 44
44 44 44 45
.5

8
12

41.5
26.5

Trip indication Trip indication


by earth fault by earth fault

57.9 57.9
48

48
46.9 46.9
16.5 23.9

23.9
257
225
215
150

257
225
215
150
41.4

41.4
48

48
Trip test button 16.5 Trip test button
for earth fault for earth fault
Residual current Residual current
(I△n) setting (I△n) setting

25 Trip test button Trip test button


95
51.1 184 109
140
113
3P 4P 145

Terminal details Connecting

30 37 .5
M10×L30 10

29.5
13

29

12.5

112
111
Panel drilling 97 Front panel cutting
"A" (Handle only) "B" (Handle and name plate) "C" (Handle, name plate & button)
CL M6 or∅6 CL M6 or∅6 CL CL CL

Slot "A"

CL CL CL CL CL CL
215

215

100

100

152

Slot "B"

Slot "C"
44 44 53 142(3p) 142(3p)
187(4p) 187(4p)
2, 3P 4P 2, 3, 4P 3, 4P 3, 4P

103
Dimensions

ELCB EBN800c EBS800c EBL800c

210
44.5
70
t
44
15

∅13.5
32

70
8

∅8
56 Trip indication by earth fault

Trip test button for earth fault


90.6
280

77.6

280
243

150

96

25

23.9
17
16.5

54.1
Residual current (I△n) setting

Trip test button


70

70 70 95
109
3P 113
145

600AF : 7t
800AF : 10t
Terminal details Connecting

44 M12×35 34.5 14

44
29
11

10.5

112
111
97
Panel drilling Front panel cutting
"A" (Handle only) "B" (Handle and name plate) "C" (Handle, name plate & button)
M6 CL CL CL

Slot "A"
243

100

100

152

Slot "B"

Slot "C"
70 59 212 212

3P

104
ELCB EBS1000b
EBS1200b

Mounting hole

Auxiliary handle

Reset

Trip test button

Trip test button


for earth fault

3P

Panel drilling Front panel cutting

60

3P 3P

105
Dimensions

Rear connection terminals

Bar type

B
A
L

D

E E E

MCCB A B C D E

ABN100c 115 37 87 ∅8.5 25


ABH125c 135 37 87 ∅8.5 30
ABH250c 144 57.5 93.5 ∅8.5 35
ABS400c 225 72 - ∅14 44
ABS800c 243 108.7 - ∅14 70

Round type

C
A

L
B
C

E E E

MCCB A B C D E

ABN100c 50AF 115 42 92 M6 25


ABN100c 100AF 115 52 102 M8 25
ABH125c 135 52 102 M8 30
ABH250c 144 70 106 M8 35

106
Rotary handles

Direct mounting type (D-Handle, 30~250AF)

t1.2~3.2
4-∅5
A

D
E
60
104 B
C

Type A (mm) B (mm) C (mm) D (mm) E (mm) Remarks

DH100 110.5 78 90 92 103.4 100AF


DH125 132 94 105 108 120 125AF
DH250 126 108 121 110 122 250AF

Direct mounting type (N-Handle, 400~800AF)

E-70, N-80
150

t1.2~3.2
75
113

51

107
Dimensions

Rotary handles

Extended mounting type (E-Handle) (30~250AF)

t1.2~3.2
2-∅6

B
B

Type A (mm) B (mm) C (mm) Remarks

EH100 min 150, max 573.5 (SHAFT469mm) 47 ∅53 100AF


EH125 min 150, max 573.5 (SHAFT469mm) 47 ∅53 125AF
EH250 min 150, max 571.5 (SHAFT469mm) 47 ∅53 250AF

Extended mounting type (N-Handle, 400~800AF)

E-70U (400AF)

E-80U (800AF)

108
Technical Information

Standard accessories

The following accessories for mounting, connection and insulation are standard
items and are packed with Metasol series circuit breakers.

Item ABN100c ABH125c ABH250c 400AF 800AF

Fixing
screw

2P: 2EA (M4×60) 2P: 2EA (M4×60) 2P: 2EA (M4×55) 2P: 2EA (M6×100) 2P: 2EA (M6×100)
3P: 2EA (M4×60) 3P: 2EA (M4×60) 3P: 4EA (M4×55) 3P: 4EA (M6×100) 3P: 4EA (M6×100)
4P: 4EA (M4×60) 4P: 4EA (M4×60) 4P: 4EA (M4×55) 4P: 4EA (M6×100) 4P: 4EA (M6×100)

Terminal 15~30A
bolt 2P: 4EA (M5×14)
3P: 6EA (M5×14)
2P: 4EA (M8×14) 2P: 4EA (M8×20) 2P: 4EA (M10×30) 2P: 2EA (M12×35)
4P: 8EA (M5×14)
3P: 6EA (M8×14) 3P: 6EA (M8×20) 3P: 6EA (M10×30) 3P: 6EA (M12×35)
40~100A
4P: 8EA (M8×14) 4P: 8EA (M8×20) 4P: 8EA (M10×30) 4P: 8EA (M12×35)
2P: 4EA (M8×14)
3P: 6EA (M8×14)
4P: 8EA (M8×14)

IB-13 IB-23 IB-23

Insulation
barrier

2P: 1EA 2P: 1EA 2P: 1EA 2P: 1EA 2P: 1EA
3P: 2EA 3P: 2EA 3P: 2EA 3P: 2EA 3P: 2EA
4P: 3EA 4P: 3EA 4P: 3EA 4P: 3EA 4P: 3EA

109
Technical Information

Connection

Terminal Tightening torque Conductor


MCCB
(mm) ∙cm)
(kgf∙ (mm)

[3~30A] M5 : 23 ~ 28 [15~30A]
M8 : 55 ~ 75
8.2

M5×14
∅5.5 ∅5.5

18 24
7.5

12.5 12.5
7 7

ABN100c
[40~100A] [40~100A]
8.2

M8×14

∅9 ∅9

18 24
7.5

15 15
7 7

M8 : 55 ~ 75
8

M8×14
∅9 ∅9

ABH125c
16 16
18 24 8 8
10

M8 : 80 ~ 130

M8×20
21

∅9 ∅9
ABH250c
28 24
25 25
10 10

110
Connection

Terminal Tightening torque Conductor


MCCB
(mm) ∙cm)
(kgf∙ (mm)

M10 : 240~300 (Terminal)


M10 : 240~300 (Busbar)

30 37
M10×L30
.5
10

400AF
13

29.5
29

12.5

M12 : 400~500
(Terminal, Busbar)

44 M12×35 34.5 14

44

800AF
29
11

10.5

111
Technical Information

Safety clearance

When installing a circuit breaker, safety clearances must be kept between the breaker and panels, bars and
other protection devices installed nearby. These safety clearances are depend on the ultimate breaking capacity
and are defined by tests carried out in accordance with standard IEC 60947-2.
When a short circuit interruption occur, high temperatures pressures are present in and above the arc chambers
of the circuit-breaker. In order to allow the pressure to be distributed and to prevent fire and arcing or short-
circuit currents, safety clearances are required.

A: Minimum distance to metallic top panels

Frame A(mm)
Description
size 460V 250V

ABN50c 40 25
ABN60c 40 25
ABN100c 50 30
100AF
ABS30c 30 25
ABS50c 40 30
ABS60c 40 30
ABS125c 50 40
125AF ABH50c 50 40
ABH125c 100 80
ABN250c 100 80
250AF ABS250c 100 80
ABH250c 100 80
A

A
ABN400c 100 80
F

ABS400c 100 80
400AF
ABH400c 100 80
ABL400c 100 80
ABN800c 100 80
800AF ABS800c 100 80
ABL800c 100 80

112
B: Minimum distance between the lower and the upper breakers
�C1: Minimum distance between the lower breaker and the bare terminal of the upper breaker
�C: C1+ the dimension of bare part of conductor

Frame C1 (mm)
Description C (mm)
size 460V 250V

ABN50c 40 25
ABN60c 40 25
ABN100c 50 30
100AF ABS30c 30 25
ABS50c 40 30
ABS60c 40 30
ABS125c 50 40 The dimension of bare conduct + C1

125AF ABH50c 50 40
ABH125c 100 80
ABN250c 100 80
250AF ABS250c 100 80
ABH250c 100 80
ABN400c 100 80

C
C

C
C1

ABS400c 100 80
C1

C1
400AF
ABH400c 100 80
ABL400c 100 80
ABN800c 100 80
800AF ABS800c 100 80
ABL800c 100 80
Direct Connection Connection
connection by using a by using a
of cable crimp-type crimp-type
terminal lug terminal lug to
the extended
terminal

113
Technical Information

Safety clearance

Insulated length of main terminal of circuit breaker


�D1: Connection by solerless terminal with taping
�D2: Connection by busbar with taping
�D3: Connection by solderless terminal and using insulation barrier
�D4: Connection by busbar and using insulation barrier

Frame D1 D2 D3 D4
Description
size (mm) (mm) (mm) (mm)

ABN50c 40 40
ABN60c 40 40
ABN100c 50 50
100AF ABS30c 30 30
ABS50c 40 40
ABS60c 40 40
The dimension of bare conduct + 20

The dimension of bare conduct + 20

ABS125c 50 50
125AF ABH50c 50 50
ABH125c 50 50
ABN250c 50 50
250AF ABS250c 50 50
ABH250c 50 50

D4
D3
D1

ABN400c 100 100


D2

ABS400c 100 100


400AF
ABH400c 100 100
ABL400c 100 100
ABN800c 150 150
800AF ABS800c 150 150
ABL800c 150 150

114
Minimum distance to metallic side panels
Frame E(mm)
Description
size 460V 250V

ABN50c 25 15
ABN60c 25 15
ABN100c 25 15
100AF ABS30c 20 15
ABS50c 25 15
ABS60c 25 15
ABS125c 25 15
125AF ABH50c 25 15
ABH125c 50 20 E E

ABN250c 50 15
250AF ABS250c 50 15
ABH250c 50 15
ABN400c 80 40
ABS400c 80 40
400AF
ABH400c 80 40
ABL400c 80 40
ABN800c 80 40
800AF ABS800c 80 40
ABL800c 80 40

115
Technical Information

Safety clearance

Distance of bare cables or busbars


Frame
Description F(mm)
size

ABN50c 10
ABN60c 10
ABN100c -
100AF ABS30c 5
ABS50c 10
ABS60c 10
ABS125c -
125AF ABH50c 10
ABH125c 20
ABN250c -
250AF ABS250c -
ABH250c -
F

ABN400c 10
ABS400c 10
400AF
ABH400c 10
ABL400c 10
ABN800c 10
800AF ABS800c 10
ABL800c 10

116
Minimal distance between two adjacent breakers (With terminal covers)
Frame
Description G(mm)
size

ABN50c 0
ABN60c 0
ABN100c 0
100AF ABS30c 0
ABS50c 0
ABS60c 0
ABS125c 0
125AF ABH50c 0
ABH125c 0
ABN250c 0
G
250AF ABS250c 0
ABH250c 0
ABN400c 0
ABS400c 0
400AF
ABH400c 0
ABL400c 0
ABN800c 0
800AF ABS800c 0
ABL800c 0

117
Technical Information

Standards & Approval

Metasol series circuit breakers and auxiliaries comply with the following
international standard:
�IEC 60947-1
Low-voltage switchgear and controlgear - Part 1: General rules

�IEC 60947-2
Low-voltage switchgear and controlgear - Part 2: Circuit-breakers

The following certificates are available on a request.


�CE Declaration of conformity
�Certificate of conformance test (CB) - IEC 60947
�Full type test report issued by KEMA

CE conformity marking
The CE conformity marking shall indicate conformity to all the obligations imposed on the
manufacturer, as regards his products, by virtue of the European Community directives providing
for the affixing of the CE marking.
When the CE marking is affixed on a product, it represents a declaration of the manufacturer or of
his authorized representative that the product in question conforms to all the applicable provisions
including the conformity assessment procedures.

118
Standard Use Environment

Standard Use Environment for Molded Case Circuit Breaker


The operation characteristic of Molded Case Circuit Breaker including short-circuit, overload, endurance and
insulation is often influenced largely by external environment and thus should be applied appropriately with
conditions of the place where it is used taken into consideration. In particular, the operation characteristic of the
circuit breaker with a thermal magnetic trip element (FTU, FMU, ATU) applied changes a bit with the ambient
temperature so you have to adjust the value of power rating accordingly when it is actually in use.

1) Ambient Temperature: Within the range of -5℃~+40℃ (However, the average for the duration of 24 hours
must not exceed 35℃.)
2) Relative Humidity: Within the range of 45~85%
3) Altitude: 2,000m or less (However, if it exceeds 1,000m, atmosphere correction through humidity test and
withstand voltage test can be considered.)
4) Atmosphere where excessive steam, oil steam, smoke, dust, salt and other corrosive materials do not exist

■ If a standard circuit breaker is used in high temperature


exceeding 40℃, you are advised to use it according to the
current corrected for each level of ambient temperature in
catalog.
■ If used in conditions of highly humidity, the dielectric strength or
electric performance may be degraded.

■ There is no problem in conduction switch, trip or short circuit


isolation in the temperature of -20℃.
■ Passing or storage in stone-cold area is allowed in the
temperature of 40℃.
■ The operating characteristic of the breaker with a thermal
magnetic trip element changes as the base ambient
temperature is adjusted to 40℃.

■ It is highly recommended to use a dust cover or anti-humid


agent if it is used in dusty and humid conditions.
■ Excessive vibration may cause a trip break such as connection
fault or flaw on mechanical parts.

■ If it is left ON or OFF for a long time, it is recommended to


switch load current on a regular basis.
■ It is recommend to put it in the sealed protection if corrosive gas
is prevalent.

119
Technical Document

Special Use Environment


Environment where Ambient Temperature Exceeds 40℃
The temperate of each module of a Molded Case Circuit Breaker is the sum of temperature increase by
conduction and ambient temperature and if the ambient temperature exceeds 40℃ the passing current needs
to be reduced so that the temperature of such element as internal insulator of MCCB exceed the maximum
allowable temperature.
The base ambient temperature of Metasol breaker is set as 40℃ so if it has to be used in conditions with higher
temperature than this, the rated current is required to be reduced a little as described in the table below.

Table of Rated Current for Metasol MCCB Corrected


according to Ambient Temperature
Ampere Rated Rated Table of Rated Current Corrected according to Ambient Temperature (A)
Model Name of Breaker
Frame current current 10℃℃ 20℃℃ 30℃℃ 40℃℃ 45℃℃ 50℃℃ 55℃℃

3 3 3 3 3 3 3 3 3
5 5 5 5 5 5 5 5 4
10 10 10 10 10 10 10 9 9
30 ABS30c
15 15 15 15 15 15 15 14 13
20 20 20 20 20 20 19 19 18
30 30 30 30 30 30 29 28 27
40 40 40 40 40 40 39 38 36
50 ABN50c, ABS50c
50 50 50 50 50 50 49 47 45
60 60 ABN60c, ABS60c 60 60 60 60 60 58 56 55
75 75 75 75 75 75 73 71 68
100 ABN100c
100 100 100 100 100 100 97 94 91
125 125 ABH50c, ABS125c, ABH125c 125 125 125 125 125 121 116 107
150 150 150 150 150 150 145 140 128
175 175 175 175 175 175 169 163 150
ABN200c, ABS200c,
250 200 200 200 200 200 200 193 186 171
ABH250c
225 225 225 225 225 225 217 209 193
250 250 250 250 250 250 241 233 214
250 250 250 250 250 250 246 242 238
300 ABN400c, ABS400c 300 300 300 300 300 295 291 287
400
350 ABH400c, ABL400c 350 350 350 350 350 345 339 332
400 400 400 400 400 400 394 388 381
500 500 500 500 500 500 492 485 477
630 ABN800c, ABS800c 630 630 630 630 630 621 611 602
800
700 ABL800c 700 700 700 700 700 689 679 668
800 800 800 800 800 800 788 776 764

120
Table of Rated Current for Metasol ELCB Corrected
according to Ambient Temperature
Ampere Rated Rated Table of Rated Current Corrected according to Ambient Temperature (A)
Model Name of Breaker
Frame current current 10℃℃ 20℃℃ 30℃℃ 40℃℃ 45℃℃ 50℃℃ 55℃℃

15 15 15 15 15 15 15 15 15
30 20 EBS30c 20 20 20 20 20 19 19 18
30 30 30 30 30 30 29 28 27
40 40 40 40 40 40 39 38 36
50 EBN50c, EBS50c
50 50 50 50 50 50 49 47 45
60 60 EBN60c, EBS60c 60 60 60 60 60 58 56 55
75 75 75 75 75 75 73 71 68
100 EBN100c
100 100 100 100 100 100 97 94 91
125 125 EBH50c, EBS125c, EBH125c 125 125 125 125 125 121 116 107
150 150 150 150 150 150 145 140 128
175 175 175 175 175 175 169 163 150
EBN200c, EBS200c,
250 200 200 200 200 200 200 193 186 171
EBH250c
225 225 225 225 225 225 217 209 193
250 250 250 250 250 250 241 233 214
250 250 250 250 250 250 246 242 238
300 EBN400c, EBS400c 300 300 300 300 300 295 291 287
400
350 EBH400c, EBL400c 350 350 350 350 350 345 339 332
400 400 400 400 400 400 394 388 381
500 500 500 500 500 500 492 485 477
630 EBN800c, EBS800c 630 630 630 630 630 621 611 602
800
700 EBL800c 700 700 700 700 700 689 679 668
800 800 800 800 800 800 788 776 764

121
Technical Document

Special Use Environment

℃ or less
Environment where Ambient Temperature is -5℃
Molded Case Circuit Breaker is subject to the effect of low temperature brittle of metal part inside and insulator,
or changes in viscosity of lubricating oil in device, extra care should be taken not to have the temperature drop
extremely with the use of such device as space heater. In addition, in case of using a thermal magnetic trip
element (FTU, FMU, ATU), the operating characteristic changes toward the difficult direction, so you should
identify the relationship of protection and correct accordingly.
Although MCCB is not affected by conduction switch, trip, or short circuit isolation in the temperature of - 20℃, it
is highly recommended to use a temperature maintaining device such as space heater. In addition,
transportation and passing in stone-cold area in the temperature as low as -40℃ is allowed but it is recommend
to leave the status of MCCB off or tripped in order to minimize the effect of brittle due to a low temperature.

High Humidity Condition (Relative Humidity 85% or more)


Using Molded Case Circuit Breaker in a place of high humidity requires a rigorous maintenance including
installation of anti-humidity agent within the structure in order to prevent the insulation sag of insulator or
corrosion of mechanical parts as a result of high humidity. Also, in case of installing MCCB within the enclosed
equipment, a space heater needs to be installed as well to prevent dew condensation that might occur due to a
drastic temperature change.

Environment where Petrochemical Gas Exists


The contact material of Molded Case Circuit Breaker is silver or silver alloy which develops creation of
petrochemical coat that might cause a poor connection if it gets in contact with petrochemical gas.
However, it is easy for petrochemical coat to be mechanically taken off so it is no problem if make-and break
operation occurs frequently but it needs to be switched back and forth between make and break if the operation
rarely occurs.
The lead wire of moving contact of Molded Case Circuit Breaker can be disconnected as it is corroded or
hardened by petrochemical gas. The silver coating is effective to prevent this from occurring and there is a need
to increase durability of MCCB with the use of silver coated lead wire if it is used in environment with thick
petrochemical gas.

Environment where Potentially Explosive Gas Exists


It is advised, in principle, not to install a Molded Case Circuit Breaker that switches and inhibits current in a
dangerous place such as this one.

Impact of Altitude
If an MCCB is used in an elevated area higher than 2000m sea level, its operating performance is subject to
dramatic drop in atmospheric pressure and temperature. For example, the air pressure is reduced to 80% of
ordinary pressure at 2,200m and further 50% at 5,500m although the short-circuit performance is not affected. If
it is used in areas of high sea level, you can do correction based on the correction parameter table in high
altitude environment, as described below.
[Correction Parameter Table for Altitude]
* Refer to the correction parameter table in high altitude Voltage Current
environment (ANSI C37. 29-1970) Altitude Correction Correction
1) How to Correct Voltage: Parameter Parameter
- If the rated voltage is AC 600V at 4,000m above sea level, 2,000m 1.00 1.00
600V (rated voltage) × 0.82 (correction parameter) = 492V. 3,000m 0.91 0.98
2) How to Correct Current: 4,000m 0.82 0.96
- If the rated voltage is AC 800A at above 4,000m sea level, 5,000m 0.73 0.94
800A (rated current) × 0.96(correction parameter) = 768A. 6,000m 0.65 0.92

122
Environment with Vibration and Impulse Exercised

Impact of Vibration and Impulse


An excessive vibration and impulse may cause damage on breaker or other security problems including
dynamic strength. An appropriate consideration is required to select a right MCCB for an adverse environmental
stress such as this one. Moreover, this stress may incur from vibration during transportation, magnetic impulse
while manipulating a switch or may be affected by equipment in surrounding area.
There is a standard call [Vibration Testing Method for Small Electric Appliances] for vibration and impulse test
for electric equipment and the seismic and endurance tests of Molded Case Circuit Breaker are conducted in
accordance with this standard, considering the circumstance mentioned above.

Vibration
The magnitude of vibration is measured by double amplitude and frequency with the following equation with
accelerator.
αg=0.002×frequency(Hz)×double amplitude (mm)
* αg: multiple of gravitational acceleration (g=9.8m/sec2)
There are three types of vibration tests including resonance test, vibration endurance test, and malfunction test
as described below.
1) Resonant Test
Alter the frequency of sinusoidal wave within the range of 0~55Hz gradually with 0.5~1mm of double
amplitude applied to see if there is any occurrence of vibration on a specific part of MCCB.
2) Vibration Endurance Test
A sinusoidal wave with double amplitude of 0.5~1mm and frequency of 55Hz(resonant frequency obtained in
previous clause if there is a resonant point) is manually created to check the operational status.
3) Malfunction Test
Apply vibration for 10 minutes for each condition of altering double amplitude and frequency to check if there
is any malfunction in MCCB.

Impulse
The magnitude of impulse is denoted by the multiple of gravitational acceleration imposed on the equipment
and part. The test is conducted through a drop impulse test.

Impact of High Frequency


In case of high frequency current, you are required to reduce the rated current of the breaker with a thermal
magnetic trip element embedded due to heat incurred by the skin effect of conductor and/or core less of
structure. The reduction rate varies according to the Frame Size and rated current and decreases down to
70~80% at 400Hz. In addition, the core loss decreases attractive force, which leads to increase of
instantaneous trip current.
* Core loss: It refers to the electrical loss in a transformer caused by magnetization of the core that changes
over time and is categorized into hysteresis loss and eddy current loss.
* Hysteresis loss: It takes up the majority portion of no-load loss of electric equipment and is calculated like this.
Ph = σfBmn
Bm: maximum value of magnetic flux density, n: constant(1.6~2.0), f: frequency, σ: hysteresis constant
* Eddy current: It refers to an induced electric current formed within the body of a conductor when it moves
through a non-uniform or changing magnetic field. The eddy current that incurs at winding of
transformer or core is considered as one of the transformer losses as a part of exciting current. It
is also called‘eddy current loss’.

123
Technical Document

Use Environment with Vibration and Impulse Applied

[Table of Seismic Performance and Internal Impulse Performance]

Test Internal Impulse

Test Mounting ● Vertical mounting ● Picture 1, 2, 3, 4

Condition Vibration, ● Top-down, Left-right, Front-back (→ represents the direction of drop)


Direction
Picture 1 Picture 2
of impulse Left-right,
Front-back

Top-down ON

ON

Line Connection Picture 3 Picture 4

Status of (1) Non-conduction (ON or OFF status) Non-conduction (ON or OFF status)
MCCB (2) Status where rated current is conducted until
the temperature of MCCB becomes
constant and keeps being conducted
Test Judgment ● If it is ON, it should not be OFF

Result Condition ● If it is OFF, it should not be ON


● No abnormal status such as damage,
transformation, or annealing of nut part
● Characteristics of switch and trip after the test
must be normal

124
Cerfications

MCCB ELCB
Type Approvals Certificates Type Approvals Certificates Type Approvals Certificates
Cerficate Safet certi IEC KEMA Cerficate Safet certi IEC KEMA Cerficate Safet certi IEC KEMA

Mark Mark Mark


and and and
name CE KEMA name CE KEMA name CE KEMA
Type Korea Europe Netherlands Type Korea Europe Netherlands Type Korea Europe Netherlands
ABS32c ● ● ● ABP104c ● ● ● EBS33c ● ● ●
ABS33c ● ● ● ABH102c ● ● ● EBS34c ● ● ●
ABS34c ● ● ● ABH103c ● ● ● EBN52c ● ● ●
ABN52c ● ● ● ABH104c ● ● ●
EBN53c ● ● ●
ABN53c ● ● ● ABN202c ● ● ●
EBS53c ● ● ●
ABN54c ● ● ● ABN203c ● ● ●
MCCB 30~250AF

EBS54c ● ● ●
ABS52c ● ● ● ABN204c ● ● ●
ABS53c ● ● ● ABS202c ● ● ● EBN63c ● ● ●

ABS54c ● ● ● ABS203c ● ● ● EBS63c ● ● ●


ABN62c ● ● ● ABS204c ● ● ● EBS64c ● ● ●
ABN63c ● ● ● ABP202c ● ● ● EBN102c ● ● ●
ABN64c ● ● ● ABP203c ● ● ● EBN103c ● ● ●
ABS62c ● ● ● ABP204c ● ● ●
EBN104c ● ● ●
ABS63c ● ● ● ABH202c ● ● ●
EBS33d ● ● ●
ABS64c ● ● ● ABH203c ● ● ●
EBS34d ● ● ●
ABN102c ● ● ● ABH204c ● ● ●
EBN52d ● ● ●
ABN103c ● ● ● ABN402c ● ● ●
ABN104c ● ● ● ABN403c ● ● ● EBN53d ● ● ●

ABS32d ● ● ● ABN404c ● ● ● EBS53d ● ● ●


ELCB 30~250AF

ABS33d ● ● ● ABS402c ● ● ● EBS54d ● ● ●


ABS34d ● ● ● ABS403c ● ● ● EBN63d ● ● ●
ABN52d ● ● ● ABS404c ● ● ●
MCCB 30~250AF

EBS63d ● ● ●
ABN53d ● ● ● ABH402c ● ● ●
EBS64d ● ● ●
ABN54d ● ● ● ABH403c ● ● ●
EBN102d ● ● ●
ABS52d ● ● ● ABH404c ● ● ●
EBN103d ● ● ●
ABS53d ● ● ● ABL402c ● ● ●
ABS54d ● ● ● ABL403c ● ● ● EBN104d ● ● ●

ABN62d ● ● ● ABL404c ● ● ● EBP53c ● ● ●


ABN63d ● ● ● ABN602c ● ● EBP54c ● ● ●
MCCB 400~800AF

ABN64d ● ● ● ABN603c ● ● EBH53c ● ● ●


ABS62d ● ● ● ABN604c ● ● EBH54c ● ● ●
ABS63d ● ● ● ABS602c ● ●
EBS103c ● ● ●
ABS64d ● ● ● ABS603c ● ●
EBS104c ● ● ●
ABN102d ● ● ● ABS604c ● ●
EBP103c ● ● ●
ABN103d ● ● ● ABL602c ● ●
EBP104c ● ● ●
ABN104d ● ● ● ABL603c ● ●
ABP52c ● ● ● ABL604c ● ● EBH103c ● ● ●

ABP53c ● ● ● ABN802c ● ● EBH104c ● ● ●


ABP54c ● ● ● ABN803c ● ● EBN202c ● ● ●
ABH52c ● ● ● ABN804c ● ● EBN203c ● ● ●
ABH53c ● ● ● ABS802c ● ● EBS203c ● ● ●
ABH54c ● ● ● ABS803c ● ●
EBS204c ● ● ●
ABS102c ● ● ● ABS804c ● ●
EBP203c ● ● ●
ABS103c ● ● ● ABL802c ● ●
EBP204c ● ● ●
ABS104c ● ● ● ABL803c ● ●
ABP102c ● ● ● ABL804c ● ● EBH203c ● ● ●

ABP103c ● ● ● EBH204c ● ● ●

Note: ●(Completion)

125

You might also like