Applying CTs in Protection Schemes For Transformers, Generators, Machines
Applying CTs in Protection Schemes For Transformers, Generators, Machines
Applying CTs in Protection Schemes For Transformers, Generators, Machines
Home / Technical Articles / Applying CTs in protection schemes for transformers, generators, machines etc.
The differential current I1 − I2 flows through the relay operating coil and the
relay operates if the operating torque is more than the re-straining
torque.
Go back to contents ↑
Go back to contents ↑
Hence IF will also be reduced but if the relay setting is kept too low, it may
respond during through faults.
Go back to contents ↑
4. Interposing CT
An intermediate CT (or shorter ICT) is used for feeding protective or
measuring devices which require operating current that is different from the
main CT secondary current .
For example, in case the main CT ratio is 50/5 A and the relay requires a
1 A rating, then an ICT of ratio 5/1 shall be used. It may be noted that the
ICT’s internal burden is to be fed by the output of the main CT.
Go back to contents ↑
Figure 4 – Core
balance scheme (Frame leakage arranged for detecting earth faults on line)
The termination of a three core cable into three separate lines or bus-bars is
through cable terminal box. The core balance protection is used along with
the cable box and should be installed before making the cable joint.
The induced current flowing through cable sheath of normal healthy cable
need particular attention with respect to the core balance protection.
The sheath current (I sh) flow through the sheath to the cover cable box and
then to earth through the earthing connection between cable box.
For eliminating the error due to sheath current (I sh) the earthing lead between
the cable box and the earth should be taken through the core of the core
balance protection.
Go back to contents ↑
6. Summation CT
A summation CT seen in Figure 4 is used for the vector addition of several
feeder currents. It may be noted that the main CT ratio of feeder CTs 1 and
2 should be the same.
Figure 4 –
Summation CT
Go back to contents ↑
7. Current Balance CT
A special use of CTs is in a current balance scheme. It comprises a set of
two numbers. The CTs used in this scheme per phase is known as a
‘current balance CT‘.
Figure 5 shows the two circuit breakers CB1 and CB2, each feeding half
the total load current (I). This arrangement is necessitated when a CB
manufacturer does not have a CB of full impedance of paths A-CB1-
B and A-CB2-B. Since the latter cannot be identical, the currents in the two
paths will be:
Figure 5 –
Current balance CT
Go back to contents ↑
For any particular rated primary current and select value of primary ampere-
turns, the lower the rated secondary current, the finer will be the
adjustment to the ratio error by the use of turns correction. The
disadvantage in selecting 1 A rated secondary current is that a more
expensive, finer gauge wire is required.
Also, 1 A secondary current would, all other things being equal, develop five
times the peak voltage that of a 5 A secondary.
Go back to contents ↑
If the rated primary current is below this value, it is suggested that wound-
primary construction be used but again there is a minimum limit
determined this time by the maximum dynamic and thermal stresses
for a given class of accuracy and burden. The lower the rated primary
current, the larger would be the core required.
Go back to contents ↑
3. Selection of Rated Burden
The ratio error for any particular value of the flux density is lowest for an
overall secondary power factor of unity. The difference between the actual
and test values of the ratio error depends upon factors such as:
The rated burden should be kept as near to the actual burden as possible
to obtain better accuracy.
Go back to contents ↑
Go back to contents ↑