Frako KBR Compensare Componente
Frako KBR Compensare Componente
Frako KBR Compensare Componente
2
Power Factor Correction Capacitors
Type LKT
3
Power Factor Correction Capacitors
Type LKT
Capacitor current
2
Power Factor Correction Capacitors
Type LKT
To verify the correct functioning of the integrated safety phase capacitors are available as Standard version.
systems, FRAKO regularly draws sample capacitors
from the production line. A constantly outstanding quality
can be achieved and maintained only this way. Rating
0.8 - 37.2 kvar; 230 - 800 V; 50 or 60 Hz (other Voltages
on request!)
Voltage Load Capacity
FRAKO Power Factor Correction Capacitors have a load
Capacitance and Rating Tolerance
capacity in accordance with EN 60831-1 and -2 as well
as IEC 831-1 and -2: ± 5%
Temperatur Class
Application up to - 40 °C; + 65 °C depending on design
FRAKO manufactures four series of Power Factor
Correction Capacitors: Basic, Standard, Premium and
NEW! Heavy Duty. Discharging
We recommend Basic Capacitors for networks with low According to EN 60831, every power capacitor must
harmonic content and normal ambient temperature. have a discharge device which guarantees a discharge
Standard Capacitors are recommended for networks to 75 V within three minutes. FRAKO capacitors have
with higher harmonic levels and/or high ambient integrated discharge resistors which guarantee a
temperature. Premium Capacitors should be used discharge to 50 V within one minute.
for demanding networks (i.e. networks with very high
harmonic levels ans/or very high ambient temperature). Accessories for FRAKO
Heavy Duty Capacitors are recommended for extreme
demanding network- and ambient conditions. All four
Power Factor Correction Capacitors
series of capacitors are of excellent FRAKO quality. All capacitors can be equipped with a patented connec-
FRAKO holds the Management System Certificate ting terminal in tension spring method against surcharge.
ISO 9001 and the Environmental Management System This connecting terminal ensures a fast, perfect and
ISO 14001. permanent electrical contact of the connecting wires. All
capacitors up to diameter 70 mm can be equipped with a
plastic cap and rubber sleeve to cover the connections.
Mechanical Construction
Article-No. Description Type
Cylindrical aluminium case with mounting stud M12 ×12,
low loss self-healing dielectric made from segmented 31-08000 Plug-in type connecting AKD 25/3
terminal for capacitors with
metallized polypropylene film. Filled with a PCB-free, ∅ 60 and ∅ 70 mm, 3-phase
flame inhibiting, mineral filler with adhesive stabilizer
31-08002 Plug-in type connecting AKD 25/2
and integrated mechanical overpressure disconnector. terminal for capacitors with
Permanently connected external discharge resistors at ∅ 60 and ∅ 70 mm, single-
the terminals. The connecting terminal, which is available phase
as an accessory, protects against direct contact of the 31-08003 Plug-in type connecting AKD 30/3
fast-on terminals and meets the protection class IP 20. terminal for capacitors with
∅ 85 mm, 3-phase
69-00352 Plastic caps for LKT with LKT 60
∅ 60 mm
Design 69-00350 Plastic caps for LKT with LKT 70
FRAKO Power Factor Correction Capacitors are availa- ∅ 70 mm
ble as three-phase capacitors in four versions: Basic, 69-00353 Rubber sleeve LKT
Standard, Premium and NEW! Heavy Duty. The single-
3
Power Factor Correction Capacitors
Type LKT
Technical Data
Technical Data Basic Capacitor Standard Capacitor Premium Capacitor Heavy Duty Capacitor
operated with operated with
DL-specification DP-specification*
NEW
Type LKT…-DB LKT…-DP/EP LKT…-DL LKT…-DL LKT…-HD
Rated reactive 1.66…36 kvar 0.8…37.2 kvar 1.4…24 kvar 1.4…29 kvar 3.3…21.6 kvar
power
Rated voltage 230…525 V 230…800 V 230…525 V 230…615 V 230…525 V
Rated frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Max. overcurrent 1.5 × lN 1.8 × lN 2.2 × lN 2.0 × lN 2.7 × lN
(permanently) (at rated voltage, (at rated voltage, (at rated voltage, (at rated voltage, (at rated voltage, 50 Hz)
50 Hz) 50 Hz) 50 Hz) 50 Hz)
Max. inrush 200 × lN 250 × lN 300 × lN 300 × lN 450 × lN
NEW
current (at rated voltage, (at rated voltage, (at rated voltage, (at rated voltage, (at rated voltage, 50 Hz)
50 Hz) 50 Hz) 50 Hz) 50 Hz)
Temperature class -25ºC / D -40 / +60ºC -40 / +65ºC -40 / +60ºC -40 / +65ºC continuous
continuous continuous continuous
Min. / max. -25ºC / +55ºC -40ºC / +60ºC -40ºC / +65ºC -40ºC / +60ºC -40ºC / +65ºC
temperature
Max. case 70ºC 75ºC 78ºC 75ºC 78ºC
temperature
Dielectric power 0.2 W/kvar 0.2 W/kvar 0.2 W/kvar 0.2 W/kvar 0.2 W/kvar
loss
Test voltage 2.15 × UN for 2 s 2.15 × UN for 2 s 2.15 × UN for 2 s 2.15 × UN for 2 s 2.15 × UN for 2 sec.
terminal / terminal 1.85 × UN for 18 s 1.85 × UN for 18 s 1.85 × UN for 18 s 1.85 × UN for 18 s 1.85 × UN for 18 sec.
NEW
Test voltage 3,900 V, 2 s 3,900 V, 2 s 3,900 V, 2 s 3,900 V, 2 s 3,900 V, 2 s
terminal / case
Isolation level 3/8 kV 3/8 kV 3/8 kV 3/8 kV 3/8 kV
Mean life 100,000 h. 130,000 h. 170,000 h. 130,000 h. 200,000 h.
expectancy
Max. humidity 95% 95% 95% 95% 95%
Max. altitude 4,000 m 4,000 m 4,000 m 4,000 m 4,000 m
Number of 20,000 40,000 60,000 60,000 100,000
annual switching
operations
Discharging level ≤ 50 V ≤ 50 V ≤ 50 V ≤ 50 V ≤ 50 V
NEW
in 60 s
Recommended for Networks with low Networks with Demanding Networks with Extreme demanding
harmonic content higher harmonic networks higher harmonic network- and ambient
and normal ambient levels and/or high (i.e. networks levels and/or conditions
temperature ambient temperature with very high high ambient
harmonic levels temperature
and/or very
high ambient
temperature)
Generally, DL-type capacitors can also be operated at higher voltages with the DP-type specification.
Please note that the DP values in the chart are marked with *.
4
Power Factor Correction Capacitors
Type LKT
Dimensions
17.0
15.0
35.0
28.0
h
h
16
16
12
12
50
67 / 77
Capacitors with Capacitors with Capacitors with Capacitors with Plastic cap and rubber sleeve
d = 60 / 70 mm d = 60 / 70 mm d = 85 mm d = 85 mm LKK 60/70 for capacitors with:
for connection with Spring tension for connection with Spring tension terminal d = 60 mm (Art.No. 69-00352) /
flat cable plug terminal flat cable plug AKD 30/3 d = 70 mm (Art.No. 69-00350)
6.3 × 0.8 mm AKD 25/3 9.5 × 1.2 mm 16 mm2 (not available for capacitors with
2 × 6 mm2 d = 85 mm)
Art.-No. 31-08003
Art.-No. 31-08000 rubber sleeve
Art.-No. 69-00353
5
Power Factor Correction Capacitors
Type LKT…-DB for 50 Hz
Basic Capacitors
Capacitor Dimensions Article-No. Rated Reactive Power in kvar at Rated Voltage 50 Hz
Type mm
230 V 250 V 300 V 400 V 415 V 440 V 460 V 480 V 525 V
Three-phase capacitors
LKT 5-400-DB 60 × 150 31-10414 1.66 2.0 2.8 5.0
LKT 6.25-400-DB 60 × 150 31-10400 2.1 2.4 3.5 6.25
LKT 7.5-400-DB 60 × 150 31-10415 2.5 2.9 4.2 7.5
LKT 10-400-DB 60 × 225 31-10416 3.33 3.9 5.6 10.0
LKT 12.5-400-DB 60 × 225 31-10401 4.17 4.9 7.0 12.5
LKT 15-400-DB 70 × 225 31-10417 5.0 5.9 8.4 15.0
LKT 20-400-DB 85 × 215 31-10418 6.66 7.8 11.3 20.0
LKT 25-400-DB 85 × 278 31-10402 8.33 9.8 14.1 25.0
LKT 30-400-DB 85 × 320 31-10403 9.9 11.7 16.9 30.0
LKT 6.25-440-DB 60 × 150 31-10404 1.7 2.0 2.9 5.2 5.6 6.25
LKT 10-440-DB 60 × 225 31-10412 2.7 3.2 4.7 8.33 8.9 10.0
LKT 12.5-440-DB 60 × 225 31-10405 3.4 4.0 5.8 10.3 11.1 12.5
LKT 15-440-DB 70 × 225 31-10406 4.1 4.8 7.0 12.4 13.3 15.0
LKT 20-440-DB 85 × 278 31-10413 5.5 6.5 9.3 16.5 17.8 20.0
LKT 25-440-DB 85 × 278 31-10407 6.8 8.1 11.6 20.7 22.2 25.0
LKT 30-440-DB 85 × 278 31-10408 8.2 9.7 14.0 24.8 26.7 30.0
LKT 6.25-525-DB 60 × 225 31-10409 3.6 3.9 4.4 4.8 5.2 6.25
LKT 12.5-525-DB 70 × 225 31-10410 7.3 7.8 8.8 9.6 10.4 12.5
LKT 15-525-DB 70 × 225 31-10419 8.7 9.4 10.5 11.5 12.5 15.0
LKT 17.2-525-DB 70 × 225 31-10434 10.0 10.8 12.1 13.2 14.4 17.2
LKT 20-525-DB 70 × 265 31-10420 11.6 12.5 14.1 15.4 16.7 20.0
LKT 25-525-DB 85 × 278 31-10411 14.5 15.6 17.6 19.2 20.9 25.0
6
Power Factor Correction Capacitors
Type LKT…-DB for 60 Hz
Basic Capacitors
Capacitor Dimensions Article-No. Rated Reactive Power in kvar at Rated Voltage 60 Hz
Type mm
230 V 250 V 300 V 400 V 415 V 440 V 460 V 480 V 525 V
Three-phase capacitors
LKT 5-400-DB 60 × 150 31-10414 2.0 2.3 3.33 6.0
LKT 6.25-400-DB 60 × 150 31-10400 2.5 2.9 4.2 7.5
LKT 7.5-400-DB 60 × 150 31-10415 3.0 3.5 5.1 9.0
LKT 10-400-DB 60 × 225 31-10416 4.0 4.7 6.8 12.0
LKT 12.5-400-DB 60 × 225 31-10401 5.0 5.9 8.4 15.0
LKT 15-400-DB 70 × 225 31-10417 6.0 7.0 10.1 18.0
LKT 20-400-DB 85 × 215 31-10418 7.9 9.4 13.5 24.0
LKT 25-400-DB 85 × 278 31-10402 9.9 11.7 16.9 30.0
LKT 30-400-DB 85 × 320 31-10403 11.9 14.1 20.3 36.0
LKT 6.25-440-DB 60 × 150 31-10404 2.0 2.4 3.5 6.2 6.7 7.5
LKT 10-440-DB 60 × 225 31-10412 3.33 3.9 5.6 9.9 10.7 12.0
LKT 12.5-440-DB 60 × 225 31-10405 4.1 4.8 7.0 12.4 13.3 15.0
LKT 15-440-DB 70 × 225 31-10406 4.9 5.8 8.4 14.9 16.0 18.0
LKT 20-440-DB 85 × 278 31-10413 6.66 7.8 11.2 19.8 21.4 24.0
LKT 25-440-DB 85 × 278 31-10407 8.2 9.7 14.0 24.8 26.7 30.0
LKT 30-440-DB 85 × 278 31-10408 9.8 11.6 16.7 29.8 32.0 36.0
LKT 6.25-525-DB 60 × 225 31-10409 4.4 4.7 5.3 5.8 6.3 7.5
LKT 12.5-525-DB 70 × 225 31-10410 8.7 9.4 10.5 11.5 12.5 15.0
LKT 15-525-DB 70 × 225 31-10419 10.5 11.3 12.6 13.8 15.1 18.0
LKT 17.2-525-DB 70 × 225 31-10434 12.0 12.9 14.5 15.9 17.3 20.6
LKT 20-525-DB 70 × 265 31-10420 13.9 15.0 16.9 18.4 20.1 24.0
LKT 25-525-DB 85 × 278 31-10411 17.4 18.8 21.1 23.0 25.1 30.0
7
Power Factor Correction Capacitors
Type LKT…-DP for 50 Hz
8
Power Factor Correction Capacitors
Type LKT…-DP for 60 Hz
9
Power Factor Correction Capacitors
Type LKT…-DP for 50 Hz and 60 Hz
Capacitor Dimensions Article-No. Rated Reactive Power in kvar at Rated Voltage 60 Hz
Type mm
525 V 570 V 600 V 615 V 690 V 750 V 760 V 800 V
Three-phase capacitors
LKT 5-690-DP 60 × 225 31-10560 3.5 4.1 4.5 4.8 6.0
LKT 10-690-DP 70 × 225 31-10561 7.0 8.2 9.1 9.5 12.0
LKT 12.5-690-DP 70 × 265 31-10562 8.7 10.2 11.3 11.9 15.0
LKT 15-690-DP 70 × 265 31-10563 10.4 12.3 13.6 14.3 18.0
LKT 20-690-DP 85 × 278 31-10564 13.9 16.4 18.2 19.1 24.0
LKT 25-690-DP 85 × 278 31-10565 17.4 20.5 22.7 23.8 30.0
LKT 28.2-760-DP 85 × 320 31-10569 21.1 22.2 27.9 33.0 33.8
LKT 6.7-800-DP 60 × 225 31-10570 4.5 4.8 6.0 7.1 8.0
LKT 10.5-800-DP 70 × 225 31-10571 7.1 7.5 9.4 11.1 12.6
LKT 13.3-800-DP 85 × 215 31-10572 9.0 9.4 11.9 14.0 16.0
LKT 21.0-800-DP 85 × 278 31-10573 14.2 14.9 18.8 22.2 25.2
LKT 26.7-800-DP 85 × 320 31-10574 18.0 18.9 23.8 28.2 32.0
10
Power Factor Correction Capacitors
Type LKT…-EP for 50 Hz and 60 Hz
Capacitor Dimensions Article-No. Rated Reactive Power in kvar at Rated Voltage 60 Hz
Type mm
230 V 250 V 300 V 400 V 415 V 440 V 460 V 480 V 525 V
Single-phase capacitors
LKT 3.3-440-EP 60 × 90 31-10526 1.1 3.3 3.6 4.0
LKT 4.17-440-EP 60 × 138 31-10527 1.4 4.1 4.5 5.0
LKT 5-440-EP 60 × 138 31-10528 1.6 5.0 5.33 6.0
LKT 9.4-440-EP 70 × 138 31-10511 3.1 9.3 10.0 11.3
LKT 2.4-480-EP 60 × 90 31-10529 2.0 2.15 2.4 2.9
LKT 3.33-480-EP 60 × 90 31-10530 2.8 3.0 3.4 4.0
LKT 3.6-480-EP 60 × 138 31-10531 1.0 3.0 3.2 3.6 4.3
LKT 4.8-480-EP 60 × 138 31-10515 1.3 4.0 4.3 4.8 5.8
LKT 6-480-EP 60 × 138 31-10514 1.66 5.0 5.4 6.0 7.2
LKT 2.8-525-EP 60 × 90 31-10532 1.9 2.4 2.8 3.4
LKT 3.33-525-EP 60 × 138 31-10533 2.3 2.5 2.8 3.1 3.3 4.0
LKT 8.33-525-EP 70 × 138 31-10518 5.8 6.3 7.0 7.7 8.33 10.0
11
Power Factor Correction Capacitors
Type LKT…-DL for 50 Hz
Premium Capacitors
Capacitor Dimensions Article- Rated Reactive Power in kvar at Rated Voltage 50 Hz
Type mm No.
230 V 250 V 300 V 400 V 415 V 440 V 460 V 480 V 525 V 570 V 615 V
Three-phase capacitors
LKT 5-400-DL 60 × 225 31-10600 1.66 2.0 2.8 5.0 5.4* 6.1*
LKT 6.25-400-DL 60 × 225 31-10601 2.1 2.4 3.5 6.25 6.7* 7.6*
LKT 9.3-400-DL 70 × 225 31-10602 3.0 3.6 5.2 9.3 10.0* 11.3*
LKT 10-400-DL 70 × 225 31-10603 3.33 3.9 5.6 10.0 10.8* 12.1*
LKT 11.7-400-DL 70 × 225 31-10604 3.9 4.6 6.66 11.7 12.6* 14.2*
LKT 12.5-400-DL 70 × 225 31-10605 4.17 4.9 7.0 12.5 13.5* 15.1*
LKT 20-400-DL 85 × 278 31-10606 6.66 7.8 11.3 20.0 21.5* 24.2*
LKT 5-440-DL 60 × 225 31-10607 1.4 1.6 2.3 4.17 4.5 5.0 5.5* 6.0*
LKT 7.6-440-DL 60 × 225 31-10608 2.1 2.5 3.5 6.25 6.8 7.6 8.33* 9.0*
LKT 9.1-440-DL 60 × 225 31-10609 2.5 2.9 4.2 7.5 8.1 9.1 10.0* 10.8*
LKT 12.1-440-DL 70 × 225 31-10610 3.33 3.9 5.6 10.0 10.8 12.1 13.2* 14.4*
LKT 17.6-440-DL 85 × 278 31-10612 4.8 5.7 8.2 14.5 15.6 17.6 19.2* 21.0*
LKT 3.6-480-DL 60 × 150 31-10613 2.5 2.7 3.0 3.33 3.6 4.3*
LKT 4.5-480-DL 60 × 150 31-10614 3.1 3.4 3.8 4.1 4.5 5.4*
LKT 7.2-480-DL 60 × 225 31-10615 5.0 5.4 6.0 6.66 7.2 8.6*
LKT 7.8-480-DL 60 × 225 31-10616 5.4 5.8 6.5 7.2 7.8 9.3*
LKT 10.4-480-DL 70 × 225 31-10617 7.3 7.8 8.8 9.6 10.4 12.4*
LKT 12.5-480-DL 70 × 265 31-10618 8.7 9.4 10.5 11.5 12.5 15.0*
LKT 15.5-480-DL 85 × 215 31-10627 10.8 11.6 13.0 14.2 15.5 18.5*
LKT 4.17-525-DL 60 × 225 31-10619 2.9 3.2 3.5 4.17 4.9* 5.7*
LKT 5.9-525-DL 60 × 225 31-10620 4.17 4.5 5.0 5.9 7.0* 8.1*
LKT 7.7-525-DL 70 × 225 31-10621 5.4 5.91 6.5 7.7 9.1* 10.6*
LKT 8.33-525-DL 70 × 225 31-10622 5.8 6.40 7.0 8.33 9.8* 11.4*
Generally, DL-type capacitors can also be operated at higher voltages with the DP-type specification.
Please note that the DP values in the chart are marked with *.
12
Power Factor Correction Capacitors
Type LKT…-DL for 60 Hz
Premium Capacitors
Capacitor Dimensions Article- Rated Reactive Power in kvar at Rated Voltage 60 Hz
Type mm No.
230 V 250 V 300 V 400 V 415 V 440 V 460 V 480 V 525 V 570 V 615 V
Three-phase capacitors
LKT 5-400-DL 60 × 225 31-10600 2.0 2.3 3.4 6.0 6.5* 7.3*
LKT 6.25-400-DL 60 × 225 31-10601 2.5 2.9 4.2 7.5 8.1* 9.1*
LKT 9.3-400-DL 70 × 225 31-10602 3.7 4.4 6.3 11.1 12.0* 13.5*
LKT 10-400-DL 70 × 225 31-10603 4.0 4.7 6.8 12.0 12.9* 14.5*
LKT 11.7-400-DL 70 × 225 31-10604 4.6 5.5 7.9 14.0 15.1* 17.0*
LKT 12.5-400-DL 70 × 225 31-10605 5.0 5.9 8.4 15.0 16.2* 18.2*
LKT 20-400-DL 85 × 278 31-10606 7.9 9.4 13.5 24.0 25.8* 29.0*
LKT 5-440-DL 60 × 225 31-10607 1.66 1.9 2.8 5.0 5.4 6.0 6.6* 7.1*
LKT 7.6-440-DL 60 × 225 31-10608 2.5 2.9 4.2 7.5 8.1 9.1 10.0* 10.9*
LKT 9.1-440-DL 60 × 225 31-10609 3.0 3.5 5.1 9.0 9.7 10.9 11.9* 13.0*
LKT 12.1-440-DL 70 × 225 31-10610 4.0 4.7 6.8 12.0 12.9 14.5 15.9* 17.3*
LKT 17.6-440-DL 85 × 278 31-10612 5.8 6.8 9.8 17.4 18.8 21.1 23.1* 25.1*
LKT 3.6-480-DL 60 × 150 31-10613 3.0 3.2 3.6 4.0 4.3 5.2*
LKT 4.5-480-DL 60 × 150 31-10614 3.8 4.0 4.6 5.0 5.4 6.5*
LKT 7.2-480-DL 60 × 225 31-10615 6.0 6.5 7.2 7.9 8.6 10.3*
LKT 7.8-480-DL 60 × 225 31-10616 6.5 7.0 7.9 8.6 9.3 11.2*
LKT 10.4-480-DL 70 × 225 31-10617 8.7 9.3 10.5 11.5 12.5 14.9*
LKT 12.5-480-DL 70 × 265 31-10618 10.4 11.2 12.6 13.8 15.0 17.9*
LKT 15.5-480-DL 85 × 215 31-10627 12.9 13.9 15.6 17.1 18.6 22.3*
LKT 4.17-525-DL 60 × 225 31-10619 3.5 3.8 4.2 5.0 5.9* 6.9*
LKT 5.9-525-DL 60 × 225 31-10620 4.97 5.5 5.9 7.1 8.4* 9.7*
LKT 7.7-525-DL 70 × 225 31-10621 6.5 7.1 7.8 9.3 10.9* 12.7*
LKT 8.33-525-DL 70 × 225 31-10622 7.0 7.6 8.33 10.0 11.8* 13.7*
Generally, DL-type capacitors can also be operated at higher voltages with the DP-type specification.
Please note that the DP values in the chart are marked with *.
13
Power Factor Correction Capacitors
Type LKT…-HD for 50 Hz and 60 Hz
Capacitor Dimensions Article-No. Rated Reactive Power in kvar at Rated Voltage 60 Hz
Type mm
230 V 250 V 300 V 400 V 415 V 440 V 460 V 480 V 500 V 525 V
Three-phase capacitors
LKT 16.8-480-HD 85 × 215 31-10580 4.6 5.5 7.9 14.0 15.1 16.9 18.5 20.2
LKT 18-480-HD 85 × 215 31-10581 5.0 5.9 8.4 15.0 16.2 18.2 19.8 21.6
LKT 15.6-500-HD 85 × 215 31-10582 4.0 4.7 6.7 12.0 12.9 14.5 15.8 17.3 18.7
LKT 16.1-500-HD 85 × 215 31-10583 4.1 4.8 7.0 12.4 13.3 15.0 16.4 17.8 19.3
LKT 16.8-500-HD 85 × 215 31-10584 4.3 5.0 7.3 12.9 13.9 15.6 17.1 18.6 20.2
LKT 18-525-HD 85 × 215 31-10585 12.5 13.5 15.2 16.6 18.1 21.6
o r s
c it
p a
a
W
y C
ut
t
rr en
yD
cu
E
e d e nt
rat urr
av es c
ed
He
7t
im at
2. e sr
pt
o t im
N
tu 50 0 h. ns
ren o4 ,00 rat
io
rc ur upt 2 00 pe
ve t o
O urren cy: ing
■ c c tan itch
sh pe l sw
Inru ee
x a
if n nu
nL
■
a 0a
Me 0 ,00
■ 10
to
Up
■
14
Basic Harmonic Filter Reactors
Type FDK
Q Low losses
Q Complete with mounting brackets and connecting clamps
Q Temperature range up to +60°C
Q Temperature switches available as option
11
Basic Harmonic Filter Reactors
Type FDK
Application Standards
Used in conjunction with LKT type power capacitors, har- IEC 60289, IEC 60076, VDE 0532
PRQLF¿OWHUUHDFWRUVEORFNLQJUHDFWRUVPDNHLWSRVVLEOH
WRLQVWDOOGHWXQHGYHUVLRQVRI¿[HGFDSDFLWRUEDQNVDQG
power factor correction systems. Applicable Standards
This enables users installing distribution boards to con- When installing and connecting power capacitors in Ger-
struct customized systems themselves. many, the standards VDE 0100 IEC 60364, VDE 0105
IEC 60050, IEC 60529, VDE 0560 Part 46 IEC 60831
and VDE 0106 Part 100 must be complied with. In
Design other countries the equivalent local regulations must
Low-loss, three-phase assembly complete with mounting be observed.
brackets.
Technical Data
Series Resonance Frequency Tolerance of inductance: +/- 5 %
Version Series Detuning For networks with Max. ambient temperature: + 60 °C
resonance factor utility company AF
frequency remote control 1) Temperature class: H 180 °C
P7 189 Hz p=7% > 228 Hz Insulation level: 3 kVac
Please refer also to the design notes given in our Manual of Power Winding material: Al
Factor Correction. (other series resonance frequencies on request) Color: red or light brown
1)
8WLOLW\FRPSDQ\VSHFL¿FDWLRQVLQFRQVLVWHQWZLWKWKHDERYHPXVWEHWDNHQLQWRDFFRXQW
Option
Mounting Temperature switch 130 °C + / - 5 °C,
Voltage 250 VAC (type FDKT)
The reactor must be mounted in a suitable enclosure
HQVXULQJ DQ DPELHQW WHPSHUDWXUH ZLWKLQ WKH VSHFL¿HG
range. Mechanical Data
Available Types
7HFKQLFDO6SHFL¿FDWLRQ
We reserve the right to make changes to the dimensions and design of the products in this data sheet.
12
Standard Harmonic Filter Reactors
Type FDR/FKD
Q Low losses
Q Complete with mounting brackets and connecting cables
Q Including temperature switches
Q Temperature range up to +60°C
13
Harmonic Filter Reactors
Type FDR / FKD
Design
Ingress Protection
Low-loss, three-phase assembly complete with mounting
brackets, connecting cables and thermal trip. IP00 to IEC 60529 for mounting within an enclosure
Mounting
The reactor must be mounted in a suitable enclosure Technical Data
HQVXULQJ DQ DPELHQW WHPSHUDWXUH ZLWKLQ WKH VSHFL¿HG Specimen order 1
range. P.F. correction stage with 7 % detuning factor 25 kvar at 400 V / 50 Hz
supply voltage
2 power capacitors
Connections Type LKT 11.7 – 400 – DL Art.-No. 31-10604
2 terminal blocks
The coil line-side (U1, V1, W1) and load-side (U2, V2, Type AKD 25/3 Art.-No. 31-08000
W2) cables can be connected to the switchgear directly ORZORVVKDUPRQLF¿OWHUUHDFWRUZLWKWHPSHUDWXUHVZLWFK
or via terminals. The temperature switch (contacts open Type FDR 25 – 400 – P7 Art.-No. 88-01768
at 140 °C) must be connected to a trip/alarm circuit in Specimen order 2
the control system. P.F. correction stage with 14 % detuning factor 12.5 kvar at 400 V / 50 Hz
supply voltage
1 power capacitor
Applicable Standards Type LKT 15.5 – 480 – DP Art.-No. 31-10513
1 terminal block
When installing and connecting power capacitors in Type AKD 25/3 Art.-No. 31-08000
Germany, the standards VDE 0100 IEC 60364, VDE ORZORVVKDUPRQLF¿OWHUUHDFWRUZLWKWHPSHUDWXUHVZLWFK
Type FKD 12.5 – 400 – P1 Art.-No. 88-01168
0105 IEC 60050, IEC 60529, VDE 0560 part 46 IEC
60831 and VDE 0106 part 100 must be complied with. Specimen order 3
In other countries the equivalent local regulations must P.F. correction stage with 14 % detuning factor 20 kvar at 400 V / 50 Hz
be observed. supply voltage
1 power capacitor
Type LKT 7.6 – 440 – DL Art.-No. 31-10608
1 power capacitor
Load Capacity Type LKT 15.5 – 480 – DP Art.-No. 31-10513
Version Power loss Permissible harmonic voltage 2 terminal blocks
W/kvar 250 Hz 350 Hz Type AKD 25/3 Art.-No. 31-08000
ORZORVVKDUPRQLF¿OWHUUHDFWRUZLWKWHPSHUDWXUHVZLWFK
P1 4-6 6% 6% Type FKD 20 – 400 – P1 Art.-No. 88-01038
P7 3.5-6 6% 6%
14
Harmonic Filter Reactors
Type FDR / FKD
Capacitors and Harmonic Filter Reactors for 230 V/50 Hz – mains network
Capacitor Reactor
LKT 10.0-400-DP
LKT 12.5-400-DP
LKT 10.0-440-DP
LKT 10.0-525-DP
Art.-No.31-10501
Art.-No.31-10502
Art.-No.31-10508
Art.-No.31-10517
Rated current of
Rated power of
combination
combination
Weight
Dimensions in mm Harmonic Filter Reactors
Capacitors and Harmonic Filter Reactors for 230 V/60 Hz – mains network
Capacitor Reactor
LKT 10.0-400-DP
Art.-No.31-10501
Art.-No.31-10523
LKT 7.1-300-DP
Rated current of
Rated power of
combination
combination
Weight
15
Harmonic Filter Reactors
Type FDR / FKD
Capacitors and Harmonic Filter Reactors for 400 V/50 Hz – mains network
Capacitor Reactor
LKT 12,5-440-DP
LKT 15.0-440-DP
Art.-No.31-10506
Art.-No.31-10608
Art.-No.31-10609
Art.-No.31-10507
Art.-No.31-10604
LKT 11.7-400-DL
Rated current of
LKT 7.6-440-DL
LKT 9.1-440-DL
Rated power of
combination
combination
Weight
Dimensions in mm Harmonic Filter Reactors
Capacitor Reactor
LKT 15.5-480-DP
Art.-No.31-10616
Art.-No.31-10621
Art.-No.31-10608
Art.-No.31-10513
Art.-No.31-10610
Art.-No.31-10609
LKT 12.1-440-DL
Rated current of
LKT 7.8-480-DL
LKT 7.7-525-DL
LKT 7.6-440-DL
LKT 9.1-440-DL
Rated power of
combination
combination
Weight
16
Harmonic Filter Reactors
Type FDR / FKD
Capacitors and Harmonic Filter Reactors for 415 V/50 Hz – mains network
Capacitor Reactor
LKT 15.5-480-DP
LKT 12.5-525-DP
Art.-No.31-10513
Art.-No.31-10516
Rated current of
Rated power of
combination
combination
Weight
Dimensions in mm Harmonic Filter Reactors
Capacitors and Harmonic Filter Reactors for 440 V/50 Hz – mains network
Capacitor Reactor
Art.-No.31-10610
LKT 12.1-440-DL
Rated current of
Rated power of
combination
combination
Weight
17
Harmonic Filter Reactors
Type FDR / FKD
Capacitors and Harmonic Filter Reactors for 440 V/60 Hz – mains network
Capacitor Reactor
LKT 15.5-480-DP
Art.-No.31-10622
Art.-No.31-10513
Art.-No.31-10610
Art.-No.31-10621
Art.-No.31-10620
Art.-No.31-10616
LKT 8.33-525-DL
LKT 12.1-440-DL
Rated current of
LKT 7.7-525-DL
LKT 5.9-525-DL
LKT 7.8-480-DL
Rated power of
combination
combination
Weight
Dimensions in mm Harmonic Filter Reactors
Capacitors and Harmonic Filter Reactors for 460 V/60 Hz – mains network
Capacitor Reactor
LKT 12.5-525-DP
Art.-No.31-10516
Rated current of
Rated power of
combination
combination
Weight
18
Harmonic Filter Reactors
Type FDR / FKD
Capacitors and Harmonic Filter Reactors for 480 V/60 Hz – mains network
Capacitor Reactor
LKT 12.5-525-DP
Art.-No.31-10516
Art.-No.31-10621
Art.-No.31-10619
Art.-No.31-10622
LKT 4.17-525-DL
LKT 8.33-525-DL
Rated current of
LKT 7.7-525-DL
Rated power of
combination
combination
Weight
Dimensions in mm Harmonic Filter Reactors
Capacitors and Harmonic Filter Reactors for 525 V/50 Hz – mains network
Capacitor Reactor
Art.-No.31-10619
Art.-No.31-10620
Art.-No.31-10621
Art.-No.31-10622
LKT 4.17-525-DL
LKT 8.33-525-DL
Rated current of
LKT 5.9-525-DL
LKT 7.7-525-DL
Rated power of
combination
combination
Weight
Capacitor Reactor
Art.-No.31-10616
Art.-No.31-10620
LKT 4.17-525-DL
Rated current of
LKT 5.9-525-DL
Rated power of
combination
combination
Weight
QLC
W W1 H D D1 kg Art.-No. Type
[kvar] In [A]
19
Harmonic Filter Reactors
Type FDR / FKD
Capacitors and Harmonic Filter Reactors for 690 V/50 Hz – mains network
Capacitor Reactor
Art.-No.31-10511
Rated current of
LKT 9.4-440-EP
Rated power of
combination
combination
Weight
Dimensions in mm Harmonic Filter Reactors
Capacitor Reactor
LKT 8.33-525-EP
Art.-No.31-10515
Art.-No.31-10514
Art.-No.31-10518
Rated current of
LKT 4.8-480-EP
LKT 6.0-480-EP
Rated power of
combination
combination
Weight
20
Capacitor Switching Contactors
Type K3...-A, K3...-K
21
Capacitor Switching Contactors
for unchoked and choked PFC Systems
Description
Capacitor contactors for Capacitor contactors for
unchoked power factor correction systems choked power factor correction systems
During the switching of unchoked power factor correction When choked power factor correction systems are
capacitors a peak-switching current of 200 times of the switched, the peak-switching current is essentially
nominal current can occur. This load is stressing the lower because of the high inductivity of the harmonic
capacitors and the switching contacts of the contactors ¿OWHUUHDFWRUDVZLWKXQFKRNHGSRZHUIDFWRUFRUUHFWLRQ
immensely. This can lead to welded main contacts of systems.
contactors.
By using special wear-resistant contact material for these
Therefore modern power factor correction systems are applications it is possible to use capacitor contactors
currently equipped with special capacitor contactors without series resistors.
VZLWFKLQJWKHFDSDFLWRUV¿UVWZLWKOHDGLQJFRQWDFWVDQG
These special capacitor contactors offer the following
additionally with resistance wires. The in-rush current will
advantages for choked power factor correction sys-
be damped strongly by the resistors. After approximately
tems:
5 ms the main contacts of the contactor are switching
in and taking over the current supply to the capacitors. Q Safe switching on and off of choked capacitor
Further to this the leading contacts open up and no cur- steps
UHQWFDQÀRZGXULQJSHUPDQHQWRSHUDWLRQ7KLVLVDOVR Q Improved voltage quality through chatter-proofed
to avoid an additional power loss. switching operations
Capacitor contactors with leading transition contact and Q Long-life of the contactors (> 100,000 switching
additional resistance wires offer the following advanta- operations)
ges to power factor correction system applications: Q High operational reliability of the power factor
Q 6LJQL¿FDQWGDPSLQJRILQUXVKFXUUHQW correction system
Q Improvement of the voltage quality during the
switching process
Q Long life of the contactors
Q High operational reliability of the power factor
correction system
Q Extension of the maintenance periods of the power
factor correction systems
Q Suitable for choked and unchoked power factor
correction systems due to leading transition
contacts opening during permanent operation.
22
Capacitor Switching Contactors
for unchoked and choked PFC Systems
Technical Data
Rated operational power at 50/60 Hz Aux. contacts Type Article-No. Weight
Ambient temperature: built-in add.
50° C 60° C Coil voltage
380 V 415 V 660 V 380 V 415 V 660 V 220–240 V 50 Hz
400 V 440 V 690 V 400 V 440 V 690 V
kvar kvar kvar kvar kvar kvar NO NC pcs. kg/pc.
0-12.5 0-13 0-20 0-12.5 0-13 0-20 1 – 11) K3-18K10 230 89-00280 0.34
10-20 10.5-22 17-33 10-20 10.5-22 17-33 – – 32) K3-24K00 230 89-00279 0.62
2)
10-25 10.5-27 17-41 10-25 10.5-27 17-41 – – 3 K3-32K00 230 89-00278 0.62
20-33.3 23-36 36-55 20-33.3 23-36 36-55 – – 32) K3-50K00 230 89-00277 1.0
20-50 23-53 36-82 20-50 23-53 36-82 – – 32) K3-62K00 230 89-00276 1.0
20-753) 23-753) 36-1203) 20-60 23-64 36-100 – – 32) K3-74K00 230 89-00286 1.0
33-80 36-82 57-120 33-75 36-77 57-120 – – 64) K3-90K00230 89-00356 2.3
33-1005) 36-1035) 57-1485) 33-905) 36-935) 57-1485) – – 64) K3-115K00230 89-00357 2.3
1) 2) 3)
1HN.. or HA.. snap-on 2HB.. for side mounting and 1HN.. or HA.. snap-on Consider the max. thermal current of the contactor K3-74 A:
4) 5)
2HB.. on the left or right side and 4 HN.. or HA.. snap-on Consider the min. cross-section of conductor at max. load Ith 130 A
6SHFL¿FDWLRQ&RQWDFWRUV..DUHVXLWDEOHIRUVZLWFKLQJORZLQGXFWLYHDQGORZORVVFDSDFLWRUVLQFDSDFLWRUEDQNV,(&DQG9'(ZLWKRXWDQGZLWKUHDFWRUV
&DSDFLWRUVZLWFKLQJFRQWDFWRUVDUH¿WWHGZLWKHDUO\PDNHFRQWDFWVDQGGDPSLQJUHVLVWRUVWRUHGXFHWKHYDOXHRIPDNHFXUUHQW[Oe .
Operating Conditions: Capacitor switching contactors are protected against contact welding for a prospective making current of 200 x le.
Technical Data acc. to IEC 947-4-1, IEC 947-5-1, EN 60947-4-1, EN 60947-5-1, VDE 0660
L1 L2 L3
Mounting Instructions
A1 1 3 5 ,QWKHDUHDRIFDSDFLWRUVZLWFKLQJFRQWDFWRUVGLI¿FXOW\
Typical Circuit Diagram A2 2 4 6 LQÀDPPDEOH DQG VHOIH[WLQJXLVKLQJ PDWHULDOV PD\ EH
used only, because abnormal temperatures within the
area of the resistor spirals cannot be excluded.
23
Capacitor Switching Contactors
for unchoked and choked PFC Systems
Technical Data
Rated operational power at 50/60 Hz Aux. contacts Type Article-No. Weight
Ambient temperature: built-in add.
50° C 60° C Coil voltage
380 V 415 V 660 V 380 V 415 V 660 V 220–240 V 50 Hz
400 V 440 V 690 V 400 V 440 V 690 V _ kg/pc.
kvar kvar kvar kvar kvar kvar NO NC pcs.
12.5 13 20 12.5 13 20 1 – 41) K3-18A10 230 89-00288 0.23
20 22 33 20 22 33 – – 62) K3-24A00 230 89-00289 0.48
25 27 41 25 27 41 – – 62) K3-32A00 230 89-00290 0.48
33.3 36 55 33.3 36 55 – – 62) K3-50A00 230 89-00291 0.85
50 53 82 50 53 82 – – 62) K3-62A00 230 89-00292 0.85
753) 753) 100 60 64 100 – – 62) K3-74A00 230 89-00293 0.85
4)
80 82 120 75 77 120 9 K3-90A00 230 89-00358 2.2
1005) 1035) 1485) 905 ) 935) 1485) 94) K3-115A00 230 89-00359 2.2
1) 2) 3)
4HN.. or HA.. snap-on 2HB11 on the left or right side and 4HN.. or HA.. snap-on Consider the max. thermal current: Ith 130 A
4) 5)
2HB.. on the left or right side and 7 HN.. or HA.. snap-on Consider the min. cross-section of conductor at max. load
L1 L2 L3
Mounting Instructions
,QWKHDUHDRIFDSDFLWRUVZLWFKLQJFRQWDFWRUVGLI¿FXOW\
A1 1 3 5
Typical Circuit Diagram A2 2 4 6
LQÀDPPDEOH DQG VHOIH[WLQJXLVKLQJ PDWHULDOV PD\ EH
used only, because abnormal temperatures within the
area of the resistor spirals cannot be excluded.
Dimensions
Capacitor switching contactors, AC-operated Contactors, AC-operated
K3-18K... 45
K3-18A10 45 65.5
98
35-36 94 35-36 61.5
ø5
ø5
49-50
85
59
49-50
59
M3.5 M3.5
6.5
6.5
50
50
K3-24K00 K3-24A00
K3-32K00 K3-32A00
45 119.5 45 87.5
35 115.5 35 83.5
ø4.5
ø4.5
74
65
60
115
74
65
60
M5
M5
6.5 6.5
63
63
24
Capacitor Switching Contactors
for unchoked and choked PFC Systems
Dimensions
Capacitor switching contactors, AC-operated Contactors, AC-operated
K3-50K00 K3-50A00
K3-62K00 K3-62A00
K3-74K00 K3-74A00
60 128.5 60 96
50 124.5 50 92
ø5.5
ø5.5
110
100
95
110
100
145
95
M6 M6
7.5 7.5
68 68
K3-90K00 K3-90A00
K3-115K00 K3-115A00
90 120
90 152.5
75 120 75 115
115
Ø6
Ø6
Ø6
Ø6
155
137
137
70
155
70
M8
M8
9
31.5 31.5 74
9
31.5 31.5 74
Technical Data
Main Contacts Type K3-18K K3-24K K3-32K K3-50K K3-62K K3-74K K3-90K K3-115K
Switching of
three-phase current pfc-systems
$PELHQWWHPSHUDWXUH&
Rated operational current le 690 V A 0–18 14–28 14–36 30–48 30–72 30–1081) 50–115 50–1442)
Rated operational power 220–240V kvar 0–7 5–11 5–14 12–20 12–28 12–33 20–45 20–552)
380–400 V kvar 0–12.5 10–20 10–25 20–33.3 20–50 20–751) 33–80 33–1002)
415–440 V kvar 0–13 10.5–22 10.5–27 23–36 23–53 23–751) 36–82 36–1032)
500 V kvar 0–15 12–25 12–30 26–40 26–60 26–75 43–100 43–1202)
525 V kvar 0–15 12–25 12–32 26–43 26–64 26–80 45–105 45–1252)
660–690 V kvar 0–20 17–33 17–41 36–55 36–82 36–120 57–120 57–1482)
1000 V kvar – – – – – – 85–160 85–2002)
$PELHQWWHPSHUDWXUH&
Rated operational current le 690 V A 0–18 14–28 14–36 30–48 30–72 30–87 50–108 50–1302)
Rated operational power 220–240 V kvar 0–7 5–11 5–14 12–20 12–28 12–30 20–40 20–502)
380–400 V kvar 0–12.5 10–20 10–25 20–33.3 20–50 20–60 33–75 33–902)
415–440 V kvar 0–13 10.5–22 10.5–27 23–36 23–53 23–64 36–77 36–932)
500 V kvar 0–15 12–25 12–30 26–40 26–60 26–70 43–90 43–1102)
525 V kvar 0–15 12–25 12–32 26–43 26–64 26–75 45–95 45–1152)
660–690 V kvar 0–20 17–33 17–41 36–55 36–82 36–100 57–120 57–1482)
1000 V kvar – – – – – – 85–150 85–1802)
1) 2)
Consider the max. thermal current: Ith 130 A Consider the min. cross-section of conductor at max. load
25
Capacitor Switching Contactors
Data according to IEC 947- 4 -1, EN 60947- 4 -1, VDE 0660
Technical Data
Main Contacts Type K3-18A K3-24A K3-32A K3-50A K3-62A K3-74A K3-90A K3-115A
Switching of
three-phase current pfc-systems
$PELHQWWHPSHUDWXUH&
Rated operational current le 690 V A 18 28 36 48 72 1081) 115 1442)
Rated operational power 220–240V kvar 7 11 14 20 28 33 45 552)
380–400 V kvar 12.5 20 25 33.3 50 751) 80 1002)
415–440 V kvar 13 22 27 36 53 751) 82 1032)
500 V kvar 15 25 30 40 60 75 100 1202)
525 V kvar 15 25 32 43 64 80 105 1252)
660–690 V kvar 20 33 41 55 82 120 120 1482)
1000 V kvar – – – – – – 160 2002)
$PELHQWWHPSHUDWXUH&
Rated operational current le 690 V A 18 28 36 48 72 87 108 1302)
Rated operational power 220–240 V kvar 7 11 14 20 28 30 40 502)
380–400 V kvar 12.5 20 25 33.3 50 60 75 902)
415–440 V kvar 13 22 27 36 53 64 77 932)
500 V kvar 15 25 30 40 60 70 90 1102)
525 V kvar 15 25 32 43 64 75 95 1152)
660–690 V kvar 20 33 41 55 82 100 120 1482)
1000 V kvar – – – – – – 150 1802)
1) 2)
Consider the max. thermal current: Ith 130 A Consider the min. cross-section of conductor at max. load
Main Contacts Type K3-18 K3-24 K3-32 K3-50 K3-62 K3-74 K3-90 K3-115
Maximum ambient temperature
Operation open °C –40 to +60 (+90)1)
enclosed °C –40 to +40
Storage °C –50 to +90
Short circuit protection
for contactors without thermal overload relay
Coordination-type “1”
according to IEC 947-4-1
Contact welding without
Hazard of persons
Max. fuse size gL (gG) A 100 100 100 160 160 160 200 250
Mechanical life
AC-operated S x 106 10 10 10 10 10 10 5 5
6
DC-operated S x 10 10 10 10 10 10 10 5 5
Short time current 10s-current A 144 184 240 360 504 592 680 880
Power loss per pole At le/AC3 400 V W 0.5 0.7 1.3 2.2 3.9 5.5 4.3 6.0
1)
With reduced control voltage range 0.9 up to 1.0 x Us and with reduced rated current Ie/AC1 according to Ie/AC3
26
Discharge Reactors
Type FR 3AC
27
Discharge Reactors
Type FR 3AC
28
Power Factor Control Relays
Type EMR1100 / EMR1100S / RM9606 / RM2106 / RM2112
29
Power Factor Control Relays
Type EMR 1100S / EMR 1100
Description Features
Microprocessor-based control relay for intelligent control Q Potential-free alarm
of capacitor banks with 12 control contacts. contact.
Q Programmable over-
current alarm threshold
Simple Commissioning limit (from 1.05 to 3.0 x Irms).
%\ DXWRPDWLF LGHQWL¿FDWLRQ RI WKUHVKROG FXUUHQW FN Q Continuous monitoring for
value), phase angle, connected capacitor stages and defective capacitor stages
switching sequences. through self adjustment of
control program.
Operator Overview Q Zero voltage and zero current tripping with alarm
signal.
Through clear digital display of key momentary values
Q Patented “kinked“ control curve characteristics
and operating parameters.
avoid overcompensation under light load.
Q Power factor (cos )
Q Four-quadrant power control with LED display
Q Apparent (RMS), active and reactive currents when active power is generated into mains.
Q 5th, 7th, 11th and 13th voltage harmonics Q Manual/automatic operation with ability to switch
Q Total capacitive power required to meet target each individual capacitor stage ON or OFF.
power factor setting Q Target power factor setting adjustable from 0.80
inductive to 0.90 capacitive in steps of 0.01.
Monitoring of Harmonic Levels Q 3UHVHWXSWRWKUHH¿[HGFDSDFLWRUVWDJHVZKLFKZLOO
be excluded from normal automatic operation.
By continuous monitoring and display of harmonic vol-
tage levels. In the event of harmonic levels exceeding Q Independent setting of capacitor switching time to
programmable limits, all capacitors will be switched off match discharge time of capacitor stages.
through overcurrent alarm. Q Suitable for current transformers with rated
secondary current of 1 A or 5 A.
30
Power Factor Control Relays
Type RM 9606
&RQ¿JXUDWLRQDQGUHPRWHLQGLFDWLRQRIWKHPHDVXULQJYDOXHV
via RS232 interface with EMR 1100.
31
Power Factor Control Relays
Type RM 2106 / RM 2112
Description Features
Microprocessor-based control relay for intelligent control Q Potential-free alarm contact.
of capacitor banks with 6 or 12 control contacts. Q Programmable overcurrent
alarm threshold limit.
Simple Commissioning Q Continuous monitoring for
defective capacitor stages
%\ DXWRPDWLF LGHQWL¿FDWLRQ RI WKUHVKROG FXUUHQW FN through self adjustment of
value), phase angle, connected capacitor stages and control program.
switching sequences.
Q Zero voltage and zero current tripping with alarm
signal.
Operator Overview Q Two control curves characteristics:
– to avoid overcompensation under light load.
Through clear digital display of key momentary values
– to avoid inductive reactive power under
and operating parameters.
regeneration conditions.
Q Power factor (cos ) Q Four-quadrant power control with LED display
Q Total harmonic voltage distortion factor (% THVD) when active power is generated into mains.
Q Number of active capacitor steps Q Manual/automatic operation with ability to switch
each individual capacitor stage ON or OFF.
Extensive Analysis Record Q Target power factor setting adjustable from 0.85
inductive to 1.00 capacitive.
When in automatic mode, display of:
Q Independent setting of capacitor switching time to
Q Connection faults match discharge time of capacitor stages.
Q Capacity step faults Q Suitable for current transformers with rated
Q Recognized step sequence secondary current of 1 A or 5 A.
Q Protection class terminals IP 20, housing IP 54
(when sealing ring is used).
Protection for Capacitors
The optional RMS current monitoring function provides
excellent protection for capacitor banks without harmonic Alarm Signals for
¿OWHUVHVSHFLDOO\ZKHQUHVRQDQFHFDXVHVDQLQFUHDVH Q Overcurrent
in harmonic levels. The threshold can be set between Q Fault in voltage circuit (U = 0 alarm)
1.05 to 1.95 x Irms.
Q Fault in capacitor stages
32
Modular Construction System
MCS System
33
Modular Construction System
MCS System
Description
The FRAKO MCS System is a modular system, with The FRAKO MCS System contains the following
which a skilled switchgear manufacturer can design a components:
technically high-quality power factor correction system. Q Power factor control relay
However, knowing our “manual of power factor correc-
Q Control terminal strip for power factor control relay
tion” is absolutely important to design such a power
and Power Factor Correction Systems
IDFWRUFRUUHFWLRQV\VWHP,QWKLVPDQXDORQHZLOO¿QGDOO
the necessary planning information as well as all the Q Control wires
important technical data. You can download the manual Q Busbar holders
free of charge from our website or order it free of charge Q NH-fuse base and NH-isolating switch
from your local FRAKO partner.
Q NH-fuse links
The FRAKO MCS System consists of selected and Q Contactors
tested components for the design of power factor cor-
rection systems. FRAKO uses these components in its Q Discharge reactors
own production of power factor correction systems in Q +DUPRQLF¿OWHUUHDFWRUV
Teningen. This way the skilled switchgear manufacturer Q Power factor correction capacitors
can gain from an experience and application know-how Q Thyristor switches (see page 52)
of almost 80 years.
Page 37 Specimen order 1 shows the combination of
all FRAKO components for a power factor correction
V\VWHP ZLWK QR KDUPRQLF ¿OWHU UHDFWRUV ZLWK D WRWDO
power of 350 kvar at 400 V, 50 Hz and a step rating of
25 kvar at a switching sequence of the capacitor steps
of: 1:1:2:2:2:2:2:2.
Page 38 Specimen order 2 shows the combination of
all FRAKO components for a choked power factor cor-
rection system with a total power of 375 kvar at 400 V,
50 Hz, a series resonance frequency of 189 Hz (p = 7 %)
and a step rating of 25 kvar at a switching sequence of
the capacitor steps of: 1:2:2:2:2:2:2:2.
34
Modular Construction System
MCS System
Technical Data
Power Factor Control Relays and accessories
For technical details on our power factor control relays pared control cables. All items can be ordered as single
we would like to refer you to our catalogue (page 29 to components or as a complete control relay package.
32). The following chart shows the different types of relays
For the relays, FRAKO recommend to use the suitable as well as the suitable accessories for the assembly and
control terminal strips, the thermal trip contact for the the connection of the devices.
monitoring of the cabinet temperature as well as the pre-
Article
number: Description: Order Code:
Power factor control relay
38-00320 with 6 control contacts RM 2106
38-00103 with 6 control contacts RM 9606
38-00340 with 12 control contacts RM 2112
38-00301 with 12 control contacts EMR 1100 S
20-50008 with 12 control contacts and bus interface to FRAKO Energy-Management-System EMR 1100
20-50013 Software-Upgrade EMR 1100 S to full version EMR 1100
Control terminal strip with thermal trip contact, pre-mounted
34-80002 suitable for RM 9606 RKL–RM 9606
34-80003 suitable for EMR 1100 / EMR 1100 S RKL–EMR 1100
34-80027 for extension units (only 12 control contacts) RKL–Z–cabinet
Control cable, prepared
89-20557 for connection of RM 9606 with control terminal strip (length: 1000 mm, 6 control contacts) RK RM 9606–1150
89-20558 for connection of RM 9606 with control terminal strip (length: 1500 mm, 6 control contacts) RK RM 9606–1500
89-20555 for connection of EMR 1100 / EMR 1100 S with control terminal strip (length: 1150 mm, 12 control contacts) RK EMR 1100–1150
89-20556 for connection of EMR 1100 / EMR 1100 S with control terminal strip (length: 1500 mm, 12 control contacts) RK EMR 1100–1500
89-20559 for connection of the “basic unit” with the “extension unit” (length: 6 m, 12 control contacts) SS 12–6000
Reactive power factor control relay package
Completely assembled and tested units comprising:
Power factor control relay with control terminal strip, thermal trip contact and relay cable, length: 1150 mm
34-72016 RM 9606, control terminal strip with thermal trip contact, cable length: 1150 mm STR–RM 9606
34-72024 EMR 1100 S, control terminal strip with thermal trip contact, cable length: 1150 mm STR–EMR 1100 S
34-72002 EMR 1100, control terminal strip with thermal trip contact, cable length: 1150 mm STR–EMR 1100
35
Modular Construction System
MCS System
Technical Data voltage of 690 VAC, can be used. These NH-fuse hol-
Copper busbar holders, NH-fuses ders are also available as bus-mounting fuse holders for
direct mounting on a busbar system with a bar centre to
For the design of power factor correction systems
centre distance of 60 mm, or for mounting on mounting
FRAKO recommend to use the below-mentioned
plates.
devices and fuses.
Article-No. Description
The busbar holders have a centre to centre distance 90-00043 NH-bus-mounting fuse base size 00, 160 A, 690 VAC
of 60 mm to the single copper busbars. The copper 34-80280 NH-bus-mounting fuse base size 00, 160 A, 690 VAC
busbars have either dimensions of 30 ×5 mm or 30 ×10 90-00162 NH-fuse base for plate mounting
mm, depending on the total power of the power factor size 00, 160 A, 690 VAC
correction system. 34-80283 NH-fuse base for plate mounting
size 00, 160 A, 690 VAC
Article-No. Description 90-00142 Cover for NH-fuses with nonisolated grip lugs
90-00046 Busbar holder with a bar centre to centre
distance of 60 mm, Cu 30x10mm
90-00046
34-80283 34-80280
Description
FRAKO MCS System, Specimen order 1 5. Step:
Example: assembly of an unchoked power factor cor- One 25 kvar step has a rated current of 36.1 A at 400 V,
UHFWLRQV\VWHPZLWKWKHIROORZLQJVSHFL¿FDWLRQ 50 Hz. This requires a protection with a 63 A, gl fuse. One
Total power: 350 kvar, 400 V, 50 Hz 50 kvar step has a rated current of 72.2 A at 400 V, 50
Step rating: 2 × 25 kvar and 6 × 50 kvar Hz. This requires a protection with a 100 A, gl fuse. For
this system we would need altogether 6 pcs NH-fuses
12-step power factor control relay with switching times 63 A, 500 V, gl (Article-No. 90-00054) and 18 pcs NH-
less than 5 seconds. fuses 100 A, 500 V, gl (Article-No. 90-00052). FRAKO
1. Step: recommend to use NH-fuses with isolated grip lugs.
The system has 8 switching stages and requires a 6. Step:
12-step power factor control relay. Please select a reac- For the fuse links, NH-bus-mounting isolating switches
tive power control relay package with relay EMR 1100 S, size 00 (article-no. 90-00166) should be selected. For
consisting of the relay, temperature switch for the moni- the 8 steps, 8 pcs. of bus-mounting isolating switches
toring of the cabinet temperature, terminal strip with will be needed.
control system fuse and connecting cables.
7. Step:
2. Step:
For the assembly of the busbar system FRAKO recom-
The system requires 2 contactors for 25 kvar, 400 V, mend a maximum space of 250 mm for the busbar
50 Hz and 6 contactors for 50 kvar, 400 V, 50 Hz. Please holders. So 8 pieces of busbar holders are needed
select contactors with series resistors: (article-no. 90-00046) for the busbar system.
25 kvar steps: contactors type K3-32K00 Due to the total rated current of the system of 505A,
Article-No.: 89-00278 copper busbars with 30 × 10 mm are required.
50 kvar steps: contactors type K3-62K00
Article-No.: 89-00276 8. Step:
3. Step: ordering chart:
Choose the power factor correction capacitors: Please
Qty Article-No. Description:
select standard power factor correction capacitors with a
rated voltage of 400 V for a mains rated voltage of 400 V. 1 34-72024 complete power factor control relay
package EMR 1100S
For the 25 kvar step rating, depending on the construc-
2 89-00278 contactor K3-32K00
tion and the available space, one can choose between
6 89-00276 contactor K3-62K00
2 pcs. of LKT 12.5-400-DP, or 1 pc. of LKT 25.0-400-DP.
28 31-10502 capacitor LKT 12.5-400-DP
For the 50 kvar step one can choose between 4 pcs. of
8 88-02013 discharge reactor
LKT 12.5-400-DP or 2 pcs. of LKT 25.0-400-DP.
6 90-00054 NH-fuse size 00, 63 A, 500 V, gl
For the complete system one requires either 28 pcs. 18 90-00052 NH-fuse size 00, 100 A, 500 V, gl
of capacitor LKT 12.5-400-DP or 14 pcs. LKT 25.0- 8 90-00166 NH-bus-mounting isolating switch size: 00, 160 A
400-DP.
8 90-00046 busbar holder, 60 mm, 30x10 mm
4. Step:
The short switching times given, require a discharge of
the capacitors by means of discharge reactors. For 25
and 50 kvar the same discharge reactor can be selected.
The 8 capacitor steps require 8 discharge reactors.
37
Modular Construction System
MCS System
Description
FRAKO MCS System, Specimen order 2 5. Step:
Example: assembly of a power factor correction system One 25 kvar step has a rated current of 36.1 A at 400 V,
ZLWKWKHIROORZLQJVSHFL¿FDWLRQ 50 Hz. This requires a protection with a 63 A, gl fuse. One
Total power: 375 kvar, 400 V, 50 Hz, series resonance 50 kvar step has a rated current of 72.2 A at 400 V, 50
frequency of 189 Hz (7 %) Hz. This requires a protection with a 100 A, gl fuse. For
this system we would need altogether 3 pcs NH-fuses
Step rating: 1 × 25 kvar and 7 × 50 kvar
63 A, 500 V, gl (Article-No. 90-00054) and 21 pcs NH-
Power factor control relay with 12 control contacts. fuses 100 A, 500 V, gl (Article-No. 90-00052). FRAKO
1. Step: recommends to use NH-fuses with isolated grip lugs.
The system has 8 switching stages and requires a 6. Step:
12-step power factor control relay. We select a com- For the fuse links, NH-bus-mounting isolating switches
plete power factor control relay package with a relay size 00 Article-No. 90-00166 should be selected. For
EMR 1100 S, consisting of the relay, temperature switch the 8 steps, 8 pcs. NH-bus-mounting isolating switches
for the monitoring of the cabinet temperature, clamp with would be needed.
control fuse and connecting cables.
7. Step:
2. Step:
For the assembly of a busbar system FRAKO recom-
The system requires one contactor for 25 kvar, 400 V, mend a maximum space of 250 mm for the busbar
50 Hz and 7 contactors for 50 kvar, 400 V, 50 Hz. Please holders. So 8 pieces of busbar holders are needed
select contactors without series resistors. (Article-No. 90-00046) for the busbar system.
25 kvar step: contactor type K3-32A00, 8. Step:
Article-No.: 89-00290 ordering chart:
50 kvar steps: contactors type K3-62A00, Qty Article-No. Description:
1 34-72024 power factor control relay
Article-No.: 89-00292 package EMR 1100S
3. Step: 1 89-00290 contactor K3-32A00
Choose the power factor correction capacitors: Please 7 89-00292 contactor K3-62A00
select standard power factor correction capacitors with 30 31-10604 capacitor LKT 11.7-400-DL
a rated voltage of 440 V or premium capacitors with 11) 88-01768 FDR 25-400-P7
a rated voltage of 400 V for a mains rated voltage of 72) 88-01769 FDR 50-400-P7
400 V. For the 25 kvar step rating we need 2 pcs. of 3 90-00054 NH-fuse size 00, 63 A, 500 V, gl
LKT 11.7-400-DL. For the 50 kvar step we need 4 pcs. 21 90-00052 NH-fuse size 00, 100 A, 500 V, gl
of LKT 11.7-400-DL. 8 90-00166 NH-bus-mounting-isolating switch size 00, 160 A
8 90-00046 busbar holder, 60 mm, 30x10 mm
4. Step:
The 25 kvar step requires one 25 kvar reactor 1) and the
7 × 50 kvar steps require 7 × 50 kvar reactors 2).
38
Modules for Power Factor Correction Systems
Type C...C / C...D / C...D-E
39
Modules for Power Factor Correction Systems
Type C
Decisive Advantages
Version Series Detuning For mains
Q Compact compensation module resonance factor with utility
– Ideal for mounting in all common switchgear frequency audiofrequency1)
systems 3 +] S +]
Q High performance in the smallest possible space 3 +] S +]
– Up to 100 kvar for each module, with or without 1)
Please observe any deviation from utility company requirements.
reactors ,QDGGLWLRQDOVRQRWHYHUVLRQVSHFL¿FDWLRQVJLYHQLQRXU
Q Up to 5 modules per cabinet Manual of Power Factor Correction.
– Supplying 500 kvar even with 7 % reactors
Q Easy to service with a common bus bar Quick Mounting with Multifunctional
– Upright bus bar and NH fuse elements. No
special cable required between the individual Rails
modules for systems with two or more units When designing this series, special attention was given
to the simplest way of installing modules in all com-
monly used switchgear systems. The mounting rails
Design used (shown in grey in the dimensional sketch) can
Mounted and fully-wired galvanized sheet steel chassis be supplied as an optional accessory. These replace
consisting of: the time-consuming work of installation and drilling.
Q Self-healing power capacitors with a low-loss Only the control unit cutout and ventilation holes are
SRO\SURS\OHQHIRLOGLHOHFWLFDQG3&%IUHH¿OOHUW\SH required. Once the rails are mounted, the modules are
LKT with discharge resistors acc. to DIN VDE 0560 VLPSO\LQVHUWHGDQG¿UPO\DWWDFKHGE\WZRVFUHZV±LW
parts 46 and 47, EN 60831-1 and 2 as well as IEC couldn’t be simpler!
831-1 and -2.
Q Capacitor contactors with leading resistor contacts
attenuate current peaks
Q Common mounting rail with locking elements
Q Fuse elements, 3-pin, NH00
Q /RZORVV¿OWHUUHDFWRUVZLWKWHPSHUDWXUHVZLWFKHV
for the following series resonance frequencies:
40
Modules for Power Factor Correction Systems
Type C
Dimensional sketch
Front view
41
Modules for Power Factor Correction Systems
Type C...C
Technical Data
Design Sheet steel chassis with premounted Discharge With discharge resistors acc. to
capacitors, fuses and contactors VDE 0560, part 46
Rated voltage Min. 440 V / 50 Hz (capacitors) Power loss Capacitors: 0.5 W / kvar
Rated power See table (at 400 V mains voltage) Standards Acc. to VDE 0560 Parts 46 and 47,
Ingress IP 00 acc. to DIN 40 050, EN 60831-1 and -2 together with
protection for control cabinet mounting IEC 831-1 and -2, VDE 0660 part
Ambient –5 ° to +60 °C acc. to DIN VDE 500 and EN 60439-1 with type test
temperature 0660 part 500 Sect. 6.1.1.1 TSK
(when assembled) Rated capacity See FRAKO Manual of Power
Air humidity Max. 90 %, no condensation determination Factor Correction
Minimum rated voltage of capacitors 440 V / 50 Hz · Rated power at 400 V / 50 Hz mains voltage · other voltages on request
Article-No. Rated Power Step Power Switching Type and order code
in kvar in kvar sequence
at 400 V at 400 V
Capacitor Module, type: C64C
34-64167 25.00 3.13 1:1:2:4 C64C 25–3.13–211–400/440–64
34-64163 25.00 6.25 1:1:2 C64C 25–6.25–21–400/440–64
34-64164 25.00 12.50 1:1 C64C 25–12.5–2–400/440–64
34-64165 25.00 25.00 - C64C 25–25–1–400/440–64
34-64170 31.25 6.25 1:2:2 C64C 31.25–6.25–12–400/440–64
34-64180 34.38 3.13 1:2:4... C64C 34.38–3.13–112–400/440–64
34-64172 37.50 6.25 1:1:2... C64C 37.5–6.25–22–400/440–64
34-64173 37.50 12.50 1:2 C64C 37.5–12.5–11–400/440–64
34-64177 43.75 6.25 1:2:4 C64C 43.75–6.25–111–400/440–64
34-64181 46.88 3.13 1:2:4:8 C64C 46.88–3.13–1111–400/440–64
34-64288 50.00 3.13 1:1:2:4:8 C64C 50–3.13–2111–400/440–64
34-64182 50.00 6.25 1:1:2:4 C64C 50–6.25–211–400/440–64
34-64185 50.00 12.50 1:1:2 C64C 50–12.5–21–400/440–64
34-64186 50.00 25.00 1:1 C64C 50–25–2–400/440–64
34-64187 50.00 50.00 - C64C 50–50–1–400/440–64
34-64193 62.50 12.50 1:2:2 C64C 62.5–12.5–12–400/440–64
34-64194 68.75 6.25 1:2:4... C64C 68.75–6.25–112–400/440–64
34-64845 75.00 12.50 1:2:3 C64C 75–12.5–11A–400/440–64
34-64200 75.00 25.00 1:2 C64C 75–25–11–400/440–64
34-64203 87.50 12.50 1:2:4 C64C 87.5–12.5–111–400/440–64
34-64205 93.75 6.25 1:2:4:8 C64C 93.75–6.25–1111–400/440–64
34-64206 100.00 12.50 1:1:2:4 C64C 100–12.5–211–400/440–64
34-64208 100.00 25.00 1:1:2 C64C 100–25–21–400/440–64
34-64188 100.00 50.00 1:1 C64C 100–50–2–400/440–64
Dimensions C64D: WxHxD 500x300x350 mm (for cabinets with a min. W / D: 600 x 400 mm)
42
Modules for Power Factor Correction Systems
Type C...C
Article-No. Rated Power Step Power Switching Type and order code
in kvar in kvar Sequence
at 400 V at 400 V
43
Modules for Power Factor Correction Systems
Type C...D
Technical Data
Design Sheet steel chassis with premounted Discharge With discharge resistors acc. to
FDSDFLWRUV¿OWHUUHDFWRUVIXVHV VDE 0560, Part 46
and contactors Power loss Capacitors: 0.5 W / kvar, reactors:
Rated voltage Min. 440 V / 50 Hz (Capacitors) 3.5–6 W / kvar (depending on ver-
Rated power See table (at 400 V mains voltage) sion and harmonic distortion)
Ingress IP 00 acc. to DIN 40 050, Standards Acc. to VDE 0560 parts 46 and 47,
protection for cabinet mounting EN 60831-1 and -2 as well as IEC
831-1 and -2, VDE 0660 part 500
Ambient –5 ° to +60 °C acc. to DIN VDE
and EN 60439-1 with type test TSK
temperature 0660 part 500 Sect. 6.1.1.1
(when assembled) Rated capacity See FRAKO Manual of Power
determination Factor Correction
Air humidity Max. 90 %, no condensation
Minimum rated voltage of capacitors 440 V / 50 Hz · Rated power at 400 V / 50 Hz mains voltage · other voltages on request
Article-No. Rated Power Step Power Switching Type and order code
in kvar in kvar Sequence
at 400 V at 400 V
44
Modules for Power Factor Correction Systems
Type C...D
Article-No. Rated Power Step Power Switching Type and order code
in kvar in kvar Sequence
at 400 V at 400 V
45
Modules for Power Factor Correction Systems
Type C
Description
RK EMR 1100-1150
Slot 5:
Space for the control unit. The mounting plate SB... has
room for the control terminal strip RKL... with control
transformer and thermostat if required.
Power Factor
Control Relay
Slot 4: EMR 1100
Space for an additional capacitor/reactor module.
Slot 1:
6SDFHIRUWKH¿UVWPRGXOH7KHEXVEDUVHW&8
$:HQDEOHVWKH¿UVWFDSDFLWRUFKRNHPRGXOHWR
be connected vertically if required.
46
Modules for Dynamic Power Factor Correction
Systems
Type C...D-E
7KHEHQH¿WV
Q Optimum network utilization
Q Improved power quality, hence best product quality
Typical Applications Q Reduced energy costs
Q Modular design, the same construction as
FRAKO C Modules
7KH 6%6 G\QDPLF SRZHU IDFWRU FRUUHFWLRQ XQLW ¿QGV Q Predictive control with superposed feedback control
application in low voltage networks:
Nothing could be faster!
Q With low short-circuit capacities where disruptions
occur when large consumers are switched on
Q Where a fast-acting power factor correction Typical low voltage networks are those supplying:
system and a large number of switching cycles are
necessary Q Spot welding machines
Q Where power factor correction is required for only Q Motors with high power ratings
a few supply cycles at a time Q Rolling mills, kneading machine drives, etc.
47
Modules for Dynamic Power Factor Correction
Systems
Type C...D-E
Act or react?
Reactive power Q
simultaneously an input signal to the FRAKO SBS, FRAKO reactive power control relays adjust the
causing it to compensate directly for the reactive power switching delay to suit the power demand. Large chan-
demand of that load. The corrective action is effective at ges of load are compensated for quickly, minor load
the latest 3 to 24 ms after the switching signal. variations more slowly. Capacitor stages of different
Nothing could be faster! sizes are switched in selectively to match the power
demand, the number of switching operations minimized
This is the solution for low voltage networks with fast-
by computation, and all equally sized capacitor stages
switching inductive loads to:
are used in rotation. These control characteristics
Q6XSSUHVVÀLFNHUDQG combine to give a uniform utilization of the capacitor
Q Stabilize the supply voltage. contactors and the lowest possible number of switching
cycles, thus reducing wear and tear in the power factor
correction system.
At the same time, critical network constellations are
avoided – unlike in the classical step-by-step switching
Control Methods process – by rapidly adjusting the capacitor allocation
a) The classical reactive power control relay using step- to match demand precisely when major load changes
by-step progressive switching occur.
Reactive power demand
0 kvar
25 kvar
approx. 150 seconds approx. 150 seconds
0 kvar
Reaction of the stages
25 kvar
approx. 50 ms approx. 50 ms
50 kvar
25 kvar
Reaction of stages
100 kvar
50 kvar
125 kvar
ces the number of switching operations in the network.
,W HIIHFWLYHO\ VXSSUHVVHV QHWZRUN ÀXFWXDWLRQV EHWWHU
0 kvar
than switching too quickly and hence overshooting and
5 - 30 seconds 5 - 30 seconds undershooting several times. This variant represents the
best solution for power factor correction in installations
such as rolling mills or kneading machines, where a
25 kvar
Reaction of the stages
100 kvar
49
Modules for Dynamic Power Factor Correction
Systems
Type C...D-E
d) Dynamic correction with the FRAKO SBS Power Factor Correction and
Reactive power demand
25 kvar
such as welding systems, it is necessary to cater
for at least 108 switching cycles. The FRAKO SBS
50 kvar
unit is designed for duties of this type.
Q FRAKO’s patented predictive control principle
100 kvar
enables the reactive power to be compensated for
Just as quick as individual power factor correction as quickly as possible for as much switched load
for each load, but considerably less expensive, due capacity as desired. The reactive power demand
to the intelligent control system, which converts the from loads of any power rating is converted without
reactive power demand from all loads into the capacitor delay into the optimum allocation of capacitor
stage allocation for the power factor correction system. stages for that load.
The fast-acting control system ensures that the required Q The greater part of the reactive power is
power factor correction is achieved within 3 – 24 ms, compensated for without delay. This eliminates
depending on the phase angle of the switching signal. PDMRUYROWDJHGLSVWKDWFRXOGUHVXOWLQÀLFNHU7KH
Just as accurate as feedback control, since a super- superposed reactive power control relay then
posed reactive power control relay compensates for the compensates for the remaining reactive power
remaining reactive power demand not covered by the demand. These signals are also processed by
predictive control system. the control unit, which determines the required
capacitor allocation from their sum total.
Q Until now, a comparable response without delay
was only possible when correcting the power factor
The Ideal Formula for large reactive loads by assigning a rapidly
Q The SBS dynamic power factor correction unit from switched-in capacitor stage to each individual load.
FRAKO switches without delay at the next voltage In contrast, the SBS is a variant that cuts costs
zero at the thyristor switch and thus avoids any and offers the fastest possible switching response.
peak inrush current. Numerous inputs with widely differing reactive
power demands are converted into the equivalent
Q Any desired frequency of switching with no contact
capacitor allocation for the power factor correction
wear and tear and no additional loss of active
system.
power. The solid-state switches function without
any problems even when the capacitors are not
discharged and without causing peak inrush
currents.
Q Power circuits are designed for a continuous
rating, i.e. no parallel auxiliary contactor is needed
to reduce the load on the thyristors. The switching
delay of at least 50 ms when using auxiliary
contactors is therefore also not necessary. Load Load Load Load ...etc.
... kvar ON ... kvar ON ... kvar ON ... kvar ON
50
Modules for Dynamic Power Factor Correction
Systems
Type C...D-E
Technical Data
Discharge With discharge resistors acc.
to VDE 0560, part 46
Design Sheet steel chassis with premoun-
Power loss Capacitors: 0.5 W / kvar
ted FDSDFLWRUV¿OWHUUHDFWRUV
fuses and contactors Reactors: 3.5-6 W / kvar
(depending on version and
Rated voltage Min. 440 V / 50 Hz (capacitors)
harmonic distortion)
Rated power See table (at 400 V mains voltage)
Standards Acc. VDE 0560 parts 46 and 47,
Protection IP 00 acc. to DIN 40 050, EN 60831-1 and -2 as well as
for cabinet mounting IEC 831-1 and -2, VDE 0660 part
Ambient –5 ° to +60 °C acc. DIN VDE 0660 500 and EN 60439-1 with type
temperature part 500 sect. 6.1.1.1 test TSK
(when assembled) Rated capacity See FRAKO Manual of Power
Air humidity Max. 90 %, no condensation determination Factor Correction
Minimum rated voltage of capacitors 440 V / 50 Hz · Rated power at 400 V / 50 Hz mains voltage · other voltages on request
Article-No. Rated Power Step Power Switching Type and order code
in kvar in kvar sequence
at 400 V at 400 V
Capacitor-Reactor-Module, type: C84D-E / C85D-E, wear-free and fast switching, with thyristors
P1: series resonance frequency 134Hz, p = 14%
- 25.00 25.00 - C84D 25–25–1–400/480–84–P1–E
- 37.50 12.50 1:2 C84D 37.5–12.5–11–400/480–84–P1–E
34-64802 50.00 25.00 1:1 C84D 50–25–2–400/480–84–P1–E
- 50.00 50.00 - C84D 50–50–1–400/480–84–P1–E
34-64376 75.00 25.00 1:2 C85D 75–25–11–400/480–85–P1–E
34-64036 100.00 50.00 1:1 C85D 100–50–2–400/480–85–P1–E
P7: series resonance frequency 189 Hz, p = 7%
34-64028 25.00 25.00 - C84D 25–25–1–400/440–84–P7–E
34-64061 37.50 12.50 1:2 C84D 37.5–12.5–11–400/440–84–P7–E
34-64029 50.00 25.00 1:1 C84D 50–25–2–400/440–84–P7–E
34-64030 50.00 50.00 - C84D 50–50–1–400/440–84–P7–E
34-64031 75.00 25.00 1:2 C85D 75–25–11–400/440–85–P7–E
34-64032 100.00 50.00 1:1 C85D 100–50–2–400/440–85–P7–E
Accessories
34-80056 Power supply 24 VDC / 2.5 A - for thyristor switches, built on the SBS-PS 24VDC-2.5A
mounting plate and wired up to the control terminal
Dimensions C84D: WxHxD 700x300x350 mm (for cabinets with a min. W / D: 800 x 400 mm)
Dimensions C85D: WxHxD 700x300x450 mm (for cabinets with a min. W / D: 800 x 500 mm)
Dimensional Sketch
51
Components for Dynamic Power Factor
Correction Systems
Thyristor switches type DCS
Description
A skilled switchgear manufacturer can easily design These dynamic components are also used in
and assemble his own Dynamic PFC System by using FRAKO‘s own modules for Dynamic Power Factor
dynamic PFC components from FRAKO. Correction Systems (see technical data, page 51).
Accessories:
39-21010 Power Supply-6-thyristor switches 115/230 VAC - 24 VDC
39-29050 with 12 control contacts, 6 with reaction time between 20/40 ms RM 2012 6+6D
39-29051 with 12 control contacts, reaction time between 20/40 ms RM 2012 12D
52
16 | 17
PowER Quality
Reactive current compensation
Reactive power controller The reactive power controllers of KBR leave nothing to
be desired. The compact controller multicomp 144 lcd
is above all used in small facilities. The multicomp 4d6
modules are bus compatible and can be integrated into
the KBR system. The modular system allows a control of
reactive current compensation to be set up quickly and
easily. By adding a safety and maintenance module to the
controller, the unique securec® procedure can protect
facilities from overvoltages and overcurrents.
Power capacitors The power capacitors multicond uhPc stand out through
their high durability at extreme ambient temperatures.
3-phase internal overpressure disconnector and 2-fold cur-
rent carrying capacity are further quality features.
Filter circuit reactors The filter circuit reactors multiind are characterized by
high linearity and low losses.
Audio frequency blocking devices The audio frequency blocking devices multiton reliably
block off the ripple signal of the energy supplier.
Thyristor switches Rapid switch actions are no problem with the thyristor
switch thyroswitch.
KBR EnergyManagement | Power Quality
multicomp
Reactive power controller
p page 96
multicond
multiind
multiton
Power capacitors
Filter circuit reactors
Audio frequency
blocking devices
p page 108
thyroswitch
Thyristor switch
p page 132
18 | 19
PowER Quality
Reactive current compensation
network quality
Compensation modules With its large range of modules, KBR provides solutions for
every cabinet system. A fast and easy installation helps to
reduce costs.
multicab-F
Fixed capacitors
p page 142
multimod-F
Compensation modules
p page 148
multicab-R
Controlled
compensation facilities
p page 166
multilog
Mobile network analysis
p page 190
BluEwaVE
Active harmonic
filters
p page 180