Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Standard Interfaces

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Elastimold® Cable Accessories

Standard Interfaces
Standard Interfaces for Separable Connectors,
Components and Equipment Bushings
ANSI/IEEE Standard 386 defines the specific interface dimensions that 200 A and 600 Series elbows, inserts, junctions, equipment bushings
and any mating components must conform to insure interchangeability. The table below provides information concerning the types of interfaces
supplied by Elastimold for various applications and is useful to assure proper matching of components.

Bushing Voltage Interface Standard No.


Interface Class Description Figure No
200 A DEEPWELL
EQUIPMENT BUSHING
200 A Bushing
A
IEEE
A 15 kV, 25 kV
and 35 kV
Well Interface
8.3 kV, 15.2 kV,
386-2001
Fig. 3
21.1 kV

200 A LOADBREAK INSERT


200 A Loadbreak B IEEE
15 kV 8.3 kV and 386-2001
B 8.3 kV/14.4 kV Fig. 5

200 A LOADBREAK INSERT


200 A Loadbreak C IEEE
25 kV 15.2 kV and 386-2001
C 15.2 kV/26.3 kV Fig. 7, Note 1

200 A LOADBREAK INSERT


200 A Loadbreak
Interface No. 2
D IEEE
35 kV 386-2001
D 21.1 kV and
21.1 kV/36.6 kV
Fig. 7, Note 1

200 A DEADBREAK INSERT


200 A Deadbreak
E IEEE
15 kV and 25 kV 386-2001
8.3 kV and 15.2 kV
E Fig. 4

600 SERIES EQUIPMENT BUSHING


600 A Deadbreak F IEEE
15 kV and 25 kV Interface No.1 386-2001
F 8.3 kV and 15.2 kV Fig. 11

600 SERIES EQUIPMENT BUSHING


600 A Deadbreak G IEEE
35 kV Interface No.1 386-2001
G 21.1 kV Fig. 13

1. Elastimold uses Fig. 7 interface for both 25 and 35 kV applications.

w w w. tnb.c a