AVF-5000…

PN16
AVF-5000…Motorized Valve
Flanged

Application

AVF-5000… series motorized valves are composed of


the electric actuators and the control valves. They are
widely applied to regulate the flow of cooling /hot water and
steam in HVAC and cooling automatic control systems.
The control valves of DN20~DN150 are matched with
the electric actuators RA-3000 of Johnson Controls. And the
control valves of DN200~DN300 are matched with the
electric actuators-PREMIO of ARI Armaturen Germany.
They all have the advantages of small、light、 reliable and so
on.

AVF-5200/5600… series two-way motorized valves are matched with the two-way single seat
valves and the two-way balance valves. The two-way balance valves are mainly applied to the situation
of higher medium pressure.
AVF-5800/5900… series three -way motorized valves are matched with the three-way mixing
valves and the three -way diverting valves. They applied for different process tube.
AVF-5200… series two-way single-seat motorized valve
AVF-5600… series two-way balance motorized valve
AVF-5800… series three-way mixing valve
AVF-5900… series three-way diverting valve

Features
Valves of DN20~DN150 are matched with monitoring.
the electric actuators RA-3000 of Johnson Valves in two-way single seat and balance,
Controls. three-way mixing and diverting
Valves of DN200~DN300 are matched with configurations.
the electric actuators-PREMIO of ARI Stainless steel Stem-plug-seat combination.
Armaturen Germany. Low leakage rate for two- and three-way
Uses synchronous motor with pressure valves.
switches, fixed close-off force. Electric and Pneumatic actuators available,
Models for 3-point and proportional 0…10 either factory mounted or for in-situation
VDC, 4…20 mADC control. Allows optimum installation, for all valve configurations.
choice of control signal Slotted stem with coupler for simple actuator
Active 0…10 VDC, 4…20 mADC position attachment, quick-fit coupler system
feedback on proportional models. Provides reduces installation
active signal for independent position

1/6
AVF-5000…

Structure and dimension

A B A B

AVF-5200… AVF-5600…

Size L D1 D2 H D3 Size L D1 D2 H D3
n n
DN mm mm mm mm mm DN mm mm mm mm mm
20 150 105 75 465 14 4 100 350 220 180 520 18 8
25 160 115 85 465 14 4 125 400 250 210 580 18 8
32 180 140 100 475 18 4 150 480 285 240 615 22 8
40 200 150 110 475 18 4 200 600 340 295 1055 22 12
50 230 165 125 480 18 4 250 730 405 355 1110 26 12
65 290 185 145 520 18 4 300 850 460 410 1110 26 12
80 310 200 160 520 18 8

A AB AB A

B
B
AVF-5800… AVF-5900…

Size L D1 D2 H1 H2 D3 Size L D1 D2 H1 H2 D3
n n
DN mm mm mm mm mm mm DN mm mm mm mm mm mm

20 150 105 75 450 105 14 4 80 310 200 160 *440/480 200 18 8

25 160 115 85 450 110 14 4 100 350 220 180 *450/490 210 18 8

32 180 140 100 460 130 18 4 125 400 250 210 500 280 18 8

40 200 150 110 470 140 18 4 150 480 285 240 520 325 22 8

50 230 165 125 480 150 18 4 200 600 340 295 985 390 22 12

65 290 185 145 *425/470 190 18 4 250 730 405 355 1110 480 26 12

* AVF5800…/AVF5900…

2/6
AVF-5000…

Technical data

Valve body
Pressure rating PN16 ISO 5209GB 12220
Size DN20~DN300
ISO 7268、EN 1333、DIN 4747、
Permissible pressure 1.6MPa (16 bar) at -25℃~180℃
DIN 3158、GB/T 1048
ISO 7005-1、DIN2543、BS4504、
Connection Flanged
GB/T 9113
Face to face ISO 5752、DIN3202、GB/T 12221
Body Cast steel WCB
Stem、Plug、 Seat Stainless steel 1Cr18Ni9Ti
Packing Teflon “V” rings PTFE
Equal percentage (2-way valves)
Flow characteristic EN 60534
Linear (3-way valves)
Single seat valves <0.01% Kvs
Leakage Balance valves <0.5% Kvs IEC 534-4
3-way valves <0.1% Kvs
Medium water、steam、oil
Fluid temperature 2℃~180℃

Electric actuator
RA-3000… ARI
AC230V, +10%/-15%
Supply voltage
AC24V±15%
Power consumption 18VA 109VA
3- point floating
Control signal DC 0V~10V (>10kΩ)
DC 4mA~20mA (<500Ω)
potentiometer1kΩ
Feedback signal DC 0V~10V
DC 4mA~20mA
Aux. Switch AC250V/5A
Speed 0.23mm/s 0.79 mm/s
Enclosure IP54 IP65 EN 60529
Temp. –15~+50 ℃
Ambient IEC 721-3-3
Hum. 5~90%Rh no dewing
Temp. –30~+65 ℃
Transport IEC 721-3-2
Hum. <95 % Rh
Temp. –15~+50 ℃
Storage IEC 721-3-1
Hum. 5~95 % Rh
CE EMC 89/336/EEC
Low voltage protection 73/23/EEC

3/6
AVF-5000…

Maximum close-off Pressure(MPa)


AVF-5200/ AVF-5800/ AVF-5900 AVF-5600
Size Kvs Stroke
RA…-7226 RA…-7326 ARI RA…-7226 RA…-7326 ARI
DN Value (mm)
(1.8kN) (3kN) (12kN) (1.8kN) (3kN) (12kN)
20 6.3 1.60 1.60 ---- 1.60 ---- ---- 16
25 10 1.60 1.60 ---- 1.60 ---- ---- 16
32 16 1.60 1.60 ---- 1.60 ---- ---- 25
40 25 1.20/1.00 1.60 ---- 1.60 ---- ---- 25
50 40 0.75/0.60 1.20 ---- 1.60 ---- ---- 25
65 63 0.40/0.30 0.30 ---- 1.60 ---- ---- 40
80 100 0.35/0.20 0.48/0.40 ---- 1.60 ---- ---- 40

100 160 0.20/0.10 0.30/0.20 ---- 1.20 1.60 ---- 40

125 250 ---- 0.18/0.10 ---- ---- 1.20 ---- 40

150 400 ---- 0.12/0.05 ---- ---- 1.20 ---- 40

200 630 ---- ---- 0.15 ---- ---- 1.0 60

250 1000 ---- ---- 0.20 ---- ---- 1.0 80

300 1100 ---- ---- 0.20 ---- ---- 1.0 80


Note: water/steam

Electrical wiring
Feedback
Potentiometer
M M

S1 S2
S1 S2
E P O S

1 2 3 16 17 10 12 11 B O O E Y
Input Output
AC24V COM 0~10V 0~10V
AC220V L 4~20mA 4~20mA
N
AC24V

Power-on Two-way Valve Three-way Mixing Valve Three -way Diverting Valve
1--2 A—B Close A—AB Open A—AB Close
1--3 A—B Open A—AB Close A—AB Open

Actuator mounting and removal information

The control valve is normally supplied complete with


actuator. It is not permitted to remove or replace an
actuator on system in operation, under operating
temperature and pressure. Service or modification should
be carried out in according with the actuator. During
mounting procedure the plug should NOT be rotated with
downward pressure. Ensure adherence to max. valve
operating forces when replacing actuator.

4/6
AVF-5000…

Code

AVF 5
Accessories
M=manual device

Auxiliary switch
0=Non
Valve body Size
1=with aux. switch
2= 2-way single seat valve DN Code
6= 2-way balance valve 15 01 Feedback signal*
8= 3-way mixing valve 20 02 0=Non
9= 3-way diverting valve 25 03 1=0~2kΩ
32 04 2=0~10V
40 05 3=4~20mA
50 06 5=0~135Ω
65 07 6=0~1kΩ
80 08 Control signal*
100 09 0=3 Point
125 10 2=0~10V
150 11 3=4~20mA
200 12
250 13 Supply voltage
300 14 6=24VAC;
7=220VAC

Installation and Servicing


When mounting the AVF-5000 series motorized On electrically actuated valve assemblies,
valves please follow the instructions below: all wiring must be in accordance with
It is recommended that the valves be applicable electrical codes and ordinances.
mounted at angles not greater than 90° from Input lines to the actuator must be wired
the upright position, in a conveniently correctly to open or close the valve as is
accessible location. functionally required.
Do not cover the actuator with insulating When servicing the AVF-5000 series motorized
material. valves, make sure that:
Sufficient clearance must be allowed for The electrical power to the actuator is
actuator removal isolated.
Install the valve as indicated by the arrow(s) You do not touch or attempt to connect or
on the valve body so that the plug seats disconnect wires when electrical power is
against the flow. on.

Danger WARNING
Safe operation of the valve is only ensured if the valve is Shock Hazard
Disconnect the power supply
installed, commissioned and serviced by qualified
before wiring connections are
personnel in compliance with warning references in this made to prevent personal injury.
SDI. In addition, the general installation- and safety Equipment Damage Hazard
regulations for pipelines respectively plant construction Make and check all wiring
and the professional use of tools and safety equipment connections before applying
power to the system. Short
must be guaranteed. Observe unconditionally during all
circuited or improperly connected
work on the control valve. Ignoring this information may wires may result in permanent
cause physical or material damages. damage to the unit.

5/6
AVF-5000…

Valve selection
The valve size for water applications can be defined using the diagrams below, where the intersection of
the pressure drop across the valve and the flow must be within the white area.

Pressure drop p in bar

2 3 4 5 6 8 10
100 1000
80 800
00 63
0
60 10 600
0
40 40
400
0
30 25 300
20 0 200
16
0
10 10 100
8 80
63
6 60
40
4 40
Flow Q 1 in m3/h

Flow Q 1 in m3/h
3 25 30
2 16 20

1 10 10
0.8 3 8
6.
0.6 6
4
0.4 4
5
0.3 2. 3
0.2 6 2
1.

0.1 1 1
0.08 0.8
1 2 3 4 5 6 8 10 20 40 60 80 100
Pressure drop p in kPa(100kPa = 1 bar)

Flow characteristic Fluid temperature limits

1
-25 -10
Pressure rating in bar

0.8
16
Flow k v / k vs

Linear 15
0.6 14
13
12
0.4

0.2 1
Equal percentage 0
-60 -40 -20 0 +20 +80 +100 +120 +140 +160 +180 +200
0
0 0.2 0.4 0.6 0.8 1 Fluid temperature in ℃
Stroke H / H100

6/6