Ls Catalog
Ls Catalog
Ls Catalog
Hỗ trợ kỹ thuật
MCCB = ELCB
I
4I
Metasol
Molded case circuit breaker / Earth leakage circuit breaker
Metasol MCCB
Upgrade breaking capacity
460V
85kA
ABL400c ABL800c
85kA 85kA
75kA
65kA
ABH400c ABS800c
50� 65kA 50� 65kA
50kA
ABH50c ABH125c ABH250c ABS400c
25� 50kA 35� 50kA 35� 50kA 35� 50kA
37kA
ABS125c ABS250c ABN400c ABN800c
25� 37kA 25� 37kA 25� 37kA 35� 37kA
26kA
ABN250c
18� 26kA
18kA
ABS50c ABS60c ABN100c
10�18kA 10�18kA 10�18kA
14kA
ABS30c ABN50c ABN60c
5�14kA 5�14kA 5�14kA
I
6I
Short-circuit breaking capacity
Metasol ELCB
Upgrade breaking capacity
460V
85kA
EBL400c EBL800c
85kA 85kA
75kA
65kA
EBH400c EBS800c
50� 65kA 50� 65kA
50kA
EBH50c EBH125c EBH250c EBS400c
25� 50kA 35� 50kA 35� 50kA 35� 50kA
37kA
EBS125c EBS250c EBN400c EBN800c
25� 37kA 25� 37kA 25� 37kA 35� 37kA
26kA
EBN250c
18� 26kA
18kA
EBS50c EBS60c EBN100c
10�18kA 10�18kA 10�18kA
14kA
EBS30c EBN50c EBN60c
5�14kA 5�14kA 5�14kA
I7
MCCB/ELCB Compatible and Standard
● 100% compatible with Meta-MEC Series.
yz
e.x
ath
nh
die
Metasol MCCB
AF
ww
ABL400c ABL800c
ABL 85kA 85kA
I
8I
● Same external dimension with MCCB and ELCB.
yz
60 mm
e.x
ath
50 mm
nh
die
Metasol ELCB
AF
ww
EBL400c EBL800c
EBL 85kA 85kA
I9
MCCB/ELCB System overview
� Breaker
� Internal auxiliaries
� Plug-in kit
�
� Rotary handle (direct)
� Rotary handle (direct, key lock)
� Rotary handle (extended)
� Rear terminal
� Terminal cover (Short, Long)
� � Insulation barrier
�
�
�
�
�
�
I 11
MCCB/ELCB Internal accessories
● ●
●
●
Internal Accessories
Internal Accessories can be commonly used in all Metasol MCCB and ELCB
(Notice: Exception of SHT, UVT in ELCB)
Internal accessories
AX AL AL AX AX AL AL AX
SHT/UVT SHT/UVT
AX AL AL AX
SHT/UVT
I 13
MCCB/ELCB External accessories
External Accessories
Designed for various mount and user safety.
External accessories
Plug-in base
It makes to extract and/or rapidly replace the circuit breaker without having to touch
connections.(Easy replacement and maintenance)
Locking device
- Fixed padlock
- Removable padlock
- Key lock device on direct handle
Insulation barrier
These allow the insulation characteristics between the phases at the connections
to be increased.
I 15
Marking and configuration
MCCB
MCCB model
�ABN: Economic type
�ABS: Standard type
�ABH: High capacity type
Standardized characteristics
Ui: Rated insulation voltage
Uimp: Impulse withstand
voltage
Ue: Rated operational voltage
Icu: Ultimate breaking
capacity
Ics: Service breaking capacity
Symbol indicating
suitability for isolation
as defined by IEC 947-2
MCCB
Upstream connections
Fixing hole
Product name
Brand name
Operating handle
Certification mark
Company logo
Fixing hole
Downstream connections
16
ELCB
ELCB model
�EBN: Economic type
�EBS: Standard type
�EBH: High capacity type
Symbol indicating
suitability for isolation
as defined by IEC 947-2
ELCB
Upstream connections
Fixing hole
Brand name
Product name
Operating handle
Residual current(I△n) setting
Company logo
Certification mark
Fixing hole
Downstream connections
17
External configuration
MCCB
① Handle
�Function of indications
- “ON” “OFF” “TRIP”
�Resetting Handle
② Arc-Extinguishing unit
LS patent technique PASQ Contact
Arc-Extinguishing unit
PASQ : Puffer Assisted Self-Quenching
�Reduction of arc voltage for a short time Mechanism
Hybrid Grid
chamber Ass’y
Trip
18
ELCB
① Residual
indication LED
19
Quick selection table
Molded Case Circuit Breakers
MCCBs
AF 30AF 50AF 60AF
AF 50
∅4.5
8 8 8 8 8 8
5 8 10 8 8 10
10 26 35 18 26 35
18 37 50 26 37 50
22 42 50 30 42 50
35 85 100 65 85 100
10 20 30 10 20 30
10 20 30 10 20 30
100 100 100 100 100 100
75×130×60mm 90×155×60mm 105×165×60mm
(Fig. 1) (Fig. 2) (Fig. 3)
40 page 42 page 44 page
87 page 88 page 89 page
93 page 94 page 95 page
∅8.2
5
50
47
100
50
155
135
59.4
102
126
144
165
CL
50
60 58
8 60 60
90 35
82 70 64
105 68.5
(Fig. 2) (Fig. 3) 86.85
21
Quick selection table
Molded Case Circuit Breakers
MCCBs
AF 400AF
AF
Type 400AF 800AF 1000AF 1200AF
ABN400c ABN800c
ABN 37kA 37kA
257
225
215
150
ABH400c
ABH 65kA
95
(Fig. 4)
22
800 AF 1000 AF 1200 AF
N-Type S-Type L-Type S-Type L-Type S-Type L-Type
8 8 8
8 10 14
25 45 65 50 75 50 50 75
37 65 85 65 85 65 65 85
45 75 100 65 85 65 65 85
50 85 125 100 125 100 100 125
10 20 40
10 20 40
100 100 75
210×280×109mm 220×400×105mm 220×400×105mm
(Fig. 5) (Fig. 6) (Fig. 6)
48 page 50 page 50 page 51 page 50 page
90 page 91 page 91 page 92 page 91 page
97 page 98 page 98 page 99 page 98 page
93
48.5
17
116
90
21.4
280
243
150
96
25
400
110
98.5
95
90
40
109 17
44 48.5
20
113 70 70 102.5
145 220 105
122.5
159
(Fig. 5) (Fig. 6) 230
23
Quick selection table
ZCT Molded Case Circuit Breakers
MCCBs
AF 30AF 50AF 60AF
Rated operational
AC(V) 690 690 690 690 690 690
voltage, Ue
Rated insulation voltage, Ui V 750 750 750 750 750 750
Rated impulse withstand
voltage, Uimp kV 8 8 8 8 8 8
50
AF
∅4.5
24
100AF 125AF 250AF
8 8 8 8 8 8
5 8 10 8 8 10
10 26 35 18 26 35
18 37 50 26 37 50
22 42 50 30 42 50
35 85 100 65 85 100
100 100 100 100 100 100
75×130×60mm 90×155×60mm 105×165×60mm
(Fig. 1) (Fig. 2) (Fig. 3)
40 page 42 page 44 page
87 page 88 page 89 page
92 page 94 page 95 page
∅8.2
5
50
47
100
50
155
135
59.4
102
126
144
165
CL
50
60 58
8 60 60
90 35
82 70 64
105 68.5
(Fig. 2) (Fig. 3) 86.85
25
Quick selection table
ZCT Molded Case Circuit Breakers
MCCBs
AF 400AF
AF
Type 400AF 800AF
ABN400c ABN800c
ABN 37kA 37kA
ABS400c ABS800c
ABS 50kA 65kA
ABH400c
ABH 65kA
ABL400c ABL800c
ABL 85kA 85kA
26
800 AF
N-Type S-Type L-Type
- - -
ABN803cZ ABS803cZ ABL803cZ
- - -
500, 630, 700, 800
8 8 8
8 10 14
25 45 65
37 65 85
45 75 100
50 85 125
100 100 75
210×280×109mm
(Fig. 5)
48 page
90 page
97 page
280
243
150
96
257
225
215
150
95
95
109
109
113 113
145
145
(Fig. 4) (Fig. 5)
27
Quick selection table
Earth Leakage Circuit Breakers
ELCBs
AF 30AF 50AF 60AF
AF
Type 30AF 50AF 60AF 100AF 125AF 250AF
(Fig. 1)
28
100AF 125AF 250AF
6 6 6
18 37 50 26 37 50
35 85 100 65 85 100
75×130×60mm 90×155×60mm 105×165×60mm
(Fig. 1) (Fig. 2) (Fig. 3)
60 page 62 page 64 page
87 page 88 page 89 page
100 page 101 page 102 page
∅5
50
∅4.5
47
100
135
155
50
102
144
165
CL
50
7
4.7
60 58
60
90 8 60 35
64
70
82 66.5
105
68.5
86.85
(Fig. 2) (Fig. 3)
29
Quick selection table
Earth Leakage Circuit Breakers
ELCBs
AF 400AF
AF
Type 400AF 800AF 1000AF 1200AF
EBN400c EBN800c
EBN 37kA 37kA
257
225
215
150
EBH400c
EBH 65kA
95
EBL400c EBL800c 109
EBL 85kA 85kA
113
145
(Fig. 4)
30
800 AF 1000 AF 1200 AF
6 6 6
0.1 sec 0.1 sec 0.1 sec 0.1 sec 0.1 sec
37 65 85 85 85
50 85 125 125 125
100 100 75
210×280×109mm 220×565×105mm
(Fig. 5) (Fig. 6)
68 page 70 page
90 page 91 page
104 page 105 page
93
48.5
17
116
90
∅8
21.4
∅13.5
206
25
400
360
110
280
243
98.5
150
96
525
165
165
95
109
90
40
113 17
44
20
48.5
145 70 70 102.5
220 105
122.5
159
(Fig. 5) (Fig. 5) 231
31
30AF MCCB
ABE30b
Ratings
c2 Note) - -
For more information d 80 80
�Drawings ▶ 92 page Weight, kg Standard 0.5 0.7
�Trip curves ▶ 87 page
Certification Pole 2p 3p
�Accessories ▶ 72 page
�Connection and mounting ▶ 100 page CE marking ○ ○
Note) Depth by door cut size : c1 for large cut, c2 for small cut
32
Ordering types
Maximum possibilities
T-position One of above auxiliaries
R-position Option of AX or AL
Note) For more detail see 72 page
External accessories
ABE30b Name
33
30AF MCCB
ABS30c
Ratings
c2 Note) 64 64 64
For more information d 82 82 82
�Drawings ▶ 93 page Weight, kg Standard 0.5 0.7 0.9
�Trip curves ▶ 87 page
Certification Pole 2p 3p 4p
�Accessories ▶ 72 page
�Connection and mounting ▶ 110 page CE marking ○ ○ ○
Note) Depth by door cut size : c1 for large cut, c2 for small cut
34
Ordering types
Electrical auxiliaries
Maximum possibilities
T-position One of above auxiliaries
R-position Option of AX or AL or AX+AL
Note) For more detail see 72 page
External accessories
ABS30c Name
35
50AF MCCB
ABN50c, ABS50c, ABH50c
Ratings
c2 Note) 64 64 64
For more information d 82 82 82
�Drawings ▶ 93 page Weight, kg Standard 0.5 0.7 0.9 0.5 0.7 0.9 0.7 1 1.2
�Trip curves ▶ 87, 88 page
Certification Pole 2p 3p 4p 2p 3p 4p 2p 3p 4p
�Accessories ▶ 72 page
�Connection and mounting ▶ 110 page CE marking ○ ○ ○
Note) Depth by door cut size : c1 for large cut, c2 for small cut
36
Ordering types
External accessories
ABN50c
ABH50c Name
ABS50c
37
60AF MCCB
ABN60c, ABS60c
Ratings
ABS62c
Rated insulation voltage, Ui AC: 750V
Rated impulse withstand voltage, Uimp 8kV
c2 Note) 64 64
For more information d 82 82
�Drawings ▶ 93 page Weight, kg Standard 0.5 0.7 0.9 0.5 0.7 0.9
�Trip curves ▶ 87 page
Certification Pole 2p 3p 4p 2p 3p 4p
�Accessories ▶ 72 page
�Connection and mounting ▶ 110 page CE marking ○ ○
Note) Depth by door cut size : c1 for large cut, c2 for small cut
38
Ordering types
External accessories
ABS60c
Name
ABN60c
IB13 Insulation barrier
TCL13 Terminal cover (Long)
TCS13 Terminal cover (Short)
DH100 Rotary handle (Direct)
DHK100 Rotary handle (Direct, Key lock)
EH100 Rotary handle (Extended)
RTB1 Rear terminal (Bar)
RTR1 Rear terminal (Round)
PB-A3 Plug-in kit
PHL100 Pad handle lock
Note) For more detail see 80 page
39
100AF MCCB
ABN100c
Ratings
c2 Note) 64 64 64
For more information d 82 82 82
�Drawings ▶ 93 page Weight, kg Standard 0.5 0.7 0.9
�Trip curves ▶ 87 page
Certification Pole 2p 3p 4p
�Accessories ▶ 72 page
�Connection and mounting ▶ 110 page CE marking ○ ○ ○
Note) Depth by door cut size : c1 for large cut, c2 for small cut
40
Ordering types
Maximum possibilities
T-position One of above auxiliaries
R-position Option of AX or AL or AX+AL
Note) For more detail see 72 page
External accessories
ABN100c Name
41
125AF MCCB
ABS125c, ABH125c
Ratings
c2 Note) 64 64
For more information d 82 82
�Drawings ▶ 94 page Weight, kg Standard 0.7 1 1.2 0.7 1 1.2
�Trip curves ▶ 88 page
Certification Pole 2p 3p 4p 2p 3p 4p
�Accessories ▶ 72 page
�Connection and mounting ▶ 110 page CE marking ○ ○
Note) Depth by door cut size : c1 for large cut, c2 for small cut
42
Ordering types
External accessories
ABS125c
Name
ABH125c
IB23 Insulation barrier
TCL23 Terminal cover (Long)
TCS23 Terminal cover (Short)
DH125 Rotary handle (Direct)
DHK125 Rotary handle (Direct, Key lock)
EH125 Rotary handle (Extended)
RTB2 Rear terminal (Bar)
RTR2 Rear terminal (Round)
PB-C3 Plug-in kit
PHL125 Pad handle lock
Note) For more detail see 80 page
43
250AF MCCB
ABN250c, ABS250c, ABH250c
Ratings
ABS204c
d
c2
a 105 105 140 105 105 140 105 105 140
a c1
b 165 165 165
c1 Note) 60 60 60
b
c2 Note) 64 64 64
For more information d 87 87 87
�Drawings ▶ 95 page Weight, kg Standard 1.1 1.2 1.6 1.1 1.2 1.6 1.1 1.2 1.6
�Trip curves ▶ 89 page
Certification Pole 2p 3p 4p 2p 3p 4p 2p 3p 4p
�Accessories ▶ 72 page
�Connection and mounting ▶ 110 page CE marking ○ ○ ○
Note) Depth by door cut size : c1 for large cut, c2 for small cut
44
Ordering types
External accessories
ABH250c Name
45
400AF MCCB
ABN400c, ABS400c, ABH400c, ABL400c
Ratings
46
Ordering types
ABL type(85kA/460V)
Rated current, In 2-pole 3-pole 4-pole
250 A ABL402c/250 ABL403c/250 ABL404c/250
300 A ABL402c/300 ABL403c/300 ABL404c/300
350 A ABL402c/350 ABL403c/350 ABL404c/350
400 A ABL402c/400 ABL403c/400 ABL404c/400
E-70U N-70
External accessories
IBL400 Insulation barrier
T1-43A Terminal cover (Long) - 2, 3pole
T1-44A Terminal cover (Long) - 4pole
N-70 Rotary handle (Direct)
E-70U Rotary handle (Extended)
MI-43 Mechanical interlock - 2, 3pole
MI-44 Mechanical interlock - 4pole
X-402 Rear terminal - 2pole
X-403 Rear terminal - 3pole
X-404 Rear terminal - 4pole
PB-I3-FR Plug-in kit
Note) For more detail see 80 page
47
800AF MCCB
ABN800c, ABS800c, ABL800c
Ratings
48
Ordering types
E-80U N-80
External accessories
49
1000/1200AF MCCB
ABS1000b/1200b, ABL1000b/1200b
Ratings
d 159 159
Weight, kg Standard 19.6 25.7
For more information
Certification Pole 3p 4p
�Drawings ▶ 98 page
�Trip curves ▶ 91 page CE marking
50
Ordering types
Option of below items for T-position Contact rating for Auxiliary and Alarm Switches
AX1 Auxiliary Switch (1c) AC DC
AX2 Auxiliary Switch (2c) Voltage Current (A) Voltage Current (A)
AL1 Alarm Switch (1c) R T (V) Resistive load Inductive load (V) Resistive load Inductive load
AL2 Alarm Switch (2c) 125 20 20 30 6 5
AX1+AL Auxiliary (1c) + Alarm (1c) Switch 250 20 20 125 0.4 0.05
AX2+AL Auxiliary (2c) + Alarm (1c) Switch 500 10 5 250 0.2 0.03
51
1200AF 전자식 MCCB
ABS1203bE
Ratings
d 159
�Drawings ▶ 99 page
�Trip curves ▶ 92 page Weight, kg Standard 21
52
Ordering types
Rated current, In 3P
1200 A ABS1203bE
AX
AL
Option of below items for T-position Contact rating for Auxiliary and Alarm Switches
AX1 Auxiliary Switch (1c) AC DC
AX2 Auxiliary Switch (2c) Voltage Current (A) Voltage Current (A)
AL1 Alarm Switch (1c) R T (V) Resistive load Inductive load (V) Resistive load Inductive load
AL2 Alarm Switch (2c) 125 20 20 30 6 5
AX1+AL Auxiliary (1c) + Alarm (1c) Switch 250 20 20 125 0.4 0.05
AX2+AL Auxiliary (2c) + Alarm (1c) Switch 500 10 5 250 0.2 0.03
53
30AF ELCB
EBS30c
Ratings
c2 Note) 64 64
For more information d 82 82
�Drawings ▶ 100 page Weight, kg Standard 0.7 0.9
�Trip curves ▶ 87 page
�Accessories ▶ 72 page Certification Pole 3p 4p
�Connection and mounting ▶ 110 page CE marking ○ ○
Note) Depth by door cut size : c1 for large cut, c2 for small cut
54
Ordering types
Electrical auxiliaries
External accessories
EBS30c Name
55
50AF ELCB
EBN50c, EBS50c, EBH50c
Ratings
c2 Note) 64 64 64
For more information d 82 82 82
�Drawings ▶ 100 page Weight, kg Standard 0.5 0.7 0.7 0.9 1 1.2
�Trip curves ▶ 87, 88 page
Certification Pole 2p 3p 3p 4p 3p 4p
�Accessories ▶ 72 page
�Connection and mounting ▶ 110 page CE marking ○ ○ ○
Note) Depth by door cut size : C1 for large cut, C2 for small cut
56
Ordering types
57
60AF ELCB
EBN60c, EBS60c
Ratings
c2 Note) 64 64 64
For more information d 82 82 82
�Drawings ▶ 100 page Weight, kg Standard 0.7 0.7 0.9
�Trip curves ▶ 87 page
Certification Pole 3p 3p 4p
�Accessories ▶ 72 page
�Connection and mounting ▶ 110 page CE marking ○ ○
Note) Depth by door cut size : C1 for large cut, C2 for small cut
58
Ordering types
External accessories
EBS60c
Name
EBN60c
IB13 Insulation barrier
TCL13 Terminal cover (Long)
TCS13 Terminal cover (Short)
DH100 Rotary handle (Direct)
DHK100 Rotary handle (Direct, Key lock)
EH100 Rotary handle (Extended)
RTB1 Rear terminal (Bar)
RTR1 Rear terminal (Round)
PB-A3 Plug-in kit
PHL100 Pad handle lock
Note) For more detail see 80 page
59
100AF ELCB
EBN100c
Ratings
c2 Note) 64 64 64
For more information d 82 82 82
�Drawings ▶ 100 page Weight, kg Standard 0.5 0.7 0.9
�Trip curves ▶ 87 page
Certification Pole 2p 3p 4p
�Accessories ▶ 72 page
�Connection and mounting ▶ 110 page CE marking ○ ○ ○
Note) Depth by door cut size : c1 for large cut, c2 for small cut
60
Ordering types
Electrical auxiliaries
△n: 100/200/500mA
Rated residual current, I△
Rated current, In
2-pole 3-pole 4-pole AX Auxiliary Switch
60 A EBN102c/60/100 EBN103c/60/100 EBN104c/60/100 AL Alarm Switch R T
75 A EBN102c/75/100 EBN103c/75/100 EBN104c/75/100 AX+AL Combination switch
100 A EBN102c/100/100 EBN103c/100/100 EBN104c/100/100
Maximum possibilities
T-position Not available
R-position Option of AX or AL or AX+AL
Note) For more detail see 72 page
External accessories
EBN100c Name
61
125AF ELCB
EBS125c, EBH125c
Ratings
c2 Note) 64 64 64 64
For more information d 82 82 82 82
�Drawings ▶ 101 page Weight, kg Standard 1 1.2 1 1.2
�Trip curves ▶ 88 page
Certification Pole 3p 4p 3p 4p
�Accessories ▶ 72 page
�Connection and mounting ▶ 110 page CE marking ○ ○ ○ ○
Note) Depth by door cut size : c1 for large cut, c2 for small cut
62
Ordering types
63
250AF ELCB
EBN250c, EBS250c, EBH250c
Ratings
c2 Note) 64 64 64
For more information d 87 87 87
�Drawings ▶ 102 page Weight, kg Standard 1.1 1.2 1.2 1.5 1.2 1.5
�Trip curves ▶ 89 page
Certification Pole 2p 3p 3p 4p 3p 4p
�Accessories ▶ 72 page
�Connection and mounting ▶ 110 page CE marking ○ ○ ○
Note) Depth by door cut size : c1 for large cut, c2 for small cut
64
Ordering types
65
400AF ELCB
EBN400c, EBS400c, EBH400c, EBL400c
Ratings
66
Ordering types
External accessories
Rated residual current, Rated residual current,
Rated IBL400 Insulation barrier
△n: 30mA
I△ △n: 100/200/500mA
I△
current, In T1-43A Terminal cover (Long) - 2, 3pole
3-pole 4-pole 3-pole 4-pole
T1-44A Terminal cover (Long) - 4pole
250 A EBL403c/250/30 EBL404c/250/30 EBL403c/250/100 EBL404c/250/100
N-70 Rotary handle (Direct)
300 A EBL403c/300/30 EBL404c/300/30 EBL403c/300/100 EBL404c/300/100
E-70U Rotary handle (Extended)
350 A EBL403c/350/30 EBL404c/350/30 EBL403c/350/100 EBL404c/350/100
MI-43 Mechanical interlock - 2, 3pole
400 A EBL403c/400/30 EBL404c/400/30 EBL403c/400/100 EBL404c/400/100
MI-44 Mechanical interlock - 4pole
X-402 Rear terminal - 2pole
X-403 Rear terminal - 3pole
X-404 Rear terminal - 4pole
PB-I3-FR Plug-in kit
Note) For more detail see 80 page
67
800AF ELCB
EBN803c, EBS803c, EBL803c
Ratings
c2 Note) 113
For more information d 145
�Drawings ▶ 104 page Weight, kg Standard 11.5
�Trip curves ▶ 90 page
Certification Pole 3p
�Accessories ▶ 72 page
�Connection and mounting ▶ 110 page CE marking -
Note) Depth by door cut size : c1 for large cut, c2 for small cut
68
Ordering types
E-80U N-80
External accessories
69
1000/1200AF ELCB
EBS1003b, EBS1203b
Ratings
a
c2
c1
a 220
b 565
c 105
b
70
Ordering types
Rated current, In 3p
1000 A EBS1003b/1000/100
AX
1200 A EBS1203b/1200/100
AL
Option of below items for T-position Contact rating for Auxiliary and Alarm Switches
AX1 Auxiliary Switch (1c) AC DC
AL1 Alarm Switch (1c) Voltage Current (A) Voltage Current (A)
AX1+AL1 Auxiliary (1c) + Alarm (1c) Switch R T (V) Resistive load Inductive load (V) Resistive load Inductive load
Note) R-position is not available.
125 20 20 30 6 5
250 20 20 125 0.4 0.05
500 10 5 250 0.2 0.03
71
Accessories
SHT
yz
Shunt Trip
e.x
AX
Auxiliary UVT
Switch
ath Undervoltage
trip
AL
Left-hand seat Right-hand seat
nh
Alarm Switch
AX
Auxiliary
Switch
die
AX+AL
AL
Alarm
Combination switch Switch
AX+AL Combination
switch
Maximum possibilities
ABN100c ABH125c ABH250c EBN100c EBH125c EBH250c
Position Type
2p 3/4p 2p 3/4p 2/3/4p 2/3/4p 3/4p 2/3/4p
AX - 1 - 1 1 1 1 1
Left-hand
AL - 1 - 1 1 1 1 1
seat
AX+AL - 1 - 1 1 1 1 1
AX 1 1 1 1 1 - - -
Right-hand AL 1 1 1 1 1 - - -
seat AX+AL 1 1 1 1 1 - - -
SHT/UVT 1 1 1 1 1 - - -
72
Electrical auxiliaries of 400~800AF
yz
e.x
AL AL
AX AX
Maximum possibilities
MCCB ELCB
Position Type
(400~800AF) (400~800AF)
AX 2 2
Left-hand
AL 2 2
seat
SHT/UVT 1 1
AX 2 -
Right-hand
AL 2 -
seat
SHT/UVT 1 -
73
Accessories
Combinations of accessories
Left-hand Right-hand Auxiliary switch (AX)
seat seat
Alarm switch (AL) Shunt trip (SHT) / Undervoltage trip (UVT)
Main breaker
AX2
AX3 (4)
AL
AL2
AL3(4)
SHT(UVT)
SHT(UVT)2
AX+AL
AX+AL2
AX+AL3(4)
AX2+AL
AX2+AL2
AX2+AL3(4)
AX3(4)+AL
AX3(4)+AL2
AX3(4)+AL3(4)
AX+SHT(UVT)
74
Left-hand Right-hand Auxiliary switch (AX)
seat seat
Alarm switch (AL) Shunt trip (SHT) / Undervoltage trip (UVT)
Main breaker
AX2+SHT(UVT)
AX2+SHT(UVT)2
AX3(4)+SHT(UVT)
AX3(4)+SHT(UVT)2
AL+SHT(UVT)
AL+SHT(UVT)2
AL2+SHT(UVT)
AL2+SHT(UVT)2
AL3(4)+SHT(UVT)
AL3(4)+SHT(UVT)2
AX+AL+SHT(UVT)
AX+AL+SHT(UVT)2
AX2+AL2+SHT(UVT)
AX2+AL2+SHT(UVT)2
AX3(4)+AL3(4)+SHT(UVT)
AX3(4)+AL3(4)+SHT(UVT)2
75
Combinations of accessories
Left-hand Right-hand
seat seat
Main breaker
Auxiliary switch (AX)
Alarm switch (AL) Shunt trip (SHT) / Undervoltage trip (UVT)
EBL 403c/404c
L-Type - EBL 603c -
EBL 803c
Pole 3, 4 Pole 3 Pole 3 Pole
AX
AX2
AL
AL2
SHT(UVT)
AX+AL
AX+AL2
AX2+AL
AX2+AL2
AX2+SHT(UVT)
AL+SHT(UVT)
AL2+SHT(UVT)
AX+AL+SHT(UVT)
AX2+AL2+SHT(UVT)
76
Auxiliary and Alarm switch
Contact (AX+AL)
MCCB ON OFF TRIP
AX
AL
Rating (AX+AL)
Conventional thermal current, Ith 5A
77
Accessories
The shunt trip opens the mechanism in response to an externally applied voltage signal. The releases include
coil clearing contacts that automatically clear the signal circuit when the breaker has tripped. This is not
available for ELCBs of 30~250AF .
78
Undervoltage release, UVT
The undervoltage release automatically opens a circuit breaker when voltage drops to a value ranging between
20% to 70% of the line voltage. The operation is instantaneous, and after tripping, the circuit breaker cannot be
re-closed again until the voltage returns to 85% of line voltage.
Continuously energized, the undervoltage release must be operating before the circuit breaker can be closed.
This is not available for ELCBs of 30~250AF .
z
- Range of tripping voltage: 0.2 ~ 0.7Vn
- Reset and closing of a breaker is possible when the control voltage is over 0.85Vn
.xy
- Frequency (Only AC): 45Hz ~ 65Hz
AC/DC 48
AC/DC 100~125
∙AC: 85~1.1Vn ∙AC: 0.2~0.7Vn
ww
Terminal numbering
Auxiliary Switch (AX) Alarm Switch (AL) Shunt Trip (SHT) Undervoltage trip (UVT)
79
Accessories
External accessories
Wide range of external accessories provides user-friendly solution for mounting, cable connection, insulation, safety lock and remote control.
Insulation barrier
Terminal cover
Rear terminal
Breaker
Rotary handle (Direct)
Rotary handle
(Direct, Key lock)
Rear terminal
Terminal cover
Insulation barrier
80
Rotary handles
Direct type
The rotary handle operating mechanism is available in either the direct version or in the extended version on the
compartment door. It is always fitted with a compartment door lock and on a request it can be supplied with a
key lock in the open position.
Type
Direct type Breaker type
Direct type Extended type
Direct type (Key lock) MCCB ELCB
ABN50c/60c/100c EBN50c/60c/100c
DH100 DHK100 EH100
ABS30c/50c/60c EBS30c/50c/60c
ABS125c EBS125c
DH125 DHK125 EH125
ABH50c/125c EBH50c/125c
ABN250c, ABS250c EBN250c, EBS250c
DH250 DHK250 EH250
ABH250c EBH250c
N-70 - E-70U ABN/S/H/L400c EBN/S/H/L400c
N-80 - E-80U ABN/S/L800c EBN/S/L800c
Key lock
(30~250AF)
Degree of protections
Type Degree of protection IP degree
Extended type
Type suffix according to the mounting position
S-Type L-Type R-Type
LINE
LOAD LINE LINE LOAD
Extended type
(30~250AF)
LOAD
ON ON
(400~800AF)
81
Accessories
Terminal covers
The terminal covers are applied to the circuit-breaker to prevent accidental contact with live parts and thereby
guarantee protection against direct contacts.
Two types by length are available and provide IP40 degree of protection.
Type Breaker
Pole
Short Type Long Type MCCB ELCB
TBS22 - 2P
ABE30b -
TBS23 - 3P
TCS12 TCL12 2P
TCS13 TCL13 3P ABN50c/60c/100c EBN50c/60c/100c
TCS14L TCL14L 4P Line ABS30c/50c/60c EBS30c/50c/60c
TCL (Long type) TCS14R TCL14R 4P Load
TCS22 TCL22 2P
TCS23 TCL23 3P ABS125c EBS125c
TCS24L TCL24L 4P Line ABH50c/125c EBH50c/125c
TCS24R TCL24R 4P Load
TCS33 TCL33 2/3P
ABN250c, ABS250c EBN250c, EBS250c
TCS34L TCL34L 4P Line
ABH250c EBH250c
TCS34R TCL34R 4P Load
- T1-43A 2, 3P
ABN/S/H/L400c EBN/S/H/L400c
- T1-44A 4P
- T1-63A 2, 3P
ABN/S/L800c EBN/S/L800c
- T1-64A 4P
Note: Terminal covers for 400AF and 800AF MCCBs are in acrylic.
82
Insulation barriers
Insulation barrier allows the insulation characteristics between the phases at the connections to be increased.
They are mounted from the front, even with the circuit-breaker already installed, inserting them into the
corresponding slots.
They are incompatible with both the insulating terminal covers.
It is possible to mount the phase separating partitions between two circuit-breakers side by side.
Breaker
Type
MCCB ELCB
ABN50c/60c/100c EBN50c/60c/100c
IB-13
ABS30c/50c/60c EBS30c/50c/60c
ABS125c EBS125c
ABH50c/125c EBH50c/125c
IB-23
ABN250c, ABS250c EBN250c, EBS250c
ABH250c EBH250c
83
Accessories
Rear connection terminals are used to adapt the circuit breakers to switchboards or
other applications that require rear connection.
There are two kinds of rear connection terminals.
- Flat type
- Round type
CL
CL
84
Plug-in devices
Plug-in device makes it possible to extract and/or rapidly replace the circuit breaker without having to touch
connections for ship and important installations.
The plug-in base is the fixed part of the plug-in version of the circuit-breaker.
It will be installed directly on the back plate of panel.
The circuit-breaker is racked out by unscrewing the top and bottom fixing screws.
Normal PB-A3-FR
Single-row PB-A3-1DB
Plug-in type MCCB ABN100c
(plug-in terminal built) Double-row PB-A3-2DB
Line-only PB-A3-FRL
Normal PB-C3-FR
Single-row PB-C3-1DB
ABH125c
Double-row PB-C3-2DB
Line-only PB-C3-FRL
ABH250c Normal PB-D3-FR
400AF Normal/Line-only PB-I3-FR/PB-I3-FRL
Normal Double-row
85
Type numbering system
MCCB
AB S 10 3 C M / 100A AX SHT=220V
MCCB Type Ampere Frame Pole Series Application Rated current Accessory Control voltage
of accessory
N N-Type 3 30AF 2 2-pole General AX Auxiliary Switch
-
S S-Type 5 50AF 3 3-pole purpose AL Alarm Switch SHT
H H-Type 6 60AF 4 4-pole Motor SHT Shunt Trip AC/DC 12V
M
L L-Type 10 100/125AF protection Undervoltage AC/DC 24V
UVT
20 225/250AF trip AC/DC 48V
40 400AF Rated current Rotary handle AC/DC 60V
DH
80 800AF (Direct) AC/DC
3A 150A
100 1000AF Rotary handle 100V~130V
5A 175A EH
120 1200AF (Extended) AC/DC
10A 200A
RTR 200V~250V
15A 225A Rear terminal
RTB AC 380V~450V
20A 250A
AC 440V~500V
30A 300A
UVT
40A 350A
AC/DC 24V
50A 400A
AC/DC 48V
60A 500A
AC/DC
75A 630A
100V~110V
100A 700A
AC/DC
125A 800A
200V~220V
150A 1200A
AC 380V~440V
AC 440V~480V
ELCB
EB S 10 3 C / 100A 30mA AX
86
Characteristics curves
ABE30b
Min.
Ambient temp. 40℃
Max.
Operational time
Min.
EBN50c/60c/100c
EBS30c/50c/60c
Ambient temp. 40℃ Rated current
Max. Max.
Operational time
Operational time
Min. Min.
Sec.
Sec.
87
Characteristics curves
Min.
ELCB
EBS125c
EBH50c/125c
Max.
Operational time
Min.
Sec.
Rated current
Min.
Max.
Operational time
Min.
Rated current
Ambient temp. 40℃
88
Breaker types Rated current: 100~225A
MCCB
ABN250c, ABS250c
ABH250c
ELCB
Min.
EBN250c, EBS250c
EBH250c
Max.
Operational time
Sec. Min.
Rated current
180
150
150 120
100
80
60
40
Min.
20
100
10
8
6
4
2
50
0 10 20 30 40 50 Max.
1
Operational time
20
10
8
6 Min.
4
Sec.
150 1
0.8
0.6
0.4
Magnetic trip
0.2
range
(960~1440%)
100
0.1
0.08
0.06
0.04
Max. breaking time
0.02
50
0 10 20 30 40 50 0.01
1 1.5 2 3 4 5 6 7 8 9 10 15 20 30 40 50 60 80 100
Ambient temp. 40℃
Rated current
89
Characteristics curves
Min.
EBN400c, EBS400c, EBH400c, EBL400c
EBN800c, EBS800c, EBL800c
Max.
Operational time
Min.
Sec.
Rated current
240
180
150
120
60
40
Min.
20
100
10
8
6
4
Max.
2
50
0 10 20 30 40 50
1
Operational time
20
10
8
6
Min.
4
2
Rated current: 500~800A
Rated current compensation rate (%)
150
Sec.
1
0.8
0.6
0.4
0.2
Magnetic trip range
100 0.1
0.08 (800~1200%)
0.06
0.04 Max. breaking time
0.02
50
0.01
0 10 20 30 40 50
1 1.25 2 3 4 5 6 7 8 9 10 15 20 30 40 50 70 100
90
Breaker types Rated current: 1000~1200A
MCCB
ABS1000b, ABL1000b
ABS1200b, ABL1200b
ELCB
Min.
EBS1003b, EBS1203b
Max.
Operational time
Compensation curves
Rated current: 1000~1200A
Rated current compensation rate (%)
Sec.
Rated current
Rated current
91
Dimensions
MCCB
ABE30b
Terminal cover
Insulation barrier Insulation
Terminal cover barrier
Terminal cover
Fixing hole
DIN-Rail
2P 3P
Terminal details
(Screw) (Screw)
(Holder) (Holder)
3P 3극
92
MCCB ABN50c ABS30c
ABN60c ABS50c
ABN100c ABS60c
25 25 25 56
50
50
50
∅7.4
50
∅4.5
22 22 22
115
130
115
130
115
130
50
84
50
84
50
84
19
19
19
13.3 13.3 13.3
58
25 50 25
Trip test button Trip test button Trip test button 60
50 75 75
64
100
68
2P 3P 4P 82
12.5
M5×14
5
9
5.
∅
∅
15
7.5
18 24 7 7
M8×14
7.5
18 24
(≥60A)
110.5
110.5
52
52
52
25 25 52 77 102
2P 3P 4P 2P 3P 4P
93
Dimensions
30 30 30
80
80
80
50
50
5
50
8.2
22 22 22
16.5
16.5
16.5
155
155
155
135
100
135
100
135
100
50
50
50
37 37 37
4
8
8
30 60 30 58
10
10
10
2P 3P 4P
M8×14
8
9
∅
16
18 24 8
10
52
52
52
132
30 30 62 92 122
2P 3P 4P 2P 3P 4P
94
MCCB ABN250c ABS250c ABH250c
56
Insulation barrier
Insulation barrier
80
80
∅8.2
∅4.5
22 47
22
14.5 14.5
102
126
144
165
59.4
59.4
102
126
144
165
CL CL
50
50
19.6
19.6
44.5 44.5
35 35 35
60
70 70 35
64
105 140
68.5
2,3P 4P 86.85
25
28 24 10
CL CL CL
126
126
52
52
53.5
35 35 35 107 142
2,3P 4P 2,3P 4P
95
Dimensions
44 44 44 44 44
Fixing hole Fixing hole Fixing hole 45
.5
.5
12
12
∅
∅
41.5
41.5
26.5
26.5
48
48
48
257
225
215
150
257
225
215
150
257
225
215
150
41
41
41
48
48
48
25 95
51 Trip test button Trip test button Trip test button
51 109
140 140 184 113
145
2P 3P 4P
30 M10×L30 37 .5
10
∅
29.5
13
29
12.5
112
Panel drilling 111 Front panel cutting
97
"A" (Handle only) "B" (Handle and name plate) "C" (Handle, name plate & button)
CL M6 or∅6 CL M6 or∅6 CL CL CL
Slot "A"
CL CL CL CL CL CL
215
215
100
100
152
Slot "B"
Slot "C"
44 44 53 142(3p) 142(3p)
187(4p) 187(4p)
2, 3P 4P 2, 3, 4P 3, 4P 3, 4P
96
MCCB ABN800c ABS800c ABL800c
70 70 70 41.5
44 44 t
15
15
32
32
13.5
70
70
8
8
56 56 56
∅8
53 53 53
25
25
25
280
280
243
150
243
280
150
243
150
96
96
96
70
70
600AF : 7t
800AF : 10t
Connecting
Terminal details
44 M12×35 34.5 14
∅
44
29
11
10.5
"A" (Handle only) "B" (Handle and name plate) "C" (Handle, name plate & button)
M6 M6
CL CL CL
Slot "A"
243
243
100
152
100
Slot "B"
Slot "C"
70 70 70 59 212(3p) 212(3p)
282(4p) 282(4p)
2, 3P 4P 2, 3, 4P 3, 4P 3, 4P
97
Dimensions
Auxiliary handle
3P 4P
or or
3P 4P 3P 4P
98
ELCB
ABS1203bE
Mounting hole
Auxiliary handle
or
99
Dimensions
56
25 Insulation barrier 25 25
Insulation barrier
50
50
∅7.4
Trip indication Trip indication
by earth fault by earth fault 50
∅4.5
Residual current Residual current
2.2
84
50
130
115
84
50
29.2 29.2
19
19
Trip test button Trip test button
13.3 for earth fault 13.3 for earth fault
68
82
Terminal details Connecting
8.2
M5×14
5
9
5.
∅
∅
12.5
15
7.5
18 24
7 7
M8×14
18 24
7.5
(≥60A)
M4 or∅5 M4 or∅5
110.5
110.5
52
52
25
25 77 102
50
2, 3P 4P 2, 3P 4P
100
ELCB EBS125c EBH50c
EBH125c
30 30
80
80
50
50
Fixing hole Fixing hole
5
Trip indication Trip indication 50
8.2
22 22 by earth fault
by earth fault
37.8 37.8
Residual current Residual current
(I△n) setting
16.5
(I△n) setting
16.5
100
100
50
50
155
135
155
135
4.7
4.7
37
2.5
Trip test button
Trip test button for earth fault 4
for earth fault
8
10
8 60
90 90
82
120
3P 4P
M8×14
9
∅
16
18 24 8
10
52
30 30 92 122
60
3P 4P 3P 4P
101
Dimensions
56
80
Fixing hole Fixing hole
∅4.5
22 22
∅8.2
47
Residual current Residual current
(I△n) setting (I△n) setting
14.5 14.5
CL
59.4
59.4
165
144
126
102
165
144
126
102
50
50
7
7
19.6
19.6
35 35 35 60
70 105 35 64
105 140 66.5
2, 3P 4P 68.5
86.85
Terminal details Connecting
10
∅9
M8×20
21
25
28 24
126
CL CL CL CL
52
52
53.5
35 35 35 107 142
2, 3P 4P 2, 3P 4P
102
ELCB EBN400c EBS400c EBH400c EBL400c
8
12
∅
41.5
26.5
57.9 57.9
48
48
46.9 46.9
16.5 23.9
23.9
257
225
215
150
257
225
215
150
41.4
41.4
48
48
Trip test button 16.5 Trip test button
for earth fault for earth fault
Residual current Residual current
(I△n) setting (I△n) setting
30 37 .5
M10×L30 10
∅
29.5
13
29
12.5
112
111
Panel drilling 97 Front panel cutting
"A" (Handle only) "B" (Handle and name plate) "C" (Handle, name plate & button)
CL M6 or∅6 CL M6 or∅6 CL CL CL
Slot "A"
CL CL CL CL CL CL
215
215
100
100
152
Slot "B"
Slot "C"
44 44 53 142(3p) 142(3p)
187(4p) 187(4p)
2, 3P 4P 2, 3, 4P 3, 4P 3, 4P
103
Dimensions
210
44.5
70
t
44
15
∅13.5
32
70
8
∅8
56 Trip indication by earth fault
77.6
280
243
150
96
25
23.9
17
16.5
54.1
Residual current (I△n) setting
70 70 95
109
3P 113
145
600AF : 7t
800AF : 10t
Terminal details Connecting
44 M12×35 34.5 14
∅
44
29
11
10.5
112
111
97
Panel drilling Front panel cutting
"A" (Handle only) "B" (Handle and name plate) "C" (Handle, name plate & button)
M6 CL CL CL
Slot "A"
243
100
100
152
Slot "B"
Slot "C"
70 59 212 212
3P
104
ELCB EBS1000b
EBS1200b
Mounting hole
Auxiliary handle
Reset
3P
60
3P 3P
105
Dimensions
Bar type
B
A
L
D
∅
E E E
MCCB A B C D E
Round type
C
A
L
B
C
E E E
MCCB A B C D E
106
Rotary handles
t1.2~3.2
4-∅5
A
D
E
60
104 B
C
E-70, N-80
150
t1.2~3.2
75
113
51
107
Dimensions
Rotary handles
t1.2~3.2
2-∅6
B
B
E-70U (400AF)
E-80U (800AF)
108
Technical Information
Standard accessories
The following accessories for mounting, connection and insulation are standard
items and are packed with Metasol series circuit breakers.
Fixing
screw
2P: 2EA (M4×60) 2P: 2EA (M4×60) 2P: 2EA (M4×55) 2P: 2EA (M6×100) 2P: 2EA (M6×100)
3P: 2EA (M4×60) 3P: 2EA (M4×60) 3P: 4EA (M4×55) 3P: 4EA (M6×100) 3P: 4EA (M6×100)
4P: 4EA (M4×60) 4P: 4EA (M4×60) 4P: 4EA (M4×55) 4P: 4EA (M6×100) 4P: 4EA (M6×100)
Terminal 15~30A
bolt 2P: 4EA (M5×14)
3P: 6EA (M5×14)
2P: 4EA (M8×14) 2P: 4EA (M8×20) 2P: 4EA (M10×30) 2P: 2EA (M12×35)
4P: 8EA (M5×14)
3P: 6EA (M8×14) 3P: 6EA (M8×20) 3P: 6EA (M10×30) 3P: 6EA (M12×35)
40~100A
4P: 8EA (M8×14) 4P: 8EA (M8×20) 4P: 8EA (M10×30) 4P: 8EA (M12×35)
2P: 4EA (M8×14)
3P: 6EA (M8×14)
4P: 8EA (M8×14)
Insulation
barrier
2P: 1EA 2P: 1EA 2P: 1EA 2P: 1EA 2P: 1EA
3P: 2EA 3P: 2EA 3P: 2EA 3P: 2EA 3P: 2EA
4P: 3EA 4P: 3EA 4P: 3EA 4P: 3EA 4P: 3EA
109
Technical Information
Connection
[3~30A] M5 : 23 ~ 28 [15~30A]
M8 : 55 ~ 75
8.2
M5×14
∅5.5 ∅5.5
18 24
7.5
12.5 12.5
7 7
ABN100c
[40~100A] [40~100A]
8.2
M8×14
∅9 ∅9
18 24
7.5
15 15
7 7
M8 : 55 ~ 75
8
M8×14
∅9 ∅9
ABH125c
16 16
18 24 8 8
10
M8 : 80 ~ 130
M8×20
21
∅9 ∅9
ABH250c
28 24
25 25
10 10
110
Connection
30 37
M10×L30
.5
10
∅
400AF
13
29.5
29
12.5
M12 : 400~500
(Terminal, Busbar)
44 M12×35 34.5 14
∅
44
800AF
29
11
10.5
111
Technical Information
Safety clearance
When installing a circuit breaker, safety clearances must be kept between the breaker and panels, bars and
other protection devices installed nearby. These safety clearances are depend on the ultimate breaking capacity
and are defined by tests carried out in accordance with standard IEC 60947-2.
When a short circuit interruption occur, high temperatures pressures are present in and above the arc chambers
of the circuit-breaker. In order to allow the pressure to be distributed and to prevent fire and arcing or short-
circuit currents, safety clearances are required.
Frame A(mm)
Description
size 460V 250V
ABN50c 40 25
ABN60c 40 25
ABN100c 50 30
100AF
ABS30c 30 25
ABS50c 40 30
ABS60c 40 30
ABS125c 50 40
125AF ABH50c 50 40
ABH125c 100 80
ABN250c 100 80
250AF ABS250c 100 80
ABH250c 100 80
A
A
ABN400c 100 80
F
ABS400c 100 80
400AF
ABH400c 100 80
ABL400c 100 80
ABN800c 100 80
800AF ABS800c 100 80
ABL800c 100 80
112
B: Minimum distance between the lower and the upper breakers
�C1: Minimum distance between the lower breaker and the bare terminal of the upper breaker
�C: C1+ the dimension of bare part of conductor
Frame C1 (mm)
Description C (mm)
size 460V 250V
ABN50c 40 25
ABN60c 40 25
ABN100c 50 30
100AF ABS30c 30 25
ABS50c 40 30
ABS60c 40 30
ABS125c 50 40 The dimension of bare conduct + C1
125AF ABH50c 50 40
ABH125c 100 80
ABN250c 100 80
250AF ABS250c 100 80
ABH250c 100 80
ABN400c 100 80
C
C
C
C1
ABS400c 100 80
C1
C1
400AF
ABH400c 100 80
ABL400c 100 80
ABN800c 100 80
800AF ABS800c 100 80
ABL800c 100 80
Direct Connection Connection
connection by using a by using a
of cable crimp-type crimp-type
terminal lug terminal lug to
the extended
terminal
113
Technical Information
Safety clearance
Frame D1 D2 D3 D4
Description
size (mm) (mm) (mm) (mm)
ABN50c 40 40
ABN60c 40 40
ABN100c 50 50
100AF ABS30c 30 30
ABS50c 40 40
ABS60c 40 40
The dimension of bare conduct + 20
ABS125c 50 50
125AF ABH50c 50 50
ABH125c 50 50
ABN250c 50 50
250AF ABS250c 50 50
ABH250c 50 50
D4
D3
D1
114
Minimum distance to metallic side panels
Frame E(mm)
Description
size 460V 250V
ABN50c 25 15
ABN60c 25 15
ABN100c 25 15
100AF ABS30c 20 15
ABS50c 25 15
ABS60c 25 15
ABS125c 25 15
125AF ABH50c 25 15
ABH125c 50 20 E E
ABN250c 50 15
250AF ABS250c 50 15
ABH250c 50 15
ABN400c 80 40
ABS400c 80 40
400AF
ABH400c 80 40
ABL400c 80 40
ABN800c 80 40
800AF ABS800c 80 40
ABL800c 80 40
115
Technical Information
Safety clearance
ABN50c 10
ABN60c 10
ABN100c -
100AF ABS30c 5
ABS50c 10
ABS60c 10
ABS125c -
125AF ABH50c 10
ABH125c 20
ABN250c -
250AF ABS250c -
ABH250c -
F
ABN400c 10
ABS400c 10
400AF
ABH400c 10
ABL400c 10
ABN800c 10
800AF ABS800c 10
ABL800c 10
116
Minimal distance between two adjacent breakers (With terminal covers)
Frame
Description G(mm)
size
ABN50c 0
ABN60c 0
ABN100c 0
100AF ABS30c 0
ABS50c 0
ABS60c 0
ABS125c 0
125AF ABH50c 0
ABH125c 0
ABN250c 0
G
250AF ABS250c 0
ABH250c 0
ABN400c 0
ABS400c 0
400AF
ABH400c 0
ABL400c 0
ABN800c 0
800AF ABS800c 0
ABL800c 0
117
Technical Information
Metasol series circuit breakers and auxiliaries comply with the following
international standard:
�IEC 60947-1
Low-voltage switchgear and controlgear - Part 1: General rules
�IEC 60947-2
Low-voltage switchgear and controlgear - Part 2: Circuit-breakers
CE conformity marking
The CE conformity marking shall indicate conformity to all the obligations imposed on the
manufacturer, as regards his products, by virtue of the European Community directives providing
for the affixing of the CE marking.
When the CE marking is affixed on a product, it represents a declaration of the manufacturer or of
his authorized representative that the product in question conforms to all the applicable provisions
including the conformity assessment procedures.
118
Standard Use Environment
1) Ambient Temperature: Within the range of -5℃~+40℃ (However, the average for the duration of 24 hours
must not exceed 35℃.)
2) Relative Humidity: Within the range of 45~85%
3) Altitude: 2,000m or less (However, if it exceeds 1,000m, atmosphere correction through humidity test and
withstand voltage test can be considered.)
4) Atmosphere where excessive steam, oil steam, smoke, dust, salt and other corrosive materials do not exist
119
Technical Document
℃
Environment where Ambient Temperature Exceeds 40℃
The temperate of each module of a Molded Case Circuit Breaker is the sum of temperature increase by
conduction and ambient temperature and if the ambient temperature exceeds 40℃ the passing current needs
to be reduced so that the temperature of such element as internal insulator of MCCB exceed the maximum
allowable temperature.
The base ambient temperature of Metasol breaker is set as 40℃ so if it has to be used in conditions with higher
temperature than this, the rated current is required to be reduced a little as described in the table below.
3 3 3 3 3 3 3 3 3
5 5 5 5 5 5 5 5 4
10 10 10 10 10 10 10 9 9
30 ABS30c
15 15 15 15 15 15 15 14 13
20 20 20 20 20 20 19 19 18
30 30 30 30 30 30 29 28 27
40 40 40 40 40 40 39 38 36
50 ABN50c, ABS50c
50 50 50 50 50 50 49 47 45
60 60 ABN60c, ABS60c 60 60 60 60 60 58 56 55
75 75 75 75 75 75 73 71 68
100 ABN100c
100 100 100 100 100 100 97 94 91
125 125 ABH50c, ABS125c, ABH125c 125 125 125 125 125 121 116 107
150 150 150 150 150 150 145 140 128
175 175 175 175 175 175 169 163 150
ABN200c, ABS200c,
250 200 200 200 200 200 200 193 186 171
ABH250c
225 225 225 225 225 225 217 209 193
250 250 250 250 250 250 241 233 214
250 250 250 250 250 250 246 242 238
300 ABN400c, ABS400c 300 300 300 300 300 295 291 287
400
350 ABH400c, ABL400c 350 350 350 350 350 345 339 332
400 400 400 400 400 400 394 388 381
500 500 500 500 500 500 492 485 477
630 ABN800c, ABS800c 630 630 630 630 630 621 611 602
800
700 ABL800c 700 700 700 700 700 689 679 668
800 800 800 800 800 800 788 776 764
120
Table of Rated Current for Metasol ELCB Corrected
according to Ambient Temperature
Ampere Rated Rated Table of Rated Current Corrected according to Ambient Temperature (A)
Model Name of Breaker
Frame current current 10℃℃ 20℃℃ 30℃℃ 40℃℃ 45℃℃ 50℃℃ 55℃℃
15 15 15 15 15 15 15 15 15
30 20 EBS30c 20 20 20 20 20 19 19 18
30 30 30 30 30 30 29 28 27
40 40 40 40 40 40 39 38 36
50 EBN50c, EBS50c
50 50 50 50 50 50 49 47 45
60 60 EBN60c, EBS60c 60 60 60 60 60 58 56 55
75 75 75 75 75 75 73 71 68
100 EBN100c
100 100 100 100 100 100 97 94 91
125 125 EBH50c, EBS125c, EBH125c 125 125 125 125 125 121 116 107
150 150 150 150 150 150 145 140 128
175 175 175 175 175 175 169 163 150
EBN200c, EBS200c,
250 200 200 200 200 200 200 193 186 171
EBH250c
225 225 225 225 225 225 217 209 193
250 250 250 250 250 250 241 233 214
250 250 250 250 250 250 246 242 238
300 EBN400c, EBS400c 300 300 300 300 300 295 291 287
400
350 EBH400c, EBL400c 350 350 350 350 350 345 339 332
400 400 400 400 400 400 394 388 381
500 500 500 500 500 500 492 485 477
630 EBN800c, EBS800c 630 630 630 630 630 621 611 602
800
700 EBL800c 700 700 700 700 700 689 679 668
800 800 800 800 800 800 788 776 764
121
Technical Document
℃ or less
Environment where Ambient Temperature is -5℃
Molded Case Circuit Breaker is subject to the effect of low temperature brittle of metal part inside and insulator,
or changes in viscosity of lubricating oil in device, extra care should be taken not to have the temperature drop
extremely with the use of such device as space heater. In addition, in case of using a thermal magnetic trip
element (FTU, FMU, ATU), the operating characteristic changes toward the difficult direction, so you should
identify the relationship of protection and correct accordingly.
Although MCCB is not affected by conduction switch, trip, or short circuit isolation in the temperature of - 20℃, it
is highly recommended to use a temperature maintaining device such as space heater. In addition,
transportation and passing in stone-cold area in the temperature as low as -40℃ is allowed but it is recommend
to leave the status of MCCB off or tripped in order to minimize the effect of brittle due to a low temperature.
Impact of Altitude
If an MCCB is used in an elevated area higher than 2000m sea level, its operating performance is subject to
dramatic drop in atmospheric pressure and temperature. For example, the air pressure is reduced to 80% of
ordinary pressure at 2,200m and further 50% at 5,500m although the short-circuit performance is not affected. If
it is used in areas of high sea level, you can do correction based on the correction parameter table in high
altitude environment, as described below.
[Correction Parameter Table for Altitude]
* Refer to the correction parameter table in high altitude Voltage Current
environment (ANSI C37. 29-1970) Altitude Correction Correction
1) How to Correct Voltage: Parameter Parameter
- If the rated voltage is AC 600V at 4,000m above sea level, 2,000m 1.00 1.00
600V (rated voltage) × 0.82 (correction parameter) = 492V. 3,000m 0.91 0.98
2) How to Correct Current: 4,000m 0.82 0.96
- If the rated voltage is AC 800A at above 4,000m sea level, 5,000m 0.73 0.94
800A (rated current) × 0.96(correction parameter) = 768A. 6,000m 0.65 0.92
122
Environment with Vibration and Impulse Exercised
Vibration
The magnitude of vibration is measured by double amplitude and frequency with the following equation with
accelerator.
αg=0.002×frequency(Hz)×double amplitude (mm)
* αg: multiple of gravitational acceleration (g=9.8m/sec2)
There are three types of vibration tests including resonance test, vibration endurance test, and malfunction test
as described below.
1) Resonant Test
Alter the frequency of sinusoidal wave within the range of 0~55Hz gradually with 0.5~1mm of double
amplitude applied to see if there is any occurrence of vibration on a specific part of MCCB.
2) Vibration Endurance Test
A sinusoidal wave with double amplitude of 0.5~1mm and frequency of 55Hz(resonant frequency obtained in
previous clause if there is a resonant point) is manually created to check the operational status.
3) Malfunction Test
Apply vibration for 10 minutes for each condition of altering double amplitude and frequency to check if there
is any malfunction in MCCB.
Impulse
The magnitude of impulse is denoted by the multiple of gravitational acceleration imposed on the equipment
and part. The test is conducted through a drop impulse test.
123
Technical Document
Top-down ON
ON
Status of (1) Non-conduction (ON or OFF status) Non-conduction (ON or OFF status)
MCCB (2) Status where rated current is conducted until
the temperature of MCCB becomes
constant and keeps being conducted
Test Judgment ● If it is ON, it should not be OFF
124
Cerfications
MCCB ELCB
Type Approvals Certificates Type Approvals Certificates Type Approvals Certificates
Cerficate Safet certi IEC KEMA Cerficate Safet certi IEC KEMA Cerficate Safet certi IEC KEMA
EBS54c ● ● ●
ABS52c ● ● ● ABN204c ● ● ●
ABS53c ● ● ● ABS202c ● ● ● EBN63c ● ● ●
EBS63d ● ● ●
ABN53d ● ● ● ABH402c ● ● ●
EBS64d ● ● ●
ABN54d ● ● ● ABH403c ● ● ●
EBN102d ● ● ●
ABS52d ● ● ● ABH404c ● ● ●
EBN103d ● ● ●
ABS53d ● ● ● ABL402c ● ● ●
ABS54d ● ● ● ABL403c ● ● ● EBN104d ● ● ●
ABP103c ● ● ● EBH204c ● ● ●
Note: ●(Completion)
125