Saudi Aramco Test Report
Saudi Aramco Test Report
Saudi Aramco Test Report
00 30-Apr-18
EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED TEST DATE & TIME ACTUAL TEST DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
TEST PROCEDURE ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.
All ends under test shall be guarded from accidental contact as well as
SAES-P-104
A5 separation from all ends or elements not being subject to test.
Sec. 4.1
NFPA 70, NEC 110.3 & NETA ATS 2009, 5.1
Low voltage (600, 450/750, or 600/1000V rated) cables shall be 1000 V SAES-P-104
A8
DC megger tested. Sec. 13.1
All conductors should be left grounded when not on test, during the testing
SAES-P-104
A9 of other conductors, until completely discharged of all DC potential.
Sec. 4.1
NFPA 70, NEC 110.3
4. The test equipment calibration cycle shall not exceed twelve months.
Schedule Q, Att. IV, Sec. 7
ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
No.
C. TEST RESULTS
D. CONCLUSIONS
ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
No.
Minimum insulation-resistance values should not be less than 50
SAES-P-104
D1 megohms.
Sec. 3.2
NETA ATS - 2009, 7.3.2.3.4
Test results are acceptable and in accordance with Saudi Aramco Schedule Q
D4
Engineering Standards and contractual requirements. Att. II
REMARKS:
ATTACHMENT(S):
1. Attachment - 1 SA-P-040 SA Pre-Com Form, Low Voltage Cables, March 2006
REFERENCE DOCUMENTS:
1. Schedule G - Material, Tools and Equipment (Pro Forma MP-IK-LS Contract), March 2006
2. Schedule Q - Quality Requirements (Pro Forma Contract), February 2008
3. Pre-Commissioning Form (SA-P-040) Low Voltage Cables, March 2006
4. Acceptance Testing Specifications - NETA (2009)
5. SAES-P-104 Wiring Methods and Materials, 01 January 2018
NOTES:
1. Approved - Acceptable to the authority having jurisdiction (i.e., Saudi Aramco ID).
2. Identified - Recognizable as suitable for the specific application by a qualified testing laboratory (i.e., listing and/or labeling).
3. Listed - Equipment and materials included in a list published by an approved qualified organization concerned with evaluation of products
or services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose listing states
that the equipment, material, or services either meets appropriate designated standards or has been tested and found suitable for a specified purpose.
4. Labeled - Equipment or materials to which has been attached a label, symbol, or other identifying mark of an approved qualified organization concerned
ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
No.
with product evaluation, that maintains periodic inspection of production of labeled equipment or materials, and by whose labeling the manufacturer
indicates compliance with appropriate standards or performance in a specified manner.
ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
No.
*Person Responsible for Implementation of Test and Analysis of Results Y = YES N = NO F = FAILED