Mobile Power: 1800 RPM Diesel

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

TS225

Mobile Power
1800 RPM Diesel

Standby Power Ratings

60HZ 225 kVA 180 kW


Prime Power Ratings

60HZ 200 kVA 160 kW

Made in USA
Generator available
with or without trailer

Baldor Mobile Power Generator Features


■ Brushless alternator for long life, low ■ Heavy gauge aluminum sound attenuated
maintenance enclosure with internally mounted muffler.
■ Voltage regulation 1/2% Durable powder coat paint finish. Pad lockable
doors
■ 60 Hertz frequency
■ Single point lifting eye
■ Industrial grade Tier 3 John Deere engine
■ Long run, internal, double wall metal fuel tank
■ Air preheater
■ 8 bolts to remove generator from trailer
■ Fuel/water separator
■ Premium grade DOT approved tandem
■ Electronic governor
axle highway trailer featuring: Torsion bar
■ Digital Controller with automatic safety suspension, diamond plate aluminum fenders,
shutdowns and digital readouts for low oil front leveling jack, running lights, hydraulic
pressure, high water temp, engine overcrank and brakes, lighted license plate bracket
engine overspeed. Low coolant, low fuel level
■ Generator available with trailer (TS225T) or
shutdown (user select). Emergency stop, battery
without trailer (TS225S)
disconnect switch, voltage adjust pot.
■ 3" pintle hitch
■ Illuminated instrumentation panel
■ Battery included
■ Main Circuit breaker – with shunt trip for main
power connection ■ Warranty:
■ Circuit breakers for single phase receptacles - limited 3 year warranty
■ Single phase receptacles are powered during all - 1 year or 3000 hours parts and labor
main voltage configurations - 3 year or 3000 hours parts

Options
■ Block heater ■ Electric brakes
■ Battery charger ■ 2" or 2-5/16" ball hitch coupler
■ Shore power inlet for easy connection to block ■ Automatic transfer switches
heater or battery charger ■ Generator without trailer
Generator Specifications – Preliminary Receptacle Specifications
Standby Output 125oC Rise kVA/kW 120 Volt 20 Amp Duplex GFCI . . . . . . . . . . . . . . . . . . . 4
Single phase @ 240V . . . . . . . . . . . . . . . . . . . 150/150 120/240 Volt 50 Amp Twistlock (CS6369) . . . . . . . . . . . 4
3 phase @ 208V . . . . . . . . . . . . . . . . . . . . . . . 225/180 Two wire remote start capability . . . . . . . . . . . . . . . . Yes
3 phase @ 240V . . . . . . . . . . . . . . . . . . . . . . . 225/180
3 phase @ 480V . . . . . . . . . . . . . . . . . . . . . . . 225/180 Fuel System Specifications
Prime Output 105oC Rise kVA/kW
Single phase @ 240V . . . . . . . . . . . . . . . . . . . 135/135 Fuel Consumption Standby Rating GPH
3 phase @ 208V . . . . . . . . . . . . . . . . . . . . . . . 200/160 1/2 load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.0
3 phase @ 240V . . . . . . . . . . . . . . . . . . . . . . . 200/160 Full load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13.7
3 phase @ 480V . . . . . . . . . . . . . . . . . . . . . . . 200/160 Approximate Run Time Hours
Amperage (Standby Rating) Amps 1/2 load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Single phase amperage @ 240/120V . . . . . 625/2X625 Full load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3 phase amperage @ 208V . . . . . . . . . . . . . . . . . . 625 Fuel Capacity
3 phase amperage @ 240V . . . . . . . . . . . . . . . . . . 541 Gallons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 260
3 phase amperage @ 480V . . . . . . . . . . . . . . . . . . 271 Fuel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Diesel
Voltage-3 phase adjustable 208/220/240/416/440/460/480
Voltage-Single phase adjustable 120/127/139/240/254/277
3 phase Power Factor . . . . . . . . . . . . . . . . . . . . . . . 0.8 Weights and Dimensions
Voltage Regulation . . . . . . . . . . . . . . . . . . . . . . . . 1/2%
Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 Hertz Weight without fuel . . . . . . . . . . . . . . . . . . . . . . . . 9015
Total Harmonic Distortion . . . . . . . . . . . . . . . . . . < 5% Weight without fuel and without trailer . . . . . . . . 7400
Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Class H Dimensions with trailer (L x W x H) . 218” x 82” x 109”
Dimensions without trailer (L x W x H) 159” x 54” x 83”
Engine Specifications
Manufacturer . . . . . . . . . . . . . . . . . . . . . . . . . John Deere Sound Level
Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6068HFG82
Cylinders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Sound level dB(A) . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Induction system . . . . Turbocharged, Charge Air Cooled 7 meters, full load
Displacement, L (cu. in.) . . . . . . . . . . . . . . . . . . . 6.8L (415)
EPA Emissions Level . . . . . . . . . . . . . . . . . . . . . . . . . Tier 3
HP @ rated speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . 284 Other Features
RPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1800
Bore and stroke . . . . . . . . . . . . . . . . . . . . . . . . 4.2” x 5.0” Start/Stop/Auto Switch, Alarm Horn, Voltage Adjust
Lubrication capacity (with filter) . . . . . . . . . . . . . . . . 34 Qts Pot, Battery Disconnect Switch, Front Storage
Battery recommendation (min. cold cranking amps) . . . . 925 Compartment, Trailer Side Markers and Running
- Batteries, battery rack and cable supplied Lights.
- Spin-on oil filter
- Thermostat controlled liquid cooling system
- 12V engine alternator
- 12V starter motor

Ratings: - Standby Ratings: Standby ratings are applicable for supplying emergency power for the duration of a utility power outage.
No overload capability for standby rating. Standby ratings in accordance with ISO 3046, BS55114, DIN 6271. Prime Power Rating:
Prime power is the maximum power available for continuous duty. A 10% overload capacity is available for 1 hour out of 12 hours of
operation. Manufacturer reserves the right to implement specifications or design changes without notice. WARNING: Do not connect
generator to any building’s electrical system unless a disconnect switch has been installed.

Distributed by:

Baldor Electric Company


P.O. Box 2400 • Fort Smith, AR 72902-2400 U.S.A.
Phone (479) 646-4711 • Fax (479) 648-5792 • International Fax (479) 648-5895
www.baldor.com
© Baldor Electric Company Printed in U.S.A.
FM24120JT3 7/11 TCP 2,000