PR200 04 514 15 PDF
PR200 04 514 15 PDF
PR200 04 514 15 PDF
INSTALLATION MANUAL
09
Doncaster
South Yorkshire Assessed to ISO 9001:2008
DN2 4NB Certification number 714w/01
TEL: +44 (0) 1302 321541 Approved to EN54-2 1997 & A1;2006
FAX: +44 (0) 1302 303220 EN54-4:1997 & A1;2002 A2:2006
Document Drg Ref PR200-04-514-15
Introduction
Introduction to the Manual
NOTICE
CAUTION
RISK OF EXPLOSION IF BATTERY IS REPLACED
BY AN INCORRECT TYPE
DISPOSE OF THE USED BATTERIES ACCORDING
TO THE INSTRUCTIONS ( Appendix Page 113 )
CF3000
Analogue Addressable Fire Detection System
Contents
Contents Page
Delete Zone 93
Add Device 94
Delete Device 95
Configure Heat sensors 96
Network 97
Password Protection 98
5.0 Appendix 99
Spur Isolator Instruction Sheet 100
4 Way Sounder Circuit Instruction Sheet 101
Zone Unit Monitor Instruction Sheet 102
Shop Unit Monitor Instruction Sheet 103
1 Way I/O Unit Instruction Sheet 104
SensorBase Instruction Sheet 105
System Wiring 106
IP66 Wall Mounted Sounder Instruction Sheet 107
Internal Wall Sounder Instruction Sheet 108
Base Sounder Instruction Sheet 109
3 Way I/O Instruction Sheet 110
Loop Powered Beacon Instruction Sheet 111
Call Point Instruction Sheet 112
Serial Number Placement 113
Battery Disposal 114
Section 1
6
Introduction
CF3000 provides all of the sophisticated features required of a leading edge analogue
addressable fire system along with the simple operation and neat installation demanded
by installers and building users.
The panel can be flush or surface mounted and the generously sized metal back box
allows ample facilities for rear or top cable entries.
It is available in single two and four loop versions, with or without an integral printer.
In addition both passive and fully functional repeater panels are available.
Each of the CF3000 system components has been specifically designed to operate as
part of a CF3000 system, this provides an assurance that the panel, the sensors, the
interfaces and the ancillaries are all fully compatible with each other and that the full
range of system functionality is supported by each device.
Each loop of a CF3000 panel can accommodate up to 200 addresses, panels are
available in one, two or four loop format. Up to 63 panels can be networked together to
form a single system capable of operating with over 32,000 devices
7
Project Planning
The following is a typical program and timetable for a CF3000 installation project, once
the initial order has been received:
1. Project Meeting
Installer and user to be present; system specifications, schematic diagram and
proposed circuit drawing to be available. CF3000 Installation & Commissioning
Guide to be provided.
2. Equipment Fix
Typically two week's notice is required for equipment to be delivered. Cable to be
installed and bases/back boxes to be fitted. Then fire sensors, call points, alarm
sounders, isolator units and interface units to be installed.
3. Address Schedule
Schedule of sensor locations to be completed by installer and returned to enable
System programming.
4. Auto Learn
Fire panel/repeater panels to be installed and terminated. System to be powered
up by installer and auto learn mode activated (see Auto Learn section). System
to be tested and verified by installer, prior to final commissioning.
5. Final Commissioning
A minimum of two weeks notice is required from receipt of Address Schedule
and Commissioning request form for a Cooper Service Engineer to attend site
and implement/oversee the final commissioning procedures (see Commissioning
section), in conjunction with the installer.
8
System Design Guidelines
Guidelines
Systems should to the relevant local standards and codes of practice, for the UK this is
BS5839 part 1. CF3000 meets all the relevant requirements of BS5839 part 1: 2002.
Installation planning is simplified by the fact that every addressable CF3000 device contains an
integral short circuit isolator. Care must be taken to ensure that local standards requirements
regarding aspects such as loop coverage, area covered by a single spur and cable
specification are observed.
There may be certain applications in which deviations from the code may be necessary and
these must be listed on the commissioning certificate. (See commissioning section)
Loop lengths
The maximum permitted loop length is 2 km measured from the near to the far terminals on the
CF3000 Motherboard PCB. There is no minimum limit to loop length. Any wiring spurs off the
loop must be included within the 2 km limit. On long loop runs, the lengths of wiring rises and
falls (between floors, down to manual call points) must be included. Remember to include
these especially when taking loop lengths from plan drawings.
9
Compatible Equipment
10
Compatible Equipment
The range of compatible sensors for the CF3000 system consists of the following:
Compatible callpoints
The range of purpose designed callpoints for CF3000 consists of a surface callpoint, a
flush callpoint and a surface weatherproof callpoint.
A range of accessories is available including a hinged protective cover, resettable
element kit and a flush bezel.
The status LED can be programmed to either be permanently off under normal
conditions or to pulse in order to confirm that it is in communication with the CF3000
control panel.
CBG370
CBG370/S
CBG370/WP
All sounders have multiple selectable volume settings, the volume setting is controlled
by the CF3000 panel and so can be altered without needing to access the sounder.
12
Compatible Equipment
Base sounder
The CAS380 has been designed specifically to complement the latest generation of
Cooper Fire Systems soft addressed sensors.
it consists of a first fix bracket, and a main body which clips onto the bracket
incorporating the sounder and a Sensormounting base in a single composite assembly.
After the body has been clicked into place and connected, a Sensor or front cover is
then added to complete a very simple, quick and neat installation.
The cover enables the CAS380 to be used as a discreet stand alone wall or ceiling
mounted device.
The sounder base design incorporates a mechanism that can be activated if required to
lock either the Sensor or the cover into place to prevent unauthorised removal.
Stand alone sounders are ideal for applications where greater sound outputs are
required than can be achieved with a base sounder or for applications requiring a higher
level of resilience or ingress protection.
Two different versions are available standard version and an IP66 rated version.
CAS381 CAS381/WP
13
Compatible Equipment
A loop powered flashing beacon is available for applications where visual alarm indication
is required such as areas of high ambient noise or buildings which are used by people
who are hard of hearing.
CAB382
14
Interfaces
CF3000 has been designed to be suitable for a wide range of applications, various
interfaces have been developed to enable the simple integration of other fire systems or
building control and safety systems. The following devices are available:
CIO351 has 3 input channels and 3 output channels, it is used to monitor up to three
separate inputs from equipment such as sprinkler flow switches and also to provide 3
separately controlled volt free output contacts which are intended to be used to control
external equipment such as air handling plant or access control systems.
All inputs and outputs operate completely independently of each other and can be
programmed using the sophisticated cause and effect capabilities of CF3000 to operate
either globally or in response to activation of specific devices or specific inputs.
Inputs are monitored for open and short circuits, a specific resistance is required to
activate an alarm condition, fully open or short circuit conditions are monitored and
generate a system fault signal.
Inputs are suitable for use as fire signal inputs such as from a sprinkler flow switch ,
however they can also be used to monitor non fire inputs such as external keyswitches.
CIO351 CMIO353
CMIO353 is a single channel input / output unit, the output is capable of switching up to
1A at 230V AC.
Commonly used for applications such as door release controls and plant shut down
signalling
The input is monitored for open and short circuits, a specific resistance is required to
activate an alarm condition, fully open or short circuit conditions are monitored and
generate a system fault signal.
The input is suitable for use as a fire signal input such as from a sprinkler flow switch,
however it can also be used to monitor non fire inputs such as an external keyswitch to
activate day night mode or other panel functions
The CIO353 is supplied in a surface mounting IP65 box.
15
Interfaces
CZUM352
Please refer to local standards e.g. BS5839 Pt1:2002 for details of the maximum
allowable area to be covered by a single spur / zone. The CSUM355 is supplied in a
surface mounting IP65 box.
CSUM355
16
Interfaces
Spur Isolator
CSI350 enables soft addressing to work when the loop contains spurs, it controls the
addressing operation so that when the system reaches a spur, all devices on the spur
are allocated an address before it continues addressing the loop.
The device also incorporates a short circuit isolator.
Because each device contains a short circuit isolator only 1 is required at the start of
each spur.
Please refer to BS5839 Pt1:2002 for details of the maximum allowable area to be
covered by a single spur / zone
CSI350
CSC354
A 4 way unit takes up a single address but each circuit can be independently controlled.
An CSC354 unit requires a local un-switched 230V supply and incorporates a back up
battery to 24 hours of standby operation followed by a minimum of 30 minutes of full
alarm ringing.
A standby of 72 hours can be achieved at the expense of reduced load capability.
17
Equipment Compatibility
Sensors
Loop wired sensors must be of the Cooper Fire Systems 300 series soft addressed
analogue type. Cooper Fire Systems 300 series conventional detectors can be
connected via an CZMU352 interface. The connection of other detector types via an
CZMU352 interface is not recommended,
Call points
Loop wired call points must be the Cooper Fire Systems 300 series soft addressed
analogue type, Cooper Fire Systems 300 series conventional callpoints can be
connected via an CZMU352 interface. The connection of other callpoint types via an
CZMU352 interface is not recommended,
Sounders
Loop powered addressable sounders must be of the Cooper Fire Systems 300
series soft addressed analogue type.
Note: It is possible to use devices outside these requirements if they are supplied
with power from a separate source and switched via a suitable relay.
Relay circuits
Additional relays can be added to the CF3000 system by using either CMIO353 or
CIO351 relay units.
1) CF3000 provides monitored outputs to drive fire and fault relays mounted in
external equipment. External relays should be suppressed. If a non-suppressed
relay is used then a diode can be connected as shown in the wiring diagram in the
appendix, to suppress any reverse EMF on the release of the relay which might
cause the panel to malfunction.
18
Equipment Compatibility
19
System Overview
The main element of the CF3000 user interface is a large (120mm x 90mm visible area)
touch screen display, which provides comprehensive user information and also acts as
a multifunctional keypad.
The CF3000 touch screen display automatically reconfigures to suit the selected
function, for example, if the change device text menu option is selected, the touch
screen is automatically formatted as a full QWERTY keyboard to enable fast and simple
text entry.
The use of the touch screen display enables a wide range of user and engineering
facilities to be incorporated into the panel whilst still offering simple operation.
As well as a large format LCD display providing full system status information, the panel
incorporates 96 traditional zone indication LED's to provide clear information about the
status and spread of a fire even to a user who is completely unfamiliar with the
operation of the system.
In addition there are a number of system status LED's designed to give clear status
information to non technical users
CF3000 has comprehensive facilities for on site system configuration, whereby the user
can add or remove simple devices or change device text directly via the panel, without
the need for a service engineer to visit site. For initial configuration or major system
changes special PC configuration software is available enabling Cooper Service
personnel to do this more efficiently than can be achieved using the system screen.
Exiting configurations can be uploaded to the PC so that changes can be made to the
existing system rather than having to revert to initial files.
CF3000 has the ability to support highly complex ringing pattern requirements.
Multistage cause and effect programming is possible whereby each addressable
sounder or output interface can be programmed independently if required and can be
set to respond to specific addresses, specific detection zones, specific panels on a
networked system or standard global ringing.
The panel supports three separate sets of programming per sounder and each stage
can be triggered differently For example, if a single sensor is triggered the panel can
20
System Overview
be programmed such that the sounder nearest to the sensor operates immediately and
continuously, the remaining sounders in the affected zone operate in pulsed mode and
the other sounders delay for a selectable period to allow the cause of the alarm to be
investigated before global ringing commences.
CF3000 utilises intelligent soft addressing technology to greatly simplify the installation
and commissioning processes.
Once the system has been installed and the autolearn menu selected, the CF3000
control panel will automatically scan the detection loops and allocate each device with
an address number corresponding with its position on the loop, this avoids the
traditional need for manual addressing of the system devices which is time consuming
and provides a potential for error.
A major innovation with CF3000 is the ability to incorporate spurs of analogue devices
which are fed from the main loop by utilising a spur isolator.
Whenever the panel detects a spur, it breaks from allocating address numbers to the
loop wired devices, allocates address numbers to each of the devices on the spur in
sequence and then continues to address the devices on the main loop.
Every CF3000 analogue device incorporates an integral short circuit isolator ensuring
maximum system integrity. A single short circuit will not disable any loop-mounted
devices, the isolators in the devices each side of the short circuit will operate and the
CF3000 control panel will drive communication from both ends of the loop.
The spur isolator also incorporates a short circuit isolator such that in the event of a
short circuit on the spur, the integrity of the main loop will not be compromised.
Please refer to local standards e.g. BS5839 Pt1:2002 for details of the maximum
allowable are to be covered by a single spur.
The CF3000 panel is designed for ease of installation, the power supply and battery are
integral to the main control panel so only a single panel is required even on large 4 loop
systems.
Systems are available with either standard or extended capacity battery configurations.
Where system loading and standby period requirements necessitate an extended
capacity battery, a deeper backbox is utilised thus avoiding the need for a separate
battery enclosure.
The CF3000 charger is suitable for both standard and extended capacity batteries.
21
System Overview
Optional printer
CF3000 panels are available with optional built in printers.
Where a printer is fitted, it is housed behind a printer cover door, which can be opened
by means of a special tool (Supplied) to provide simple and safe access to the printer
paper roll without exposure to any live equipment.
Paper replacement is extremely simple due to the drop in loading method and auto feed
printer design, the paper roll is simply dropped into the purpose designed cradle and the
end of the roll is then offered up to the printer, which will then automatically load the
paper ready for use.
The printer can be set to either print automatically or to print on demand
When a printer is not fitted, a removable, flush fitting blanking plate is used to cover the
printer paper aperture to enhance the appearance of CF3000 and to preserve its
ingress protection rating.
22
Technical Specification
Power Supply (Approved EN54 pt 4)
Mains
Nominal Voltage : 230 Vac + 10%, -15%
Nominal Current : 75mA
Maximum Current : 750mA
Input Fuse R1 : NTC SG39 Imax 4Amp
Output Voltage including tolerances : 26V = 18.5 to 29.5Volts
: 26V RAW = 18.5 to 29.5Volts
: 5Volt Output = 4.6V to 5.5V
Ripple Voltages : 26V = 800mV
: 26V RAW = 800mV
: 5Volt Output = 430mV
Maximum Loadings : 26V O/P
: 26V RAW O/P
= 0.98A
= 1.7A } * I max b
: 5V = 0.5A
Standby Current (4 Loops Loaded) : 26V
: 26V RAW
= 280mA
}
= 150mA * I max a
: 26V
: 26V RAW }
= 280mA * I min
= 150mA
: 5V = 43mA
DF6000 is protected by an internal thermal device, this requires no maintenance
* I max a, I max b & I min = Current as specified in BSEN54-4 Published 2006 (Amendments 1 & 2)
Batteries
Number of Batteries :2
Manufacturer: :YUASA NP12-12
Capacity : 12 Ah
Battery Fuse : 6.3A Anti-Surge (F4)
Maximum battery current; : 3.5 Amps
Standby current (mA) : 175 (4 loops), 125 (2 loops)
Maximum Charging Current to the Batteries : 1.0amp
Float Voltage : 27.4 Volts
Final Voltage : 21.0Volts
Charging Characteristics : Constant Voltage with 0.970A
limit with temperature compensation
Maximum current drawn from the batteries : 3.5Amps
when the mains is not available
Deep Discharge Protection : 20.6 Volts
Battery Internal Impedance Fault : >0.5 ohms
Inputs
Addressable Loops
Max Number :1-4
Max Loop Load per loop : 220 ma
Max Number of Addressable Devices per loop : 200
Class Change : Operated by external volt free contact
Outputs
Conventional sounder circuits
Number of sounder circuits :4
Total sounder Load : 1.5 Amps
Sounder Circuit Fuses (F1/2/3/4) : 1.6 Amp (Quick Blow)
End of line resistor : 6k8
Weight : 250g
Material used : Poly Carbonate
Flammability Rating : UL 94 5VA
TERMINAL BLOCKS : DO NOT USE EXCESSIVE FORCE WHEN TIGHTENING THE SCREWS ON
THE TERMINAL BLOCK
CAUTION
RISK OF EXPLOSION IF BATTERY IS REPLACED
BY AN INCORRECT TYPE 24
DISPOSE OF THE USED BATTERIES ACCORDING
TO THE INSTRUCTIONS
Optional Functions as per EN54 P2&4
CF3000 is approved to EN54 Parts 2 & 4 including all the following options which can be selected
as required
Panel Outputs
Two pairs of outputs are provided. ONLY polarised equipment should be used.
Ensure the polarity of the connections are observed at all times and end of line resistors (6K8 5%)
are fitted for correct operation.
The total alarm load across all sounder outputs = 1.5 Amp
All outputs are fused with 1.6 Amp Glass fuse Alarm devices should be spread equally across the
4 sounder circuits.
WARNING: DO NOT EXCEED THE RATED OUTPUT CURRENT
25
Optional Functions as per EN54 P2&4
The CF3000 has the facility to inhibit the operation of the output sounders, Output to Fire routing
equipment and the output of the fire protecting equipment until one more confirmatory signals are
received from different zones. This feature is programmable using CF3000 Site Installer Software.
26
Optional Functions as per EN54 P2&4
This output is ON in alarm condition to indicate that the CF3000 Control and indicating equipment
has operated the fire protecting equipment (option 7.10 of EN54 pt2 )
This output is ON in alarm condition to indicate that the CF3000 Control and indicating equipment
has operated the fire routing equipment (option 7.9 of EN54 pt2 ).
This output is ON to indicate that the fire Protecting equipment has been disabled either by the
CF3000 Control and indicating equipment or the Fire Brigade Panel.
27
Optional Functions as per EN54 P2&4
all inputs are held high via a weak pull up (logic high), the action of short circuiting any of the five
inputs to there respective 0v will result in a logic low.
Monitored Inputs
In Fault / Extinguisher Active
Relay Outputs
Normal status-> input sees a 3K3 resistor.
Active status-> input sees a 680 ohm resistor.
Outputs
1: Extinguisher released -> output high 26v
2: FRE operated
3: FPE disabled
4: FRE disabled
5: Panel in fire, will remain on after panel soft reset for > 15 minutes, or extinguish immediately
with interface reset
6: disable all sounders.
28
Optional Functions as per EN54 P2&4
This output is ON to indicator that the fire routing equipment has been disabled either by the
CF3000 Control and indicating equipment or the Fire Brigade Panel.
This output is ON to indicate that the CF3000 control and indicating Equipment is in alarm
condition. This output will remain on for at least 15mins after reset or when the reset has been
activated from the Fire Alarm Brigade Panel
This output is ON to indicate that the sounders have been disabled either by the CF3000 control
and indicating equipment or the Fire Brigade Panel.
Inputs
Input 1: Reset
This input is used to test the output to the fire routing equipment
This input is used to disable the fire routing equipment output of the CF3000. Whilst the FRE is
disabled by this input, it can not be re-enabled by the CF3000 control panel
This input is used to disable the fire protecting equipment output of the CF3000. Whilst the FRE is
disabled by this input, it can not be re-enabled by the CF3000 control panel
This input is used to disable the sounders of the CF3000. The disablement of sounders from the
Fire Brigade Panel can be re-abled from the CF3000 control panel only when the system is not
Alarm State.
29
Optional Functions not approved to EN54 P2&4
This mode is programmed at access level 3. One of the Swedish requirements is that access
level 2 & 3 is only avalailabe by the access of the keyswitch. The key switch is wired to the class
change input.
This mode is set on at access level 3 and is a commonly used by Eastern European
Countries.
In the event of a Fire the timer T1 can be set from 0 to 3 min where the alarm will be displayed on the
panel and no output activation, if during this time the alarm is acknowledged then timer T2 can be set
from 0-10 min where the alarm can be investigated and alarm reset.
However if timer T1 & T2 time out during alarm activation, the outputs will be activated.
Timer T1/T2 with Call point Override (Option not required by EN54 pt2)
This is similar to the above except a call point alarm will activate the output instantly
30
Cable & Wiring
Only the cable types listed below are allowable for loop connections.
When choosing your preferred cable type, you must take note of the following cable and
wiring requirements.
Cable Resistance
Core Diameter Typical FP200 Resistance
1.0mm² 18.1 Ohms/km/Core
1.5mm² 12.1 Ohms/km/Core
2.5mm² 7.41 Ohms/km/Core
4.0mm² 4.61 Ohms/km/Core
Cable Anchorage
The mains cable must be fixed securely with a 20mm cable gland. Remove a suitably
located knockout feed the cable through the gland and bolt the gland to the CF3000
backbox as shown. Secure the cable to the side of the box using the cable clip
provided.
The panel should be installed in a clean, dry, reasonably well ventilated place, and not in
direct sunlight. Temperatures in excess of 40°C and below 5°C should be avoided, if in
doubt consult Cooper Service. The panel should be located away from any potential
hazard, in a position where it is readily accessible to authorised staff, and the fire services,
ideally on the perimeter of a building near a permanent entrance. Mount the panel to the
wall using dimensions provided on page 32. Do not drill through the panel to the wall as
dust will contaminate the circuitry.
Installation Guide
! Never carry out insulation tests on cables connected to electronic equipment.
! DO NOT OVER TIGHTEN TERMINAL CONNECTOR SCREWS
! Always use the correct type of cables specifically designed for the operation of fire
detection and alarm circuits.
! Always adhere to volt drop limitation when sizing cables
! Always observe polarity throughout. Non colour coded conductors should be
permanently identified.
! Screen continuity must be maintained throughout the entire loop circuit including at
each junction point and at each device, terminals are provided on each device to
facilitate this.
! The screen should be earthed at the connection point provided at the CF3000 panel
and not at any other point. Both the loop start and the loop end must be connected
to the appropriate earthing points.
Care must be taken to avoid connecting the screen to the earthed body of any metal
devices, enclosures or cable containment. The screen or drain wire of the loop
cables should not be considered as safety earth and therefore should not be
connected to terminals marked with the earth symbol, except at the panel, and
should not be insulated with green and yellow sleeving.
! CF3000 utilises intelligent soft addressing technology to greatly simplify the
installation and commissioning processes. Once the system has been installed and
the autolearn menu selected, the CF3000 control panel will automatically scan the
detection loops and allocate each device with an address number corresponding
with its position on the loop, this avoids the traditional need for manual addressing
of the system devices which is time consuming and provides a potential for error.
! It is of vital importance that accurate details are kept of the exact wiring route in
order to determine which address has been allocated to each device.
32
Fixing details
Read all the installation instructions before commencing with the installation. The
installation of this panel must be carried out by a suitably qualified /trained person. The
installation must comply with IEE wiring regulations and with BS5839 part 1 2002
The electronic components within the fire panel are Static Sensitive. Do not
touch the electronics directly.
1, Surface Mount; drill four holes and fix the backbox to the wall.
2, Flush mounting the backbox requires a hole 364x 472 with a depth of 117mm
(standard battery / backbox ) or 217 mm if deep backbox is used.
479mm
400mm
227mm
364mm
309mm
117mm
132mm 472mm
Installing Cabling
Once the backbox is mounted the next stage is to install the power and loop cables and
fit the glands.
33
External Connections (Mains Supply)
The mains supply should be installed in accordance with the current edition of the IEE
wiring regulations. Connection to the mains supply must be via an isolating device (e.g.
an isolating fuse rated at 3Amps maximum) reserved solely for the fire alarm system.
The cover should be coloured red and labelled “FIRE ALARM - DO NOT SWITCH OFF”.
The isolating protective device should be secure from unauthorised operation and
ideally installed in a securely closed box with a breakable cover.
a) The isolating protective device is fed from the live side of the main isolating
device in which case the label on the isolating protective device, should read
in addition - “WARNING: THIS SUPPLY REMAINS ALIVE WHEN THE MAIN
SWITCH IS TURNED OFF”. A further label should be placed on the main
isolating device reading “WARNING: THE FIRE ALARM SUPPLY REMAINS
LIVE WHEN THIS SWITCH IS TURNED OFF.
Or
b) If the isolating protective device is fed from the dead side of the main
isolating device, a label should be fixed to the main isolating device reading
“WARNING: THIS SWITCH ALSO CONTROLS THE SUPPLY TO THE FIRE
ALARM SYSTEM”.
Cable Segregation
All cables for the fire alarm system should be segregated from any other
cables/wiring/services.
Wiring configurations
Spurs can be taken off the loop in the following ways:
34
Networking
Up to sixty three CF3000 panels, or passive repeaters can be networked together to
operate as a single networked system. To achieve this each panel must be fitted with a
network card (supplied at additional cost.)
When operating as a networked system all fire and fault event information is displayed
at every panel, silencing and resetting of alarms can also be carried out from any panel
on a networked system if panels are suitably configured.
Networked panels can be used as active repeaters, alternatively a low cost passive
repeater is available.
This can either be connected to a loop of an individual panel or it can be connected to
the network, via a network card.
The recommended network cable for the network connection between panels is an
enhanced Firetuf cable Manufactured by Draka cables (part number 910234.)
Screen continuity must be maintained throughout the entire network circuit including at
each junction point. The cable should be grounded at least once per segment, and
preferably at each device. Grounding the shield at every device assists in suppressing
50/60 Hz standing waves. The screen or drain wire of the network cable should not be
considered as a safety earth and therefore should not be connected to terminals
marked with the earth symbol, except at the panel, and should not be insulated with
green and yellow sleeving
Where the network cable passes between buildings, screen continuity should not be
maintained from building to building. A booster device must however be used
irrespective of cable length and should be fitted at a suitable point in the link between
buildings. The cable screen should be connected to the earth of one panel in each
building.
Network Cable
CF3000
CF3000
Power
ON FIRE General
FAULT
System
DISABLE
System
FAULT
System
TEST
Charge
FAULT
Battery
FAULT CF3000 ANALOGUE ADDRESSABLE FIRE PANEL Power
ON FIRE General System
DISABLE
System System
TEST
Charge Battery
FAULT CF3000 ANALOGUE ADDRESSABLE FIRE PANEL
FAULT FAULT FAULT
Zones Zones
1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12
13 14 15 16 17 18 19 20 21 22 23 24 13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32 33 34 35 36 25 26 27 28 29 30 31 32 33 34 35 36
37 38 39 40 41 42 43 44 45 46 47 48 37 38 39 40 41 42 43 44 45 46 47 48
49 50 51 52 53 54 55 56 57 58 59 60 49 50 51 52 53 54 55 56 57 58 59 60
61 62 63 64 65 66 67 68 69 70 71 72 61 62 63 64 65 66 67 68 69 70 71 72
73 74 75 76 77 78 79 80 81 82 83 84 73 74 75 76 77 78 79 80 81 82 83 84
85 86 87 88 89 90 91 92 93 94 95 96 85 86 87 88 89 90 91 92 93 94 95 96
A B X Y
Network
Card
(Panel 1)
A B X Y
Network
Card
(Panel 2)
35
Input/Outputs
PANEL INPUTS
Class Change: ( OPTION NOT REQUIRED BY EN54)
A pair of terminals are provided for class change. By shorting these terminals together
(e.g. Switch, Time clock) the alarm will sound (Panel sounders + loop sounders only).
The Panel will not indicate a Fire. The alarm will cancel when the short circuit is
removed. If the short circuit is not removed the alarms will not cancel.
Class Change
-
Switch/Contactor
timer etc.
+
PANEL OUTPUTS (Apply NO voltage)
Panel Sounders: (OPTION 7.8 EN54 PT 2)
Two pairs of outputs are provided. ONLY polarised equipment should be used.
Ensure the polarity of the connections are observed at all times and end of line resistors
(6K8 5%) are fitted for correct operation. The total alarm load across all sounder
outputs = 1.5 Amp. All outputs are fused with 1.6 Amp Glass fuse Alarm devices
should be spread equally across the 4 sounder circuits.
This output, which is fused and monitored using a 6.8k end of line resistor, is used for
the automatic transmission of the fire signals to fire alarm routing equipment (e.g. Fire
brigade). It operates by providing 12 Volt output to an auxiliary device ( e.g. relay).
It is current limited to 30 mA using a resettable polyswitch.
Class change and test conditions do not operate this output. If operated under a fire
alarm condition, the indication will be displayed on the Touch screen display and will
remain until the fire alarm is reset.
Ensure the polarity of the connections are observed at all times and end of line resistors
( 6K8 5% ) are fitted for correct operation.
36
Input/Outputs
This output, which is fused and monitored using 6.8k end of line resistor is used for the
transmission of the fire signals to controls for automatic fire protecting equipment (e.g.
Door release units etc).It operates by providing 24 Volt output to an auxiliary device
( e.g. relay).
It is current limited to 30 mA using a resettable polyswitch.
Class change and test conditions do not operate this output. If operated under a fire
alarm condition , this output remains activated until the fire alarm is reset.
Ensure the polarity of the connections is observed at all times and end of line resistors
( 6K8 5% ) are fitted for correct operation. All activated devices must be polarised.
This output, which is fused and monitored using 6.8k end of line resistor is used for the
transmission of fault signals to fault warning routing equipment This output is monitored
using 6k8 end of line resistor and it current limited to 30 mA.
Under normal conditions it operates by providing 24vdc which can be connected directly
to a 24v auxiliary device( relay).It is current limited to 30 mA.
Under fault conditions or even if the CF3000 is switched off, this output will switch to 0
volts. Ensure the polarity of the connections is observed at all times and end of line
resistors ( 6K8 5% ) are fitted for correct operation.
A 24 Vdc output is provided. This output is protected by a polyswitch. This output can be
used to power fire or fault auxiliary equipment. Please ensure that all equipments
connected to this output will only draw current when a fire condition exists.
This RS485 output is used to send data to a mimic display or a repeater panel. The
maximum distance is 2km.
37
Maintenance
Quarterly
Check all previous log book entries and verify that remedial action has been taken.
Carry out the weekly test. Visually examine the batteries and their connections, by
loosening the screws behind printer door and opening the hinged front from the
right hand side.
Disconnect the mains supply and check that the battery is capable of supplying the
alarm sounders, by operating a call point.
Annual Test
As Weekly Test and Quarterly Test above. Additionally test all sensors and call
points and check operation.
Every 5 Years
Replace sealed lead acid battery.
Servicing: Cooper Service can offer a regular servicing contract. Further copies
of this log book are obtainable from:-
Cleaning: When cleaning the panel, use a moist cloth. Do not use solvents or
harsh abrasives.
38
Section 2
39
Attaching the door
The door is designed as a drop on fit. Offer the door up to the back box in the open
position as shown below. Align the hinges and lower the door onto the hinge pins.
Check the hinges are secure.
40
Installing a hinged cover
An option hinged cover is available as an optional extra item for CF3000. This can be
fitted as standard equipment prior to despatch or retro-fitted later. The method for fitting
a cover is shown below.
41
Fitting Printer Paper Roll
Open the printer access door on the right hand side of the panel using the key provided.
Drop the paper roll into the paper holder and feed paper into the printer. The printer will
then automatically pull the paper through if the panel is powered up. Tear off the excess
paper them close and secure the printer access door.
Please note for paper feed to operate correctly, paper end must be straight
42
Section 3
Commissioning CF3000
43
Commissioning CF3000
Commissioning mode
Walk test mode allows a single engineer to test the various sensors and call points on a
system without always having to return to the panel either to reset the system or silence
the alarms. When in COMMISSIONING MODE, the system operates as normal except
that when a Sensoror call point goes into alarm, the alarms only operate for a few
seconds and then will silence. The panel then tries to reset the device automatically and,
if successful, the alarms are operated again for a few seconds and the installation
engineer can move on to the next sensor. After a full test has been carried out the
engineer can check the order in which the sensors/call points were operated using the
DISPLAY LOG mode. This information can also be printed on the optional printer.
When the panel is in “Walk Test Mode” the control panel inserts a different code into the
log and also onto the print-out. This is to distinguish between when a device has been
tested in “Walk Test Mode” and when a device has been triggered while in normal
operation.
The following differences will occur:
a) When in the LOG mode, "One man walk test”" will appear on the display followed by
the address text and device type.
b) On the printout a “One man walk test” message will appear will appear followed by the
address text and device type.
C)During a real fire “FIRE !” Will appear on the display followed by the address text and
device type.
44
Configuration
DB Level Check
CF3000 includes the facility to test and set the system sounders with the minimum
amount of disturbance. In sounder test mode, the sounders will sound for 30 seconds
on then 30 seconds off. This facility can be accessed via the engineering menu.
The PC Software enables the address, location text, device type and any comments to
be downloaded to the CF3000 panels.
The PC is connected to each Panel on the network in turn. All data for the Panel is
downloaded.
For networked systems, panels are identified by panel number, P1, P2 etc.
CF3000
Power
ON FIRE General
FAULT
System
DISABLE
System
FAULT
System
TEST
Charge
FAULT
Battery
FAULT CF3000 ANALOGUE ADDRESSABLE FIRE PANEL
Zones
1 2 3 4 5 6 7 8 9 10 11 12
13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32 33 34 35 36
37 38 39 40 41 42 43 44 45 46 47 48
49 50 51 52 53 54 55 56 57 58 59 60
61 62 63 64 65 66 67 68 69 70 71 72
73 74 75 76 77 78 79 80 81 82 83 84
85 86 87 88 89 90 91 92 93 94 95 96
45
Panel Fault Finding
C
AUX
-
RELAY
FAULT
}
V No Fires
+26V
F-
= As Above
LOOP 2
F-
F+
LOOP CIRCUITS
S+
S-
LOOP 3
= As Above
F-
F+
S+
S-
LOOP 4
= As Above
-F-
F+
CHANGE
CLASS
V
CIRCUIT 1
SOUNDER
}
+
See Scope
2 -
Conditions
+
2 -
}
Rx
MODEM/PC
Rs232
CTS RTS
46
Protocol Format
Fig. 1 Full Protocol Format (Not including Repeaters)
1.1 ms
300us
Command Mode
Response ID Flags Address
Start Byte 1 Byte 2 Byte 3
Parity
8 bits 5 bits 3 bits 8 bits
Loop Current
Each Packet of Comms above must be separated by a gap of 20ms minimum where the line is held at 24v
Loop 2: Using a Digital Storage Oscilloscope, connect one channel to R?? on the Loop
Driver Card; probe 0V clip to the 'in-board' side of the resistor; I/P to the '????????' side. This
will display the loop current.
Connect the other channel to Loop 2, S+ terminal on the main mother board. DO NOT
connect the 0v clip of this probe
47
PC Comissioning Software
Non-Latching -> device won't latch in alarm condition, used in conjunction with isolates.
Day / Night
devices affected :
User can define between zones or addresses to be isolated on activation of the device.
The isolate list button enables the user to enter upto 8 unique zones or addresses.
If non-latching has been enabled, Isolated devices can be un-isolated as the triggered device
returns to normal operation. (a call point keyswitch is an example for this application)
48
PC Comissioning Software
Device Outputs
Delay configuration
The output of a device when triggered can be delayed - based on a user defined value
in minutes.
This programming option is enabled when a value other than zero is entered inside the
'Delay' window.
D Override
This option is a manual intervention override, when enabled (check in box) the delay
can be overridden from any call point on the loop when triggered.
DayNight
See dependence detection below
49
PC Comissioning Software
Panel Outputs
Coincidence detection
Each panel output can be assigned a unique list of zones derived from the zones available on the
loop, to activate this output, two unique zones from this list have to be in fire or alternatively any
zone outside this list will trigger the output also. When the 'Coincidence' box is checked - the
'Allocate device' button allows the user to populate this list.
50
Section 4
51
Panel Controls & Indicators
1. System LED’s
2. Zonal LED’s
3. Touch Screen Display
4. Printer Access Door
5. Slot for Optional Printer
1 2 3 4
CF3000
Power
ON FIRE General
FAULT
System
DISABLE
System
FAULT
System
TEST
Charge
FAULT
Battery
FAULT CF3000 ANALOGUE ADDRESSABLE FIRE PANEL
Zones
1 2 3 4 5 6 7 8 9 10 11 12
13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32 33 34 35 36
37 38 39 40 41 42 43 44 45 46 47 48
49 50 51 52 53 54 55 56 57 58 59 60
61 62 63 64 65 66 67 68 69 70 71 72
73 74 75 76 77 78 79 80 81 82 83 84
85 86 87 88 89 90 91 92 93 94 95 96
1 2 3 4 5 6 7 8 9 10 11
Zones
52
Panel Controls & Indicators
Power
ON FIRE General
FAULT
System
DISABLE
System
FAULT
System
TEST
Charge
FAULT
Battery
FAULT CF3000 CF3000 ANALOGUE ADDRESSABLE FIRE PANEL
Zones
1 2 3 4 5 6 7 8 9 10 11 12
13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32 33 34 35 36
37 38 39 40 41 42 43 44 45 46 47 48
49 50 51 52 53 54 55 56 57 58 59 60
61 62 63 64 65 66 67 68 69 70 71 72
73 74 75 76 77 78 79 80 81 82 83 84
85 86 87 88 89 90 91 92 93 94 95 96
3 4
53
Touch Screen Display
System Healthy
XX Zones Active
Tuesday
dd-mm-yyyy
16:25.25
BST On
The Touch Screen is a multi-function display consisting 320x240 dots featuring high
intensity backlighting. In normal operation, the display indicates as above with the
backlighting off.
During an event on the system the display shows the FIRST EVENT and LAST
EVENT plus other events as space allows.
The last 2 lines are normally used to display the total number of events, but they are
also used for scrolling fire conditions, faults, pre alarms or disabled devices
independently or for displaying a reduced menu when in fire condition.
When an event occurs the Touch Screen backlighting comes on unless there is a mains
power supply fault.
Use the Touch Screen to scroll through all active events on the system by using the
SCROLL UP and SCROLL DOWN buttons (available at access level 1). You can display
the contents of the log and also view details of any fires, faults, pre-alarms,faults or
disablements. When displaying the system menu on the touch screen, the last 5 lines of
the display are shown in reverse text.
54
Panel Operation
System Healthy
XX Zones Active
Tuesday
dd-mm-yyyy
16:25.25
BST On
Pressing a field will highlight it and forward to the next screen as shown below.
Supervisor Fires Pre Faults Disabled Supervisor Fires Pre Faults Disabled
FRE Off 1 Alarms 0 0 / Test FRE Off 1 Alarms 0 0 / Test
System Healthy
10 Zones Active Total Fires= 1 Print All Help
Tuesday
dd-mm-yyyy
Tuesday
16:25.25 Dd-mmm-yyy
BST On 16:25.25
BST On
55
Public Access Level 1
Public access level does not require an access code and allows anybody to review the
functions outlined below.
System Healthy
10 Zones Active
Tuesday
dd-mm-yyyy
16:25.25
BST On
Supervisor Fires Pre Faults Disabled Supervisor Fires Pre Faults Disabled
FRE off 1 Alarms 0 0 / Test FRE off 0 Alarms 6 0 / Test
Supervisor Fires Pre Faults Disabled Supervisor Fires Pre Faults Disabled
FRE off 0 Alarms 6 0 / Test FRE off 0 Alarms 6 5 / Test
56
Evacuate (Access Level 2)
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
passcode.
Enter the Supervisor Mode Passcode and select “Evacuate” on the menu at the top of
the screen.
View Others
View Faults
Disabled
View Fires View Pre
AC = 0 Alarms
Supervisor
FRE off
Yes No
57
Silence Alarms
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
passcode.
Enter the Supervisor Mode Passcode and select “Silence Alarms” button as the top of
View Others
View Fires
AC = 0 View Pre Faults
Alarms View
Disabled
I/O Zone: 0
Addresses: 0
Touch button to
View list
Supervisor
FRE off
Yes No
58
Mute Buzzer
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
passcode.
Enter the Supervisor Mode and Select “Mute Buzzer” from the Top Menu
View Fires
AC = 19 View Pre
Alarms View
Disabled View
Faults Others
Reset
Enter the Supervisor Mode and Select “Reset” from the top Menu. Select “Yes” to reset
the panel.
001 14:22:49
Mains Failure Yes No
59
Pre-Alarms
Others
View
View Faults
Disabled
View Fires View Pre
AC = 0 Alarms
Disabled Devices
View Others
View Fires
AC = 0 View Pre Faults
Alarms View
Disabled
I/O Zone: 0
Addresses: 0
Touch button to
View list
The individual buttons show which devices and the number of devices which have been
disabled. Press one of the buttons to display detailed information for a particular
category
60
Faults
Fires Others
AC = 0 Pre
Alarms Disabled
Faults
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
passcode.
Enter the Supervisor Mode passcode and select the “Others” tab.
Fires
AC = 0 Pre
Alarms Disabled
Faults
Others
Check
Lamp test
Auto Config.
61
Enable/Disable (others Menu) Cont.
Enable/Disable I/O
Enable All
Exit
Yes No
Zone 003 Zone 3 Disabled
62
Print
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
passcode.
Enter the Supervisor Mode and Select the “Others” Tab. Press “Print”
View Fires
AC = 19 View Pre
Alarms View
Disabled View
Faults Others
Check
Lamp test
Auto Config.
Select the Information You wish to Print from the Buttons Listed.
63
Lamp Test
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
passcode.
Enter the Supervisor Mode and Select the “Others” Tab. Press “Lamp Test”
View Fires
AC = 19 View Pre
Alarms View
Disabled View
Faults Others
Supervisor
FRE off
Lamp Test
Ok Cancel
64
Weekly Test
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
passcode. Select the others tab as shown below. Press Weekly test.
Supervisor Silence Mute
Evacuate Reset
FRE off Alarms Buzzer
View Fires
AC = 19 Pre
Alarms Disabled
Faults
Others
Supervisor
FRE off
Weekly test
Do you want to continue? Will reset after 4 minutes
Yes No Cancel
The panel will automatically return to the system healthy screen once the weekly test has been
completed.
65
Viewing Events
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
passcode.
Enter the Supervisor Mode Passcode. Select the “Others” tab and press View Log.
View Fires
Pre
AC = 19
Alarms Disabled
Faults
Others
Use the scroll bar to view the list of upto 10,000 events.
The DF6000 event log stores up to 10,000 events including, fires, faults, resets and address
changes. Once the maximum 10,000 events has been reached DF6000 will automatically overwrite
the oldest event every time a new event is stored. The event log can only be reset by an approved
service engineer.
66
Check Auto Config
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
passcode.
Enter the Supervisor Mode and Select the “Others” Tab. Press Check Auto Config.
This feature will scan the loop and pinpoint the exact location of any break in the loop
wiring and will also identify any changes in the loop configuration (e.g. New devices
added or changed device types).
Supervisor Silence Mute
Evacuate Reset
FRE off Alarms Buzzer
Fires
AC = 0 View Pre
Alarms View
Disabled View
Faults Others
Supervisor
FRE Off
Replace Device
Exit
Supervisor
FRE Off Press the Supervisor
Evacuate
Silence Mute Reset
FRE Off Alarms Buzzer
Supervisor
Mode Print Exit
Check button at
Auto Config the top left
of the
Yes No screen.
67
Replace Device
Replace device enables an existing device to be replaced with a new device without
losing the existing text and sounder programming.
Replace a single device then use use the replace device menu to allocate an existing
address to the new device
Fires
AC = 0 View Pre
Alarms View
Disabled View
Faults Others
Check
Change Device
Auto Config.
Supervisor
FRE Off
Replace Device
Exit
Supervisor Supervisor
FRE Off FRE Off
Enter Loop 1 Address
Select a Loop
Loop 1 0 1 2 3
Loop 2
Del 4 5 6
Exit Ok 7 8 9
Exit
68
Test Device (Access Level 3)
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the service mode touch the supervisor button and enter supervisor
passcode.
Service
Exit
Mute
Reset Enter the Service
FRE Off Buzzer mode. Select
“Test”.
Commission
Configure
Test
Service
Exit
Mute
Reset
Select the “Test
FRE Off Buzzer Device” button.
Test Device
Test Zone
69
Test Zone
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
service passcode.
Enter the Service Mode, Select “Test” and on the Screen Shown Below Press “Test
Zone”
Service Mute
Exit Reset
FRE Off Buzzer
Test Device
Test Zone
Service Reset
Exit
FRE Off
70
Sounder Level Test Mode
Enter the Service Mode and Select Test. From the Test Menu Select “Sounder Level
Test Mode”
Test Device
Commission
Test Zone
Configure
Sound Level Test Mode
Test
One Man Walk Test
Yes No
Stop
71
Global Flashing LED On/Off
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
service passcode.
Test
Test Zone
Flashing Off
72
One Man Walk Test
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
service passcode.
Service Mute
Exit Buzzer
FRE Off
Commission
Configure
Test
Service
Exit
Mute
Reset
Select “One Man
FRE Off Buzzer Walk Test” from the
Test Menu Screen.
Test Device
Test Zone
Stop
Yes No
73
Commission: Load CDR from Laptop
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
service passcode.
Enter the Service Mode and Select Commission..
Service Mute
Exit Reset
Buzzer
Commission
Configure
Test
Service Mute
FRE Off
Exit Reset Select “Load CDR from
Buzzer
Laptop” from the
Load CDR from Laptop Analogue Level
Commission Menu”
Yes No
74
Commission: Download CDR to Laptop
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
service passcode.
Enter the Service Mode and Select Commission.
Service Mute
Exit Reset
Buzzer
Commission
Configure
Test
Service Mute
Exit Reset
FRE Off Buzzer
Select “Download CDR
Load CDR from Laptop Analogue Level
from Laptop” from the
Commission Menu
Download CDR to Laptop Printer Settings
Screen.
Auto Learn Change Panel Number
Start PC program
OK Cancel
75
Commission: Auto Learn
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
service passcode.
Enter the Service Mode and Select Commission.
Service Mute
Exit Reset
FRE off Buzzer
Commission
Configure
Test
Service Important:
Exit Auto Learn
FRE Off
Activating autolearn will
erase all existing
programming, text and
Do you want to continue ? configuration data.
No
76
Erase Log
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
service passcode.
Enter the Service Mode and Select Commission.
Service Mute
FRE off Exit Reset
Buzzer
Commission
Configure
Test
Yes No
77
System Details
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
service passcode.
Enter the Service Mode and Select Commission, then Press “System Details”.
Service Mute Service Mute
Exit Reset Exit Reset
FRE off Buzzer FRE Off Buzzer
Service Service
FRE off Print Exit Reset
FRE off
Print Exit Reset
Service
FRE off
Print Exit Reset
SCU 0 0 0 0
Voice Annunciator 13 14 0 0
Repeater 0 0 0 0
ZMU/{SUM 0 0 0 0
Beam Detector 0 0 0 0
Technical Timer 2 1 0 0
Access Control 0 0 0 0
Emerg.Light.Module 0 0 0 0
Carbon Monoxide 0 0 0 0
78
Analogue Level
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
service passcode.
Enter the Service Mode and Select Commission then press “Analogue Levels”.
Service Mute Service Mute
FRE Off Exit Reset FRE Off
Exit Reset
Buzzer Buzzer
Service Reset
Exit Goto
FRE off
1 2 3
Enter Address
..................
4 5 6
Loop 1 0 - 13
Loop 2 0-0
Loop 3
Loop 4
0-0
0-0
7 8 9
Cancel
ok 0
79
Printer Settings
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
service passcode.
Enter the Service Mode and Select Commission then press “Printer settings”.
Commission
Configure
Test
Service Mute
Exit Reset
FRE Off Buzzer
Service
FRE off Exit Reset
Auto
Request
80
Change Panel Number
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
service passcode.
Enter the Service Mode and Select Commission then press “Change Panel Number”
Commission
Configure
Test
Service Mute
Exit Reset
FRE Off Buzzer
1 2 3
Change Panel Number
0
..............................
4 5 6
7 8 9
Cancel
ok 0 81
Number of Panels in Network
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
service passcode.
Enter the Service Mode and Select Commission then press “Number of Panels in
Commission
Configure
Test
Service Mute
Exit Reset
FRE Off Buzzer
1 2 3
Number of Panels
in Network
1
..............................
4 5 6
7 8 9
Cancel
ok 0
82
Screen Cover
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
service passcode.
Enter the Service Mode and Select Commission then press “Screen Cover”
Commission
Configure
Test
Service Mute
Exit Reset
FRE Off Buzzer
Service
FRE off Exit Reset
Installed
Not Required
83
Programming I/O and Sounders
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
service passcode.
Enter the Service Mode and Select Configure.
Service Mute
FRE off Exit Reset
Buzzer
Commission
Configure
Service Mute
Exit Reset
FRE off Buzzer
Programming I/O
and Sounders
Add/Delete
Service
Exit Reset
FRE off
Press panel outputs -
T1 Panel Outputs NOTE Interface
Inputs/Interface
T2 Auxiliary Board Outputs are only used
in certain export
markets
T1/T2 Call Point Overide Alarm Verification Feature
84
Sound Settings
Touch sound settings .
Service
Exit Reset
FRE off
Sound Settings
Selections from the screens below will become the global settings for all loop sounders.
Service Service
Exit Reset Exit Reset
FRE off FRE off
Volume
This will effect all sounders
Volume Low
Medium
Sound High
Service Service
Exit Reset Exit Reset
FRE off FRE off
Sound
This will effect all sounders
Volume Slow Woop
Two Tone
Sound Continuous
85
Change Date/Time
Enter the Service Mode and Select Configure. Select Change Date/Time.
Service Mute
Exit Reset
FRE Off Buzzer
BST On
+1 +1 +1
Current Date: Day Month Year
-1 -1 -1
Wednesday
Day Month Year
dd-mmm-yyyy
86
Change Text
Enter the Service Mode and Select Configure. Select “Change Text”
Service Mute
Exit Reset
FRE Off Buzzer
Select the Address you wish to change and edit using the keyboard
Service Reset Name for address 1
Exit
FRE Off
Address1
...........................................................................
Show Show Show Show
All Detectors Alarms I/O Units
87
Change Zone Text
Enter the Service Mode and Select Configure. Select “Change Text”
Service Mute
Exit Reset
FRE Off Buzzer
Select the zone you wish to Change and Edit Using the Keyboard
Service
Reset
FRE Off Enter the name for Zone 2
Exit
Zone 2
.......................................................................................
88
Change Panel Text
Enter the Service Mode and Select Configure. Select “Change Text”
Service Mute
Exit Reset
FRE Off Buzzer
DF6000
.......................................................................................
1 2 3 4 5 6 7 8 9 0
Q W E R T Y U I O P
A S D F G H J K L
CAPS Z X C V B N M , .
89
Configure Zones
Enter the Service Mode and Select Configure. Select “Configure Zones”
Service Mute
Exit Reset
FRE Off Buzzer
Service Reset
Select Zone into which
Exit
FRE Off device will be added
90
Change User Code
Enter the Service Mode and Select Configure. Select “Change User Code”
Service
Exit Reset
FRE off
Service Mute
Exit Reset
1 2 3
FRE off Buzzer Please enter Passcode:
..............................
..............................
4 5 6
Change User code
Verify New Code:
..............................
7 8 9
Cancel
ok 0
Ok Ok Ok
91
Add Zone
Enter the Service Mode and Select Configure. Select “Add Zone”
Service Mute
Exit Reset
FRE off Buzzer
Service
Exit Reset
FRE Off
Add Zone
Delete Zone
Add Device
Delete Device
Add Zone ?
Yes No
92
Delete Zone
Enter the Service Mode and Select Configure, select “Add/Delete” then “Delete Zone”
Service
Exit Reset
FRE Off
Add Zone
Delete Zone
Add Device
Delete Device
Confirm or
Cancel
Deletion
Delete Zone 2?
Yes No
93
Add Device
Enter the Service Mode and Select Configure, select “Add/Delete” then “Add Device”
Service
Exit Reset
FRE Off
Add Zone
Delete Zone
Add Device
Delete Device
Loop 2
Loop 3
Loop 4
Exit
Confirm
New
Device
and Loop
Loop 2
Scanning Loop
Exit
94
Delete Device
Enter the Service Mode and Select Configure, select “Add/Delete” then “Delete Device”
Service
Exit Reset
FRE Off
Add Zone
Delete Zone
Add Device
Delete Device
Confirm or
Cancel
Deletion
Delete Device 3?
Device 3
Loop 1, Address 3, Device Type Opto/thermal
Yes No
95
Configure Heat Detectors
Enter the Service Mode and Select Configure. Select “Configure Heat Detectors”
Service Mute
Exit Reset
FRE off Buzzer
Thermal A1R
Thermal BS
Thermal CS
Exit
96
Network
Enter the Service Mode and Select Configure. Select “Network”, This menu defines
whether messages are broadcast across the network or remain local.
Service Mute
Exit Reset
FRE off Buzzer
Service
Exit Receive message over network
FRE Off
Reset Network
Evacuate Network
Silence Network
Fire Network
Fault Network
Pre-Alarm Network
97
Password Protection
Service
FRE Off
98
Section 5
Appendix
99
Spur Isolator CSI350
Installation
Notes:
A Spur Isolator must be used when making spurs from the analogue addressable panel
loop. Without this unit, the self addressing features of the system will not function
correctly.
No addressing of the interface is required. See control panel operation for details.
Standard Connections
E
OUT
-
+
ANALOGUE
ADDRESSABLE NO END OF LINE
RESISTOR REQUIRED
E
LOOP
E
IN
-
SPUR
-
+
Notes:
1. Only connect cable screen to its adjacent earth terminal.
2. For maximum spur length / load see BS5839 Pt1:2002.
3. This unit can only be used with Cooper CAB300 and CDB300/I Sensor bases
and compatible sensors.
100
4 Way Sounder Controller CSC354
Installation
Notes:
No addressing of the interface is required. See control panel operation for details.
This unit requires a permanent 230V AC supply.
Standard Connections
6k8 6k8 6k8 6k8
ANALOGUE
ADDRESSABLE
LOOP
230V AC MAINS
FIRE RELAY
N/O C N/C
L N E E + - E + - E + - E + - E - + E - +
OUT IN
+
+
BACK UP
BATT BATTERY
-
-
Notes:
1. Only connect cable screen to its adjacent earth terminal .
2. The end of line resistors must always be fitted, even if the sounder circuits are
Unused
101
Zone Monitor Unit CZMU352
Installation
Notes:
No addressing of the interface is required. See control panel operation for details.
EOLM-1
Standard Connections
12K
- OUT +
- IN +
E - + E - + E - + E - +
Callpoints can be
connected with detectors
on detector zone if
preferred
Notes:
1. This unit can only be used with CDB300/I detector base and compatible detectors .
2. Only connect cable screen to its adjacent earth terminal .
3. The end of line resistor must always be fitted, even if the spur is unused.
4. Maximum spur length - See BS5839 Pt1:2002 for Zone Coverage.
5. Maximum number of call points allowed is unlimited .
6. Detector zone end of line device is EOLM-1 (supplied)
7 Callpoint zone has end of line resistor
102
Shop Monitor Unit CSUM355
Installation
Notes:
No addressing of the interface is required. See control panel operation for details.
Fault
Contact 24V
6K8 12K 12K N/O O/P
- OUT +
- IN +
12K - +
E - + E - + E - + E - + C N/C + - + - E - +
N/O
Notes:
1. This unit can only be used with CDB300/I detector base and compatible
detectors.
2. Only connect cable screen to its adjacent earth terminal .
3. The end of line resistor must always be fitted, even if the spur is unused.
4. Maximum spur length - See BS5839 Pt1:2002 for Zone Coverage.
5. Maximum number of call points allowed is unlimited .
6. Detector zone end of line device is EOLM-1
7 Callpoint zone has end of line resistor
103
1 way Input Output Unit CMIO353
Installation
1. Separate the two halves of the unit.
2. Drill out (or knock out) the required cable entries in the surface mounting back -
box.
3. Fit the back-box in position and pass the wires into it.
4. Connect the unit according the diagram below .
Notes:
No addressing of the interface is required. See control panel operation for details.
Standard Connections
5k6
22k
Analogue Addressable Loop
Volt-Free Output
230V Rated
- - - E C N/C N/O
E + E + +
IN OUT SPUR
INPUT
Notes:
1. Only connect cable screen to its adjacent earth terminal .
2. The end of line resistor must always be fitted, even if the spur is unused.
104
SensorBase Wiring CAB300
Supply Voltage 18 - 30 V DC
Cable Size 0.5 - 2.5mm²
Recommended cable types FIRETUF,FP200 or MICC
Mounting Hole Centres 50 - 80mm
Wiring Hints
! Each terminal is suitable for clamping up to 2 wires
! Clamping of 2 wires of very different diameters under one screw is not
recommended.
! Suitable for mounting to mounting boxes with 50-80mm fixing centres.
General
If difficulty is experienced when mounting the sensor, this may be due to the following:
+ Remote
Indicator
LED
+VIN (optional)
Loop Start
S+
Analogue Addressable
_
S
Fire Alarm Panel
_
_
CF3000
_
_
_
Loop Finish
F
F+
_
__
_
105
106
Any 300 Series Analogue Sensorcan be Connected to the Loop
System Wiring
Installation
1.Drill required holes for the cable gland fixing
Connections
WARNING : Do NOT use high voltage testers if ANY equipment is connected to the
system. Earth scrreen must be continuous along entire length of loop.
IN OUT
E - + E - +
107
Internal wall Sounder CAS380/LPS
Installation
1.Fix to mounting surface using two suitable screws - the rear gasket fits
underneath the base and the sounder gask et fits inside the base.
Connection
WARNING : Do NOT use high voltage testers if ANY equipment is connected to the
system. Earth scrreen must be continuous along entire length of loop.
IN OUT
E - + E - +
NOTE
Care should be taken to ensure the cable does not put stress on the circuit board
108
Base Sounder (CAS380 + CASC)
- +- + - +- +
Loop Start
S+
Analogue Addressable
_
S
Fire Alarm Panel
_
_
CF3000
_
_
_
Loop Finish
F
F+
_
__
_
109
3 way Input output unit CIO351
Installation
Notes:
No addressing of the interface is required. See control panel operation for details.
Standard Connections
ANALOGUE
ADDRESSABLE LOOP
OUTPUTS
E - + E - + - + - + - + N/O C N/C N/O C N/C N/O C N/C
IN OUT INPUTS
LOOP
Notes:
1. Only connect cable screen to its adjacent earth terminal.
2. The end of line resistor must always be fitted, even if the inputs are unused.
3. Monitored inputs can detect open or short circuit faults.
4. Output relays are volt-free contacts and are not monitored.
110
Loop Powered Beacon (CAB382)
Connection Details
Warning:
Do NOT use high voltage testers if any equipment is connected to the system.
IN OUT
E - + E - +
111
Call Point (CBG370, CBG370/S, CBG370/WP)
IN OUT
E - + E - +
112
EN54 Spec label positioning
EN54 Product Spec Label
Note: X=2 on a 2 Loop Panel
or
X=4 on a 4 Loop Panel
Label: D6K XB
PR200-04-517-01
Label: D6K XA
PR200-04-518-01 CF3000
Power
ON FIRE General
FAULT
System
DISABLE
System
FAULT
System
TEST
Charge
FAULT
Battery
FAULT
Zones
1 2 3 4 5 6 7 8 9 10 11 12
13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32 33 34 35 36
37 38 39 40 41 42 43 44 45 46 47 48
49 50 51 52 53 54 55 56 57 58 59 60
61 62 63 64 65 66 67 68 69 70 71 72
73 74 75 76 77 78 79 80 81 82 83 84
85 86 87 88 89 90 91 92 93 94 95 96
NOTE : If the panel is recessed this label must be placed on the front of the panel as
indicated.
113
Battery Disposal Instructions
Although batteries contain lead and small amounts of antimony and arsenic, they are
safe if handled according to the accompanying guide. The battery cells must not be
dismantled as this involves several hazards, which are best handled under controlled
conditions, using specialised equipment. No attempt should be made to repair any
batteries; they should be treated as disposable when they have outlived their use.
Batteries must be disposed of in accordance with current waste disposal and pollution
legislation and in particular; The Environment Protection Act 1990, Special Waste
Regulation 1996. It is recommended that the following authorities are contacted before
any attempt is made to dispose of batteries; Environment Agency Local office, Local
Authority Environmental Health or Waste Handling department.
114
CE Marking
09 O
N
CERTIF
IC 09 O
N
CERTIF
IC
I
AT
AT
PREVENT
PREVENT
IO
IO
LPCB LPCB
N BO
N BO
SS
SS
AR
AR
LO D D
LO
09 09
115