Seismic Piping Support

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 41

Determination Of The requirement Of Bracing Sy

Province

1.Determination of SDS & SD1 VALUES

S1 (the mapped maximum considered earthquake spectral response


acceleration at a period of 1-sec)
Ss the mapped maximum considered earthquake spectral response
acceleration at short periods

Fa ( FUNCTION OF SITE CLASS AND MAPPED SHORT PERIOD)

Fv (FUNCTION OF SITE CLASS AND MAPPED 1-SECOND PERIOD)

SMS (The maximum considered earthquake spectral


response acceleration for short periods
SM1 (The maximum considered earthquake spectral
response acceleration at 1-sec )

SDS (Design earthquake spectral


response acceleration at short periods)
SD1 (Design earthquake spectral
response acceleration at 1-sec period)

2.Determination of Occupancy Risk Category


Ocuupany Risk category shall be determined as per SBC 201 Table 1604.5

BUILDING RISK CATEGORY =

3.Determination of Seismic Design Category


Each building and structure shall be assigned to the most severe Seismic Design Category in

BUILDING SEISMIC DESIGN CATEGORY As Per Table 9.6.a =

BUILDING SEISMIC DESIGN CATEGORY As Per Table 9.6.b =

BUILDING SEISMIC DESIGN CATEGORY =

3.Determination of Importance Factor (Ip)


As per SBC 301 Clause no.12.1.5, Ip = 1.5 for life safety component required to function a
system)
4.Determination of The Requirement Of Bracing system I

As per SBC 301 CHAPTER 12, All architectural, mechanical, electrical, and other non-structural com
to resist the equivalent static forces and displacements Except :
1.All Components in Seismic Design Categoty A.
2.All Mechanical and Eelectrical componenets in Seismic Design Category B.
3.Mechanical and electrical components in structures assigned to Seismic Design Category C provid
4. Mechanical and electrical components in Seismic Design Category D where Ip = 1.0 and flexible c
ductwork, piping, and conduit are provided and that are mounted at (1.25 m) or less above a floor
5.Mechanical and electrical components in Seismic Design Category D weighing (100 N) or less whe
components and associated ductwork, piping, and conduit
are provided, or for distribution systems, weighing (7 N/m) or less.

Bracing system For Sprinkler Network is not required for Seismic design categor

Bracing system is
uirement Of Bracing System in Fire sprinkler Network

Madina

Code Reference SBC 301

0.073 Figures 9.4.1(b) through 9.4.1(i)

0.25 Figures 9.4.1(b) through 9.4.1(i)

1 Table 9.4.3.a

1 Table 9.4.3.b

0.25 Clause No.9.4.3- Eqn 9.4.3-1 ( SMS=Ss*Fa)

0.073 Clause No.9.4.3- Eqn 9.4.3-2 ( SM1=S1*Fv)

0.16666666666667 Clause No.9.4.4- Eqn 9.4.4-1 ( SDS=(2/3)*SMS)

0.04866666666667 Clause No.9.4.4- Eqn 9.4.4-2 ( SD1=(2/3)*SM1)

Table 1604.5

IV
st severe Seismic Design Category in accordance with SBC 301 Table 9.6.a or 9.6.b

component required to function after an earthquake (e.g., fire protection sprinkler


quirement Of Bracing system In Fire Sprinkler Network

ectrical, and other non-structural components in structures shall be designed and constructed
pt :

sign Category B.
ed to Seismic Design Category C provided that the importance factor (Ip) is equal to 1.0.
Category D where Ip = 1.0 and flexible connections between the components and associated
unted at (1.25 m) or less above a floor level and weigh (1800 N) or less.
ategory D weighing (100 N) or less where Ip = 1.0 and flexible connections between the

or less.

uired for Seismic design category A or B, only IS required for Category C or D

Required