The Effect of Power System Stabilizers (PSS) On Synchronous Generator Damping and Synchronizing Torques
The Effect of Power System Stabilizers (PSS) On Synchronous Generator Damping and Synchronizing Torques
The Effect of Power System Stabilizers (PSS) On Synchronous Generator Damping and Synchronizing Torques
Asst. Lecturer Fadhil M. Kalaf
ABSTRACT
Technical College
101
Asst. Lecturer Fadhil M. Kalaf
INTRODUCTION
102
Al-Mansour Journal Issue (18) 2012 (18) ﻣﺠﻠﺔ اﻟﻤﻨﺼﻮر اﻟﻌﺪد
2. PLANT MODEL
To investigate the effectiveness of using the power system stabilizer
(PSS) with the automatic voltage regulator (AVR), the plant model
which is the exciter-generator is shown in Figure 1 below. A
mathematical model for the exciter-generator plant was derived
depending on the Swing Equation viewpoint. The equation of central
importance in power system stability analysis are the rotational inertia
equation describing the effect of unbalance between the electromagnetic
torque and the mechanical torque of the individual machines.
The normalized swing equation then can be expressed as two first order
differential equations, then
d ( r ) 1
(Tm Te K D r )
dt 2H
(1)
d
o r
dt
(2)
The plant model will be introduced in the form of state space vector
differential equation x Ax Bu . [8, 9, 10, 11]
103
Asst. Lecturer Fadhil M. Kalaf
Vref
K4
RegulatorExciter Pm
+ +
1 K 3 E ' + Pe - 1 r o
Σ KA K2 Σ
K E sTE E Σ 1 sT3 Σ 2 Hs K s
- fd + D
K1
Et K6
+
+
Σ K5
KD K1 K2
0 0
r 2 H 2H 2H r 1
o 0 0 0 0 P
d 2 H
K3K 4 1 K 3 0 m
dt E ' 0 E ' 0 V
T3 T3 T3 0 KA ref
E fd 0 KAK 5 KAK 6
K E fd 0
E
TE
TE TE TE
(3)
104
Al-Mansour Journal Issue (18) 20012 (18) ﻣﺠﻠﺔ اﻟﻤﻨﺼﻮر اﻟﻌﺪد
KD K1 K2
2H 0
2H 2H
0 0 0
o
A 0 K3 K 4 1 K3 and
T3 T3 T3
KAK 5 KAK 6 KE
0
TE TE TE
1 0
2H 0
B 0 0
0 KA
0 T
E
Et K 5 K 6 E '
(4)
or in a matrix form
r
Et 0 K 5 K6 0
E '
E fd
(5)
105
Asst. Lecturer Fadhil M. Kalaf
(Note: if Vref is taken to be zero p.u, then the output will be the rate of
change of the terminal voltage Et , else if Vref is taken to be 1p.u then the
output will be the terminal voltage Et , which is the case in this paper).
106
Al-Mansour Journal Issue (18) 2012 (18) ﻣﺠﻠﺔ اﻟﻤﻨﺼﻮر اﻟﻌﺪد
Settling Time
Terminal Voltage
1
0.5
0
0 10 20 30 40 50 60
Time (sec)
1.8
1.6
1.4
Terminal Voltage
1.2
0.8
0.6
0.4
0.2
0
0 10 20 30 40 50 60
Time (sec)
107
Asst. Lecturer Fadhil M. Kalaf
Terminal Voltage
1.5
0.5
0
0 10 20 30 40 50 60
Time (sec)
2
Terminal Voltage
1.5
0.5
0
0 10 20 30 40 50 60
Time (sec)
PSS
K4
v
T m
+ +
1 K 3 E ' T e + 1 o
Vref
+
Σ KA +Σ K2 + Σ Σ
- E sTEE sT3 - Hs K D r s
fd +
E
K1
K6
+
Σ K5
+
Figure 4 Block diagram representation with
109
Asst. Lecturer Fadhil M. Kalaf
Phase
Washout Compensation
Gain
sTw v2 1 sT1
r K STAB vs
1 sTw 1 sT2
110
Al-Mansour Journal Issue (18) 20012 (18) ﻣﺠﻠﺔ اﻟﻤﻨﺼﻮر اﻟﻌﺪد
KD K1 K2
0 0 0
2H 2H 2H
0 0 0 0 0
r o r
K K 1 K3
0 3 4
0 0
T3 T3 T3
d E' KAK5 KAK6 KE E'
0 E
dtEfd 0 0
TE TE TE fd
v2 K K K K K v2
2KSTAB 1
D STAB 1 STAB
0 0
vs 2H 2H 2H Tw vs
T1KDKSTAB T1K1KSTAB T1K2KSTAB 1 T1 1
2HT 0
2 2HT2 2HT2 T2 T2Tw T2
0
0
0
KA Vref
T
E
0
0
(8)
112
Al-Mansour Journal Issue (18) 20012 (18) ﻣﺠﻠﺔ اﻟﻤﻨﺼﻮر اﻟﻌﺪد
Terminal Voltage 1
0.5
0
0 10 20 30 40 50 60
Time (sec)
1.8
1.6
1.4
Terminal Voltage
1.2
0.8
0.6
0.4
0.2
0
0 10 20 30 40 50 60
Time (sec)
113
Asst. Lecturer Fadhil M. Kalaf
Terminal Voltage
1.5
0.5
0
0 10 20 30 40 50 60
Time (sec)
2
Terminal Voltage
1.5
0.5
0
0 10 20 30 40 50 60
Time (sec)
114
Al-Mansour Journal Issue (18) 2012 (18) ﻣﺠﻠﺔ اﻟﻤﻨﺼﻮر اﻟﻌﺪد
5. CONCLUSIONS
In this paper at first the conventional AVR was adopted to the
synchronous generator whose data are given in Appendix A. The
synchronizing torque coefficient and the damping torque coefficient
are given in Table 1 and the time domain responses are displayed in
Figures 2 and 3. Then the conventional AVR with the power system
stabilizer (PSS) was adopted to the same synchronous generator. The
synchronizing torque coefficient and the damping torque coefficient
are given in Table 2 and the time domain responses are displayed in
Figures 6 and 7.
From the evaluated Tables and the time domain plots it is
shown that the damping is low, and if the gain of the regulator is
increased then the damping will be less. In order to solve this problem
and to increase damping, the Power System Stabilizer (PSS) was
used. Then KD was increased after using the PSS from 0.1033 to
0.7112 for a gain KA = 90, also the settling time was enhanced and
decreased from 504 sec to 73.8 sec and the same thing is true for the
other gains. It is clear that the synchronizing torque does not so
effected by the PSS as shown in Tables 1 and 2.
115
Asst. Lecturer Fadhil M. Kalaf
REFERENCES
1. MAURY, F.: Summary of the answers to the questionnaire on the
dynamic performances of future power system, CIGRE, Electra, pp. 87-100,
1975
116
Al-Mansour Journal Issue (18) 2012 (18) ﻣﺠﻠﺔ اﻟﻤﻨﺼﻮر اﻟﻌﺪد
List of symbols
APPENDIX (A)
The power system data are as follows:
K A = (1 to 90), K D = 0, K 1 = 0.7643, K 2 = 0.8649, K 3 = 0.323, K 4 =
1.4187, K 5 = -0.1463, K 6 = 0.4168, K E = -0.02, H= 3.5 MW.s/MVA,
TE = 0.56, T3 = 2.465 s.
117
Asst. Lecturer Fadhil M. Kalaf
أن اﻟﻨَﺘﺎﺋِﺞ اﻟﻤﻜﺘﺴﺒﺔ ﻗُﻮرﻧﺖْ ﺑﺈﺳﺘﻌﻤﺎل ﻣﻨﻈّﻢِ اﻟﻔﻮﻟﻄﯿﺔِ اﻵﻟﻲِ اﻟﺘﻘﻠﯿﺪيِ )(AVR
وﺑﺄﺳﺘﺨﺪام اﻟُﻠﻐﺔَ اﻟﺒﺮﻣﺠﯿﺔ .MATLAB 7
اﻟﻜﻠﯿﺔ اﻟﺘﻘﻨﯿﺔ
118