HITACHI PACKAGED AIR CONDITIONERS

─ ─ AIR-COOLED TYPE ─ ─

Nominal Capacity Range Technical Catalog I


12,500 kcal/h to 78,000 kcal/h at 50Hz
14,500 W to 90,700 W at 50Hz
-Design Information-
49,600 Btu/h to 309,500 Btu/h at 50Hz Models:
Free-Blow Type
13,500 kcal/h to 84,000 kcal/h at 60Hz Indoor Units: Outdoor Units:
15,700 W to 97,700 W at 60Hz RP-5A4 RCR-5A4
53,600 Btu/h to 333,300 Btu/h at 60Hz RP-8A4 RCR-8A4
RP-10A4 RCR-10A4

Duct Connection Type


Indoor Units: Outdoor Units:
RP-5AL4 RCR-5A4
RP-8AL4 RCR-8A4
RP-10AL4 RCR-10A4
RP-15AL2 RCR-15A4
RP-20AL1 2×RCR-10A4
RP-30AL3(S) 2×RCR-16A4

These HITACHI air-cooled type packaged air conditioners, standing cabinet, which match any interior decor.
which are a combination of an indoor unit and an
air-cooled outdoor unit, have been developed for
free-blow or duct connection type air conditioning
systems in domestic, commercial and industrial
applications.
The indoor unit is composed of hermetic type
compressor(s), an evaporator, an evaporator fan(s), a fan
motor and auxiliary components enclosed in a floor

1 TA-TC1-03, 2001
The outdoor unit is composed of an air-cooled
condensers, a propeller fan(s) and a fan motor(s). The
weather-proof structure makes the outdoor unit suitable
for rooftop, on-the-ground or other outdoor installations.
These completely factory-assembled and tested units
provide minimum installation work and excellent
performance, matching modern air conditioning
requirements.
The heating operation and the humidifying operation are
applicable, by equipping optional accessories.

2
FEATURES

STREAMLINED SHAPE AND


5 ~ 10HP MODELS
HITACHI has developed packaged air
conditioners < air-cooled type > with
a sleek new look. In addition to
excellent performance providing high
efficiency, high reliability and low
noise, the design has been upgraded. Air Outlet Grill
Moreover, a slim design has further
relaxed restrictions on installation.
The air conditioners of this type are
available for use in factories, stations,
exhibition halls, art museums and
similar places. An extensive lineup
features 5 to 30 horsepower models.
In particular, 5 to 10 horsepower
models adopt a high-efficiency scroll
compressor. Users can choose the
optimum model according to
applications or purposes. Air Inlet Grill

Indication Lamps

NEW DESIGN
Operation Panel Cover

NEW DESIGNS HAVE FURTHER


EASED RESTRICTIONS ON
INSTALLATION AND
APPLICATION
Air conditioners installed indoor units
require not only functional elements Model: RP-5A4
but also design elements. HITACHI′s
packaged air conditioners have been
newly designed. Popular horizontal EXCELLENT ENERGY
stripes are used with discharge and
EFFICIENCY REDUCES
suction grills. The form is generally
rounded producing a soft image. A SCROLL RUNNING COSTS
slimmer type models can be installed Excellent energy efficiency results
in various places. The UTOPIA beige
COMPRESSORS from less loss caused by leakage from
color offers easy harmony with any the high-pressure section to the
wall. 5~10HP low-pressure section and no energy
loss due to valve vibration.

ADOPTION OF WORLD′S FIRST Compression Principle of Scroll


HIGH-PERFORMANCE SCROLL Compressor
COMPRESSORS
The 5 to 10 horsepower models
incorporate the world′s first, unique,
epoch-making scroll compressors
featuring a completely new principle of
compression which allows
simultaneous operation of suction,
compression and discharge, thus
providing much less running loss, lower
vibration, lower noise and higher
reliability.

Scroll Compressor

2
FEATURES

TOP OF THE LINE PERFORMANCE


WITH A HIGH-EFFICIENCY SCROLL
MAXIMUM PIPING LENGTH OF
50M
The maximum piping length of 50m
enables a remarkable extension of
distance compared with the
conventional length of 30m. This
relaxes restrictions on installation, so
the air conditioners can even be
installed on the roof.
Fan Motor

Fan Casing HIGH RELIABILITY


Safety devices such as a quick
response overcurrent relay and a
pressure switch assure high reliability.

Air Filter LOW NOISE AND LOW


VIBRATION
Evaporator Vibration-proof rubber seals and
cabinet acoustic materials provide low
noise and low vibration.

EASY MAINTENANCE
Indication Lamps There is an enough maintenance
space inside the unit to further
Operation Panel facilitate maintenance.

Magnetic Switch Box

Compressor

Accumulator
ACCESSORIES
Model : RP-5A4

HIGH RELIABILITY FURTHER FUNCTIONAL


To get high reliability, each of EXPANSION
the scroll compressors consists Various options are available such as
of only five parts and has no an electric heater, a hot water heater,
valve, which was one of the main FEATURES a steam heater and a humidifier. Easy
problems with conventional installation of such options enables
reciprocating units further expansion of functions.

Standard Accessories
CENTRALIZED CONTROL ON
OPERATION PANEL 1. Hexagon Wrench and Spindle
Fixed for Stop Valve
Scroll Every running status can be controlled
from the operation panel installed on
front of the unit and checked by
indication lamps. The operation panel
Rotating is excellent in functionality as well as
operability.
Scroll
Oldham 2. Refrigerant Pipe Connection Set
Ring ENERGY CONSERVATION
HITACHI‘s unique compressor,
Shaft evaporator and condenser greatly
improve energy efficiency, thus
contributing to energy conservation.

Frame

3
GENERAL DATA
Unit General Data
Indoor Units: Direct Blow Type
Model RP-5A4 RP-8A4 RP-10A4
kcal/h 12,500 18,500 25,000
50Hz W 14,500 21,500 29,100
Nominal
Btu/h 49,600 73,400 99,200
Cooling
Capacity* kcal/h 13,500 20,000 26,500
60Hz W 15,700 23,300 30,800
Btu/h 53,600 79,400 105,200
Capacity Control % 100, 0 100, 0 100, 0
Cabinet Color Synthetic Resin Paint Baked on Finished Steel Plates
Front Panel, Side Panel Beige Beige Beige
(MUNSELL Code) (2.5Y 8/2) (2.5Y 8/2) (2.5Y 8/2)
Air Outlet Grill Gray Gray Gray
(MUNSELL Code) (2.5Y 4.5/0.7) (2.5Y 4.5/0.7) (2.5Y 4.5/0.7)
Height mm 1,950 1,950 1,950
(in.) (76-3/4) (76-3/4) (76-3/4)
Outer Width mm 800 1,100 1,400
Dimensions (in.) (31-1/2) (43-5/16) (55-1/8)
Depth mm 500 500 500
(in.) (19-11/16) (19-11/16) (19-11/16)
Net Weight kg 150 250 295
(lbs.) (331) (551) (650)
Refrigerant R-22(Holding - Charged)
Flow Control Capillary Tube
Number of Circuits 1 1 1
Compressor Hermetic Scroll Hermetic Scroll Hermetic Scroll
Model 500DH 750EL 1000EL
Quantity 1 1 1
Evaporator Multi-Pass Cross-Finned Tube
Evaporator Fan Multi-Blade Centrifugal Fan
Nominal Air m3/min 44/38 66 88
Flow (Hi/Lo) m3/s 0.73/0.63 1.10 1.47
(cfm) (1,554/1,342) (2,330) (3,108)
Motor kW 0.13 0.25 0.30
(HP) (0.17) (0.33) (0.40)
Quantity 1 1 1
Connections
Refrigerant Piping
Gas Outlet
Size mm 15.88** 19.05** 22.2**
(in.) (5/8) (3/4) (7/8)
Type Brazing Brazing Brazing
Quantity 1 1 1
Liquid Inlet
Size mm 12.7** 12.7** 15.88**
(in.) (1/2) (1/2) (5/8)
Type Brazing Brazing Brazing
Quantity 1 1 1
Condensate Drain Female Piping Thread Screw ( Prepared on Both Sides)
Size FPT 1 1 1
Emergency Drain
Size FPT 1/2 1/2 1/2
Wiring Hole (Prepared on Both Sides)
Size mm 40.5 40.5 40.5
(in.) (1-5/8) (1-5/8) (1-5/8)
Approximate Packing List
Shipping Weight kg 195 300 355
(lbs.) (430) (661) (783)
Height mm 2,125 2,125 2,125
(in.) (83-11/16) (83-11/16) (83-11/16)
Width mm 914 1,214 1,514
(in.) (36) (47-13/16) (59-5/8)
Depth mm 628 628 628
(in.) (24-3/4) (24-3/4) (24-3/4)
Measurements m3 1.22 1.62 2.02

4
GENERAL DATA
Unit General Data (Continued)
Indoor Units: Duct Connection Type
Model RP-5AL4 RP-8AL4 RP-10AL4 RP-15AL2 RP-20AL1 RP-30AL3(S)
kcal/h 12,500 18,500 25,000 39,000 52,000 78,000
50Hz W 14,500 21,500 29,100 45,300 60,500 90,700
Nominal
Btu/h 49,600 73,400 99,200 154,800 206,400 309,500
Cooling
Capacity* kcal/h 13,500 20,000 26,500 42,000 56,000 84,000
60Hz W 15,700 23,300 30,800 48,800 65,100 97,700
Btu/h 53,600 79,400 105,200 166,700 222,200 333,300
Capacity Control % 100, 0 100, 0 100, 0 100, 50, 0 100, 50, 0 100, 50, 0
Cabinet Color Synthetic Resin Paint Baked on Finished Steel Plate
Front Panel, Side Panel Beige Beige Beige Beige Beige Beige
(MUNSELL Code) (2.5Y 8/2) (2.5Y 8/2) (2.5Y 8/2) (2.5Y 8/2) (2.5Y 8/2) (2.5Y 8/2)
Height mm 1,730 1,730 1,730 1,850+30 1,850+30 2,000+30
(in.) (68-1/8) (68-1/8) (68-1/8) (72-13/16+1-3/16) (72-13/16+1-3/16) (78-3/4+1-3/16)
Outer Width mm 800 1,100 1,400 1,400 1,700 2,000
Dimensions (in.) (31-1/2) (43-5/16) (55-1/8) (55-1/8) (66-15/16) (78-3/4)
Depth mm 500 500 500 750 750 900+65
(in.) (19-11/16) (19-11/16) (19-11/16) (29-1/2) (29-1/2) (35-7/16+2-9/16)
Net Weight kg 135 240 280 410 500 669
(lbs.) (297) (529) (617) (904) (1,100) (1,475)
Refrigerant R-22 (Holding-Charged)
Flow Control Capillary Tube
Number of Circuits 1 1 1 2 2 2
Compressor Hermetic Scroll Hermetic Scroll Hermetic Scroll Hermetic Reciprocating Hermetic Reciprocating Hermetic Reciprocating
Model 500DH 750EL 1000EL 753FH3-T 1001FH4-T CB-150
Quantity 1 1 1 2 2 2
Evaporator Multi-Pass Cross-Finned Tube
Evaporator Fan Multi-Blade Centrifugal Fan
3
Nominal Air m /min 44 66 88 130 180 260
3
Flow (Hi/Lo) m /s 0.73 1.10 1.47 2.17 3.0 4.33
(cfm) (1,554) (2,330) (3,108) (4,590) (6,360) (9,180)
Motor kW 0.28 0.35 0.6 2.2 3.7 5.5
(HP) (0.37) (0.5) (0.8) (3) (5) (7-1/2)
Quantity 1 1 1 1 1 1
Connections
Refrigerant Piping
Gas Outlet
Size mm 15.88** 19.05** 22.2** 19.05** 22.2** 25.4**
(in.) (5/8) (3/4) (7/8) (3/4) (7/8) (1)
Type Brazing Brazing Brazing Brazing Brazing Brazing
Quantity 1 1 1 2 2 2
Liquid Inlet
Size mm 12.7** 12.7** 15.88** 15.88** 15.88** 19.05**
(in.) (1/2) (1/2) (5/8) (5/8) (5/8) (3/4)
Type Brazing Brazing Brazing Brazing Brazing Brazing
Quantity 1 1 1 2 2 2
Condensate Drain Female Piping Thread Screw ( Prepared on Both Sides)
Size FPT 1 1 1 1 1 1
Emergency Drain Female Piping Thread Screw ( Prepared on Both Sides)
Size FPT 1/2 1/2 1/2 1/2 1/2 1/2
Wiring Hole (Prepared on Both Sides)
Size mm 40.5 40.5 40.5 62 62 62
(in.) (1-5/8) (1-5/8) (1-5/8) (2-7/16) (2-7/16) (2-7/16)
Approximate Packing List
Shipping Weight kg 175 280 335 520 620 755
(lbs.) (386) (617) (739) (1,146) (1,367) (1,665)
Height mm 1,905 1,905 1,905 2,070 2,070 2,225
(in.) (75) (75) (75) (81-1/2) (81-1/2) (87-5/8)
Width mm 914 1,214 1,514 1,510 1,810 2,160
(in.) (36) (47-13/16) (59-5/8) (59-7/16) (71-1/4) (85-1/16)
Depth mm 628 628 628 880 880 1,105
(in.) (24-3/4) (24-3/4) (24-3/4) (34-5/8) (34-5/8) (43-1/2)
3
Measurements m 1.09 1.45 1.81 2.75 3.30 5.31

NOTE:
1. Piping sizes with asterisks (**) indicate the connection sizes of field-supplied copper pipes.
2. Connection pipes for liquid refrigerant and gas refrigerant between the refrigerant pipes for liquid r e f r i g e r a n t a n d g a s r e f r i g e r a n t
b e t w e e n the refrigerant stop valve in the unit and a field-supplied copper pipe are shipped with the units as a standard accessory.

5
GENERAL DATA
Unit General Data (Continued)
Outdoor Units
Model RCR-5A4 RCR-8A4 RCR-10A4 RCR-15A4 RCR-16A4
Cabinet Color Synthetic Resin Paint Baked on Finished Steel Plate
Panel Beige Beige Beige Beige Beige
(MUNSELL Code) (2.5Y 8/2) (2.5Y 8/2) (2.5Y 8/2) (2.5Y 8/2) (2.5Y 8/2)
Height mm 780 880 1,226 1,226 955
(in.) (30-11/16) (34-5/8) (48-1/4) (48-1/4) (37-5/8)
Outer Width mm 795 795 940 940 966
Dimensions (in.) (31-1/4) (31-1/4) (37) (37) (38-1/32)
Depth mm 895 895 1,155 1,850 1,806
(in.) (35-5/8) (35-5/8) (45-1/2) (72-13/16) (71-1/8)
Net Weight kg 70 85 115 180 177
(lbs.) (154) (187) (254) (396) (390)
Refrigerant R-22(Holding-Charged)
Number of Circuits 1 1 1 2 1
Condenser Multi-Pass Cross-Finned Tube
Condenser Fan Direct Drive Propeller Fan
#
Motor kW 0.25 0.4 0.4 0.3 0.6
(hp) (1/3) (1/2) (1/2) (1/2.5) (1/1.25)
Quantity 1 1 1 2 2
Connections
Refrigerant Piping
Gas Inlet
Size mm 15.88 19.05 22.2 19.05 25.4
(in.) (5/8) (3/4) (7/8) (3/4) (1)
Type Brazing Brazing Brazing Brazing Brazing
Quantity 1 1 1 2 1
Liquid Outlet
Size mm 12.7 12.7 15.88 15.88 19.05
(in.) (1/2) (1/2) (5/8) (5/8) (3/4)
Type Brazing Brazing Brazing Brazing Brazing
Quantity 1 1 1 2 1
Approximate Packing List
Shipping Weight kg 100 110 155 260 230
(lbs.) (221) (243) (342) (572) (507)
Height mm 913 1,013 1,383 1,383 1,135
(in.) (35-15/16) (39-7/8) (54-7/16) (54-7/16) (44-11/16)
Width mm 869 869 1,066 1,066 2,005
(in.) (34-5/16) (34-5/16) (41-15/16) (41-15/16) (78-15/16)
Depth mm 1,039 1,039 1,330 2,020 1,055
(in.) (40-15/16) (40-15/16) (52-3/8) (79-1/2) (41-9/16)
3
Measurements m 0.82 0.91 1.96 2.98 2.40
NOTE :
1. The condenser fan motor marked with a sharp ( # ) for 380V 50Hz and 415V 50Hz, when the power source is 220V 60Hz or 220V 50Hz
the output of condenser fan motor will be 0.4 kW .
2. The nominal cooling capacity is the combined capacity when the indoor unit is connected with the HITACHI s t a n d a r d o u t d o o r
u n i t . a n d i s bas ed o n the s tan da rd of JIS B8616-1984.
3. Temperature Conditions: Evaporator Air Inlet Temperature: 27℃DB/19.5℃WB (80.6℉ DB/67.1℉WB)
Condenser Air Inlet Temperature: 35℃DB (95℉DB)
Piping Length : 5 Meters

Standard Power Source Working Range


Main (3φ ) Control (1φ ) (For HITACHI Standard Outdoor Unit Combinations)
220V 60Hz 220V 60Hz
220V 50Hz 220V 50Hz Evaporator Air Inlet Temperature:
380V 50Hz 220V 50Hz Maximum: 32℃DB/22.5℃WB (89.6℉DB/72.5℉WB)
415V 50Hz 240V 50Hz
Minimum: 19.5℃DB/14℃WB (67.1℉DB/57.2℉WB)
HITACHI Standard Combinations (However, when the unit is operating at an outdoor
Indoor Units Outdoor Units temperature of 52℃DB (125.6℉DB) the maximum wet bulb
RP-5A4 + RCR-5A4 temperature shall be 18℃WB (64.4℉WB).)
RP-5AL4 + RCR-5A4
RP-8A4 + RCR-8A4
RP-8AL4 + RCR-8A4 Condenser Air Inlet Temperatures: ℃(℉)DB
RP-10A4 + RCR-10A4
Unit Power Frequency Maximum Minimum
RP-10AL4 + RCR-10A4
50Hz 52(126)++
RP-15AL2 + RCR-15A4 21(69.8)
60Hz 50(122)++
RP-20AL1 + 2×RCR-10A4 ++The air flow cannot be increased exceeding the standard
RP-30AL3(S) + 2×RCR-16A4 air flow. Refer to the “Fan Performance Curve”.

6
DIMENSIONAL DATA
Unit Dimensions
Free - Blow Type Indoor Units

RP-5A4

RP-8A4

7
DIMENSIONAL DATA
Unit Dimensions (Continued)
Free-Blow Type Indoor Units (Continued)

RP-10A4

Duct Connection Type Indoor Units

RP-5AL4

8
DIMENSIONAL DATA
Unit Dimensions (Continued)
Duct Connection Type Indoor Units (Continued)

RP-8AL4

RP-10AL4

9
DIMENSIONAL DATA
Unit Dimensions (Continued)
Duct Connection Type Indoor Units (Continued)

RP-15AL2

RP-20AL1

10
DIMENSIONAL DATA
Unit Dimensions (Continued)
Duct Connection Type Indoor Units (Continued)

RP-30AL3(S)

Outdoor Units

RCR-5A4

11
DIMENSIONAL DATA
Unit Dimensions (Continued)
Outdoor Units (Continued)

RCR-8A4

Outdoor Units

RCR-10A4

12
DIMENSIONAL DATA
Unit Dimensions (Continued)
Outdoor Units (Continued)

RCR-15A4

RCR-16A4

13
SELECTION DATA
Operation Space

Indoor Unit Outdoor Unit

Dimensions(mm) NOTES:
Model 1. Interchange “B” and “C” when left-hand side refrigerant piping
A B C D
is prepared.
RP-5A4 1,000 500 500 ─ 2. Dimension “D” for model RP-30AL3(S) indicates the case
RP-5AL4 1,000 500 500 ─ where suction ducting is not installed. Change dimension “D”
to 1,500mm, when the suction duct is required.
RP-8A4 1,000 500 500 ─ 3. Dimension “C” for model RP-30AL3(S) indicates the service
RP-8AL4 1,000 500 500 ─ space for the air filter equipped with the unit. Change
dimension “B” to 1,000mm, when the service space for the air
RP-10A4 1,000 500 500 ─ filter from the left side is required.
RP-10AL4 1,000 500 500 ─
RP-15AL2 1,000 500 500 ─
RP-20AL1 1,000 500 500 ─
RP-30AL3(S) 1,000 500 1,000 1,000

Weight Balance
Indoor Unit
Model RP-5A4 RP-5AL4 RP-8A4 RP-8AL4 RP-10A4 RP-10AL4 RP-15AL2 RP-20AL1 RP-30AL3(S)
Location Weight Distribution (kg)
33.8 30.4 58.0 55.7 66.2 62.9 92 114 144
34.1 30.7 54.5 52.3 73.5 69.7 111 123 180
41.2 37.1 66.5 63.9 81.7 77.5 113 137 192
40.9 36.8 71.0 68.1 73.6 69.9 94 126 153
Length Center of Gravity (mm)
A 438 438 605 605 737 737 705 868 1,030
B 362 362 495 495 663 663 695 780 970
C 249 249 258 258 237 237 340 350 390
D 251 251 242 242 263 263 410 380 490
Approximate Operating Weight (kg)
150 135 250 240 295 280 410 500 669

Outdoor Unit Indoor Unit


Model RCR-5A4 RCR-8A4 RCR-10A4 RCR-15A4 RCR-16A4
Location Weight Distribution (kg)
18.1 20.0 29.0 1.3 24
17.9 23.7 28.7 1.3 22
17.1 20.8 31.1 3.7 33
16.9 20.5 26.2 3.5 35
─ ─ ─ 88.7 30
─ ─ ─ 81.5 33 Outdoor Unit
Length Center of Gravity (mm)
A 435 435 580 940 940
B 460 460 575 910 910
C 400 400 430 470 470
D 395 395 510 470 470
Approximate Operating Weight (kg)
70 85 115 180 177

14
SELECTION DATA
Selection Guide
Selection Example
1. Determine the System Requirements 4. Correct the Sensible Heat Capacity (If Required)
Calculate the total cooling load. sensible heat Correct the sensible heat capacity for the given 29℃
load and external static pressure of the evaporator
evaporator air inlet dry bulb temperature from the
fan, if required, according to the design
conditions which include the condenser air tabulated 27℃dry bulb temperature (DB*) according
inlet temperature, evaporator air inlet dry bulb to the following formula.
temperature, evaporator air inlet wet bulb SHC = SHC*+CR×(DB-DB*), where
temperature and evaporator air flow. Clarify the
SHC = sensible heat capacity given in the table
power source frequency and the air supply
system (direct-blow or duct distribution). (×1000kcal/h),
SHC* = sensible heat capacity given in the table
Given Conditions:
Total Cooling Load 18,000 kcal/h (×1000kcal/h),
Sensible Heat Load 11,000 kcal/h DB = given evaporator air inlet dry bulb temperature
Condenser Air Inlet Temperature 35 ℃ (℃), and
Evaporator Air Inlet Dry Bulb 29 ℃ DB* = evaporator air inlet dry bulb
temperature given in the table (℃).
Evaporator Air Inlet Wet Bulb 20 ℃
Evaporator Air Flow 63 m3/min. For this example.
External Static Pressure 8 mmAq
Air Supply System By Ducting SHC = 12.9+0.908×(29-27)=14.7(×1000kcal/h).
Power Source Frequency 50 Hz

2. Select a Matching Packaged Air Conditioner NOTES:


Select models RP-8AL4 + RCR-8A4 by entering 3 5 1. The units cannot be operated under the conditions
℃ condenser air inlet temperature and 20 indicated by blank mark (-) in the table.
2. Direct interpolation is permissible. Do not
℃ evaporator inlet wet bulb (WB) at 60m 3/min,
extrapolate.
evaporator air flow (QA) in the cooling capacity
table.

3. Read the Performances


The total cooling capacity ( TC ), sensible
heat capacity (SHC*) at the dry bulb given in the
table, compressor power input (IPT) and
sensible heat correction factor (CR) can be
determined by interpolation (some can be
directly read from the table when the conditions
coincide with the tabulated figures).

At 20℃WB
TC SHC* IPT CR
(x1000kcal/h) (x1000kcal/h) (kW)
At 60 m3/min.QA 18.4 12.5 6.5 0.869
At 66 m3/min.QA 19.0 13.2 6.6 0.946

At 63 m3/min.QA 18.7 12.9 6.6 0.908

15
SELECTION DATA
Cooling Capacities
─ 50Hz ─ Conversion Multiplier: 1 kcal/h = 1.163 W
= 3.968 Btu/h
Evaporator Inlet Air Condenser Air Inlet Temperature (℃)
Model QA WB DB* 20 25 30 35 40 46 52
-CR- (℃) TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT
18 25 12.6 8.3 3.7 12.2 8.1 4.0 11.7 7.9 4.2 11.2 7.7 4.5 10.6 7.4 4.7 9.9 7.1 5.1 9.0 6.7 5.4
35
20 27 13.5 8.3 3.8 13.1 8.1 4.1 12.5 7.9 4.3 12.0 7.6 4.6 11.4 7.4 4.8 10.6 7.0 5.2 9.7 6.7 5.5
-0.473-
22 30 14.1 8.6 3.9 13.6 8.4 4.2 13.1 8.1 4.4 12.5 7.9 4.7 11.9 7.7 5.0 11.1 7.4 5.3 10.2 7.0 5.7
16 23 12.1 8.8 3.6 11.7 8.6 3.9 11.2 8.4 4.2 10.7 8.1 4.4 10.2 7.9 4.6 9.4 7.5 5.0 8.7 7.2 5.3
40 18 25 13.1 8.9 3.8 12.7 8.6 4.0 12.2 8.4 4.3 11.6 8.2 4.5 11.1 7.9 4.8 10.3 7.6 5.1 9.4 7.2 5.5
-0.532- 20 27 14.1 8.8 3.9 13.6 8.6 4.1 13.0 8.4 4.4 12.4 8.1 4.6 11.8 7.9 4.9 11.0 7.5 5.3 10.1 7.2 5.6
22 30 14.7 9.1 4.0 14.1 8.9 4.2 13.6 8.7 4.5 13.0 8.5 4.8 12.3 8.2 5.0 11.5 7.9 5.4 10.6 7.6 5.7
14 20 11.3 8.5 3.6 10.9 8.3 3.8 10.5 8.1 4.1 10.0 7.8 4.3 9.5 7.6 4.5 8.9 7.3 4.9 8.1 6.9 5.2
16 23 12.5 9.2 3.7 12.0 9.0 3.9 11.5 8.8 4.2 11.0 8.5 4.4 10.5 8.3 4.7 9.7 7.9 5.0 8.9 7.6 5.3
44
RP-5A4 18 25 13.5 9.3 3.8 13.1 9.1 4.1 12.5 8.8 4.3 12.0 8.6 4.6 11.4 8.3 4.8 10.6 8.0 5.2 9.6 7.6 5.5
-0.577-
RP-5AL4 20 27 14.5 9.2 3.9 14.0 9.0 4.2 13.4 8.8 4.4 12.8 8.5 4.7 12.2 8.3 5.0 11.3 7.9 5.3 10.4 7.6 5.6
+ 22 30 15.1 9.6 4.0 14.6 9.4 4.3 14.0 9.2 4.5 13.4 8.9 4.8 12.7 8.7 5.1 11.8 8.3 5.5 10.9 8.0 5.8
RCR-5A4 14 20 11.6 8.9 3.6 11.2 8.7 3.9 10.8 8.4 4.1 10.3 8.2 4.3 9.8 8.0 4.6 9.1 7.6 4.9 8.4 7.3 5.2
16 23 12.8 9.6 3.7 12.4 9.4 4.0 11.9 9.2 4.2 11.4 8.9 4.5 10.8 8.7 4.7 10.0 8.3 5.1 9.2 8.0 5.4
48
18 25 13.9 9.7 3.8 13.4 9.5 4.1 12.9 9.2 4.4 12.3 9.0 4.6 11.7 8.7 4.9 10.9 8.4 5.2 9.9 8.0 5.6
-0.621-
20 27 14.9 9.7 3.9 14.4 9.4 4.2 13.8 9.2 4.5 13.2 9.0 4.7 12.5 8.7 5.0 11.7 8.3 5.4 10.7 8.0 5.7
22 30 15.6 10.0 4.0 15.0 9.8 4.3 14.4 9.6 4.6 13.8 9.4 4.8 13.1 9.1 5.1 12.2 8.8 5.5 11.2 8.4 5.9
14 20 12.0 9.3 3.6 11.6 9.1 3.9 11.2 8.9 4.1 10.7 8.7 4.4 10.1 8.4 4.6 9.4 8.1 5.0 8.6 7.7 5.3
16 23 13.3 10.1 3.8 12.8 9.9 4.0 12.3 9.7 4.3 11.8 9.4 4.5 11.2 9.2 4.8 10.4 8.8 5.1 9.5 8.5 5.5
53
18 25 14.4 10.2 3.9 13.9 10.0 4.1 13.4 9.8 4.4 12.8 9.5 4.7 12.1 9.2 4.9 11.3 8.9 5.3 10.3 8.5 5.6
-0.673-
20 27 15.4 10.2 4.0 14.9 10.0 4.3 14.3 9.7 4.5 13.7 9.5 4.8 13.0 9.2 5.1 12.1 8.8 5.4 11.1 8.5 5.8
22 30 16.1 10.6 4.1 15.5 10.4 4.4 14.9 10.1 4.6 14.2 9.9 4.9 13.5 9.6 5.2 12.6 9.3 5.6 11.6 9.0 5.9
18 25 18.4 12.4 5.2 17.8 12.1 5.6 17.1 11.8 5.9 16.3 11.4 6.2 15.5 11.1 6.6 14.4 10.6 7.1 13.1 10.0 7.6
50
20 27 19.7 12.3 5.3 19.0 12.0 5.7 18.3 11.7 6.1 17.5 11.4 6.4 16.6 11.0 6.8 15.4 10.5 7.3 14.2 10.0 7.7
-0.738-
22 30 20.6 12.8 5.5 19.8 12.5 5.9 19.0 12.1 6.2 18.2 11.8 6.6 17.3 11.5 7.0 16.1 11.0 7.5 14.9 10.6 7.9
16 23 17.9 13.4 5.1 17.2 13.1 5.5 16.6 12.8 5.9 15.8 12.5 6.2 15.0 12.1 6.5 14.0 11.6 7.0 12.8 11.1 7.5
60 18 25 19.4 13.5 5.3 18.7 13.2 5.7 18.0 12.9 6.0 17.2 12.5 6.4 16.3 12.2 6.7 15.2 11.7 7.2 13.8 11.1 7.7
-0.869- 20 27 20.8 13.5 5.4 20.1 13.2 5.8 19.3 12.8 6.2 18.4 12.5 6.5 17.5 12.1 6.9 16.2 11.6 7.4 14.9 11.1 7.9
22 30 21.7 14.0 5.6 20.9 13.7 6.0 20.1 13.4 6.3 19.2 13.1 6.7 18.2 12.7 7.1 17.0 12.2 7.6 15.6 11.8 8.1
14 20 16.7 13.0 5.0 16.1 12.7 5.4 15.5 12.4 5.7 14.8 12.1 6.0 14.1 11.7 6.4 13.1 11.2 6.9 12.0 10.7 7.3
16 23 18.4 14.1 5.2 17.8 13.8 5.6 17.1 13.5 5.9 16.3 13.2 6.2 15.5 12.8 6.6 14.4 12.3 7.1 13.2 11.8 7.5
66
RP-8A4 18 25 20.0 14.2 5.3 19.3 13.9 5.7 18.5 13.6 6.1 17.7 13.2 6.4 16.8 12.9 6.8 15.6 12.4 7.3 14.3 11.8 7.8
-0.946-
RP-8AL4 20 27 21.4 14.2 5.5 20.7 13.9 5.9 19.8 13.5 6.2 19.0 13.2 6.6 18.0 12.8 7.0 16.7 12.3 7.5 15.4 11.8 8.0
+ 22 30 22.3 14.8 5.6 21.5 14.5 6.0 20.7 14.1 6.4 19.8 13.8 6.8 18.8 13.4 7.2 17.5 13.0 7.7 16.1 12.5 8.2
RCR-8A4 14 20 17.2 13.6 5.1 16.6 13.3 5.4 16.0 13.0 5.8 15.2 12.7 6.1 14.5 12.3 6.4 13.5 11.8 6.9 12.3 11.3 7.4
16 23 19.0 14.8 5.2 18.3 14.5 5.6 17.6 14.2 6.0 16.8 13.8 6.3 15.9 13.5 6.7 14.8 13.0 7.2 13.6 12.4 7.6
72
18 25 20.6 14.9 5.4 19.9 14.6 5.8 19.1 14.3 6.1 18.2 13.9 6.5 17.3 13.5 6.9 16.1 13.0 7.4 14.7 12.4 7.8
-1.02-
20 27 22.0 14.8 5.5 21.3 14.5 5.9 20.4 14.2 6.3 19.5 13.8 6.6 18.5 13.4 7.0 17.2 13.0 7.6 15.8 12.4 8.0
22 30 23.0 15.5 5.7 22.2 15.2 6.1 21.3 14.9 6.5 20.3 14.5 6.8 19.3 14.1 7.2 18.0 13.7 7.8 16.6 13.2 8.3
14 20 17.8 14.4 5.1 17.3 14.1 5.5 16.6 13.8 5.8 15.8 13.4 6.2 15.0 13.1 6.5 14.0 12.6 7.0 12.8 12.1 7.4
16 23 19.7 15.7 5.3 19.0 15.4 5.7 18.2 15.1 6.0 17.4 14.7 6.4 16.5 14.3 6.7 15.4 13.8 7.3 14.1 13.3 7.7
80
18 25 21.4 15.8 5.5 20.6 15.5 5.8 19.8 15.2 6.2 18.9 14.8 6.6 18.0 14.4 7.0 16.7 13.9 7.5 15.2 13.3 7.9
-1.12-
20 27 22.9 15.7 5.6 22.1 15.4 6.0 21.2 15.1 6.4 20.3 14.7 6.7 19.2 14.3 7.1 17.9 13.8 7.7 16.4 13.3 8.1
22 30 23.9 16.5 5.7 23.0 16.2 6.2 22.1 15.8 6.5 21.1 15.5 6.9 20.1 15.1 7.3 18.7 14.6 7.9 17.2 14.1 8.3
18 25 24.7 16.4 6.4 23.9 16.0 6.8 22.9 15.6 7.3 21.9 15.1 7.7 20.8 14.6 8.1 19.3 14.0 8.7 17.6 13.2 9.3
65
20 27 26.5 16.4 6.5 25.5 16.0 7.0 24.5 15.5 7.4 23.4 15.0 7.9 22.2 14.5 8.3 20.7 13.9 8.9 19.0 13.2 9.5
-0.955-
22 30 27.6 16.9 6.7 26.6 16.5 7.2 25.5 16.1 7.6 24.4 15.6 8.1 23.2 15.1 8.5 21.6 14.5 9.2 19.9 13.9 9.7
16 23 24.0 17.8 6.3 23.1 17.4 6.7 22.2 16.9 7.2 21.2 16.5 7.6 20.1 16.0 8.0 18.7 15.3 8.6 17.1 14.7 9.1
78 18 25 26.0 17.9 6.5 25.1 17.5 6.9 24.1 17.1 7.4 23.0 16.6 7.8 21.9 16.1 8.3 20.3 15.4 8.9 18.5 14.7 9.4
-1.13- 20 27 27.9 17.8 6.6 26.9 17.4 7.1 25.8 17.0 7.6 24.7 16.5 8.0 23.4 16.0 8.5 21.8 15.3 9.1 20.0 14.7 9.7
22 30 29.1 18.5 6.8 28.0 18.1 7.3 26.9 17.7 7.8 25.7 17.2 8.2 24.4 16.7 8.7 22.7 16.1 9.4 21.0 15.5 9.9
14 20 22.5 17.4 6.2 21.8 17.0 6.6 20.9 16.6 7.0 20.0 16.1 7.4 19.0 15.6 7.9 17.7 15.0 8.4 16.2 14.3 9.0
16 23 24.9 18.9 6.4 24.0 18.5 6.8 23.0 18.1 7.3 22.0 17.6 7.7 20.9 17.1 8.1 19.4 16.4 8.7 17.8 15.7 9.3
88
RP-10A4 18 25 27.0 19.1 6.6 26.1 18.6 7.0 25.0 18.2 7.5 23.9 17.7 7.9 22.7 17.2 8.4 21.1 16.5 9.0 19.2 15.8 9.5
-1.26-
RP-10AL4 20 27 28.9 19.0 6.7 27.9 18.6 7.2 26.8 18.1 7.7 25.6 17.6 8.1 24.3 17.1 8.6 22.6 16.4 9.2 20.7 15.7 9.8
+ 22 30 30.2 19.8 6.9 29.1 19.3 7.4 27.9 18.9 7.9 26.7 18.4 8.3 25.3 17.9 8.8 23.6 17.3 9.5 21.8 16.7 10.0
RCR-10A4 14 20 23.4 18.4 6.2 22.6 18.0 6.7 21.7 17.6 7.1 20.7 17.1 7.5 19.7 16.6 7.9 18.3 16.0 8.5 16.8 15.3 9.1
16 23 25.8 20.1 6.4 24.9 19.6 6.9 23.9 19.2 7.3 22.8 18.7 7.8 21.7 18.2 8.2 20.1 17.5 8.8 18.5 16.8 9.4
98
18 25 28.0 20.2 6.6 27.0 19.8 7.1 26.0 19.3 7.6 24.8 18.8 8.0 23.6 18.3 8.5 21.9 17.6 9.1 20.0 16.8 9.7
-1.38-
20 27 30.0 20.1 6.8 29.0 19.7 7.3 27.8 19.2 7.8 26.5 18.7 8.2 25.2 18.2 8.7 23.4 17.5 9.3 21.5 16.8 9.9
22 30 31.3 21.0 7.0 30.2 20.6 7.5 29.0 20.1 8.0 27.7 19.6 8.4 26.3 19.1 8.9 24.5 18.5 9.6 22.6 17.8 10.2
14 20 24.0 19.1 6.3 23.2 18.7 6.7 22.2 18.3 7.2 21.3 17.8 7.6 20.2 17.3 8.0 18.8 16.7 8.6 17.2 16.0 9.1
16 23 26.4 20.9 6.5 25.5 20.4 7.0 24.5 20.0 7.4 23.4 19.5 7.8 22.2 19.0 8.3 20.6 18.3 8.9 18.9 17.6 9.4
105
18 25 28.7 21.0 6.7 27.7 20.5 7.2 26.6 20.1 7.6 25.4 19.6 8.0 24.1 19.1 8.5 22.4 18.4 9.2 20.5 17.6 9.7
-1.46-
20 27 30.7 20.9 6.9 29.7 20.5 7.4 28.5 20.0 7.8 27.2 19.5 8.3 25.8 18.9 8.7 24.0 18.3 9.4 22.0 17.5 10.0
22 30 32.1 21.8 7.0 30.9 21.4 7.5 29.7 21.0 8.0 28.3 20.5 8.5 26.9 20.0 9.0 25.1 19.3 9.7 23.1 18.6 10.2

QA: Evaporator Air Flow (m3/min) TC: Total Cooling Capacity (×1000 kcal/h)
CR: Sensible Heat Correction Factor SHC*: Sensible Heat Capacity (×1000 kcal/h)
WB: Evaporator Air Inlet Wet Bulb (℃) (Given for Each WB and DB*)
DB*: Evaporator Air Inlet Dry Bulb (℃) Given for Each WB IPT: Input Power of One Compressor (kW)

16
SELECTION DATA
Cooling Capacities (Continued)
─ 50Hz ─ Conversion Multiplier: 1 kcal/h = 1.163 W
= 3.968 Btu/h
Evaporator Inlet Air Condenser Air Inlet Temperature (℃)
Model QA WB DB* 20 25 30 35 40 46 52
-CR- (℃) TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT
18 25 38.4 26.0 11.2 37.0 25.4 12.2 35.6 24.8 13.0 34.0 24.0 13.6 32.3 23.3 14.4 30.0 22.3 15.2 28.4 21.7 15.8
95
20 27 41.4 25.9 11.6 39.7 25.3 12.4 38.1 24.6 13.2 36.4 23.9 14.0 34.5 23.2 14.8 32.1 22.2 15.6 30.4 21.5 16.2
-1.60-
22 30 42.9 26.9 12.0 41.3 26.3 12.4 39.7 25.6 13.6 37.9 24.9 14.4 36.0 24.2 15.2 33.5 23.3 16.0 31.7 22.6 16.6
16 23 37.3 28.4 11.2 36.0 27.8 12.0 34.5 27.2 12.8 33.0 26.5 13.6 31.3 25.7 14.2 29.1 24.7 15.0 27.5 24.1 15.6
115 18 25 40.5 28.6 11.6 39.1 28.0 12.4 37.5 27.3 13.2 35.8 26.6 14.0 34.0 25.9 14.6 31.6 24.9 15.6 30.0 24.2 16.0
-1.90- 20 27 43.3 28.5 11.8 41.8 27.9 12.8 40.2 27.2 13.6 38.4 26.5 14.2 36.4 25.7 15.0 33.9 24.7 16.0 32.1 24.0 16.4
22 30 45.2 29.7 12.1 43.6 29.1 13.0 41.8 28.4 14.0 40.0 27.7 14.6 38.0 27.0 15.4 35.4 26.1 16.4 33.5 25.4 16.8
14 20 35.1 27.9 11.0 33.9 27.3 11.8 32.6 26.6 12.6 31.1 26.0 13.2 29.5 25.2 14.0 27.5 24.3 14.8 25.9 23.6 15.2
16 23 38.7 30.4 11.4 37.4 29.8 12.2 35.9 29.1 13.0 34.3 28.4 13.8 32.5 27.6 14.4 30.2 26.6 15.2 28.6 25.9 15.8
130
18 25 42.1 30.6 11.8 40.6 29.9 12.6 39.0 29.3 13.4 37.2 28.5 14.2 35.4 27.8 14.8 32.9 26.7 15.8 31.2 26.0 16.2
-2.11-
20 27 45.0 30.4 12.0 43.5 29.8 12.8 41.7 29.1 13.8 39.9 28.4 14.4 37.8 27.6 15.2 35.2 26.6 16.2 33.3 25.9 16.6
RP-15AL2 22 30 47.0 31.8 12.4 45.3 31.2 13.2 43.5 30.5 14.0 41.5 29.8 14.8 39.5 29.1 15.6 36.8 28.1 16.6 34.8 27.4 17.2
+ ─ ─ ─
RCR-15A4 14 20 36.4 29.6 11.2 35.2 29.0 12.0 33.8 28.3 12.6 32.3 27.6 13.4 30.6 26.9 14.2 28.5 25.9 15.0
16 23 40.2 32.3 11.6 38.8 31.7 12.4 37.2 31.0 13.2 35.6 30.3 13.8 33.7 29.5 14.6 31.4 28.5 15.4 ─ ─ ─
145
18 25 43.7 32.5 11.8 42.1 31.9 12.8 40.5 31.2 13.6 38.6 30.4 14.2 36.7 29.6 15.0 34.1 28.6 16.0 ─ ─ ─
-2.33-
20 27 46.7 32.4 12.2 45.1 31.7 13.0 43.3 31.0 13.8 41.4 30.3 14.6 39.2 29.5 15.4 36.5 28.4 16.4 ─ ─ ─
22 30 48.8 33.9 12.4 47.0 33.3 13.4 45.1 32.6 14.2 43.1 31.9 15.0 40.9 31.1 15.8 38.2 31.0 16.8
─ ─ ─
─ ─ ─
14 20 37.3 30.7 11.2 36.1 30.1 12.0 34.6 29.5 12.8 33.1 28.8 13.6 31.43 28.0 14.2 29.2 27.0 15.0
16 23 41.1 33.6 11.6 39.7 33.0 12.4 38.1 32.3 13.2 36.4 31.5 14.0 4.6 30.7 14.6 32.1 29.7 15.6 ─ ─ ─
155
18 25 44.8 33.8 12.0 43.1 33.1 12.8 41.4 32.4 13.6 39.6 31.7 14.4 37.6 30.9 15.2 34.9 29.8 16.0 ─ ─ ─
-2.46-
20 27 47.9 33.6 12.2 46.2 33.0 13.2 44.3 32.2 14.0 42.3 31.5 14.8 40.2 30.7 15.6 37.4 29.6 16.4 ─ ─ ─
22 30 49.9 35.3 12.6 48.2 34.6 13.4 46.2 33.9 14.4 44.1 33.2 15.2 41.9 32.4 16.0 39.1 31.4 17.0
─ ─ ─
18 25 51.1 34.8 14.2 49.2 34.0 15.4 47.3 33.1 16.4 45.2 32.2 17.2 42.9 31.2 18.2 39.9 29.9 19.2 37.8 29.0 19.8
130
20 27 54.6 34.7 14.8 52.7 33.9 15.8 50.6 33.0 16.8 48.3 32.0 17.8 45.9 31.0 18.6 42.7 29.8 19.8 40.4 28.9 20.4
-2.15-
22 30 57.0 36.0 15.2 54.9 35.2 16.2 52.7 34.3 17.2 50.4 33.4 18.2 47.9 32.5 19.2 44.6 31.2 20.2 42.2 30.4 21.0
16 23 49.8 38.5 14.2 48.0 37.6 15.2 46.1 36.8 16.2 44.0 35.8 17.2 41.8 34.8 18.0 38.8 33.6 19.0 36.7 32.6 19.6
160 18 25 54.1 38.7 14.6 52.2 37.9 15.6 50.1 37.0 16.6 47.9 36.0 17.6 45.5 35.0 18.6 42.2 33.7 19.6 40.0 32.8 20.2
-2.61- 20 27 57.9 38.5 15.0 55.9 37.7 16.0 53.6 36.8 17.2 51.2 35.8 18.0 48.6 34.8 19.0 45.2 33.5 20.2 42.8 32.6 20.8
22 30 60.4 40.2 15.4 58.2 39.4 16.6 55.9 38.5 17.6 53.4 37.6 18.6 50.7 36.6 19.6 47.3 35.4 20.8 44.7 34.5 21.4
14 20 46.8 37.6 13.8 45.2 36.8 15.0 43.4 36.0 15.8 41.5 35.1 16.8 39.4 34.1 17.6 36.7 32.9 18.6 34.6 31.9 19.2
16 23 51.6 41.1 14.4 49.8 40.2 15.4 47.8 39.3 16.4 45.7 38.4 17.4 43.4 37.4 18.2 40.3 36.1 19.4 38.1 35.1 20.0
180
18 25 56.2 41.3 14.8 54.1 40.4 15.8 52.0 39.5 17.0 49.7 38.6 17.8 47.2 37.5 18.8 43.8 36.2 20.0 41.5 35.3 20.6
-2.91-
20 27 60.1 41.1 15.2 58.0 40.3 16.2 55.6 39.3 17.4 53.1 38.4 18.4 50.4 37.3 19.2 46.9 36.0 20.4 44.4 35.1 21.0
RP-20AL1 22 30 62.7 43.0 15.6 60.4 42.2 16.8 58.0 41.3 17.8 55.4 40.3 18.8 52.6 39.4 19.8 49.0 38.1 21.0 46.4 37.2 21.6
+ ─ ─ ─
RCR-10A4 x2 14 20 48.5 39.9 14.0 46.9 39.1 15.0 45.0 38.2 16.0 43.0 37.3 17.0 40.8 36.3 17.8 38.0 35.0 18.8
16 23 53.5 43.6 14.6 51.6 42.8 15.6 49.6 41.9 16.6 47.4 40.9 17.6 44.9 39.9 18.4 41.8 38.5 19.6 ─ ─ ─
200
18 25 58.2 43.9 15.0 56.1 43.0 16.0 53.9 42.1 17.0 51.5 41.1 18.0 48.9 40.0 19.0 45.4 38.7 20.2 ─ ─ ─
-3.19-
20 27 62.2 43.6 15.4 60.1 42.8 16.4 57.6 41.9 17.6 55.1 40.9 18.6 52.3 39.8 19.4 48.6 38.4 20.6 ─ ─ ─
22 30 64.9 45.8 15.8 62.6 45.0 17.0 60.1 44.0 18.0 57.4 43.1 19.0 54.5 42.1 20.0 50.8 40.8 21.2
─ ─ ─
─ ─ ─
14 20 49.8 41.6 14.2 48.1 40.8 15.2 46.2 39.9 16.2 44.1 39.0 17.0 41.9 38.0 18.0 39.0 36.7 19.0
16 23 54.9 45.6 14.6 53.0 44.7 15.8 50.9 43.8 16.8 48.6 42.8 17.6 46.1 41.7 18.6 42.8 40.4 19.6 ─ ─ ─
215
18 25 59.7 45.8 15.2 57.6 44.9 16.2 55.3 44.0 17.2 52.8 43.0 18.2 50.1 41.9 19.2 46.6 40.5 20.2 ─ ─ ─
-3.40-
20 27 63.9 45.5 15.4 61.6 44.7 16.6 59.2 43.7 17.6 56.5 42.7 18.6 53.6 41.6 19.6 49.9 40.2 20.8 ─ ─ ─
22 30 67.9 47.9 16.0 64.2 47.0 17.0 61.6 46.1 18.2 58.9 45.1 19.2 55.9 44.1 20.2 52.1 42.8 21.4
─ ─ ─
18 25 76.4 51.4 20.4 73.6 50.1 21.8 70.7 48.8 23.2 67.5 47.4 24.5 64.1 45.9 26.0 59.6 43.9 27.9 54.3 41.7 29.6
185
20 27 81.7 51.2 20.9 78.8 49.9 22.4 75.7 48.6 23.8 72.3 47.2 25.1 68.6 45.6 26.6 63.8 43.7 28.6 58.6 41.6 30.4
-3.10-
22 30 85.2 53.0 21.4 82.2 51.7 23.0 78.8 50.4 24.4 75.3 49.1 25.8 71.6 47.6 27.4 66.7 45.8 29.4 61.5 43.9 31.2
16 23 74.6 56.8 20.2 72.0 55.6 21.6 69.1 54.2 23.0 66.0 52.8 24.3 62.6 51.3 25.7 58.2 49.4 27.7 53.3 47.2 29.4
230 18 25 81.1 57.2 20.8 78.2 55.9 22.3 75.1 54.6 23.7 71.7 53.1 25.0 68.1 51.6 26.5 63.3 49.6 28.5 57.7 47.3 30.3
-3.77- 20 27 86.7 56.9 21.3 83.7 55.7 22.9 80.4 54.3 24.3 76.8 52.9 25.7 72.9 51.3 27.2 67.8 49.3 29.3 62.2 47.2 31.1
22 30 90.5 59.3 21.9 87.3 58.1 23.5 83.7 56.7 25.0 80.0 55.3 26.4 76.0 53.9 27.9 70.8 52.0 30.0 65.3 50.0 31.9
14 20 70.2 55.6 19.7 67.9 54.5 21.2 65.2 53.2 22.5 62.3 51.8 23.8 59.1 50.3 25.2 55.0 48.4 27.1 50.4 46.3 28.8
16 23 77.5 60.7 20.4 74.8 59.4 21.9 71.8 58.1 23.3 68.6 56.7 24.6 65.1 55.1 26.1 60.5 53.1 28.0 55.1 50.9 29.8
260
18 25 84.3 61.1 21.1 81.2 59.8 22.6 78.0 58.4 24.0 74.5 56.9 25.4 70.8 55.4 26.9 65.8 53.3 28.9 59.9 51.0 30.7
RP-30AL3(S) -4.21-
20 27 90.1 60.8 21.6 87.0 59.5 23.1 83.5 58.1 24.6 79.8 56.6 26.0 75.7 55.1 27.6 70.4 53.0 29.6 64.6 50.9 31.5
+
22 30 94.0 63.5 22.2 90.7 62.2 23.8 87.0 60.9 25.3 83.1 59.5 26.7 79.0 58.0 28.3 73.6 56.1 30.4 67.8 54.0 32.3
RCR-16A4 x2
14 20 72.8 59.1 20.0 70.5 57.9 21.4 67.6 56.6 22.8 64.6 55.2 24.1 61.3 53.6 25.5 57.1 51.7 27.4 52.2 49.5 29.1
16 23 80.4 64.5 20.7 77.6 63.3 22.2 74.5 61.9 23.6 71.2 60.4 24.9 67.5 58.9 26.4 62.8 56.8 28.4 57.5 54.6 30.1
290
18 25 87.4 64.9 21.3 84.3 63.6 22.8 81.0 62.2 24.3 77.3 60.7 25.7 73.4 59.1 27.2 68.3 57.0 29.2 62.2 54.6 31.0
-4.63-
20 27 93.5 64.6 21.8 90.3 63.3 23.4 86.6 61.9 24.9 82.8 60.4 26.3 78.5 58.8 27.9 73.0 56.7 30.0 67.1 54.5 31.8
22 30 97.5 67.7 22.4 94.1 66.4 24.0 90.3 65.0 25.6 86.2 63.5 27.0 81.9 62.0 28.6 76.4 60.1 30.8 70.4 58.0 32.7
14 20 74.6 61.3 20.1 72.2 60.2 21.6 69.3 58.8 23.0 66.2 57.4 24.2 62.8 55.8 25.7 58.5 53.9 27.6 53.5 51.7 29.3
16 23 82.3 67.1 20.8 79.4 65.8 22.3 76.3 64.4 23.8 72.9 62.9 25.1 69.2 61.3 26.6 64.3 59.2 28.6 58.9 57.0 30.3
310
18 25 89.6 67.5 21.5 86.3 66.1 23.0 82.9 64.7 24.5 79.2 63.2 25.8 75.2 61.5 27.4 69.9 59.4 29.5 63.7 57.0 31.6
-4.90-
20 27 95.8 67.1 22.0 92.5 65.8 23.6 88.7 64.4 25.1 84.7 62.8 26.5 80.4 61.2 28.1 74.8 59.1 30.2 68.7 56.8 32.1
22 30 99.9 70.4 22.6 96.4 69.1 24.2 92.5 67.7 25.8 88.3 66.2 27.2 83.9 64.7 28.8 78.2 62.7 31.0 72.1 60.6 32.9

17
QA: Evaporator Air Flow (m3/min.) TC: Total Cooling Capacity (×1000 kcal/h)
CR: Sensible Heat Correction Factor SHC*: Sensible Heat Capacity (×1000 kcal/h)
WB: Evaporator Air Inlet Wet Bulb (℃) (Given for Each WB and DB*)
DB*: Evaporator Air Inlet Dry Bulb (℃) Given for Each WB IPT: Total Input Power of Compressors (kW)

18
SELECTION DATA
Cooling Capacities (Continued)
─ 60Hz ─ Conversion Multiplier: 1 kcal/h = 1.163 W
= 3.968 Btu/h
Evaporator Inlet Air Condenser Air Inlet Temperature (℃)
Model QA WB DB* 20 25 30 35 40 46 50
-CR- (℃) TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT
18 25 13.7 8.8 4.3 13.2 8.6 4.7 12.6 8.3 4.9 12.1 8.1 5.2 11.5 7.8 5.5 10.7 7.4 5.9 9.7 7.0 6.3
35
20 27 14.6 8.8 4.5 14.1 8.6 4.8 13.5 8.3 5.1 12.9 8.0 5.4 12.3 7.8 5.7 11.4 7.4 6.1 10.5 7.0 6.5
-0.473-
22 30 15.2 9.0 4.6 14.7 8.8 4.9 14.1 8.6 5.2 13.5 8.3 5.5 12.8 8.0 5.8 11.9 7.7 6.3 11.0 7.3 6.6
16 23 13.1 9.3 4.3 12.6 9.0 4.6 12.1 8.8 4.9 11.6 8.5 5.1 11.0 8.2 5.4 10.2 7.9 5.9 9.4 7.5 6.2
40 18 25 14.2 9.4 4.4 13.7 9.1 4.7 13.1 8.9 5.0 12.6 8.6 5.3 11.9 8.3 5.6 11.1 7.9 6.0 10.1 7.5 6.4
-0.532- 20 27 15.2 9.3 4.5 14.7 9.1 4.8 14.1 8.8 5.1 13.4 8.6 5.4 12.8 8.3 5.8 11.9 7.9 6.2 10.9 7.5 6.6
22 30 15.8 9.6 4.6 15.3 9.4 5.0 14.7 9.1 5.3 14.0 8.9 5.6 13.3 8.6 5.9 12.4 8.3 6.3 11.4 7.9 6.7
14 20 12.2 8.9 4.2 11.8 8.7 4.5 11.3 8.5 4.8 10.8 8.2 5.0 10.3 8.0 5.3 9.6 7.6 5.7 8.8 7.2 6.1
16 23 13.5 9.7 4.3 13.0 9.5 4.6 12.5 9.2 4.9 11.9 8.9 5.2 11.3 8.7 5.5 10.5 8.3 5.9 9.6 7.9 6.3
44
RP-5A4 18 25 14.6 9.8 4.4 14.1 9.5 4.8 13.5 9.3 5.1 12.9 9.0 5.3 12.3 8.7 5.7 11.4 8.3 6.1 10.4 7.9 6.5
-0.577-
RP-5AL4 20 27 15.6 9.7 4.6 15.1 9.5 4.9 14.5 9.2 5.2 13.8 9.0 5.5 13.1 8.7 5.8 12.2 8.3 6.2 11.2 7.9 6.6
+ 22 30 16.3 10.1 4.7 15.7 9.8 5.0 15.1 9.6 5.3 14.4 9.3 5.6 13.7 9.0 6.0 12.8 8.7 6.4 11.8 8.3 6.8
RCR-5A4 14 20 12.6 9.3 4.2 12.1 9.1 4.5 11.7 8.9 4.8 11.1 8.6 5.1 10.6 8.3 5.4 9.8 8.0 5.8 9.0 7.6 6.1
16 23 13.9 10.1 4.4 13.4 9.9 4.7 12.8 9.6 5.0 12.3 9.4 5.2 11.6 9.1 5.5 10.8 8.7 6.0 9.9 8.3 6.3
48
18 25 15.1 10.2 4.5 14.5 10.0 4.8 13.9 9.7 5.1 13.3 9.4 5.4 12.7 9.1 5.7 11.8 8.8 6.1 10.7 8.3 6.5
-0.621-
20 27 16.1 10.2 4.6 15.5 9.9 4.9 14.9 9.7 5.2 14.3 9.4 5.5 13.5 9.1 5.9 12.6 8.7 6.3 11.6 8.3 6.7
22 30 16.8 10.5 4.7 16.2 10.3 5.1 15.5 10.0 5.4 14.9 9.8 5.7 14.1 9.5 6.0 13.2 9.1 6.5 12.1 8.8 6.9
14 20 13.0 9.8 4.3 12.6 9.6 4.6 12.1 9.3 4.9 11.5 9.1 5.1 10.9 8.8 5.4 10.2 8.4 5.8 9.3 8.0 6.2
16 23 14.3 10.7 4.4 13.8 10.4 4.7 13.3 10.2 5.0 12.7 9.9 5.3 12.1 9.6 5.6 11.2 9.2 6.0 10.3 8.8 6.4
53
18 25 15.6 10.7 4.5 15.0 10.5 4.9 14.4 10.2 5.2 13.8 9.9 5.5 13.1 9.6 5.8 12.2 9.2 6.2 11.1 8.8 6.6
-0.673-
20 27 16.7 10.7 4.7 16.1 10.4 5.0 15.5 10.2 5.3 14.8 9.9 5.6 14.0 9.6 5.9 13.0 9.2 6.4 12.0 8.8 6.8
22 30 17.4 11.1 4.8 16.8 10.9 5.1 16.1 10.6 5.4 15.4 10.3 5.7 14.6 10.0 6.1 13.6 9.7 6.5 12.6 9.3 6.9
18 25 19.9 13.1 6.5 19.2 12.8 6.9 18.5 12.4 7.4 17.6 12.0 7.8 16.8 11.6 8.2 15.6 11.1 8.9 14.2 10.5 9.4
50
20 27 21.3 13.0 6.6 20.6 12.7 7.1 19.8 12.3 7.6 18.9 12.0 8.0 17.9 11.6 8.4 16.7 11.0 9.1 15.3 10.5 9.6
-0.738-
22 30 22.2 13.4 6.8 21.5 13.1 7.3 20.6 12.8 7.8 19.7 12.4 8.2 18.7 12.0 8.7 17.4 11.5 9.3 16.1 11.0 9.9
16 23 19.3 14.1 6.4 18.6 13.8 6.8 17.9 13.4 7.3 17.1 13.1 7.7 16.2 12.7 8.1 15.1 12.1 8.8 13.8 11.6 9.3
60 18 25 21.0 14.2 6.6 20.3 13.9 7.1 19.5 13.5 7.5 18.6 13.2 7.9 17.7 12.7 8.4 16.4 12.2 9.0 15.0 11.6 9.6
-0.869- 20 27 22.5 14.2 6.7 21.7 13.9 7.2 20.8 13.5 7.7 19.9 13.1 8.1 18.9 12.7 8.6 17.6 12.2 9.2 16.1 11.6 9.8
22 30 23.4 14.7 6.9 22.6 14.4 7.4 21.7 14.0 7.9 20.7 13.6 8.3 19.7 13.2 8.8 18.3 12.7 9.5 16.9 12.2 10.1
14 20 18.0 13.6 6.2 17.4 13.3 6.7 16.7 13.0 7.1 16.0 12.6 7.5 15.2 12.2 7.9 14.1 11.7 8.5 12.9 11.2 9.1
16 23 19.9 14.8 6.4 19.2 14.5 6.9 18.4 14.1 7.4 17.6 13.8 7.8 16.7 13.4 8.2 15.5 12.8 8.8 14.2 12.2 9.4
66
RP-8A4 18 25 21.6 14.9 6.6 20.9 14.6 7.1 20.0 14.2 7.6 19.1 13.8 8.0 18.2 13.4 8.5 16.9 12.9 9.1 15.4 12.3 9.7
-0.946-
RP-8AL4 20 27 23.1 14.9 6.8 22.3 14.5 7.3 21.4 14.2 7.8 20.5 13.8 8.2 19.4 13.4 8.7 18.1 12.8 9.3 16.6 12.3 9.9
+ 22 30 24.1 15.5 7.0 23.3 15.1 7.5 22.3 14.8 8.0 21.3 14.4 8.4 20.3 14.0 8.9 18.9 13.5 9.6 17.4 12.9 10.2
RCR-8A4 14 20 18.6 14.3 6.3 18.0 14.0 6.7 17.2 13.6 7.2 16.5 13.2 7.6 15.6 12.8 8.0 14.6 12.3 8.6 13.3 11.8 9.2
16 23 20.5 15.5 6.5 19.8 15.2 7.0 19.0 14.8 7.4 18.1 14.4 7.8 17.2 14.0 8.3 16.0 13.5 8.9 14.7 12.9 9.5
72
18 25 22.3 15.6 6.7 21.5 15.3 7.2 20.6 14.9 7.6 19.7 14.5 8.1 18.7 14.1 8.6 17.4 13.6 9.2 15.9 12.9 9.8
-1.02-
20 27 23.8 15.6 6.9 23.0 15.2 7.4 22.1 14.9 7.8 21.1 14.5 8.3 20.0 14.0 8.8 18.6 13.5 9.4 17.1 12.9 10.0
22 30 24.9 16.2 7.1 24.0 15.9 7.6 23.0 15.5 8.0 22.0 15.1 8.5 20.9 14.7 9.0 19.5 14.2 9.7 17.9 13.7 10.3
14 20 19.3 15.1 6.4 18.6 14.8 6.8 17.9 14.4 7.3 17.1 14.0 7.7 16.2 13.6 8.1 15.1 13.1 8.7 13.8 12.5 9.3
16 23 21.3 16.5 6.6 20.5 16.1 7.1 19.7 15.7 7.5 18.8 15.3 7.9 17.9 14.9 8.4 16.6 14.4 9.0 15.2 13.8 9.6
80
18 25 23.1 16.6 6.8 22.3 16.2 7.3 21.4 15.8 7.7 20.5 15.4 8.2 19.4 15.0 8.7 18.1 14.4 9.3 16.5 13.8 9.9
-1.12-
20 27 24.7 16.5 7.0 23.9 16.1 7.5 22.9 15.8 7.9 21.9 15.3 8.4 20.8 14.9 8.9 19.3 14.4 9.5 17.8 13.8 10.1
22 30 25.8 17.2 7.1 24.9 16.9 7.7 23.9 16.5 8.1 22.8 16.1 8.6 21.7 15.7 9.1 20.2 15.1 9.8 18.6 14.6 10.4
18 25 26.2 17.1 7.5 25.3 16.7 8.0 24.3 16.2 8.5 23.2 15.7 9.0 22.0 15.2 9.5 20.5 14.5 10.2 18.7 13.7 10.9
65
20 27 28.0 17.1 7.7 27.1 16.6 8.2 26.0 16.2 8.7 24.8 15.6 9.2 23.6 15.1 9.8 21.9 14.4 10.5 20.1 13.7 11.1
-0.955-
22 30 29.3 17.6 7.9 28.2 17.2 8.4 27.1 16.7 9.0 25.9 16.2 9.5 24.6 15.7 10.0 22.9 15.0 10.8 21.1 14.4 11.4
16 23 25.4 18.5 7.4 24.5 18.0 7.9 23.5 17.6 8.4 22.5 17.1 8.9 21.3 16.5 9.4 19.8 15.8 10.1 18.2 15.1 10.7
78 18 25 27.6 18.6 7.6 26.6 18.2 8.2 25.6 17.7 8.7 24.4 17.2 9.2 23.2 16.6 9.7 21.6 15.9 10.4 19.6 15.1 11.1
-1.13- 20 27 29.5 18.6 7.8 28.5 18.1 8.4 27.4 17.6 8.9 26.1 17.1 9.4 24.8 16.6 9.9 23.1 15.9 10.7 21.2 15.1 11.3
22 30 30.8 19.2 8.0 29.7 18.8 8.6 28.5 18.3 9.1 27.2 17.8 9.6 25.9 17.3 10.2 24.1 16.6 11.0 22.2 15.9 11.7
14 20 23.9 18.1 7.2 23.1 17.7 7.7 22.2 17.2 8.2 21.2 16.7 8.7 20.1 16.2 9.2 18.7 15.5 9.9 17.1 14.8 10.5
16 23 26.4 19.6 7.5 25.4 19.2 8.0 24.4 18.7 8.5 23.3 18.2 9.0 22.1 17.7 9.5 20.6 17.0 10.3 18.9 16.2 10.9
88
RP-10A4 18 25 28.7 19.8 7.7 27.6 19.3 8.3 26.5 18.8 8.8 25.4 18.3 9.3 24.1 17.8 9.8 22.4 17.1 10.6 20.4 16.2 11.2
-1.26-
RP-10AL4 20 27 30.7 19.7 7.9 29.6 19.2 8.5 28.4 18.8 9.0 27.1 18.2 9.5 25.8 17.7 10.1 24.0 17.0 10.8 22.0 16.2 11.5
+ 22 30 32.0 20.5 8.1 30.8 20.0 8.7 29.6 19.5 9.2 28.3 19.0 9.8 26.9 18.5 10.3 25.0 17.8 11.1 23.1 17.1 11.8
RCR-10A4 14 20 24.8 19.1 7.3 24.0 18.7 7.8 23.0 18.2 8.3 22.0 17.7 8.8 20.9 17.2 9.3 19.4 16.5 10.0 17.8 15.8 10.6
16 23 27.3 20.8 7.6 26.4 20.3 8.1 25.3 19.9 8.6 24.2 19.3 9.1 23.0 18.8 9.6 21.3 18.1 10.4 19.6 17.3 11.0
98
18 25 29.7 20.9 7.8 28.7 20.5 8.4 27.5 20.0 8.9 26.3 19.4 9.4 25.0 18.9 9.9 23.2 18.2 10.7 21.2 17.3 11.3
-1.38-
20 27 31.8 20.8 8.0 30.7 20.4 8.6 29.5 19.9 9.1 28.1 19.3 9.6 26.7 18.8 10.2 24.8 18.1 11.0 22.8 17.3 11.6
22 30 33.2 21.7 8.2 32.0 21.2 8.8 30.7 20.8 9.4 29.3 20.2 9.9 27.9 19.7 10.5 26.0 19.0 11.2 23.9 18.3 11.9
14 20 25.4 19.8 7.4 24.6 19.4 7.9 23.6 18.9 8.4 22.5 18.4 8.9 21.4 17.9 9.4 19.9 17.2 10.1 18.2 16.4 10.7
16 23 28.0 21.6 7.6 27.0 21.1 8.2 26.0 20.6 8.7 24.8 20.1 9.2 23.5 19.6 9.7 21.9 18.8 10.4 20.0 18.0 11.1
105
18 25 30.5 21.7 7.9 29.4 21.3 8.4 28.2 20.8 9.0 26.9 20.2 9.4 25.6 19.7 10.0 23.8 18.9 10.8 21.7 18.1 11.4
-1.46-
20 27 32.6 21.6 8.1 31.5 21.2 8.6 30.2 20.7 9.2 28.8 20.1 9.7 27.4 19.5 10.3 25.5 18.8 11.0 23.4 18.0 11.7
22 30 34.0 22.6 8.3 32.8 22.1 8.9 31.5 21.6 9.4 30.0 21.1 9.9 28.6 20.5 10.5 26.6 19.8 11.3 24.5 19.1 12.0

QA: Evaporator Air Flow (m3/min.) TC: Total Cooling Capacity (×1000 kcal/h)
CR: Sensible Heat Correction Factor SHC*: Sensible Heat Capacity (×1000 kcal/h)
WB: Evaporator Air Inlet Wet Bulb (℃) (Given for Each WB and DB*)
DB*: Evaporator Air Inlet Dry Bulb (℃) Given for Each WB IPT: Input Power of One Compressor (kW)

19
SELECTION DATA
Cooling Capacities (Continued)
─ 60Hz ─ Conversion Multiplier: 1 kcal/h = 1.163 W
= 3.968 Btu/h
Evaporator Inlet Air Condenser Air Inlet Temperature (℃)
Model QA WB DB* 20 25 30 35 40 46 50
-CR- (℃) TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT
18 25 41.4 27.4 13.5 39.9 26.7 14.3 38.3 26.0 15.3 36.6 25.2 16.1 34.7 24.4 17.0 32.3 23.3 18.0 ─ ─ ─
95
20 27 44.2 27.3 13.7 42.7 26.6 14.7 41.0 25.9 15.7 39.2 25.1 16.6 37.2 24.3 17.4 34.6 23.2 18.4 ─ ─ ─
-1.60-
22 30 46.2 28.2 14.1 44.5 27.5 15.1 42.7 26.8 16.1 40.8 26.1 17.0 38.8 25.3 17.8 36.1 24.3 18.8 ─ ─ ─
16 23 40.1 29.8 13.2 38.7 29.1 14.3 37.2 28.4 15.1 35.5 27.6 15.91 33.7 26.8 16.8 31.3 25.7 17.8 ─ ─ ─
115 18 25 43.6 30.0 13.7 42.1 29.3 14.7 40.4 28.6 15.5 38.6 27.8 6.4 36.7 27.0 17.4 34.1 25.9 18.4 ─ ─ ─
-1.90- 20 27 46.7 29.9 14.1 45.1 29.2 14.9 43.2 28.5 15.9 41.3 27.7 16.8 39.2 26.8 17.8 36.5 25.7 18.8 ─ ─ ─
22 30 48.7 31.1 14.3 47.0 30.4 15.3 45.1 29.6 16.3 43.0 28.9 17.4 40.9 28.1 18.2 38.1 27.0 19.3 ─ ─ ─
14 20 37.8 29.2 13.0 36.5 28.6 13.9 35.1 27.8 14.7 33.5 27.1 15.5 31.8 26.3 16.3 29.6 25.3 17.4 ─ ─ ─
16 23 41.7 31.8 13.5 40.2 31.1 14.3 38.6 30.4 15.3 36.9 29.6 16.1 35.0 28.7 17.0 32.5 27.6 18.0 ─ ─ ─
130
18 25 45.4 32.0 13.9 43.7 31.3 14.9 42.0 30.5 15.7 40.1 29.7 16.6 38.1 28.9 17.6 35.4 27.8 18.6 ─ ─ ─
RP-15AL2 -2.11-
20 27 48.5 31.9 14.1 46.8 31.2 15.1 44.9 30.4 16.1 42.9 29.6 17.0 40.7 28.7 18.0 37.9 27.6 19.0 ─ ─ ─
+
22 30 50.6 33.2 14.5 48.8 32.5 15.5 46.8 31.8 16.6 44.7 31.0 17.6 42.5 30.2 18.4 39.6 29.1 19.5 ─ ─ ─
RCR-15A4
14 20 39.2 30.9 13.0 37.9 30.3 14.1 36.4 29.6 14.9 34.8 28.8 15.7 33.0 28.0 16.6 ─ ─ ─ ─ ─ ─
16 23 43.3 33.7 13.7 41.7 33.1 14.5 40.1 32.3 15.5 38.3 31.5 16.4 36.3 30.6 17.2 ─ ─ ─ ─ ─ ─
145
18 25 47.1 34.0 14.1 45.4 33.2 14.9 43.6 32.5 15.9 41.6 31.6 16.8 39.5 30.8 17.8 ─ ─ ─ ─ ─ ─
-2.33-
20 27 50.3 33.8 14.3 48.6 33.1 15.3 46.6 32.3 16.4 44.5 31.5 17.2 42.3 30.6 18.2 ─ ─ ─ ─ ─ ─
22 30 52.5 35.3 14.7 50.6 34.6 15.7 48.6 33.8 16.8 46.4 33.0 17.8 44.1 32.2 18.6 ─ ─ ─ ─ ─ ─
14 20 40.2 32.1 13.2 38.8 31.5 14.1 37.3 30.7 15.1 35.6 29.9 15.9 33.8 29.1 16.8 ─ ─ ─ ─ ─ ─
16 23 44.3 35.0 13.7 42.8 34.3 14.7 41.1 33.6 15.5 39.2 32.8 16.6 37.2 31.9 17.4 ─ ─ ─ ─ ─ ─
155
18 25 48.2 35.3 14.1 46.5 34.5 15.1 44.6 33.7 16.1 42.6 32.9 17.0 40.5 32.0 17.8 ─ ─ ─ ─ ─ ─
-2.46-
20 27 51.5 35.1 14.5 49.8 34.4 15.5 47.7 33.6 16.6 45.6 32.7 17.4 43.3 31.8 18.2 ─ ─ ─ ─ ─ ─
22 30 53.8 36.7 14.9 51.9 36.0 15.9 49.8 35.2 17.0 47.5 34.4 17.8 45.2 33.6 18.8 ─ ─ ─ ─ ─ ─
18 25 55.0 36.7 16.6 53.05 35.7 17.8 50.9 34.8 18.8 48.6 33.7 20.0 46.2 32.6 21.0 42.9 31.2 22.2 ─ ─ ─
130
20 27 58.8 36.5 17.0 6.8 35.6 18.2 54.5 34.6 19.4 52.0 33.6 20.4 49.4 32.5 21.6 45.9 31.1 22.8 ─ ─ ─
-2.16-
22 30 61.4 37.7 17.4 59.2 36.9 18.6 56.8 35.9 19.8 54.2 34.9 21.0 51.5 33.9 22.0 48.0 32.5 23.4 ─ ─ ─
16 23 53.6 40.3 16.4 51.7 39.4 17.6 49.6 38.4 18.6 47.4 37.4 19.8 45.0 36.3 20.8 41.8 34.9 22.0 ─ ─ ─
160 18 25 58.3 40.6 16.8 56.2 39.6 18.2 54.0 38.6 19.2 51.5 37.6 20.4 48.9 36.5 21.4 45.5 35.0 22.6 ─ ─ ─
-2.61- 20 27 62.3 40.4 17.4 60.2 39.5 18.6 57.7 38.5 19.8 55.2 37.4 20.8 52.3 36.3 22.0 48.7 34.9 23.2 ─ ─ ─
22 30 65.0 42.0 17.8 62.7 41.1 19.0 60.2 40.1 20.2 57.5 39.1 21.4 54.6 38.0 22.6 50.9 36.7 23.8 ─ ─ ─
14 20 50.4 39.3 16.0 48.7 38.5 17.2 46.8 37.6 18.2 44.7 36.6 19.4 42.4 35.5 20.4 39.5 34.1 21.6 ─ ─ ─
16 23 55.6 42.9 16.6 53.6 42.0 17.8 51.5 41.0 19.0 49.2 40.0 20.0 46.7 38.8 21.0 43.4 37.4 22.2 ─ ─ ─
180
18 25 60.5 43.2 17.0 58.3 42.2 18.4 56.0 41.2 19.6 53.5 40.2 20.6 50.8 39.0 21.6 47.2 37.6 23.0 ─ ─ ─
RP-20AL1 -2.91-
20 27 64.7 43.0 17.6 62.4 42.1 18.8 59.9 41.0 20.0 57.2 40.0 21.2 54.3 38.8 22.2 50.5 37.4 23.6 ─ ─ ─
+
22 30 67.5 44.8 18.0 65.1 43.9 19.4 62.4 42.9 20.6 59.6 41.9 21.6 56.7 40.8 22.8 52.8 39.4 24.2 ─ ─ ─
2xRCR-10A4
14 20 52.2 41.7 16.2 50.5 40.8 17.4 48.4 39.9 18.6 46.3 38.9 19.6 43.9 37.8 20.6 ─ ─ ─ ─ ─ ─
16 23 57.6 45.5 16.8 55.6 44.6 18.0 53.4 43.6 19.2 51.0 42.5 20.2 48.4 41.4 21.2 ─ ─ ─ ─ ─ ─
200
18 25 62.7 45.8 17.2 60.4 44.8 18.6 58.0 43.8 19.8 55.4 42.7 20.8 52.6 41.6 22.0 ─ ─ ─ ─ ─ ─
-3.19-
20 27 67.0 45.5 17.8 64.7 44.6 19.0 62.1 43.645 20.2 59.3 42.5 21.4 56.3 41.3 22.4 ─ ─ ─ ─ ─ ─
22 30 69.9 47.6 18.2 67.4 46.7 19.6 64.7 .7 20.8 61.8 44.7 22.0 58.7 43.6 23.0 ─ ─ ─ ─ ─ ─
14 20 53.6 43.4 16.4 51.8 42.6 17.6 49.7 41.6 18.6 47.5 40.6 19.6 45.1 39.4 20.8 ─ ─ ─ ─ ─ ─
16 23 59.1 47.4 17.0 57.0 46.5 18.2 54.8 45.5 19.2 52.3 44.4 20.4 49.7 43.3 21.4 ─ ─ ─ ─ ─ ─
215
18 25 64.3 47.7 17.4 62.0 46.7 18.6 59.5 45.7 19.8 56.9 44.6 21.0 54.0 43.4 22.0 ─ ─ ─ ─ ─ ─
-3.40-
20 27 68.8 47.5 17.8 66.4 46.5 19.2 63.7 45.5 20.4 60.8 44.4 21.6 57.8 43.2 22.6 ─ ─ ─ ─ ─ ─
22 30 71.7 49.7 18.4 69.2 48.8 19.6 66.4 47.8 21.0 63.4 46.7 22.2 60.3 45.6 23.2 ─ ─ ─ ─ ─ ─
18 25 82.2 54.2 26.2 79.3 52.7 28.1 76.1 51.3 29.9 72.7 49.7 31.5 69.1 48.0 33.4 64.2 45.9 35.9 ─ ─ ─
185
20 27 87.9 53.9 26.8 84.9 52.6 28.8 81.5 51.1 30.6 77.8 49.5 32.3 73.9 47.8 34.3 68.7 45.7 36.8 ─ ─ ─
-3.10-
22 30 91.7 55.7 27.6 88.5 54.3 29.5 84.9 52.8 31.4 81.1 51.3 33.2 77.1 49.7 35.2 71.8 47.7 37.8 ─ ─ ─
16 23 80.3 59.5 25.9 77.5 58.2 27.8 74.4 56.7 29.6 71.1 55.2 31.2 67.5 53.5 33.1 62.7 51.3 35.6 ─ ─ ─
18 25 87.3 60.0 26.7 84.2 58.6 28.7 80.9 57.1 30.5 77.2 55.5 32.2 73.4 53.8 34.1 68.2 51.6 36.7 ─ ─ ─
230
20 27 93.4 59.7 27.4 90.2 58.3 29.4 86.5 56.8 31.3 82.7 55.2 33.0 78.5 53.5 35.0 73.0 51.4 37.6 ─ ─ ─
-3.77-
22 30 97.5 62.0 28.1 94.0 60.6 30.2 90.2 59.2 32.1 86.1 57.6 33.9 81.9 56.0 35.9 76.3 54.0 38.6 ─ ─ ─
14 20 75.6 58.3 25.4 73.1 57.0 27.2 70.2 55.6 29.0 67.1 54.1 30.6 63.6 52.4 32.4 59.3 50.4 34.9 ─ ─ ─
16 23 83.5 63.4 26.3 80.5 62.1 28.2 77.3 60.6 30.0 73.9 59.0 31.7 70.1 57.3 33.5 65.1 55.1 36.1 ─ ─ ─
260
18 25 90.8 63.9 27.1 87.5 62.5 29.0 84.0 61.0 30.9 80.3 59.3 32.6 76.2 57.6 34.6 70.9 55.4 37.2 ─ ─ ─
RP-30AL3(S) -4.21-
20 27 97.1 63.6 27.8 93.7 62.2 29.8 89.9 60.7 31.7 85.9 59.1 33.4 81.5 57.3 35.4 75.8 55.1 38.1 ─ ─ ─
+
22 30 101.3 66.2 28.5 97.6 64.9 30.6 93.7 63.4 32.5 89.5 61.8 34.3 85.0 60.2 36.4 79.3 58.1 39.1 ─ ─ ─
2xRCR-16A4
14 20 78.5 61.8 25.7 75.9 60.5 27.6 72.8 59.0 29.3 69.6 57.5 31.0 66.0 55.8 32.8 ─ ─ ─ ─ ─ ─
16 23 86.6 67.4 26.6 83.5 66.0 28.5 80.2 64.5 30.3 76.7 62.9 32.0 72.7 61.1 33.9 ─ ─ ─ ─ ─ ─
290
18 25 94.2 67.8 27.4 90.8 66.3 29.4 87.2 64.8 31.3 83.3 63.2 33.0 79.1 61.4 35.0 ─ ─ ─ ─ ─ ─
-4.63-
20 27 100.7 67.5 28.1 97.2 66.1 30.1 93.3 64.5 32.1 89.1 62.8 33.8 84.6 61.1 35.9 ─ ─ ─ ─ ─ ─
22 30 105.1 70.5 28.8 101.3 69.0 30.9 97.2 67.5 32.9 92.9 65.9 34.7 88.2 64.3 36.8 ─ ─ ─ ─ ─ ─
14 20 80.4 64.1 25.9 77.7 62.8 27.8 74.6 61.3 29.5 71.3 59.8 31.2 67.6 58.0 33.0 ─ ─ ─ ─ ─ ─
16 23 88.7 70.0 26.8 85.6 68.5 28.7 82.2 67.0 30.6 78.5 65.4 32.3 74.5 63.6 34.2 ─ ─ ─ ─ ─ ─
310
18 25 96.4 70.4 27.6 93.0 68.9 29.6 89.3 67.3 31.5 85.3 65.7 33.2 81.0 63.9 35.2 ─ ─ ─ ─ ─ ─
-4.90-
20 27 103.1 70.0 28.3 99.6 68.6 30.3 95.5 67.0 32.3 91.3 65.3 34.1 86.6 63.5 36.1 ─ ─ ─ ─ ─ ─
22 30 107.6 73.2 29.1 103.8 71.8 31.2 99.6 70.3 33.2 95.1 68.6 35.0 90.4 66.9 37.1 ─ ─ ─ ─ ─ ─

QA: Evaporator Air Flow (m3/min.) TC: Total Cooling Capacity (×1000 kcal/h)
CR: Sensible Heat Correction Factor SHC*: Sensible Heat Capacity (×1000 kcal/h)
WB: Evaporator Air Inlet Wet Bulb (℃) (Given for Each WB and DB*)
DB*: Evaporator Air Inlet Dry Bulb (℃) Given for Each WB IPT: Total Input Power of Compressors (kW)

20
SELECTION DATA
Fan Performance Curve

RP-5AL4
RP-5A4 Standard Motor Output : 0.28kW
Standard Motor Output : 0.13kW ◎ : Factory Set Point

RP-8A4 and RP-8AL4 RP-10A4 and RP-10AL4


Standard Motor Output Factory Set Point Standard Motor Output Factory Set Point
RP-8A4: 0.25kW z RP-8A4 RP-10A4: 0.30kW z RP-10A4
RP-8AL4: 0.35kW ◎ RP-8AL4 RP-10AL4:0.60kW ◎ RP-10AL4

21
SELECTION DATA
Fan Performance Curve (Continued)
RP-15AL2 RP-20AL1
Standard Motor Output : 2.2kW Standard Motor Output:3.7kW
⊗ : Factory Set Point ( 50Hz, 740rpm ) ⊗ : Factory Set Point ( 50Hz, 841rpm )
◎ : Factory Set Point ( 60Hz, 893rpm ) ◎ : Factory Set Point ( 60Hz, 1020rpm )
Static Pressure (mmAq)

Static Pressure (mmAq)

3
3
Air Flow (m /min) Air Flow (m /min)

RP-30AL3(S)
Standard Motor Output : 5.5kW
◎ : Factory Set Point ( 890rpm )
Static Pressure (mmAq)

3
Air Flow (m /min)

22
SELECTION DATA
Fan Speed Adjustment
Fan speed Adjustment by Motor Pulley
Regulation Space × of Motor Pulley (mm) Factory Set Point RPM/
Model
0 1 2 3 4 5 6 7 8 X RPM PD Turn*
RPM 890/1,074 864/1,044 840/1,014 814/983 790/953 764/923 740/893 715/863
RP-15AL2 ─ 6 740/893 93.1 38/45
PD 112 108.8 105.7 102.5 99.4 96.2 93.1 90

RPM 988/1,198 967/1,173 946/1,148 925/1,122 904/1,096 883/1,071 863/1,046 841/1,020 820/995
RP-20AL1 7 841/1,020 127.7 43/50
PD 150 146.9 143.7 140.5 137.3 134.1 131.0 127.7 124.6
RPM : Fan Speed (rpm) (50Hz/60Hz)
PD : Pitch Diameter (mm)
* : Fan Speed Change Per One Turn of Movable Motor Pulley Flange (rpm/turn)

Fan Pulley Dimensions V-Belt


Model a P.D. b Model Form Length Number of Belts
RP-30AL3(S) RP-15AL2 B 914 1
for 50Hz 226 215 196
RP-20AL1 B 1,092 2
RP-30AL3(S) RP-30AL3(S)
269 258 239 B 1,295 2
for 60Hz for 50Hz
RP-30AL3(S) B 1,346 2
for 60Hz

Fan Pulley for RP-15AL2 Fan Pulley for RP-20AL1 Fan Pulley for RP-30AL3(S)

Motor Pulley for RP-15AL2 Motor Pulley for RP-20AL1 Motor Pulley for RP-30AL3(S)

23
SELECTION DATA
Electrical Data
Indoor Unit
Quantity × Value
Compressor Motor Maximum
Unit Main Power Applicable Voltage Evaporator Fan Motor*
Model (Three-Phase) Current**
VOL Hz Maximum Minimum STC RNC IPT RNC IPT RNC
220 60 242 198 132 14.9 5.4 1.5 0.32 27
RP-5A4 220 50 242 198 129 13.2 4.6 1.3 0.28 24
380/415 50 456 342 67 7.6 / 7.7 4.6 1.3 / 1.4 0.28 / 0.33 14
220 60 242 198 132 14.9 5.4 2.5 0.54 27
RP-5AL4 220 50 242 198 129 13.2 4.6 2.1 0.46 24
380/415 50 456 342 67 7.6 / 7.7 4.6 2.1 / 2.2 0.46 / 0.50 14
220 60 242 198 208 24.1 8.1 1.61 0.46 48
RP-8A4 220 50 242 198 229 19.7 6.5 1.21 0.38 40
380/415 50 456 342 100 / 108 11.4 / 11.5 6.5 0.70 / 0.69 0.38 23
220 60 242 198 208 24.1 8.1 2.02 0.6 48
RP-8AL4 220 50 242 198 229 19.7 6.5 1.77 0.54 40
380/415 50 456 342 100 / 108 11.4 / 11.5 6.5 1.05 / 1.07 0.54 23
220 60 242 198 227 28.1 9.4 2.06 0.62 53
RP-10A4 220 50 242 198 252 23.2 8.0 1.77 0.54 47
380/415 50 456 342 123 / 134 13.4 / 13.9 8.0 1.03 / 1.04 0.54 27
220 60 242 198 227 28.1 9.4 2.83 0.83 53
RP-10AL4 220 50 242 198 252 23.2 8.0 2.52 0.72 47
380/415 50 456 342 123 / 134 13.4 / 13.9 8.0 1.36 / 1.25 0.72 27
220 60 242 198 147 2x23.8 2x8.5 5.8 1.9 82
RP-15AL2 220 50 242 198 159 2x22.5 2x7.2 4.8 1.5 74
380/415 50 456 342 81 / 88 2x12.3 / 2x12.1 2x7.2 2.7 1.5 41
220 60 242 198 186 2x29.7 2x10.5 10.6 3.6 101
RP-20AL1 220 50 242 198 201 2x27.7 2x9.1 7.4 2.4 93
380/415 50 456 342 100 / 109 2x15.0 / 2x14.8 2x9.1 4.2 / 3.9 2.4 57
220 60 242 198 330 2x45.9 2x16.6 13.6 4.1 179
RP-30AL3(S) 220 50 242 198 339 2x36.6 2x12.9 12.6 4.0 152
380/415 60 456 342 168 / 183 2x21.1 / 2x19.3 2x12.9 7.1 / 6.8 4.0 81

Outdoor Unit
Quantity × Value
Condenser Fan Motor
Unit Main Power Applicable Voltage
Model (Three-Phase)
VOL Hz Maximum Minimum RNC IPT
220 60 242 198 1.9 0.60
RCR-5A4 220 50 242 198 2.1 0.50
380/415 50 456 342 1.1 0.50
220 60 242 198 2.4 0.76
RCR-8A4 220 50 242 198 2.4 0.70
380/415 50 456 342 1.4 0.70
220 60 242 198 2.4 0.76
RCR-10A4 220 50 242 198 2.4 0.70
380/415 50 456 342 1.4 0.70
220 60 242 198 2x1.6 2x0.45
RCR-15A4 220 50 242 198 2x1.5 2x0.37
380/415 50 456 342 2x0.8 / 2x0.7 2x0.37
220 60 242 198 2x2.3 2x0.78
RCR-16A4 220 50 242 198 2x1.9 2x0.63
380/415 50 456 342 2x1.1 / 2x1.0 2x0.63
VOL : Unit Power Supply Rated(Plated) Voltage(V)
Hz : Frequency(Hz)
STC : Starting Current(A)
RNC : Running Current(A)
IPT : Input(kW)

NOTE :
1. These data are based on the same conditions as the nominal cooling capacity. Refer to the notes for the Unit General Data.
2. The starting current is indicated for each compressor motor.

24
SOUND DATA AND WORKING RANGE
Sound Data for Indoor Unit
Frequency Band (Hz)
Unit
Sound 45 90 180 355 710 1400 2800 5600
Model Power
Level ~ ~ ~ ~ ~ ~ ~ Overall
~
(Hz)
90 180 355 710 1400 2800 5600 11200
SPL-A 30.2 40.2 42.8 46.2 46.8 44.6 40.4 33.2 52
RP-5A4
50/60 SPL-C 56.8 55.8 52.2 49.6 47.0 43.0 38.8 31.3 61
RP-5AL4
PWL 64.8 63.8 60.2 57.6 55.0 51.0 46.8 39.3 69
SPL-A 33.1 41.4 44.4 47.5 47.3 46.1 39.0 30.6 53
RP-8A4
50/60 SPL-C 59.7 57.0 53.8 50.9 47.5 44.5 37.4 28.7 63
RP-8AL4
PWL 67.7 65.0 61.8 58.9 55.5 52.5 45.4 36.7 71
SPL-A 33.8 43.8 46.7 51.8 49.7 48.1 41.3 34.8 56
RP-10A4
50/60 SPL-C 60.4 59.4 56.1 55.2 49.9 46.5 39.7 32.9 65
RP-10AL4
PWL 68.4 67.4 64.1 63.2 57.9 54.5 47.7 40.9 73
SPL-A 40 44 45 55 57 52 48 39 61
RP-15AL2 50/60 SPL-C 68 62 55 60 57 51 46 38 70
PWL 88 82 76 80 78 73 69 61 90
SPL-A 41 44 56 57 60 55 51 40 64
RP-20AL1 50/60 SPL-C 69 62 66 61 60 54 49 39 72
PWL 89 82 89 87 89 86 84 75 96
SPL-A 43 45 58 60 62 57 53 42 66
RP-30AL3(S) 50/60 SPL-C 71 63 68 64 62 56 51 41 74
PWL 91 85 92 90 91 88 86 78 98
SPL-A: A Scale Sound Pressure Level(dB)
SPL-C: C Scale Sound Pressure Level(dB)
PWL: Sound Power Level(dB)

NOTES:
1. The measuring point is 1.0 meter from the center of the machine surface and 1.0 meter from the floor level.
2. The units are operating under the standard working conditions.
3. The above data was measured in an anechoic chamber so that reflection sound should be taken into consideration.

Working Range
Power Supply
The applicable voltage range for each unit is given in “Electrical Data”. The working range among the three phases must be
balanced within a 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher than
85% of the rated voltage.

Connecting Piping
Maximum Lift (m) Connection Maximum Piping Length
Model
Indoor Unit Above Outdoor Unit Above -One Way-(m)
RP-5A4
to 15 35 50
RP-30AL3(S)

Outdoor and Indoor Temperatures


Outdoor Temp.* Indoor Temp.
Unit Power
Model -Dry Bulb-(℃) -Dry/Wet Bulb-(℃)
Frequency (Hz)
Max. Min. Max. Min.
RP-5A4+RCR-5A4 50 52 21 32 / 22.5 21 / 15.5
to
RP-30AL3(S)+RCR-16A4 60 50 21 32 / 22.5 21 / 15.5

*The outdoor and indoor temperature range are based on the following evaporator air flow range, excluding blanked
conditions in the cooling capacity table: 70%to 120%

25
ACCESSORY AND COMPONENT DATA
Optional Accessory Availability
Optional Accessories*
Model AUTO-SWEEP** Long Life
Electric Heater Hot Water Heater Steam Heater Humidifier
Mechanism Air-filter
RP-5A4 Yes
Yes Yes Yes Yes Yes
RP-5AL4 NO
RP-8A4 Yes
Yes Yes Yes Yes Yes
RP-8AL4 NO
RP-10A4 Yes
Yes Yes Yes Yes Yes
RP-10AL4 NO
RP-15AL2 Yes Yes Yes Yes NO Yes

RP-20AL1 Yes Yes Yes Yes NO Yes

RP-30AL3(S) Yes Yes Yes Yes NO Yes


* : Detailed information is available upon request with the expanded data.
** : Factory-Equipped Option

Optional Auxiliary
Electric Heater
Optional Optional
Auxiliary Auxiliary Evaporator
Electric Electric
Heater Heater

Evaporator Evaporator
Optional
Spray Type
Optional Optional Humidifier
Spray Type Spray Type
Humidifier Humidifier Supporter*
* : Filed-Installed

For Models:RP-5A4, RP-8A4 For Models: RP-5AL4, RP-8AL4 For Models: RP-15AL2, RP- 20AL1
and RP-10A4 and RP-10AL4 and RP-30AL3(S)

Component Detailed Data


Compressor (Indoor Unit)
Compressor Model 500DH 750EL 1000EL 753FH3-T 1001FH4-T CB150
Compressor Type Hermetic Hermetic Hermetic Hermetic Hermetic Hermetic
Scroll Scroll Scroll Reciprocating Reciprocating Reciprocating
Number of Cylinders ─ ─ ─ 3 4 4
Revolutions 50Hz rpm 2,880 2,880 2,880 2,880 2,880 2,880
60Hz rpm 3,470 3,470 3,470 3,470 3,470 3,470
3
Piston 50Hz m /h 13.82 22.10 27.60 27.47 36.62 49.50
3
Displacement 60Hz m /h 16.66 26.60 33.30 33.10 44.13 59.38
Air-Tight Pressure
2
Discharge kg/cm G 30.0 30.0 30.0 28.0 28.0 28.0
MPa 2.94 2.94 2.94 2.75 2.75 2.75
2
Suction kg/cm G 15.3 15.3 15.3 15.0 15.0 15.0
MPa 1.50 1.50 1.50 1.47 1.47 1.47
Motor Type Special Squirrel-Cage Three-Phase Motor
Starting Method Direct-On-Line Starting
Nominal Output kW 3.75 5.5 7.5 5.5 7.5 10.8
Poles 2 2 2 2 2 2
Insulation Class E E E E E E
Oil Type Equivalent Oil : SUNISO-4GDI-HT SUNISO 3GS Equivalent Barrel Freeze 26S
Charge Liters 1.8 3.5 3.0 3.5 3.8

26
COMPONENT DATA
Component Detailed Data
Evaporator and Fan Section (Indoor Unit)
Model RP-5A4 RP-5AL4 RP-8A4 RP-8AL4 RP-10A4 RP-10AL4 RP-15AL2 RP-20AL1 RP-30AL3(S)
Evaporator Multi-Pass Cross-Finned Tube
Tube Material Copper Tube
Outer Diameter mm 9.53 9.53 9.53 9.53 9.53 9.53 9.53 9.53 9.53
Rows 3 3 3 3 3 3 4 4 4
Number of Tubes/Evaporator 72 72 72 72 72 72 120 120 144
Fin Material Aluminum
Pitch mm 2.2 2.2 2.0 2.0 2.0 2.0 2.2 2.2 2.2
Number of
Evaporators/Unit 1 1 1 1 1 1 1 1 1
Total Face Area m2 0.393 0.3930.573 0.573 0.753 0.753 0.90 1.13 1.62
Maximum Applicable kg/cm2G 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0
Pressure MPa 1.275 1.2751.275 1.275 1.275 1.275 1.275 1.275 1.275
Evaporator Fan Multi-Blade Centrifugal Fan (Double Suction)
Number/Unit 1 1 2 2 2 2 1 1 2
Outer Diameter mm 264 264 264 264 264 264 385 385 385
3
Total Nominal Air m /min 44/38* 44 66 66 88 88 130 180 260
3
Flow m /s 073/0.63* 0.73 1.10 1.10 1.47 1.47 2.17 3.0 4.33
Evaporator Fan Motor Drip-Proof Type Enclosure
Starting Method Capacitor Starting Direct-On-Line Starting
Nominal Output kW 0.13 0.28 0.25 0.35 0.30 0.6 2.2 3.7 5.5
Poles 6 6 6 6 6 6 4 4 4
Phases 1 1 3 3 3 3 3 3 3
Insulation Class E E E E E E B E B
Number/Unit 1 1 1 1 1 1 1 1 1
Air Filter Permanent Washable
Material Polyvinyl Chloride
* : Hi/Lo

Outdoor Unit
Model RCR-5A4 RCR-8A4 RCR-10A4 RCR-15A4 RCR-16A4
Condenser Coil Multi-Pass Finned Tube
Tube Material Copper Tube
Outer Diameter mm 9.53 9.53 9.53 9.53 9.53
Rows 2 2 2 2 3
Number of Tubes/Condenser 72 108 76 76 96
Fin Material Aluminum Aluminum Aluminum Aluminum Aluminum
Pitch mm 2.2 2.2 2.0 2.0 2.0
Maximum Operating kg/cm2G 28.0 30.0 30.0 28.0 28.0
Pressure MPa 2.746 2.942 2.942 2.746 2.746
Number of Condensers/Unit 1 1 1 2 2
Total Face Area m2 0.91 1.05 2.45 2.70 2.63
Condenser Fan Direct Driven Propeller Fan
Outer Diameter mm 610 660 760 714 660
Revolutions rpm 930/1110* 920/980* 920/980* 655/677* 860/870*
3
Nominal Air Flow/Fan m /min 130/135* 160/170* 230/240* 300/330* 270/275*
Number of Fans/Unit 1 1 1 2 2
Condenser Fan Motor Drip-Proof Type Enclosure
Starting Method Direct-On - Line Starting
Nominal Output kW 0.25 0.4 0.4 0.3 0.6/0.4**
Poles 6 6 6 8 6/8*
Phases 3 3 3 3 3
Insulation Class B/F* B/F* B/F* B/F* F
Number of Motors/Unit 1 1 1 2 2
* : 50Hz/60Hz
** : (380/415V)/220V

27
CONTROL SYSTEM
Refrigerant and Electrical Control
Refrigerant Cycle of Indoor Unit
Models from RP-5A4 through RP-10AL4 are composed of one refrigeration cycle, and the other models are
composed of two independent refrigeration cycles. In addition to the basic components (a compressor and an
evaporator), each refrigeration cycle is equipped with the following components.
Stop Valves for Gas Outlet and Liquid Inlet –
These stop valves are equipped at the unit piping connections, and facilitate the evacuation and charging work.
Liquid Line and Suction Line Strainer ⎯
A brazing connection type strainer is equipped.(suction line for RP-5A4 through RP-10AL4)

Refrigerant Flow Control ⎯ Capillary tubes are applied.

Accumulator ⎯ An accumulator is equipped at the compressor suction side in order to avoid liquid refrigerant
flooding back to the compressor.

Pressure Gauge ⎯ (For RP-30AL3(S) Only) ⎯A high pressure gauge and a low pressure gauge are mounted
for each refrigeration cycle of this model.

Standard Electrical Control Sequence


Model RP-5A4 through RP-10AL4 and RP-30AL3(S)
When the main power source is supplied to the indoor unit, the crankcase heater is energized. A control switch
manually selects the ventilating and the cooling/heating operation. When the control switch is set at “COOL” and
all electrical protective devices are satisfied, the red pilot lamp is activated, and the built-in thermostat controls
the compressor operation, (see “Operating Sequence Chart”) The heating operation can be selected by the
control switch when an electrical heater is provided in the field.

Models RP-15AL2 and RP-20AL1


When the main power source is supplied to the indoor unit, the white-pilot lamp is activated, and the crankcase
heater is energized. An operation switch, the three-position push-button type, manually selects the ventilating
and the cooling operation. When the operation switch is set at “COOL” and all electrical protective devices are
satisfied, the red pilot lamp is activated, and the built-in thermostat controls the compressor operation (see
“Operating Sequence Chart“). The heating operation can be selected by the “COOL-HEAT“ selection switch
when an electrical heater is provided in the field.
Capacity Control (Dual Cycle Units) –
The two-stage thermostat, equipped with dual-circulated models, controls each compressor responding to the
return air temperature. This system enable full-load, half-load and no-load (ceasing two compressors) operation.

28
CONTROL SYSTEM
Refrigerant and Electrical Control (Continued)
Operating Sequence Chart for Models RP-5A4 through RP-10AL4
{:ON ⊗:OFF
Main Power Switch ⊗ {
Operational
Equipment
Operation Switch** ⊗ ⊗ FAN COOL
Room Thermostat { { { { ⊗
Pilot Lamp (Red) ⊗ ⊗ { { {
Indoor Fan Motor ⊗ ⊗ { { {
Electrical
Component
Compressor ⊗ ⊗ ⊗ { ⊗
Crankcase Heater ⊗ { { ⊗ {
Outdoor Fan Motor ⊗ ⊗ ⊗ { ⊗
** : Selection Switch COOL

Operating Sequence Chart for Models RP-15AL2 and RP-20AL1


{:ON ⊗:OFF
Main Power Switch ⊗ {
Operational Operation Switch ⊗ ⊗ FAN COOL
Equipment 1st Stage (Higher) ─ ─ ─ { { ⊗ ⊗
Thermostat
2nd Stage (Lower) ─ ─ ─ { { { ⊗
Pilot Lamp (White) ⊗ { { { { { {
Pilot Lamp (Red) ⊗ ⊗ ⊗ { { { {
Indoor Fan Motor ⊗ ⊗ { { { { {
Compressor 1 ⊗ ⊗ ⊗ { { { ⊗
Electrical
Component
Compressor 2 ⊗ ⊗ ⊗ ⊗ { ⊗ ⊗
Crankcase Heater 1 ⊗ { { ⊗ ⊗ ⊗ {
Crankcase Heater 2 ⊗ { { { ⊗ { {
Outdoor Fan Motor 1 ⊗ ⊗ ⊗ { { { ⊗
Outdoor Fan Motor 2 ⊗ ⊗ ⊗ ⊗ { ⊗ ⊗

Operating Sequence Chart for Model RP-30AL3(S)


{:ON ⊗:OFF
Main Power Switch ⊗ {
Operational Operation Switch ⊗ ⊗ FAN COOL
Equipment 1st Stage (Higher) ─ ─ ─ { { ⊗ ⊗
Thermostat
2nd Stage (Lower) ─ ─ ─ { { { ⊗
Pilot Lamp (Red) ⊗ ⊗ { { { { {
Indoor Fan Motor ⊗ ⊗ { { { { {
Compressor 1 ⊗ ⊗ ⊗ { { { ⊗
Electrical Compressor 2 ⊗ ⊗ ⊗ ⊗ { ⊗ ⊗
Component Crankcase Heater 1 ⊗ { { ⊗ ⊗ ⊗ {
Crankcase Heater 2 ⊗ { { { ⊗ { {
Outdoor Fan Motor 1 ⊗ ⊗ ⊗ { { { ⊗
Outdoor Fan Motor 2 ⊗ ⊗ ⊗ ⊗ { ⊗ ⊗

29
CONTROL SYSTEM
Typical Wiring
For Models : RP-5A4+RCR-5A4

30
CONTROL SYSTEM
Typical Wiring (Continued)
For Models: RP-5AL4+RCR-5A4

31
CONTROL SYSTEM
Typical Wiring (Continued)
For Models: RP-8A4+RCR-8A4 and RP-10A4+RCR-10A4
RP-8AL4+RCR-8A4 and RP-10AL4+RCR-10A4

32
CONTROL SYSTEM
Typical Wiring (Continued)
For Models : RP-15AL2+RCR-15A4 and RP-20AL1+2xRCR-10A4

33
CONTROL SYSTEM
Typical Wiring (Continued)
For Models: RP-30AL3(S) + 2xRCR-16A4

34
PROTECTION AND SAFETY CONTROL
Protection and Safety Control
Compressor Protection Crankcase Heater ─ Bound around the compressor
The compressor is protected by the following devices chamber for the hermetic compressor, this heater
and the combination of the devices: protects the compressor against oil foaming during
High Pressure Switch─ Leading the pressure from cold starting, as it is energized while the
the compressor discharge line, this switch cuts compressor is stopped. This heater is
out the operation of each compressor, when the factory-equipped for all models.
discharge pressure exceeds the setting. Other Protection
Internal Thermostat─ Embedde d in the compressor Overcurrent Relay for Fan Motor─ A manual reset
winding, this thermostat cuts out the operation of each type thermal overcurrent relay protects against the
motor when the compressor is excessively heated(for Models overload operation of the fan motor.
:RP-15AL2 through RP-30AL3(S)).
Manual Resetting System ─ Compressor
Quick Response Overcurrent Relay─ Equipped in cycling operation due to automatic reset of the
the magnetic switch box, this relay quickly cuts out the protective devices is protected by the manual
operation of each compressor, when the current in resetting system; when one of the protection
any phase exceeds this setting. devices is tripped, an auxiliary relay in the holding
circuit is de-energized, and requires
re-manipulation of the operation switch .

Safety and Control Devices Setting


Model RP-5A4 RP-5AL4 RP-8A4 RP-8AL4 RP-10A4 RP-10AL4 RP-15AL2 RP-20AL1 RP-30AL3(S)
For Compressor Automatic Reset , Non-Adjustable
Pressure Switch (One Switch for Each Compressor)
2
High Cut-Out kg/cm G 28.0 28.0 30.0 30.0 30.0 30.0 28.0 28.0 28.0
MPa 2.746 2.746 2.942 2.942 2.942 2.942 2.746 2.746 2.746
2
Cut-In kg/cm G 22.0 22.0 24.0 24.0 24.0 24 24.0 24.0 22.0
MPa 2.157 2.157 2.354 2.354 2.354 2.354 2.354 2.354 2.157
- - - - - - -
2
Low Cut-Out kg/cm G 2.0 2.0
MPa - - - - - - 0.196 0.196 -
- - - - - - -
2
Cut-In kg/cm G 4.0 4.0
MPa - - - - - 0.392 0.392 -
Overcurrent Relay Automatic Reset , Non-Adjustable
(One-Two Phase Set for Each Compressor)
220V 60Hz A 32 32 46 46 60 60 46 60 74
220V 50Hz A 32 32 46 46 60 60 46 60 74
380V/415V 50Hz A 17 17 25 25 32 32 25 32 43.5
Internal Thermostat Automatic Reset , Non-Adjustable
(One Thermostat for Each Compressor)
Cut-Ou ℃ - - - - - - 105 105 90
t ℃ - - - - - - 90 90 73
Cut-In
Crankcase Heater On Heater for Each Compressor
Capacity W 40 40 60 60 60 60 60 60 70
Discharge Gas Thermostat Automatic Reset, Non- Adjustable
Cut-Ou ℃ 130 130 130 130 130 130 - - 135
t ℃ 100 100 100 100 100 100 - - 105
Cut-In
For Evaporator Fan Motor Manual Reset, Adjustable
Overcurrent Relay (One Two-Phase Set for Each Fan Motor)
220V 60Hz A - - 2.5 4.1 2.5 4.1 9.0 14.0 21.0
220V 50Hz A - - 2.5 4.1 2.5 4.1 9.0 14.0 21.0
380V/415V 50Hz A - - 0.9 1.4 1.6 2.6 6.0 8.0 11.0
For Fan Motor Internal Automatic Reset ,Non-Adjustable
Thermostat (One Thermostat for Each Fan Motor
Cut-Out ℃ 130 130 - - - - - - -
Cut-in ℃ 100 100 - - - - - - -
Freeze Protection
Thermostat Cut-Out ℃ -4 -4 -4 -4 -4 -4 1 1 -4
Cut-in ℃ 4 4 4 4 4 4 7 7 4
For Condenser Fan Motor Manual Reset, Adjustable
Overcurrent Relay (One Two-Phase Set for Each Fan Motor)
220V 60Hz A 2.1 2.1 4.0 4.0 4.0 4.0 2x2.1 2x4.0 2x7.5
220V 50Hz A 2.1 2.1 4.0 4.0 4.0 4.0 2x1.3 2x4.0 2x7.5
380V/415V 50Hz A 1.3 1.3 2.1 2.1 2.1 2.1 2x0.9 2x2.1 2x3.3
For Control Circuit One Fuse for Each Unit (380V/415V,50Hz)
Fuse Two Fuse for Each Unit (220V,50/60Hz)
Capacity A 3 3 3 3 3 3 3 3 3
For Refrigerant Circuit
Fusible Plug
Melting Temperature ℃ - - - - - - 72 72 -
Operation Control
Built-In Thermostat
Adjustable Range ℃ 15~30.5 15~30.5 15~30.5 15~30.5 15~30.5 15~30.5 15~32 15~32 15~32

35
Differential 3 3 3 3 3 3 1.5 1.5 2
Stage ℃ 1 1 1 1 1 1 2 2 2

36
INSTALLATION DATA
Foundation Provisions
Maximum Foundation Gradient
The unit should be installed in the upright position within the gradient shown in the figures:

Indoor Model RCR-5A4 through RCR-10A4 RCR-15A4 and RCR-16A4

Indoor Unit Outdoor Unit


Dimensions Dimensions
Model A B Model A B
degree mm degree mm degree mm degree mm
RP-5A4 0.7 10 0.5 4
RCR-5A4 1 15 1 14
RP-5AL4 0.7 10 0.5 4
RP-8A4 0.7 13 0.5 4 RCR-8A4 1 15 1 14
RP-8AL4 0.7 13 0.5 4 RCR-10A4 1 20 1 15
RP-10A4 0.7 17 0.5 4 RCR-15A4 1 30 1 15
RP-10AL4 0.7 17 0.5 4 RCR-16A4 1 32 1 17
RP-15AL2 0.7 17 0.4 5
RP-20AL1 0.7 21 0.4 5
RP-30AL3(3) 0.7 24 0.4 6

Recommended Concrete Curbs


Model A B C D E F G H
RCR-5A4 1,020 212 100 680 122 920 ⎯ 50
RCR-8A4 1,020 212 100 680 122 920 ⎯ 50
RCR-10A4 1,250 200 100 966 100 1,050 ⎯ 100
RCR-15A4 1,940 200 100 966 100 1,740 870 100
RCR-16A4 1,925 212 100 440 90 1,825 ⎯ 50

Model RCR-5A4 through RCR-15A4 RCR-16A4

Refrigerant Piping Arrangement


A: Piping Length 5m~20m
B: Piping Length 25m~35m
C: Piping Length 40m~50m

37
INSTALLATION DATA
Piping Sizes and Charging Data
Equivalent Piping Length (One Way for Each Cycle)
Model
5m 10m 15m 20m 25m 30m 35m 40m 45m 50m
RP-5A4 LIQUID ODxT 12.7x0.8 12.7x0.8 12.7x0.8 12.7x0.8 12.7x0.8 12.7x0.8 12.7x0.8 12.7x0.8 12.7x0.8 12.7x0.8
RP-5AL4 + GAS ODxT 15.88x1.0 15.88x1.0 15.88x0.8 15.88x0.8 19.05x1.0 19.05x1.0 19.05x1.0 22.2x1.2 22.2x1.2 22.2x1.2
RCR-5A4 REF CHG/CKT*(kg) 3.6 4.3 5.0 5.7 6.4 7.1 7.8 8.5 9.2 10.0
RP-8A4 LIQUID ODxT 12.7x0.8 12.7x0.8 12.7x0.8 15.88x1.0 15.88x1.0 15.88x1.0 15.88x1.0 15.88x1.0 15.88x1.0 15.88x1.0
RP-8AL4 + GAS ODxT 19.05x1.0 19.05x1.0 19.05x1.0 19.05x1.0 22.2x1.2 22.2x1.2 22.2x1.2 25.4x1.2 25.4x1.2 25.4x1.2
RCR-8A4 REF CHG/CKT*(kg) 5.7 6.7 7.6 8.6 9.6 10.6 11.6 12.6 13.6 14.6
RP-10A4 LIQUID ODxT 15.88x1.0 15.88x1.0 15.88x1.0 15.88x1.0 15.88x1.0 15.88x1.0 15.88x1.0 15.88x1.0 15.88x1.0 15.88x1.0
RP-10AL4 + GAS ODxT 22.2x1.2 22.2x1.2 22.2x1.2 22.2x1.2 25.4x1.2 25.4x1.2 25.4x1.2 28.5x1.6 28.5x1.6 28.5x1.6
RCR-10A4 REF CHG/CKT*(kg) 9.8 10.7 11.7 12.6 13.5 14.5 15.4 16.3 17.3 18.2
RP-15AL2 LIQUID ODxT 15.88x1.0 15.88x1.0 15.88x1.0 15.88x1.0 15.88x1.0 15.88x1.0 15.88x1.0 15.88x1.0 15.88x1.0 15.88x1.0
+ GAS ODxT 19.05x1.0 19.05x1.0 19.05x1.0 22.2x1.2 22.2x1.2 22.2x1.2 22.2x1.2 25.4x1.2 25.4x1.2 25.4x1.2
RCR-15A4 REF CHG/CKT*(kg) 6.5 7.3 8.2 9.2 10.1 11.0 11.9 12.8 13.7 14.6
RP-20AL1 LIQUID ODxT 15.88x1.0 15.88x1.0 15.88x1.0 15.88x1.0 15.88x1.0 15.88x1.0 15.88x1.0 15.88x1.0 15.88x1.0 15.88x1.0
+ GAS ODxT 22.2x1.2 22.2x1.2 22.2x1.2 22.2x1.2 28.5x1.6 28.5x1.6 28.5x1.6 28.5x1.6 28.5x1.6 28.5x1.6
2xRCR-10A4 REF CHG/CKT*(kg) 8.5 9.4 10.3 11.2 14.1 15.5 16.8 18.1 19.4 20.5
RP-30AL3(S) LIQUID ODxT 19.05x1.0 19.05x1.0 19.05x1.0 19.05x1.0 19.05x1.0 19.05x1.0 19.05x1.0 19.05x1.0 19.05x1.0 19.05x1.0
+ GAS ODxT 25.4x1.2 25.4x1.2 25.4x1.2 25.4x1.2 28.5x1.6 28.5x1.6 28.5x1.6 28.5x1.6 28.5x1.6 28.5x1.6
2xRCR-16A4 REF CHG/CKT*(kg) 13.8 15.0 16.2 17.4 18.9 20.2 21.5 22.8 24.1 25.4
ODxT : Outer Diameter and Thickness of Pipe(mm)
REF CHG/CKT : Refrigerant charge per Refrigeration Cycle.
*For One Refrigerant Cycle of HITACHI Air-Cooled Packaged Air Conditioners.
NOTE:
1. The indoor units are factory-charged with a refrigerant quantity which equivalent piping length is 5 meters. The outdoor units have only
holding charge of refrigerant.
2. An additional oil-charge of 0.11 liters for an additional refrigerant charge of 1 kilogram is required when the piping length exceeds 20
meters.
Field Piping Provisions
Refrigerant Piping Drain Piping
These units are pre-piped at the factory: the required field Condensate Drain Piping─ A female piping thread drain
piping is connection piping between the indoor u nit an d
connection is provided at both sides of the unit.
the outdoor unit. T o e n s u r e s a t i s f a c t o r y operation,
When air intake ducts are installed, trap deeper than half
the following piping arr ang e ment s must be provided in
of the duct pressure drop in the water gauge should be
the field for each refrigerant cycle.
provided at a lower level than the drain pan in the drain
Loop and Trap─ When the indoor unit is installed b elo w line.
the outdo or unit, a liqu id loop an d oil traps should Emergency Drain ─ An emergency drain from the
be provided.
machine compartment can be disposed of from an
F i l t e r - D r ye r ─ It is recomme n ded th at a emergency drain connection provided at both the bottom
f ield- supplied serviceable filter-dryer be installed in each sides of the unit.
liquid line as near to the indoor unit as possible.

Basic Indoor Unit Below Basic Indoor Unit Above Drain Piping
NOTES:
1. These piping arrangements should be performed for both refrigeration cycles of
the dual-circuited indoor units.
2. Do not connect the dual-circuited indoor unit with one single-circuited
condenser.

Refrigerant Piping Arrangement

38
DUCTING PROVISIONS
For Models RP-5A4, RP-8A4 and RP-10A4 For Models RP-5AL4, RP-8AL4, RP-10AL4,
RP-15AL2 and RP-20AL1
Auxiliary Duct─ For practical air discharge by duct,
an auxiliary duct can be connected on the top of the Rear Side Air Intake─ Rear side air intake by duct is
plenum chamber. applicable by shutting the front air intake grilles. (Models
RP-5AL4, RP-8AL4 and RP-10AL4 are Factory-Equipped
Rear Side Air Intake─ Rear side air intake by duct is Option)
applicable by shutting the front air intake grilles.
(Factory-Equipped Option) Fresh Air Intake─ A fresh air intak e open ing is
provided at both sides of the unit for short ducting.
Fresh Air Intake─ A fresh air intak e open ing is
provided at both sides of the unit for short ducting. For Model RP-30AL3(S)
Field Optional Ducting Arrangement ─ The
factory-sta nd ard re ar si de a ir inta ke can be
altere d to the front side.

Installation Example

39
SPECIFICATIONS
Standard Specifications
AIR-COOLED PACKAGED AIR CONDITIONER ─ spaced at more than 12 fins per 25.4 mm. The coils
shall be cleaned, dehydrated and tested for leakage
The air-cooled packaged air conditioner shall be
at the factory.
composed of an indoor unit with refrigeration
cycle(s) and air-cooled remote condenser(s)
for application with R-22 refrigerant. The indoor unit
shall include an evaporator, compressor(s),
evaporator fan(s), a fan motor, and other
auxiliary and control components enclosed in a
cabinet for indoor installation. Optional accessories
shall also be provided upon customer request. The
air-cooled remote condenser shall include condensers,
condenser fan(s), fan motor(s), and other auxiliary
components enclosed in a weather-proof cabinet.
Both units shall be properly assembled, internally
wired, thoroughly tested and holding charged with
R-22 refrigerant at the factory, and shall comply with
Japanese Industrial Standards and other Japanese
industrial standardization statutes.
CAPACITY ─ The total cooling capacity of the
air-cooled packaged air conditioner shall be
kcal/h or greater, and the sensible heat capacity shall
be
kcal/h with ℃ evaporator air inlet
dry bulb temperature, ℃ evaporator air inlet
wet bulb temperature, ℃ condenser air inlet
temperature and m3/min, evaporator air flow.
The (total of ) compressor power input shall not
exceed kW.

INDOOR UNIT
CABINET ─ The cabinet shall be constructed of
finished steel, baked with synthetic resin paint for
front and side panels, and galvanized steel for top
and rear panels. The cabinet interior shall be
insulated by incombustible and self-extinguishable
adiabatic material. The service panels shall be easily
removable for service access to the unit components.
REFRIGERATION CYCLE─ Each refrigeration cycle
shall be equipped with a stop valve for liquid inlet, a
fusible plug for models RP-15AL2 and RP-20AL1, a
strainer, capillary tubes, an evaporator coil, a
compressor and a stop valve for the gas outlet. A
check joint for high pressure and a check joint for low
pressure for RP-15AL2 through RP-30AL3(S) shall
also be provided for each refrigeration cycle of all
units. A high pressure gauge and a low pressure
gauge shall be provided for each refrigeration cycle of
RP-30AL3(S).
COMPRESSOR ─ The unit shall contain hermetic
multi-cylinder reciprocating compressor(s) or scroll
compressor(s). Each compressor shall be the
direct-on-line type, and equipped with vibration-proof
rubber. The hermetic compressor shall be the welded
shell type, and shall be spring suspended internally.
EVAPORATOR COIL─ The evaporator coil shall be the
multi-pass cross-finned tube type, equipped with
aluminum plate fins, mechanically bonded to
seamless oxygen-free copper tubes. The fins shall be

40
EVAPORATOR FAN SECTION─ The evaporator fan(s) The motors shall be permanently lubricated, and shall
shall be the forward-curved centrifugal type, statically be protected from water invasion.
and dynamically balanced, and belt-driven by a
kW motor. The fan motor shall be permanently
lubricated. The fan(s) shall deliver m3/min,
with
mmAq external static pressure at
rpm. A plenum chamber with an air discharge grille
shall be provided for models RP-5A4, RP-8A4 and
RP-10A4, Models RP-5A4 through RP-10AL4 is
equipped with a direct-drive type fan motor.
FILTERS─ Washable filters shall be equipped at the air
intake of the unit.
PROTECTION DEVICES ─ Each compressor shall be
protected against a breakdown by a quick response
overcurrent relay, a pressure switch and a built-in
internal thermostat(for Models RP-15AL2 through
RP-30AL3(S)).A crankcase heater shall also be
equipped. The evaporator fan motor and condenser
fan motor(s) shall be protected from overload
operation by thermal overcurrent relays equipped in
the unit.
CONTROL─ The unit shall be equipped with operation
switch(es), pilot lamp(s) and a thermostat mounted on
the unit control panel. For models RP-15AL2 and
RP-20AL1, the operation switch shall include a
OFF-FAN-COOL(HEAT) three-position push button
switch and a COOL-HEAT selection switch. For
models RP-5A4 through RP-10AL4 and RP-30AL3(S),
the operation switch is a HEAT-FAN-OFF-FAN-COOL
five position rotary switch. The operation control shall
conform to manual starting, automatic continuous
operation whenever the thermostat requires and the
protection devices allow, and a manual resetting
system after activation of a protection device.
The two compressors of the dual-circuited units shall
be started sequentially, and shall provide 50%
capacity control by a two-stage thermostat.
OPTIONAL ACCESSORIES─ Optional accessories shall
include electric heaters, hot water heaters, steam
heaters and humidifiers.

OUTDOOR UNIT
CABINET ─ The cabinet shall be constructed of
finished steel, baked with synthetic resin paint. The
fan guard wire net shall be mounted on top of unit.
REFRIGERATION CYCLE ─ The condenser shall be
composed of one refrigeration cycle, and shall be
composed of a gas inlet connection, a condenser coil
and a liquid outlet connection.
CONDENSER COIL─ The condenser coil(s) shall be
the multi-pass cross-finned tube type, equipped with
aluminum plate fins mechanically bonded to seamless
oxygen-free copper tubes. The coil(s) shall be
cleaned, dehydrated and tested for leakage at the
factory.
CONDENSER FAN AND MOTOR─ The condenser fan(s)
shall be the aluminum propeller type, statically and
dynamically balanced, and each fan shall be directly
driven by a W motor for up-flow air discharge.

41