JZ10-11-UN20: Environmental Considerations
JZ10-11-UN20: Environmental Considerations
JZ10-11-UN20: Environmental Considerations
Failure to comply with appropriate safety guidelines can cause severe injury or property damage.
Do not attempt to use this device with parameters that exceed permissible levels.
To avoid damaging the system, do not connect/disconnect the device when power is on.
Environmental Considerations
Do not install in areas with: excessive or conductive dust, corrosive or flammable gas,
moisture or rain, excessive heat, regular impact shocks or excessive vibration.
Ventilation: 10mm space required between the controllers top/bottom edges & enclosure walls.
Do not place in water or let water leak onto the unit.
Do not allow debris to fall inside the unit during installation.
Mounting
Dimensions
147.5 mm (5.807") 12 mm (0.472") 16.8 mm (0.661")
85.7 mm (3.374")
117 mm (4.606")
7.5 mm (0.295")
4 mm (0.157")
113.7 mm (4.476")
46.6 mm (1.835") 13.2 mm (0.52")
Bracket
Gasket
Unitronics
www.klinkmann.com
5 / 2011
www.klinkmann.com
DIN-rail mounting
Mounting Removal
Snap PLC onto the DIN rail Push mounting clip down
(1.378")
35 mm
. .
(2.087")
53 mm
Note: Removing the unit requires clearance space. Recommendation: approximately 40mm (1.58).
Wiring
Note: All diagrams are based on the rear view of the OPLC.
Use crimp terminals for wiring; use 26-12 AWG wire (0.13 mm 23.31 mm2).
1. Strip the wire to a length of 7±0.5mm (0.2500.300 inches).
2. Unscrew the terminal to its widest position before inserting a wire.
3. Insert the wire completely into the terminal to ensure a proper connection.
4. Tighten enough to keep the wire from pulling free.
Input or output cables should not be run through the same multi-core cable or share the same wire.
Allow for voltage drop and noise interference with input lines used over an extended distance. Use
wire that is properly sized for the load.
The controller, I/O signals, and outputs power supply must be connected to the same 0V signal.
2 Unitronics
5 / 2011
JZ10-11-UN20 www.klinkmann.com
Inputs
This model comprises a total of 13 inputs in 4 groups.
1. I0 to I8 are digital inputs. They may be wired, in a group, as either npn or pnp.
2. I9 and I10 may be wired as either digital or analog inputs. These may be wired as either:
npn digital inputs
pnp digital inputs
analog (voltage) inputs
In addition, 1 input may be wired as a pnp input, while the other is wired as an analog input.
Note that if 1 input is wired as an npn input, the other may not be wired as an analog input.
3. AN1 is an analog (current) input that may be wired using 2, 3, or 4 wires.
4. Analog Input 0 can function as either thermocouple or PT100 input.
Digital Inputs
Note: The inputs are arranged in two groups. You can wire one group as npn and the other as pnp,
or wire both groups as npn, or as pnp. In either case, the npn/pnp pins must be connected.
Input wiring, npn (sink)
Unitronics 3
5 / 2011
www.klinkmann.com
Analog Inputs
Note: Shields should be connected at the signal source.
Analog Input wiring, current, 2 wire, AN1
4 Unitronics
5 / 2011
JZ10-11-UN20 www.klinkmann.com
RTD
PT100 (Sensor 0): use both inputs related to CM signal
Unitronics 5
JZ10-11-UN20
Relay Outputs
Unitronics_Manuals_JZ10-11-UN20_Install_en_0511.pdf