Tutorial - Wind Load Calculation Example
Tutorial - Wind Load Calculation Example
Summary
• (Method 1) Without significant • (Method 2) With significant
resonant dynamic response resonant dynamic response
1. Calculate design wind 1. Calculate design hourly mean
pressure (Table 1) wind pressure (Table 2)
2. Determine topography factor 2. Compute gust response factor
Sa (Appendix C) G (Appendix F)
3. Calculate force coefficients Cf 3. Determine topography factor
(Appendix D) Sa (Appendix C)
4. Calculate total wind force 4. Calculate force coefficients Cf
(Appendix D)
F C f qz Az
5. Calculate total wind force
F GC f qz Az
3
Example 1
Determine the base shear and overturning moment.
H = 60 m 30 m
h=3m
x = 50 m 40 m
Wind direction
HU = 100 m
LU = 500 m LD = 1000 m
4
Solution
Checking for resonant effect
H 60 m 100 m Without significant resonant
dynamic response (Clause 3.3)
H / d 60 / 30 2 5
Topography effect
100 100
upwind slope 𝛼𝑈 = = 0.2 downwind slope 𝛼𝐷 = = 0.1
500 1000
Significant
5
Topography factor
𝑆𝑎 = (1 + 1.2𝛼𝑒 𝑠)2 𝑥 50
= = 0.05
𝐿𝐷 1000
C f Ch Cs 1.1
8
Breadth = 40 m
Projected area = 40 x 60 = 2400 m2
Reduction factor = 0.94
9
Further Question
If the building height is now modified to 110 m with damping
ratio of 2%, dynamic resonant effect should be considered.
𝑔 2 𝑆𝐸
G-factor calculation 𝐺 = 1 + 2𝐼ℎ 𝑔𝑣 2 𝐵 +
𝑓
𝜁
𝑔𝑣 = 3.7
46 46
𝑛𝑎 = = = 0.4182 Hz
ℎ 110
1 1
𝐵= = = 0.7129
36ℎ2 + 64𝑏 2 36(110)2 +64(40)2
1+ 1+
𝐿ℎ 1821.16
where
ℎ 110 0.25
𝐿ℎ = 1000( )0.25 = 1000( ) = 1821.16 m
10 10
where
𝑉ℎ = 50.3 m/s
𝑛𝑎 𝐿ℎ 0.4182 × 1821.16
𝑁= = = 15.1527
𝑉ℎ 50.3
14
1 1
𝑆= = = 0.1022
3.5𝑛𝑎 ℎ 4𝑛𝑎 𝑏 3.5(0.4182)(110) 4(0.4182)(40)
1+ 1+ 1+ 1+
𝑉ℎ 𝑉ℎ 50.3 50.3
2𝐵
𝑔𝑓 2 𝑆𝐸
𝐺 = 1 + 2𝐼ℎ 𝑔𝑣 +
𝜁