Saudi Aramco Test Report

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 7

SAUDI ARAMCO ID/PIEU -3- July-2018 - REV. 2018.04.00 (Standards Cutoff -April 30, 2018) Rev. 2018.04.

00 30-Apr-18

SAUDI ARAMCO TEST REPORT SATR NUMBER DATE APPROVED QR NUMBER

Low Voltage Power and Control Cable (On Reel), Continuity


SATR-P-3201 3-Jul-18 ELECT-
and Megger Insulation Resistance Testing
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED TEST DATE & TIME ACTUAL TEST DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

ITEM
TEST PROCEDURE ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.

A. TEST PROCEDURE AND CHECKLIST

Inspection shall be performed by the project approved Quality Control Schedule Q


A1 Inspector (QCI) and witness point shall be coordinated with the Contractor
and Company. Att. IV Sec. 3
Check physical condition of drum for apparent damage. SAES-P-104
A2
NETA ATS - 2009, 7.3.2.1.2 Sec. 3.2
Compare cable data with drawings and specifications. SAES-P-104
A3
NETA ATS - 2009, 7.3.2.1.1 Sec. 3.2
SAES-P-104
A4 Check cable color coding with applicable specifications.
Sec. 6.10.3

All ends under test shall be guarded from accidental contact as well as
SAES-P-104
A5 separation from all ends or elements not being subject to test.
Sec. 4.1
NFPA 70, NEC 110.3 & NETA ATS 2009, 5.1

Perform continuity test of each core of cable drum to ensure no conductor


SAES-P-104
A6 is broken with certified and calibrated Ohm-meter.
Sec. 3.2
NETA ATS - 2009, 7.3.2.3.2.3

Perform Insulation Resistance (Megger) Test on each core of cable on


drum with certified and calibrated meter. The Ohmic values shall be
recorded:
SAES-P-104
A7 For cables 250 volt and less use 500 volt megger
Sec. 3.2
For cables 250 volt to 600 volt use 1000 volt megger
For cables above 600 volt and less than 1200 volt use 2500 volt megger
NETA ATS - 2009, 7.3.2.2.2

Low voltage (600, 450/750, or 600/1000V rated) cables shall be 1000 V SAES-P-104
A8
DC megger tested. Sec. 13.1

All conductors should be left grounded when not on test, during the testing
SAES-P-104
A9 of other conductors, until completely discharged of all DC potential.
Sec. 4.1
NFPA 70, NEC 110.3

Test Records and Receipt documents are to be carefully presented in SAES-P-104


A10
original. Sec. 3.2

B. TEST EQUIPMENT AND MATERIALS CRITERIA

1. Digital / Analog Multimeter for Continuity Test.

2. Megger for Insulation Resistance Test.

3. For measurement of time, the instruments’ accuracy shall be ±1% or better.

4. The test equipment calibration cycle shall not exceed twelve months.
Schedule Q, Att. IV, Sec. 7

Test Equipment Manufacturer: Serial Number:

Scale Range and accuracy: Calibration date:

Saudi Aramco: Company General Use


Calibration Company and Technician: Calibration Expiration Date:

Saudi Aramco: Company General Use


SAUDI ARAMCO ID/PIEU -3- July-2018 - REV. 2018.04.00 (Standards Cutoff -April 30, 2018) Rev. 2018.04.00 30-Apr-18
SATR NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO TEST REPORT
Low Voltage Power and Control Cable (On Reel), Continuity
SATR-P-3201 3-Jul-18 ELECT-
and Megger Insulation Resistance Testing
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
No.

C. TEST RESULTS

D. CONCLUSIONS

ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
No.
Minimum insulation-resistance values should not be less than 50
SAES-P-104
D1 megohms.
Sec. 3.2
NETA ATS - 2009, 7.3.2.3.4

Investigate deviations between adjacent phases. SAES-P-104


D2
NETA ATS - 2009, 7.3.2.3.4 Sec. 3.2

If cable megger test result from conductor to sheath is less than 20 M


SAES-P-104
D3 Ohms, the cable shall not be used.
4.1
NFPA 70, NEC 110.3

Test results are acceptable and in accordance with Saudi Aramco Schedule Q
D4
Engineering Standards and contractual requirements. Att. II

REMARKS:

ATTACHMENT(S):
1. Attachment - 1 SA-P-040 SA Pre-Com Form, Low Voltage Cables, March 2006

REFERENCE DOCUMENTS:
1. Schedule G - Material, Tools and Equipment (Pro Forma MP-IK-LS Contract), March 2006
2. Schedule Q - Quality Requirements (Pro Forma Contract), February 2008
3. Pre-Commissioning Form (SA-P-040) Low Voltage Cables, March 2006
4. Acceptance Testing Specifications - NETA (2009)
5. SAES-P-104 Wiring Methods and Materials, 01 January 2018
NOTES:
1. Approved - Acceptable to the authority having jurisdiction (i.e., Saudi Aramco ID).
2. Identified - Recognizable as suitable for the specific application by a qualified testing laboratory (i.e., listing and/or labeling).
3. Listed - Equipment and materials included in a list published by an approved qualified organization concerned with evaluation of products
or services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose listing states
that the equipment, material, or services either meets appropriate designated standards or has been tested and found suitable for a specified purpose.
4. Labeled - Equipment or materials to which has been attached a label, symbol, or other identifying mark of an approved qualified organization concerned

Saudi Aramco: Company General Use


SAUDI ARAMCO ID/PIEU -3- July-2018 - REV. 2018.04.00 (Standards Cutoff -April 30, 2018) Rev. 2018.04.00 30-Apr-18
SATR NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO TEST REPORT
Low Voltage Power and Control Cable (On Reel), Continuity
SATR-P-3201 3-Jul-18 ELECT-
and Megger Insulation Resistance Testing
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
No.
with product evaluation, that maintains periodic inspection of production of labeled equipment or materials, and by whose labeling the manufacturer
indicates compliance with appropriate standards or performance in a specified manner.

Saudi Aramco: Company General Use


SAUDI ARAMCO ID/PIEU -3- July-2018 - REV. 2018.04.00 (Standards Cutoff -April 30, 2018) Rev. 2018.04.00 30-Apr-18
SATR NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO TEST REPORT
Low Voltage Power and Control Cable (On Reel), Continuity
SATR-P-3201 3-Jul-18 ELECT-
and Megger Insulation Resistance Testing
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
No.

Contractor / Third-Party Saudi Aramco


Technician Performing Test* PMT Representative
Test Performed Successfully and Results are Acceptable: T&I Witnessed QC Record Reviewed Work Verified
Name, Title, Department,
Name, Initials and Date:
Company, Initials and Date:

QC Inspector PID Representative


Witnessed Test Work / Rework May Proceed T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Supervisor Proponent and Others


Quality Record Approved: T&I Witnessed QC Record Reviewed Work Verified
Name, Organization,
Name, Sign and Date:
Initials and Date:

*Person Responsible for Implementation of Test and Analysis of Results Y = YES N = NO F = FAILED

Saudi Aramco: Company General Use


SAUDI ARAMCO ID/PIEU -3- July-2018 - REV. 2018.04.00 (Standards Cutoff -April 30, 2018) Rev. 2018.04.00 30-Apr-18
SATR NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO TEST REPORT
Low Voltage Power and Control Cable (On Reel), Continuity
SATR-P-3201 3-Jul-18 ELECT-
and Megger Insulation Resistance Testing

Attachment - 1 (Pre-Com Form, SA-P-040)

Saudi Aramco: Company General Use


SAUDI ARAMCO ID/PIEU -3- July-2018 - REV. 2018.04.00 (Standards Cutoff -April 30, 2018) Rev. 2018.04.00 30-Apr-18
SATR NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO TEST REPORT
Low Voltage Power and Control Cable (On Reel), Continuity
SATR-P-3201 3-Jul-18 ELECT-
and Megger Insulation Resistance Testing

Saudi Aramco: Company General Use