Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Combination Arrestor, 3-Pole + NPE: Technical Data Sheet Surge Protection, Arrestor, Type 1+2 (Office and Housing)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Technical data sheet

Surge protection, arrestor, type 1+2 (office and housing)

Combination arrestor, 3-pole + NPE

V 25-B+C/...: Combination arrestor set, lightning and surge arrestor Type 1+2 to DIN EN
61643-11 (B+C to VDE 0675 Part 6).

• With new Multibase base with multi connection terminals


• Complete unit consisting of cover and base, pre-mounted and ready for connection
• Suitable for any TN-S and TT systems
• Plug-in arrestor with dynamic isolating device
• Visual function display
• Protection level <0.9 kV
• Encapsulated non-extinguishing zinc oxide varistor arrestor for use in standard distribu-
tor housings
• Marked connections

Application example: Building with open-wire power supply or for setting up lightning pro-
tection equipotential bonding in residential buildings.
Dimensions Type Highest Version Pack. Weight Item No.
continu- pcs kg/100 pcs.
ous
voltage
V
V25-B+C 3+NPE 280 3-pole complete with NPE 1 51,000 5094463

Connection options V25-B+C 3+NPE


Nominal voltage V UN 230
SPD to EN 61643-11 Type 1+2
SPD to IEC 61643-11 Class I+II
Lightning protection zone LPZ 0→2
Impulse discharge current (10/350) kA Iimp 7
Total discharge current (10/350) kA Itotal 25
Nominal discharge current (8/20) kA In 30
Arrestor surge current (8/20) [total] kA ITotal 8/20 120
Maximum discharge current (8/20 μs) kA Imax 50

Voltage protection level kV Up <0,9
Response time ns tA < 25
Maximum back-up fuse A 160
Temperature range °C ϑ -40-80
Division unit TE (17.5 mm) 4
Protection rating IP20
Connection cross-section rigid mm² 2,5-35
Connection cross-section, multi-wire mm² 2,5-35
Connection cross-section, flexible mm² 2,5-25

1 OBO | 7/2017