Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Fiberglass Reinforced Polyester (FRP) Link Boxes: Description

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Fiberglass Reinforced Polyester (FRP) Link Boxes

DESCRIPTION Advantages of new generation


Link boxes may be installed in of EMELEC FRP link boxes:
corrosive environments such as - Excellent resistance to corrosion
offshore and marine applications. (off-shore and marine
The original industry standards applications),
for these boxes were developed - Excellent UV performance,
for metals, but most metals are - Excellent chemical resistance,
problematic alternatives for - Low water absorption,
such a harsh environment. - Self-extinguishing ammability,
Stainless steel provides more - High dielectric Strength,
corrosion resistance but for - High mechanical strength
long term operations there (tensile, bending and impact
s h o u l d b e a m o re re l i a b l e strength)
alternative. After long time
- Can be used in ambient
R&D activities and investments
temperature range of -40°C
on FRP link boxes, now this type
to 90°C,
of link boxes is available to be
manufactured in EMELEC - Light weight
production line. Raw material EMELEC FRP link boxes type
for this link boxes is SMC (Sheet tested and fully comply with
Moulding Compound) that has international standards. IP68
excellent properties. Specially tests as well as heating cycle
designed molds are used to test (7 cycles immersed in
produce lid and body of link water: heated up to 40°C for
box. Moulding process 5 hours cooled to ambient
provides precious products temperature) for this link boxes
with continuous quality has been performed.
This link boxes also can
withstand Internal arc and
short circuit currents. These
features make EMELEC FRP link
boxes exclusive compared to
other products.
16.03.03 LINK BOX SPECIFICATION (TYPE LB.U.CB.3SA.3.1)
IP protection level IP68
Internal arc 20 kA rms -0.1
Short circuit 50kA rms -1sec
AC voltage withstand 20 kVrms -1min
DC voltage withstand 25 kVrms -5min
Lightning voltage withstand 60/40 kVpeak
Insulation resistance @5kdc (20 °C) >100 G Ω
Operation temperature range -20°C :90°C
Color RAL7038
Dimensions 677x677x370 (LxWxH)
Bonding cable 95-400 mm 2
weight 62 kg
Gland material FRP

www.emelec.com.tr
Fiberglass Reinforced Polyester (FRP) Link Boxes

RAW MATERIAL (SMC) SPECIFICATION

Propert es Method Un t Value


Water Absorbt on ISO 62 % <_ 0.2
Tens le Strenght ISO 527-4 MPa 70
Flexural Strenght ISO 14125 MPa 190
Impact Strenght ISO 179 Kj/m² 70
Volume Res st v ty IEC 60093 Ohm-cm -
Surface Res stance IEC 60093 Ohm 10E11
Max mum Serv ce C° 165
Temperature, A r
M n mum Serv ce C° -40
Temperature, A r
Flammab l ty UL 94 V0 V0
Glow W re Test IEC 60695-2-12 C° 960

IPX8 (water heating cycle) test internal arc test of FRP link box in Dekra high power Lab (VEIKI VNL)

EMELEC Electr cal Eng neer ng and Trad ng Co.


Eski Ankara Asfaltı (İTOSB) Istanbul Tuzla Org. San. Bölgesi 4. Cad. No: 25 34959 Tepeören, Tuzla / Istanbul / Turkey,
EMC.22.013 REV00 nfo@emelec.com.tr - www.emelec.com.tr