Power Quality Disturbance PDF
Power Quality Disturbance PDF
Power Quality Disturbance PDF
3.1 INTRODUCTION
This chapter discusses the cause effect of several important types of power quality
problems. According to IEEE standard 1159 [90], power quality refers to a wide variety
of electromagnetic phenomena that characterize the voltage and current at a given time
Power quality problems started since the inception of power systems [81]. In
1930’s, the main power quality problem was the light flicker due to mass- production
machinery. In 1950’s power quality problems came from air conditioners. In 1990’s, the
utility and customer standards. In most cases, power quality problems are caused by
improper wiring and grounding [82]. Power system disturbances are also caused by
natural disruptions (such as lightning strokes), large non linear loads (such as arc
furnace), large rotating loads (such as large motors) and electronic equipment.
Sometimes, some power quality problems are generated by temperature, humidity, radio
frequency interference, equipment EMI, corona, operator errors and software bugs. The
most frequent power quality problems include temporary and sustained voltage sags,
interruptions and harmonics [29]. The less frequent ones include high impedance faults,
low and high frequency oscillatory transients, voltage swells, switching transients,
lightning induced overvoltages, motor starting voltage sags and incipient faults.
32
3.3 POWER QUALITY TERMS AND DEFINITIONS
Committee 22 (IEEE SCC 22) [92] comprising of Industrial Applications Society, Power
Electric Systems organized by CIGRE has framed the standards to coordinate power
table 3.1
33
Table 3.2 shows the categorization of electromagnetic phenomena used for the
power quality community. The information regarding typical spectral content, duration
and magnitude for each category of electromagnetic phenomena [62] and also the
probable causes of occurrence of power system disturbances are listed in table 3.2. The
TYPICAL TYPICAL
TYPICAL POSSIBLE
S.No. CATEGORIES SPECTRAL VOLTAGE
DURATION CAUSES
CONTENT MAGNITUDE
1 Transients
Impulsive
1.1 Transients Lightning
Ferroresonance,
Very Low <300 Hz Transformer
1.2.1
Frequency Energisation
34
Short
2 Duration
Variations
2.1 Instantaneous
Power System
0.5-30 Faults
<0.1 pu
2.1.1 Interruption cycles Equipment Failures
<1 min Control
Malfunctions
Power System
Faults(slg),
Switching on
Heavy loads
Utility or Source
disturbances
Load Interaction
0.5 - 30 with Wiring
0.1-0.9 pu
2.1.2 Sag cycles (especially during
2 ms-1 min equipment Startup)
Load interaction
with voltage source
Impedance
Loose wiring
UPS or Motor-
Generator
Instability
Power System
Faults(slg),
Switching on
0.5 - 30 1.1-1.8 pu
2.1.3 Swell Heavy loads
cycles
Switching of a
large Capacitor
Banks
2.2 Momentary
30 cycles -
2.2.1 Interruption <0.1 pu
3s
30 cycles -
2.2.2 Sag 0.1-0.9pu
3s
30 cycles - 1.1-1.4 pu
2.2.3 Swell
3s
2.3 Temporary
2.3.1 Interruption 3 s - 1 min <0.1 pu
2.3.2 Sag 3 s - 1 min 0.1-0.9 pu
2.3.3 Swell 3 s - 1 min 1.1-1.2 pu
35
Long
3 Duration
Variations
Short Term
Outages can be
caused by utility
breaker tripping to
clear a fault and
then reclosing
automatically. Long
Sustained term outages
3.1 Interruptions >1 min 0 pu typically result
from accidents
involving power
lines, utility
transformers, utility
power and
alternative power
source failures.
Load activation
Variations in the
reactive
compensation of
the system
(switching off a
capacitor bank),
utility brownouts,
Undervoltages
3.2 >1 min 0.8-0.9 pu incorrectly selected
transformer taps,
misadjusted voltage
regulators,
unintentional line
overloading on the
same transmission
line
Switching off of
loads, Variations in
the reactive
compensation of
the system
3.3 Overvoltages >1 min 1.1 -1.2 pu
(switching on a
capacitor bank) and
improperly adjusted
internal voltage
regulators.
36
Voltage
4 Steady state 0.5 - 2%
imbalance
Magnitude Single phasing
4.1
Imbalance conditions, load
imbalance,
Phase excessive losses in
4.2
Imbalance the feeder circuit
conductors
Waveform
5
distortion
Geomagnetic
Disturbances,
Switching of a
synchronous
5.1 DC Offset Steady state 0 0.1 %
-
machine and
presence of
Switched Mode
Power Supplies.
Nonlinear devices
and loads on the
O-lOO"1 power systems such
0-20 % as computers ,
5.2 Harmonics harm Steady state
variable speed
drives, UPS,
electronic phone
systems.
Static Frequency
Converters, cyclo
0-2%
5.3 Interharmonics Steady state converters,
induction motors
and arcing devices.
Normal operation
of power electronic
devices at the
5.4 Notching 0-6 KHz Steady state instants of current
commutation from
one phase to
another.
Power electronic
devices, control
circuits, arcing
equipments, loads
5.5 Noise broadband Steady state 0-1%
with solid state
rectifiers and
switching power
supplies.
37
Any load that has
significant current
Voltage variations,
6 <25 Hz Intermittent 0.1-7%
fluctuations especially in the
reactive component
such as arc furnaces
Faults on the bulk
power transmission
system, a large
Power
block of loads
7 freauencv <10s
being disconnected
variations
or a large source of
generation going
off-line.
Phase angle
controlled loads
(eg. SCR
Controlled Loads),
Repetitive
8 Variable Speed
Events
Drives, Large UPS
Systems, Light
Dimmers, Arc
Welders
For steady state phenomena, the attributes used are Amplitude, Frequency,
Spectrum, Modulation, Source impedance, Notch depth, Notch area and for the non
steady state phenomena, other attributes required are Rate of rise, Amplitude, Duration,
properties specified in table 3.2 along with attributes clearly describe power systems
disturbance.
simulink models were generated to simulate the disturbances like fault simulation,
38
3.4.1 Transients
term is a surge as the transient resulting from a lightning stroke for which a surge arrester
is used for protection. The transients are of two types: impulsive and oscillatory.
transients are normally characterized by their rise and decay times, which can also be
Impulsive transient-medium
am plitude in pu
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1
time in ms
39
Impulsive transient-long
0 0.01 a02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1
time in sec
state condition of voltage, current or both, that includes both positive and negative
polarity values. As the instantaneous changes are rapid, the spectral content (predominant
and distribution systems and is caused by many types of events. In distribution systems,
the oscillatory transients are due to transformer energisation and ferroresonance caused
40
The most frequent is capacitor bank energisation, which typically results in an
oscillatory voltage transient with a primary frequency between 300 and 900 Hz. The peak
magnitude can approach between 1.3-1.5 p.u. with duration between 0.5 and 3 cycles
depending on the system damping. Transients caused by capacitor switching are shown in
fig. 3.2 a-d. The low frequency range is usually defined as 500 Hz to 2 kHz, and the high
frequency range is usually defined as greater than 2 kHz. The frequency of a transient is
banks are commonly used in power systems for power factor correction. Major
semiconductor device damage, short circuits and loss of data or stability [87].
capacitor switching
1.5
otn
am plitude in pu
0.5
-
41
Oscillatory transient-short duration(300 Hz)
amplitude in pu
0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1
time in s
42
Fig. 3.2 d Short Circuit Waveform Assuming the Short Circuit is Applied at the
Instant when the Rotor Direct Axis is along the Magnetic Axis of 0° phase angle
This category covers the IEC category of voltage dips and short interruptions.
Depending on the duration of the voltage variations, the variations can be designated as
fault conditions, the energisation of large loads which require high starting currents, or
intermittent loose connections in power wiring. Depending on the fault locations and the
system conditions, the fault can cause either temporary voltage drops(sags), or voltage
rise(swell) or a complete loss of voltage (interruptions). The fault condition can be close
to or remote from the point of interest. In either case, the impact on the voltage during the
43
actual fault condition is of short duration variation until protective devices operate to
clear the fault. The simulations are shown in fig. 3.3 a-c
44
500
Vci
__ l 0
volt
-500
Ij
Bus voltage
Fig. 3.3 c System Transients with Temporary Overvoltage
From the fig. 3.3 c it is observed that initially the bus experiences a high overvoltage due
to the system ringing. The system ringing is the result of resonance between the bus
capacitance and the line inductance. This part of the response decays according to the
system damping determined by the line resistance. As the system approaches steady
state, the bus experiences a sustained overvoltage that is due to excessive reactive power
production by the bus capacitor. This temporary overvoltage increases the requirements
3.4.2.1 Interruption
to less than 0.1 pu for a period of time not exceeding 1 minute. Interruptions can be the
result of power system faults, equipment failures and control malfunctions. The
interruptions are measured by their duration since the voltage magnitude is always less
than 10% of nominal. The duration of an interruption due to a fault on the utility system
is determined by the operating time of utility protective devices [45]. The table 3.3 and
45
fig 3.4 shows the diagrammatic chart representations of the site survey. The table 3.3 lists
Year Customer
point
interruption
1992 1.05
1993 1.18
1994 0.7
1995 0.98
1996 0.9
1997 1.2
1998 1.17
1999 0.6
2000 0.9
permanent fault to less than 30 cycles. Delayed reclosing of the protective device may
46
Fig. 3.5 Momentary Interruptions - long duration
47
momentary interruptions
amplitude in pu
connections can be irregular. Some interruptions may be preceded by a voltage sag when
these interruptions are due to faults on the source system. The voltage sag occurs between
the time a fault initiates and the protective device operates and is shown in fig. 3.9.
momentary interruptions
Fig. 3.9 The Voltage Sag at the Initiation of a Fault and the Protective Device Operates
49
3.42.2 Sag (dips)
A sag is a decrease to between 0.1 and 0.9 pu in rms voltage or current at the
power frequency for durations from 0.5 cycles to 30 cycles. Voltage sags are usually
associated with system faults but can also be caused by energisation of heavy loads or
starting of large motors [54]. Momentary sags (2 to 5 seconds) are usually due to cleared
faults, while sustained sags lasting over 1 minute are usually due to permanent faults or
hours of downtime and loses millions of dollars for wasting materials on the fabrication.
Table 3.4 gives a few important voltage sag diagnostic examples [12].
Periodic sags with high resistive currents Laser Printer, Copier, Fax
The common solutions for sags include repairing wiring, replacing faulty
breakers, adding larger wiring, installing voltage regulator or power conditioner for small
sags, adding UPS, ferroresonant transformers, etc., Figures 3.10-3.12 shows the different
50
Sag-short duration
Sag-short duration
51
momentary interruptions along with sag
9
CO
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2
time in m
3.4.2.3 Swell
current at the power frequency for durations from 0.5 cycles to 1 minute. As with sags,
swells are associated with system fault conditions. When a SLG fault occurs, voltage
swell is induced in the unfaulted phases. Swells are also caused by switching off a large
load or energizing a large capacitor bank. Swells are characterized by their magnitude
and duration. The severity of a voltage swell during a fault condition is a function of the
infinite zero sequence impedance, the line to ground voltages on the ungrounded phases
52
will be 1.73 pu during a SLG fault condition and is shown in fig. 3.13. Close to the
substation on a grounded system, there will be little or no voltage rise on the unfaulted
phase because the substation transformer is usually connected delta-wye, providing a low
impedance zero - sequence path for the fault current. Fig. 3.14 shows a short duration
Swell-short duration
53
Swell-short duration
root mean square deviations at power frequencies for longer than 1 minute. The voltage
variations are caused by load variations on the system and system switching operations.
3.4.3.1 Overvoltage
power frequency for a duration longer than 1 minute. Overvoltages are usually the result
of load switching (e.g., switching off a large load, or energizing a capacitor bank). If the
54
system is either too weak for the desired voltage regulation or voltage controls are
inadequate, the system leads to overvoltages. Incorrect tap settings on transformers can
also result in system overvoltages. Fig. 3.15 - 3.16 shows the overvoltage caused due to
55
3.4.3.2 Undervoltages
An undervoltage is a decrease in the rms ac voltage to less than 90% at the power
frequency for a duration longer than 1 minute. Undervoltages are the result of the events
that cause overvoltages. A load switching on or a capacitor bank switching off can cause
an undervoltage until voltage regulation equipment on the system can bring the voltage
back to within tolerances. Overloaded circuits can also result in undervoltages. The term
When the supply voltage is zero for a period of time in excess of 1 minute, the
interruptions more than 1 minute are often permanent and require human intervention to
Voltage imbalance is defined as the maximum deviation from the average of the
three phase voltages or currents, divided by the average of the three phase voltages or
components. The ratios between the symmetrical components are used to specify the
percent of unbalance.
The primary source of voltage imbalance less than two percent is single phase
loads on a three phase circuit. Voltage imbalance can also be the result of blown fuses in
56
one phase of a three phase capacitor bank [88]. Severe voltage imbalance (greater than
5% ) can result from single phasing conditions. Figs.3.17-3.20 shows the unbalance
57
Amplitude in pu
58
3.4.5 Waveform Distortion
• dc offset
• Harmonics
• Interharmonics
• Notching
• Noise
3.4.5.1 DC offset
This can occur as the result of a geomagnetic disturbance or due to the effect of half wave
rectification. Incandescent light bulb life extenders, for example, may consist of diodes
that reduce the rms voltage supplied to the light bulb by half wave rectification. Direct
current in alternating current networks can have a harmful effect by biasing transformer
cores so that they saturate in normal operation. This causes additional heating and loss of
transformer life. Direct current may also cause the electrolytic erosion of grounding
electrodes and other connectors. Fig. 3.21 shows the transient phenomenon of the
59
current waveform with no dc offset and with maximum dc offset
3.45.2 Harmonics
Harmonics are sinusoidal voltages or currents having frequencies that are integral
multiples of the frequency at which the supply system is designed to operate. Harmonic
distortion levels are described by the complete harmonic spectrum with magnitudes and
phase angles of each individual harmonic component. Total Harmonic Distortion (THD)
is a measure of the effective value of harmonic distortion [3]. Fig. 3.22 - Fig. 3.25 shows
sample waveforms of these events recorded from real systems. The simulink models are
distortion is the most frequently encountered power quality problem. Because of the
60
increasing popularity of electronic and other non-linear loads, such as adjustable-speed
drives, arc furnaces, and induction furnaces, perfect sinusoid waveforms often become
distorted by both even and odd harmonics. Transformer core saturation is another cause
overheating, excessive currents and voltage, and tripping of protective relays [67].
i i v Ti m* i i
61
bus voltage
Amplitude in p u
62
3.4.5.3 Interharmonics
Interharmonics are voltages or currents having frequencies that are not integral
multiples of the frequency at which the supply system is designed to operate. They can
in networks of all voltages classes [79]. The main sources of interharmonic waveform
distortion are static frequency converters, cycloconverters, induction motors and arcing
devices. Power line carrier signals can also be considered as interharmonics. Fig. 3.26
shows a signal that involves interharmonics. Fig. 3.27 shows a harmonic signal measured
from a drive that contains both interharmonics and subharmonic contents. The details are
given in appendix B.
harmonics
amplitude in pu
' 0 0.005 0.01 0.015 0.02 0.02S 0.03 0.035 0.04 0.045 0.05
time in ms
63
Fig. 3.27 Harmonic Signal Measured from a Drive that Contains both Interharmonics and
Subharmonics Contents
3.4.5.4 Notching
power electronics devices when current is commutated from one phase to another. Since
64
Notching
oin
amplitude in pu
o
9
m
' 0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 0.045 0.05
time in msec
3.4.5.S Noise
content lower than 200 KHz superimposed upon the power system voltage or current in
phase conductors, or found on neutral conductors or signal lines. Noise in power systems
is caused by power electronic devices, control circuits, arcing equipments, loads with
65
3.4.6 Voltage Fluctuations
of random voltage changes, the magnitude of which does not normally exceed the voltage
ranges of 0.9 - 1.1 pu. Fig. 3.29 and Fig. 3.30 shows a measured high and low frequency
flicker waveform.
66
low frequency flicker
Ol
o
amplitude in pu
O
tfl
6
Power frequency variations are defined as the deviation of the power system
fundamental frequency from its specified nominal value. The Power frequency variations
are directly related to the rotational speed of the generators supplying the system. There
arc slight variations in frequency as the dynamic balance between load and generation
changes. The size of the frequency shift and its duration depends on the load
characteristics and the response of the generation control systems to load changes.
Frequency variations that go outside of accepted limits for normal steady state operation
of the power system can be caused by faults on the bulk power transmission system, a
large block of load being disconnected, or a large source of generation going offline.
67
3.4.8 Repetitive Events
Phase angle controlled loads (eg. SCR Controlled Loads), Variable Speed Drives,
Large UPS Systems, Light Dimmers, Arc Welders causes repetitive events. Fig. 3.31
shows a signal that is repetitive in nature. The events may be periodic or aperiodic or
sporadic occurrence.
waveforms are listed in Table 3.5 along with its controlling parameters.
68
Table 3.5 Mathematical Models Used To Simulate The Power Quality Events
S.NO. EVENT CONTROLLING EQUATIONS
PARAMETERS
1 Pure Sine F = 50 Hz V(t) = sin(cot)
V= 230 V
2 Sudden Sag 0.1 <a <0.9 V(t)=A[ 1 -a(u(t2)-u(ti))] sin(cot)
t<t2-ti<9t
3 Sudden Swell 0.1 <a <0.9 V(t)=A[ 1 +a(u(t2)-u(ti))] sin(tot)
t<t2-ti<9t
4 Harmonics 0.1<a3<0.9 V(t)=A[ ai sin((ot) + a3 sin(3tot) +
0.1<a5<0.9 as sin(5tot) + a7 sin(7o)t)]
0.1<a7<0.9
Ia,2=l
5 Flicker 0.1 <a <0.2 V(t)=A[ 1 +asin(p(ot)] sin(tot)
0.1 <3 <0.5
6 Oscillatory 0.1 <a <0.9 V(t)=A[sin(0)t)+a sin(0)n (t-
Transients 0.5t<t2-ti <3t ti)) (u(t2)-u(ti)) ]
0.1 <x <0.2
7 Notch Vb=230 V, fb=50Hz, V(t)=V2Vb sin(2 7t fb t) + Vn
Vn= Notch Signal
8 Outage 0.9<a<l V(t)=A[ 1 -a(u(t2)-u(ti))]
t<t2-ti<9t
9 Sag with 0.1<a<0.9 V(t)=A[ 1 -a(u(t2)-u(ti))]
harmonics t<t2-ti<9t (sin(cot)+ a3 sin(3a)t) + as sin(5cot)
0.05<a3<0.15 +...]
0.05<as<0.15
10 Swell with 0.1 <a <0.8 V^ACl+aCufel-udO)]
harmonics t<t2-ti<9t (sinftot) + a3 sin(3tot) + as sin(5a>t)
0.05 <a3 <0.15 +...]
0.05<as<0.15
3.6 CONCLUSION
The different power system disturbances have been simulated using MATLAB
mathematical models in a m-file, simulink models, power sight manager [97], mathcad
tools. The disturbances simulated are pure and also with an addition of noise upto the
69