Technical Review On Parallel Ground Continuity Conductor of Underground Cable Systems
Technical Review On Parallel Ground Continuity Conductor of Underground Cable Systems
Technical Review On Parallel Ground Continuity Conductor of Underground Cable Systems
250~256, 2012
http://dx.doi.org/10.5370/JICEE.2012.2.3.250
Abstract – The Induced sheath voltage is significantly increased at single point bonding section when the
ground fault occurs on power cable system because there is no return path of fault current. For solving
this problem, therefore, many researchers recommend the PGCC (Parallel Ground Continuity Conductor).
In this paper, the characteristics of PGCC are extensively analyzed for reducing the level of induced
sheath voltage at the single point bonded section for Korea underground power cable system
where, Ib is conductor current of phase B and S1C, S2C As shown in Equation (6), the sheath voltage can be
and S3C are axial spacings between PGCC and conductor of influenced by the distance between PGCC and phase
phase A, Phase B and C, respectively. conductor. GMR of PGCC(rg) can be also influenced when
If Ia or Ic is considered
onsidered in Equation (1), Ib can be the PGCC is installed on the sys
system. The sheath voltage is
alternated by a ∙ I or a ∙ I , respectively. Where, a is reduced by closer distance of S and thicker GMR of rg.
√
− +j . Also, the maximum overvoltage between sheath
and earth can be expressed by Equations (2) to (5) when the
single line to ground fault occurs
urs on underground power
cable system. For a trefoil arrangement (S12=S23=S13=S)
which is considered for PGCC installation in this paper, the
sheath voltages are equal and are expressed by Equation (6).
√
E = jωI (2 × 10)[− ln ∙ + j
ln ( ) (2)
∙ √
E = jωI (2 × 10 )[ ln
+j
ln ( ) (3)
3. Model System
where, S12 is axial spacing
ing between phase A and phase B,
S23 is axial spacing between phase B and phase C, S13 is The diagram of a real power cable system discussed in
axial spacing between phase A and phase C and d is this paper is shown in Fig. 3. It is a single core cable
geometric mean sheath diameter. transmission system with the voltage of 154 kV. The total
length of the cable is 3.392 km. It consists of three
E = jωI (2 × 10 ) ln (5) crossbonded major sections with three minor sections for
each major section. Joint No. 9 is the single point bonded
Fig. 1 and Fig. 2 illustrate the overvoltage induced on section. As usual, the sheaths
ths are jointed and cross bonded
SVL at single point bonded section according to installation between two sections.
of PGCC or not. As shown in Fig. 1, in the absence of a
PGCC, if the ground fault occurs on a cable, in the case of
trefoil arrangement, the overvoltage induced
ced on SVL is the
vectorial sum of voltage gradient on sheath(Es) expressed in
Equation (5) and the earth potential rise(Ve). Accordingly,
in this case, it is possible to damage SVL according the
amplitude of added overvoltage.
However, as shown in Fig. 2, if PGCC is installed in
same system, the fault current is distributed to sheath and
PGCC because PGCC provides a return path of fault
current. Consequently, the overvoltage induced on SVL is
significantly reduced to ‘Es-Ec’. Equation (6) shows the
voltage gradient on sheath when the PGCC is installed on
underground power cable system. Where, S is the distance Fig. 2. SVL overvoltage in case of installation of PGCC
PGCC.
between PGCC and phase conductor, rg is GMR(geometric
mean radius) of PGCC. In this paper, the single line to ground fault is supposed
to occur at 1.065 km from A S/S to test the effects of PGCC.
EMTP/ATP is used forr system modeling and simulation.
E = jωI (2 × 10 ) ln[
] (6)
252 Jong-Beom Lee and Chae-Kyun Jung
Table 2. Dimension
imension of PGCC according to kinds of conducto
conductor size
Radius of Radius of
Type Permittivity
conductor [m] insulation [m]
TFR-CV
0.00915 0.01085 2.4
240 ㎟
TFR-CV
0.0132 0.0174 2.4
500 ㎟
where,
() θ θ
k = ln (1 + ) (8)
ρ θ
for both conductor sizes are 62.1 % and 66.3 %. The arrangement of Type 1 listed in Table 3. PGCC is installed
difference is very small. Accordingly, although TFR CV closely to Phase C. Fig. 9 shows the simulation results
500 ㎟ is a little better, TFR CV 240 ㎟ is more when the single line to ground fault occurs on each phase.
economical for optimal conductor size of PGCC because As shown in Fig. 9, averagely, the reduction rate of faulty
the reduction difference is not big. phase C is better than other phase faults because of position
of PGCC. The average reduction rates of faulty phase A, B
and C are 62.1 %, 68.8 % and 72.4 %, respectively.
Next, the sheath voltage reduction rate is also discussed
in case of the use of two PGCCs in trefoil arrangement of
Type 1. Its result is compared with result of one PGCC. The
detailed arrangement information is listed in Table 5.
Fig. 7. Sheath voltage reduction rate according to change of Fig. 10 shows the simulation results when one PGCC and
conductor size in duct formation. two PGCCs are installed on power cable system. As shown
in Fig. 10, the reduction rate of two PGCCs is better than
one PGCC. The average reduction rates of one PGCC and
two PGCCs are 62.1 % and 83.9 %, respectively. From
these results, it proves that two PGCCs is much more
effective than one PGCC, its difference rate is 21.8 %.
However, for use of two PGCCs on real power cable
system, the economical estimation will be performed in the
near future.
Table 6. Case of transposed PGCC more economical than Type 2 considering installation
Arrangement Type Conductor size length of PGCC. Therefore, in this paper, Type 1 is selected
Trefoil for optimal installation section of PGCC. In addition, the
Type 1 TFR-CV 240 ㎟
(Transposed PGCC)
reduction effect of trefoil arrangement is better than duct
because of closer distance between phase conductor and
PGCC.
In trefoil arrangement, the reduction effect of TFR CV
500 ㎟ is also slightly better than that of TFR CV 240 ㎟.
The average reduction rates for both conductor sizes are
62.1 % and 66.3 %, the difference is very small. Two
PGCCs are much more effective than one PGCC with
difference rate of 21.8 %. Finally, the average reduction
rate of transposed PGCC is 70.8 %, 8.7 % better than no
transposed PGCC. Comparing duct formation and directly
buried formation, there is little difference in trefoil
arrangement because the spacing between phase conductors
Fig. 11. Sheath voltage reduction rate comparison of no
of trefoil arrangement is closer than duct or directly buried
transposed PGCC with transposed PGCCs.
formation.
Korea electric power company is now planning for
In Fig. 11, the sheath voltage reduction rate of transposed
adopting PGCC based on the results of this paper.
PGCC is compared with no transposed PGCC. As shown in
Accordingly, in the near future, the results of this paper will
Fig. 11, the effect of transposed PGCC is better than no
contribute to the application of PGCC on real power cable
transposed PGCC. The average reduction rate of transposed
system in Korea.
PGCC is 70.8 %, about 8.7 % better than no transposed
PGCC. Consequently, the difference is not big compared
with duct formation or directly buried formation because
the spacing between phase conductors is closer than duct or References
directly buried formation.
[1] CIGRE WG B1.18, “Special Bonding of High Voltage
Power Cables, Oct. 2005
[2] IEEE, “IEEE Guide for the Application of Sheath
7. CONCLUSION
Bonding Methods for Single-conductor Cables and
This paper describes the characteristics of PGCC for Calculation of induced Voltage and Current in Cable
single point bonded underground power cable systems. The Sheaths, ANSI/IEEE Std. 575-19980
optimal PGCC conductor size and installation section are [3] J. W. Kang, C. K. Jung, K. K. Choi, T. I. Jang, H. H.
selected, in addition, the various analysis considering Yoon, “A Study on Transient Analysis by Installation
conductor size, two PGCCs and transposed installation are of Earth Continuity Conductor on Underground Power
also performed. The detailed results are the following; Cable Systems, 2008 ICEE Conference, July 2008
The conductor size of PGCC has been determined by [4] KEPRI, “A Study on the Establishment of Grounding
IEC 60364-5-54, the calculated conductor size is 201.3 ㎟. Technology for the Underground Power Transmission
System, 1998
Accordingly, the conductor size of 240 ㎟ is selected as
[5] KEPCO, “Underground Transmission Cable System”,
optimal conductor size for PGCC.
Dec. 2002
For selection of optimal installation section, 3 kinds of
[6] IEC 60364-5-54, “Electrical installations of buildings –
installation types are proposed in duct as well as trefoil
Part 5-54 : Selection and erection of electrical
arrangement. In duct formation, averagely, each sheath
equipment – Earthing arrangements, protective
voltage reduction rate of Type 1 and Type 2 is 36.1 % and
conductors and protective bonding conductors”, June
34.8 %, respectively, but Type 3 is just 5.07 %. In trefoil
2002
arrangement, the sheath voltage reduction rate of Type 1,
[7] J. B. Lee and C. K. Jung, “Parallel Ground Continuity
Type 2 and Type 2 are 62.1 %, 62.3 % and 4.19 %. Type 1
Conductor in Single Pont Bonded Section, “ICEE 2011
and Type 2 are also similarly reduced, but Type 3 is just
Conference Proceedings, July 2011
slightly reduced. Comparing Type 1 and Type 2, Type 1 is
256 Jong-Beom Lee and Chae-Kyun Jung