Schneider Catalogue
Schneider Catalogue
Schneider Catalogue
ComPact NS
Catalogue 2019
Circuit breakers and switch-disconnectors
from 630b to 3200 A
schneider-electric.com
Green Premium TM
schneider-electric.com/compactns
II | CompPact NS schneider-electric.com/compactns
More than 10 years of long-felt techniques and technologies ahead quite simple
and convenient.
Type N – 50 kA In (A)
2500 3200
1600 2000
1000 1250
630 800
> MasterPact > ComPact > ComPact INS/INV > Source-changeover > Complementary
MTZ NSXm/NSX systems technical information
Fixed device • Minimum distances (safety clearance) between 2 circuit breakers are
reduced thanks to the arc chute filters.
• A solution for all your applications:
– generator protection
– motor protection up to 750 kW with coordination between breakers
Withdrawable device and contactors (coordination type 1 and type 2)
– source-changeover.
• Best combination of size (small depth), performance with no derating
up to 65 °C (vertical connection) and flexible mounting options.
• Ensure continuity of service:
– Total control of selectivity for the whole Schneider Electric circuit
CAF1 breakers range from moulded circuit breaker to air circuit breaker
CAF2
CAO1
CAO2 – High withstand of the devices to various envrionmental stresses.
OF1
OF2 • Bring flexibility to your installation:
OF3
SD Interchangeable trip units, standardized accessories, adjustable
MN or MX
SDE
rating and scalable indication and control functions.
COM
SDE
OF3
OF2
OF1
MN or MX
COM
CT1
CE3
CE2
CE1
CD2
CD1
Withdrawable device.
schneider-electric.com/compactns ComPact NS | V
I operate my installation
Architecture overview
4- Act
3- Connect
Give a voice to the panel
Safe Ethernet network data transmission
is now part of the intrinsic design of
protection and metering devices
2- Measure
Keeping a close eye
on energy flows
The switchboard plays a key role
in capturing building-related data,
by gathering the critical protection
and metering components.
1- Protect
Electrical protection is
at the core of Smart Panel
Reliable and high-performance
technology is present in every breaker
and every residual current device.
schneider-electric.com/compactns ComPact NS | VII
Architecture overview
Optimizing energy-efficiency
PB111801-60.eps
Architecture overview
Accounting energy
p Record power meter data on dashboards.
DB425334.ai
Installation recommendations
B
Electrical diagrams
D
Additional characteristics
E
1
Presentation - Applications www.schneider-electric.com
or
5.0 E
Micrologic
I ON
push
H
OOFF
push
NS 1200Uimp 12kV
Ui 1000V
8kV
menu
alarm
time tr 8 12
long
(s) 4 16
Ir .8 .9
2 20
.95
.6.7 1 24
.98 .5 at 6 Ir
.5 1 instantaneous
.4 x In Ii 8 1012
6
short
time tsd .4 .4 .3 4
(s) .2 15
Isd3 4 5 .3 .1 3 off
6 2
2.5
.2 0 x In
8
53
012
H
NS 1200Uimp 12kV
Ui 1000V
8kV
Uimp Icu
Ue (kA)
100 % (V) 100
220/240 85
480/690
menu
alarm
time tr 8 12
long
(s) 4 16
Ir .8 .9
2 20
.95
.6.7 1 24
.98 .5 at 6 Ir
.5 1 instantaneous
.4 x In Ii 8 1012
6
short
time tsd .4 .4 .3 4
(s) .2 15
Isd3 4 5 .3 .1 3 off
6 2
2.5
.2 0 x In
8 .1 2
2 I t
10 on
1.5 delay
x Ir
setting
cables and the starter against short-circuits. ensures type-2 coordination with the motor
Equipped with an electronic trip unit, starter, in compliance with
ComPact NS circuit breakers also protect the standard IEC 60947-4-1.
cables, starter and motor against overloads.
Service connection
DB403918.eps
b lead seals and locking systems breakers to constitute the various types of
b tripping curves certified by utilities service connections and meet the needs of all
H
NS 1200Uimp 12kV
Ui 1000V
8kV
Uimp Icu
Ue (kA)
100 % (V) 100
220/240 85
480/690
Icu
100%
40 % Ics =
menu
time tr 8 12
long
(s) 4 16
Ir .8 .9.95
2 20
.6.7 1 24
.98 .5 at 6 Ir
.5 1 instantaneous
.4 x In Ii 8 1012
6
short
time tsd .4 .4 .3 4
(s) .2 15
Isd3 4 5 .3 .1 3 off
6 2
2.5
.2 0 x In
8 .1 2
2 I t
10 on
1.5 delay
x Ir
setting
supplied, etc.
or
A switch-disconnector version of ComPact NS For information on other switch-disconnector
I ON
push
H
OOFF
NS 1200Uimp 12kV
push
Ui 1000V
8kV
Uimp Icu
Ue (kA)
(V) 100
220/240 85 discharged
480/690
Icu
Ics =
100%
O OFF
947-2 UNE NEMA
IEC CEI
BS
UTE VDE
012
53
circuit breakers exists for circuit control and ranges, see the ComPact INS/INV (offering
isolation. positive contact indication and visible break)
All the additional functions may be combined and FuPact (fuse switch) catalogues.
with the basic switch-disconnector function,
including:
b earth-leakage protection
b motor mechanism.
discharged discharged
O OFF O OFF
the source "S1" is not available. switching from one source to the other on the
53 53
012 012
They can be combined with the FDM121 switchboard display unit to provide all the functions of a Power Meter as well
as operating assistance.
PB111801-32_r.eps
All ComPact circuit breakers are equipped with a Micrologic
control unit that can be changed on site.
PB119233.eps
PB104839_ME.eps
Operating-assistance functions > page
A-20
PB111801-19_r.eps
Communication
> page A-28
ComPact NS equipped with Micrologic provide communication
screen 2b.eps
PB119112.eps
PB119111.eps
3
Presentation www.schneider-electric.com
Introduction
General characteristics for NS630b to 3200 range
NS1600 H ComPact NS circuit breakers and auxiliaries comply with the following:
Ui 800 V Uimp 8 kV
b international recommendations:
Ue (V) Icu(kA) Ics(kA) v IEC 60947-1 - general rules
v IEC 60947-2 - circuit breakers
220/240 a 70 37 v IEC 60947-3 - switches, disconnectors, switch-disconnectors, etc.
380/415 a 70 37 v IEC 60947-4 - contactors and motor starters
440 a 65 37 v IEC 60947-5.1 and following - control circuit devices and switching elements;
500/525 a 50 30 automatic control components
660/690 a 42 22 b European (EN 60947-1 and EN 60947-2) and the corresponding national
Icw 19.2kA / 1s cat B standards:
v France NF
v Germany VDE
v U.K. BS
v Australia AS
50/60Hz IEC 60947-2 v Italy CEI
b the specifications of the marine classification companies (Veritas, Lloyd’s Register
Electrically operated ComPact NS circuit breaker. of Shipping, Det Norske Veritas, etc.)
b French standard NF C 79-130 and the recommendations issued by the CNOMO
organisation for the protection of machine tools.
Compact For U.S. UL, Canadian CSA, Mexican NOM and Japanese JIS standards, please
consult us.
DB421307.eps
NS1600 H
Pollution degree
Ui 800 V Uimp 8 kV
Ue (V) Icu(kA) Ics(kA) ComPact NS circuit breakers are certified for operation in pollution-degree 3
environments as defined by IEC standard 60947 (industrial environments).
220/240 a 85 37
380/415 a 70 37
Tropicalisation
440 a 65 37 ComPact NS circuit breakers have successfully passed the tests prescribed by the
500/525 a 50 30 following standards for extreme atmospheric conditions:
b IEC 60068-2-1 - dry cold (-55 °C)
660/690 a 42 22
b IEC 60068-2-2 - dry heat (+85 °C)
Icw 19.2kA / 1s cat B b IEC 60068-2-30 - damp heat (95 % relative humidity at 55 °C)
b IEC 60068-2-52 - salt mist (severity level 2).
Environmental protection
ComPact NS circuit breakers take into account important concerns for environmental
50/60Hz IEC 60947-2
protection. Most components are recyclable and the parts of ComPact NS630b to
NS3200 circuit breakers are marked as specified in applicable standards.
Manually operated ComPact NS circuit breaker. Ambient temperature
b ComPact NS circuit breakers may be used between -25 °C and +70 °C.
Standardised characteristics indicated on the rating plate: For temperatures higher than 40 °C (65 °C for circuit breakers used to protect motor
Ui: rated insulation voltage feeders), devices must be derated as indicated in the documentation.
Uimp: rated impulse withstand voltage b circuit-breakers should be put into service under normal ambient operating-
Icu: ultimate breaking capacity, for various values
temperature conditions. Exceptionally, the circuit breaker may be put into service
of the rated operational voltage Ue
cat: utilisation category
when the ambient temperature is between -35 °C and -25 °C.
Icw: rated short-time withstand current the permissible storage-temperature range for ComPact NS circuit breakers in the
Ics: service breaking capacity original packing is -50 °C [1] to +85 °C.
In: rated current Selectivity
suitable for isolation
As standard, the ComPact NS range ensures selectivity between two circuit
breakers positioned in series in an installation.
DB424549.eps
CB1
CB2
4
www.schneider-electric.com
Presentation
Introduction
General characteristics for NS630b to 3200 range
DB401831.eps
b the isolation position corresponds to the O (OFF) position
b the operating handle cannot indicate the "OFF" position unless the contacts are
effectively open
b padlocks may not be installed unless the contacts are open.
Installation of a rotary handle or a motor mechanism does not alter the reliability
of the position-indication system.
The isolation function is certified by tests guaranteeing:
b the mechanical reliability of the position indication system
b the absence of leakage currents
b overvoltage withstand capacity between upstream and downstream connections.
Installation in class II switchboards
All ComPact NS circuit breakers are class II front face devices. They may be
installed through the door of class II switchboards (as per IEC standard 60664),
without downgrading switchboard insulation. Installation requires no special
operations, even when the circuit breaker is equipped with a rotary handle or a motor
mechanism.
Degree of protection
As per standards IEC 60529 (IP degree of protection) and EN 50102
(IK degree of protection against external mechanical imPacts).
MCC IP435
CNOMO IP547
tripped
reset
5
Presentation www.schneider-electric.com
DB417642.eps
DB417643.eps
DB425841.eps
I ON
push
O OFF
push
d
discharge
O OFF
DB128023.eps
53
012
Power distribution
Selection of circuit breakers from 630 to 3200 A page A-2
Rated current (A) 630 800 1000 1250 1600
ComPact NS630b NS800 NS1000 NS1250 NS1600
PB104839_ME.eps
PB104831_ME.eps
Breaking capacity N 50 50 50 50 50
(kA rms) H 70 70 70 70 70
380/415 V L 150 150 150 - -
LB [1] 200 200 - - -
Rated current (A) 1600 2000 2500 3200
ComPact NS1600b NS2000 NS2500 NS3200
PB104843.eps
Breaking capacity N 70 70 70
(kA rms) H 85 85 85
380/415 V
6
ComPact NS630b to 3200 www.schneider-electric.com
A-1
Functions and characteristics www.schneider-electric.com
lcs AC 220/240 V
50/60 Hz 380/415 V
440 V
500/525 V
660/690 V
Electrical lcu AC 220/240 V
50/60 Hz 380/415 V
440 V
ComPact NS1600H. 500/525 V
660/690 V
lcs AC 220/240 V
50/60 Hz 380/415 V
440 V
500/525 V
660/690 V
Short-time withstand current (kA rms) lcw AC 1s
50/60 Hz 3s
PB104843.eps
ComPact NS2000H.
[1] 65 °C with vertical connections. See the temperature
derating tables for other types of connections.
A-2
www.schneider-electric.com
Functions and characteristics
Protection of distribution systems
ComPact NS circuit breakers from 630b up to 3200 A
(except LB) -
N H L LB N H L N H N H N H
-
- -
- - - - - - -
- -
- -
N H L LB N H L N H N H N H
85 85 150 200 85 85 150 85 85 85 85 85 125
50 70 150 200 50 70 150 50 70 50 70 70 85
50 65 130 200 50 65 130 50 65 50 65 65 85
40 50 100 100 40 50 100 40 50 40 50 65 -
30 42 - 75 30 42 - 30 42 30 42 65 -
50 50 150 200 50 52 150 50 52 37 37 65 94
50 50 150 200 50 52 150 50 52 37 37 52 64
50 50 130 200 50 48 130 50 48 37 37 65 64
40 40 100 100 40 37 100 40 37 30 30 65 -
30 30 - 75 30 31 - 30 31 22 22 65 -
50 70 150 - 50 70 150 50 70 50 70 -
50 70 150 - 50 70 150 50 70 50 70
50 65 130 - 50 65 130 50 65 50 65
40 50 100 - 40 50 100 40 50 40 50
30 42 - - 30 42 - 30 42 30 42
37 37 150 - 37 37 150 37 37 37 37 -
37 37 150 - 37 37 150 37 37 37 37
37 37 130 - 37 37 130 37 37 37 37
30 30 100 - 30 30 100 30 30 30 30
22 22 - - 22 22 - 22 22 22 22
19.2 19.2 - - 19.2 19.2 - 19.2 19.2 19.2 19.2 -
- - - - - - - - - - - 32
40 40 - - 40 40 - 40 40 40 40 130
B B A A B B A B B B B B
10000 10000 10000 10000 5000
6000 6000 4000 4000 6000 6000 4000 5000 5000 3000
5000 5000 3000 3000 5000 5000 3000 4000 2000 2000
4000 4000 3000 3000 4000 4000 3000 3000 2000 2000
2000 2000 2000 2000 2000 2000 2000 2000 1000 1000
3 3 3 3 3
A-3
Functions and characteristics www.schneider-electric.com
instantaneous Ii (In x …)
Earth-fault protection lg (In x …)
Residual earth-leakage protection I∆n
Zone selective interlocking ZSI
Protection of the fourth pole
Current measurements
Electrically operated device. Power measurements
Advanced protection
Quick view
A-4
www.schneider-electric.com
Functions and characteristics
Protection of distribution systems
ComPact NS circuit breakers from 630b up to 3200 A
- - - - - - - - -
- - - - - - - - - - -
- - -
- - -
- - - - - - -
- - - - - - - - - -
- - - - - - - - - -
- - -
- - -
- - -
A-5
Functions and characteristics www.schneider-electric.com
All ComPact circuit breakers are equipped with a Micrologic control unit that can be changed on site.
A Control units are designed to protect Power circuits and loads. Alarms may be programmed for remote indications.
Measurements of current, voltage, frequency, power and power quality optimise continuity of service and energy
management.
Dependability
Integration of protection functions in an ASIC electronic component used in all
Micrologic control units guarantees a high degree of reliability and immunity to
conducted or radiated disturbances.
On Micrologic A, E and P control units, advanced functions are managed by
an independent microprocessor.
Accessories
Certain functions require the addition of Micrologic control unit accessories,
described on page A-28.
The rules governing the various possible combinations can be found in
the documentation accessible via the Products and services menu of
the www.schneider-electric.com web site.
2.0 E Protection:
long time
X Y Z + instantaneous
DB128024.eps
X: type of protection
b 2 for basic protection
b 5 for selective protection
b 6 for selective + earth-fault protection
b 7 for selective + earth-leakage protection.
Y: control-unit generation
Identification of the control-unit generation. Micrologic 5: selective protection
“0” signifies the first generation. Protection:
Z: type of measurement long time
+ short time
DB128025.eps
b A for “ammeter”
+ instantaneous
b E for “energy”
b P for “power meter”
PB100772R-32.eps
PB106351A32.eps
+ instantaneous
+ earth fault
DB128045.eps
+ instantaneous
+ earth leakage up to 3200A
A-6
www.schneider-electric.com
Functions and characteristics
Micrologic control units
Overview of functions
DB128290.eps
DB128302.eps
100 % 100 %
40 % 40 %
menu menu
4260A
DB128374.eps
DB128299.eps
DB128306.eps
DB128308.eps
N 1 2 3
100
100 % 100 % 50
0
40 % 40 %
menu menu
short time instantaneous short time instantaneous short time instantaneous short time instantaneous
Isd tsd tsd Ii tsd Ii
.4 .4 .3 .4 .4 .3
Ii Isd 4 Isd 4 Isd tsd Ii
3
4
5
(s) .4 .4 .3 6
8
10 3 5 (s) 6
8 10 3 5 (s) 6
8 10
3
4
5 (s) .4 .4 .3 6 8 10
2.5 6 .3 .2 4 12 2.5 6 .3 .2 4 12 2.5 6 .3 .2 4 12 2.5 6 .3 .2 4 12
2 8 .2 .1 3 15 2 8 .2 .1 3 15 2 8 .2 .1 3 15 2 8 .2 .1 3 15
1.5 10 .1 2 0 2 off 1.5 10 .1 2 0 2 off 1.5 10 .1 2 0 2 off 1.5 10 .1 2
0 2 off
x Ir on I t x In on I t on I t x Ir on I t off x In
x Ir x In x Ir x In
setting delay setting delay setting delay setting delay
test
6.0
Micrologic 6.0
DB128300.eps
DB128307.eps
DB128309.eps
4260A
N 1 2 3
100
100 % 100 % 50
0
40 % 40 %
menu menu
DB128321.eps
4260A
N 1 2 3
100
100 % 50
0
40 %
menu
A-7
Functions and characteristics www.schneider-electric.com
Micrologic 2.0, 5.0 and 6.0 control units protect power circuits. Micrologic 5.0 and 6.0 offers time selectivity
Protection thresholds and delays are set using the adjustment dials.
Overload protection
G
True rms long-time protection.
Thermal memory: thermal image before and after tripping.
Setting accuracy may be enhanced by limiting the setting range using a different
long-time rating plug.
Overload protection can be cancelled using a specific LT rating plug "Off".
Short-circuit protection
Short-time (rms) and instantaneous protection.
Selection of I2t type (ON or OFF) for short-time delay.
Earth-fault protection
Residual or source ground return earth fault protection.
Selection of I2t type (ON or OFF) for delay.
Neutral protection
On three-pole circuit breakers, neutral protection is not possible.
On four-pole circuit breakers, neutral protection may be set using a three-position
switch: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/2) or
neutral protection at Ir (4P 4d).
Indications
Overload indication by alarm LED on the front; the LED goes on when the current
exceeds the long-time trip threshold.
Test
long time B
Ir
.7
.8
.9
tr
(s) 4
8
12
alarm
A mini test kit or a portable test kit may be connected to the test connector on the
A .6 .95 2 16 E front to check circuit-breaker operation after installing the trip unit or accessories.
.5 .98 1 20
.4
x In
1 .5
at 6 Ir
24 Fault indications (only for micrologic 6.0)
Isd
short time
tsd Ii
instantaneous LEDs indicate the type of fault:
3
4 5 (s) . 4 .4 . 3 6
8 10
b overload (long-time protection Ir)
C 2.5 6 .3 .2 4 12 D
2 8 .2 .1 3 15 b short-circuit (short-time Isd or instantaneous li protection)
.1 2 0
1.5
x Ir
10
on I t
2
x In
off
b earth fault or earth leakage (Ig)
setting delay
test b internal fault (Ap).
tg
Ig
D E F (s) . 4 .4 . 3 Battery power
H C G .3 .2
B H .2 .1 F The fault indication LEDs remain on until the test/reset button is pressed. Under
A I .1 2 0
normal operating conditions, the battery supplying the LEDs has a service life of
on I t off
ground fault
approximately 10 years.
A-8
www.schneider-electric.com
Functions and characteristics
Micrologic control units
For ComPact NS630b to 3200
Micrologic 2.0
Long-time
Current setting (A) Ir = In x … 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1 A
tripping between 1.05 and 1.20 x Ir other ranges or disable by changing long-time rating plug
DB419088.eps
Micrologic 6.0
Earth fault
Pick-up (A) Ig = In x … A B C D E F G H J
Accuracy: ±10 % In y 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
DB419090.eps
400 A < In < 1250 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
In u 1250 A 500 640 720 800 880 960 1040 1120 1200
Time setting tg (s) Settings I2t Off 0 0.1 0.2 0.3 0.4
I2t On - 0.1 0.2 0.3 0.4
Time delay (ms) tg = max resettable time 20 80 140 230 350
at In or 1200 A tg = max break time 80 140 200 320 500
(I2t Off or I2t On)
Note: all current-based protection functions require no auxiliary source.
The test / reset button resets maximeters, clears the tripping indication and tests the battery.
[1] 0 to -40 % - [2] 0 to -60 %
A-9
Functions and characteristics www.schneider-electric.com
Micrologic A control units protect power circuits. They also offer measurements, display, communication and current
"Ammeter" measurements
DB128033.eps
A-10
www.schneider-electric.com
Functions and characteristics
Micrologic control units
Micrologic A "ammeter"
Micrologic 2.0 A
Long-time ANSI Code 49
Current setting (A) Ir = In x … 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98
Other ranges or disable by changing long-time
1 A
rating plug
DB419088.eps
rating plug
Time setting exemple: tr (s) 0.5 1 2 4 8 12 16 20 24
time delay (s) Accuracy: 0 to -30 % 1.5 x Ir 12.5 25 50 100 200 300 400 500 600
Accuracy: 0 to -20 % 6 x Ir 0.7[1] 1 2 4 8 12 16 20 24
Accuracy: 0 to -20 % 7.2 x Ir 0.7[2] 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
Thermal memory 20 minutes before and after tripping
Short-time ANSI Code 51
Pick-up (A) Isd = Ir x … 1.5 2 2.5 3 4 5 6 8 10
Accuracy: ±10 %
Time setting tsd (s) Settings I2t Off 0 0.1 0.2 0.3 0.4
I2t On - 0.1 0.2 0.3 0.4
Operating time at 10 x Ir tsd (max resettable time) 20 80 140 230 350
I2t Off or I2t On tsd (max break time) 80 140 200 320 500
Instantaneous ANSI Code 50
Pick-up (A) Ii = In x … 2 3 4 6 8 10 12 15 off
Accuracy: ±10 %
Operating time max resettable time 20 ms
max break time 50 ms
Micrologic 6.0 A
Earth fault ANSI Code 51N
Pick-up (A) Ig = In x … A B C D E F G H J
Accuracy: ±10 % In y 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
DB419090.eps
400 A < In < 1250 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
In u 1250 A 500 640 720 800 880 960 1040 1120 1200
Time setting tg (s) Settings I2t Off 0 0.1 0.2 0.3 0.4
I2t On - 0.1 0.2 0.3 0.4
Time delay (ms) tg = max resettable time 20 80 140 230 350
at In or 1200 A tg = max break time 80 140 200 320 500
(I2t Off or I2t On)
Micrologic 7.0 A
Residual earth leakage (Vigi) ANSI Code
51G
Sensitivity (A) IΔn 0.5 1 2 3 5 7 10 20 30
Accuracy: 0 to -20 %
DB419091.eps
A-12
www.schneider-electric.com
Functions and characteristics
Micrologic control units
Micrologic E “energy”
Micrologic 2.0 E
Long-time ANSI Code 49
Current setting (A) Ir = In x … 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1 A
Other ranges or disable by changing long-time
DB419088.eps
rating plug
Time setting exemple: tr (s) 0.5 1 2 4 8 12 16 20 24
time delay (s) Accuracy: 0 to -30 % 1.5 x Ir 12.5 25 50 100 200 300 400 500 600
Accuracy: 0 to -20 % 6 x Ir 0.7[1] 1 2 4 8 12 16 20 24
Accuracy: 0 to -20 % 7.2 x Ir 0.7[2] 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
Thermal memory 20 minutes before and after tripping
Instantaneous ANSI Code 50
Pick-up (A) Isd = Ir x … 1.5 2 2.5 3 4 5 6 8 10
Accuracy: ±10 %
Time delay Max resettable time: 20 ms
Max break time: 80 ms
Micrologic 5.0 / 6.0 E
Long-time ANSI Code 49
Current setting (A) Ir = In x … 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1
Tripping between 1.05 and 1.20 x Ir Other ranges or disable by changing long-time
DB419089.eps
rating plug
Time setting exemple: tr (s) 0.5 1 2 4 8 12 16 20 24
time delay (s) Accuracy: 0 to -30 % 1.5 x Ir 12.5 25 50 100 200 300 400 500 600
Accuracy: 0 to -20 % 6 x Ir 0.7[1] 1 2 4 8 12 16 20 24
Accuracy: 0 to -20 % 7.2 x Ir 0.7[2] 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
Thermal memory 20 minutes before and after tripping
Short-time ANSI Code 51
Pick-up (A) Isd = Ir x … 1.5 2 2.5 3 4 5 6 8 10
Accuracy: ±10 %
Time setting tsd (s) Settings I2t Off 0 0.1 0.2 0.3 0.4
I2t On - 0.1 0.2 0.3 0.4
Operating time at 10 x Ir tsd (max resettable time) 20 80 140 230 350
I2t Off or I2t On tsd (max break time) 80 140 200 320 500
Instantaneous ANSI Code 50
Pick-up (A) Ii = In x … 2 3 4 6 8 10 12 15 off
Accuracy: ±10 %
Operating time max resettable time 20 ms
max break time 50 ms
Micrologic 6.0 E
Earth fault ANSI Code 51N
Pick-up (A) Ig = In x … A B C D E F G H J
Accuracy: ±10 % In y 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
DB419090.eps
400 A < In < 1250 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
In u 1250 A 500 640 720 800 880 960 1040 1120 1200
Time setting tg (s) Settings I2t Off 0 0.1 0.2 0.3 0.4
I2t On - 0.1 0.2 0.3 0.4
Time delay (ms) tg = max resettable time 20 80 140 230 350
at In or 1200 A tg = max break time 80 140 200 320 500
(I2t Off or I2t On)
A-13
Functions and characteristics www.schneider-electric.com
Micrologic P control units include all the functions offered by Micrologic A. In addition, they measure voltages and
A calculate power and energy values. They also offer new protection functions based on currents, voltages, frequency
and power reinforce load protection in real time.
Protection
I
Protection settings
J The adjustable protection functions are identical to those of Micrologic A (overloads,
DB128042.eps
A-14
www.schneider-electric.com
Functions and characteristics
Micrologic 5.0 / 6.0 / 7.0 P (Protection)
Long-time ANSI Code 49
Current setting (A) Ir = In x … 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1
Tripping between 1.05 and 1.20 x Ir Other ranges or disable by changing long-time rating plug
DB425221.eps
In u 1250 A 500 640 720 800 880 960 1040 1120 1200
Time setting tg (s) Settings I2t Off 0 0.1 0.2 0.3 0.4
I2t On - 0.1 0.2 0.3 0.4
Time delay (ms) tg = max resettable time 20 80 140 230 350
at In or 1200 A (I2t Off or I2t On) tg = max break time 80 140 200 320 500
Accuracy: 0 to -20 %
Time delay Δt (ms) Settings 60 140 230 350 800
max resettable time 60 140 230 350 800
max break time 140 200 320 500 1000
A-15
Functions and characteristics www.schneider-electric.com
Measurements
A DB101134.eps
The Micrologic P control unit calculates in real time all the electrical values (V, A, W,
VAR, VA, Wh, VARh, VAh, Hz), power factors and cosj factors.
The Micrologic P control unit also calculates demand current and demand power
over an adjustable time period. Each measurement is associated with a minimeter
DB101133.eps
and a maximeter.
In the event of tripping on a fault, the interrupted current is stored. The optional
external power supply makes it possible to display the value with the circuit breaker
open or not supplied.
Instantaneous values
The value displayed on the screen is refreshed every second.
Display of a maximum Minimum and maximum values of measurements are stored in memory (minimeters
Default display.
current. and maximeters).
Currents
I rms A 1 2 3 N
A E-fault E-leakage
DB101133.eps
DB101133.eps
I max rms A 1 2 3 N
A E-fault E-leakage
Voltages
U rms V 12 23 31
V rms V 1N 2N 3N
U average rms V (U12 + U23 + U31) / 3
U unbalance %
Power, energy
P active, Q reactive, S apparent W, Var, VA Totals
E active, E reactive, E apparent Wh, VARh, Totals consumed - supplied
VAh Totals consumed
Totals supplied
Display of a voltage. Display of a power. Power factor PF Total
Frequencies
F Hz
DB101137.eps
DB101138.eps
Demand metering
The demand is calculated over a fixed or sliding time window that may be
programmed from 5 to 60 minutes. According to the contract signed with the power
supplier, an indicator associated with a load shedding function makes it possible to
avoid or minimise the costs of overrunning the subscribed power. Maximum demand
values are systematically stored and time stamped (maximeter).
Currents
I demand A 1 2 3 N
A E-fault E-leakage
I max demand A 1 2 3 N
A E-fault E-leakage
Display of a frequency. Display of a demand
Power
power. P, Q, S demand W, Var, VA Totals
P, Q, S max demand W, Var, VA Totals
No external power supply module is required (max. drift of 1 hour per year).
Reset
An individual reset, via the keypad or remotely, acts on alarms, minimum and
maximum data, peak values, the counters and the indicators.
Additional info
Accuracy of measurements (including sensors):
b voltage (V) 0.5 %
b current (A) 1.5 %
b frequency (Hz) 0.1 %
PME software. b power (W) and energy (Wh) 2 %.
A-16
www.schneider-electric.com
Functions and characteristics
Micrologic control units
Micrologic P "power"
DB117041.eps
DB101140.eps
displayed on the screen:
b tripping history:
v type of fault
v date and time
v values measured at the time of tripping (interrupted current, etc.)
b alarm history:
v type of alarm
v date and time
v values measured at the time of the alarm.
All the other events are recorded in a third history file which is only accessible
through the communication network. Display of a tripping Display after
b Event log history (only accessible through the communication network) history. tripping.
v modifications to settings and parameters
v counter resets
v system faults
v fallback position
v thermal self-protection
v loss of time
v overrun of wear indicators
v test-kit connections
v etc.
Note: all the events are time stampled: time-stamping is activated as soon as time is set manually
or by a supervisor. No external power supply module is required (max. drift of 1 hour per year).
Maintenance indicators with COM option (BCM ULP)
A number of maintenance indicators may be called up on the screen to better plan
for device maintenance:
b contact wear
b operation counter:
v cumulative total
v total since last reset.
Additional maintenance indicators are also available through the COM network,
and can be used as an aid in troubleshooting:
b highest current measured
b number of test-kit connections
b number of trips in operating mode and in test mode.
Additional technical characteristics
Safety
Measurement functions are independent of the protection functions. The high-accuracy
measurement module operates independently of the protection module.
Simplicity and multi-language
Navigation from one display to another is intuitive. The six buttons on the keypad
provide access to the menus and easy selection of values. When the setting cover is
closed, the keypad may no longer be used to access the protection settings, but still
provides access to the displays for measurements, histories, indicators, etc.
Micrologic is also multi-language, including the following languages: English,
Spanish, Portuguese, Russian, Chinese, French, German...
Intelligent measurement
Measurement-calculation mode:
b energies are calculated on the basis of the instantaneous power values, in two
manners:
v the traditional mode where only positive (consumed) energies are considered
v the signed mode where the positive (consumed) and negative (supplied) energies
are considered separately
b measurement functions implement the new “zero blind time” concept which consists
in continuously measuring signals at a high sampling rate. The traditional “blind
window” used to process samples no longer exists. This method ensures accurate
energy calculations even for highly variable loads (welding machines, robots, etc.).
Always powered
All current-based protection functions require no auxiliary source. Voltage-based
protection functions are connected to AC power via a voltage measurement input
built into the circuit breaker.
Stored information
The fine setting adjustments, the last 100 events and the maintenance register
remain in the control-unit memory even when power is lost.
A-17
Functions and characteristics www.schneider-electric.com
Metering
Control
Display
S1-1 - Lighting/Level1
Quick view
Alarms Measures
Open Auto
OK Control
I3 225 A IN 225 A
Using an IFE Ethernet interface for LV breakers.
Quick view I U-V PQS E
I Current
184 10 Measures
I1 431 A
A A Alarm history
Control
I2 385 A For all FDM, in addition to the information displayed on the Micrologic LCD, the FDM
I3 426 A
screen shows demand, power quality and maximeter/minimeter values along with
888
Maintenance IN 2 A
0 225 A
DB432518.eps
phases and neutral (Imax). The navigation buttons can be used to scroll through the
20.12.2011 12:00:05
I1= 186 A
0 225 A
0
I2= 179 A
225 A
S1-1 - Lighting/Level1
Alarm history
VL L
VL-L
V12 406 V
In the event of a fault trip, the trip cause is displayed.
IN= 10 A
Control
V23
V31
415
409
V
V The Micrologic A measures phase, neutral, ground fault currents.
The Micrologic E offers voltage, power, Power Factor, measurements in addition to
Maintenance
ESC 1/10
PQS 6/8
DB414402.eps
with a maximeter/minimeter. The maximeters for the highest current of the 3 phases
DB432519.eps
Qtot 85 kVAr S1-1 - Lighting/Level1 and neutral, the demand current and power can be reset via the FDM display unit or
Stot 138 kVA
Quick view
Measures
I
PQS
U-V PQS E
the communication system.
Ptot 127 kW
Alarm history
Control
Qtot
Stot
13 kVAr
129 kVA
Energy metering
Maintenance
ESC 1/12 The Micrologic E/P also measures the energy consumed since the last reset of the
meter. The active energy meter can be reset via Micrologic keypad or the FDM
display unit or the communication system.
FDM121 display: FDM128 display: power.
power.
Demand and maximum demand values
Micrologic E/P also calculates demand current and power values. These calculations
can be made using a block or sliding interval that can be set from 5 to 60 minutes in
FDM121
Energy 7/8
DB414403.eps
DB432520.eps
Ep 15 kwh 20.12.2011 12:00:05 steps of 1 minute. The window can be synchronised with a signal sent via the
Eq 12 kVArh S1-1 - Lighting/Level1 communication system. Whatever the calculation method, the calculated values can
be recovered on a PC via Modbus communication.
Quick view I U-V PQS E
Es 20 kVAh Measures
E cumul Reset
165 kWh
Ordinary spreadsheet software can be used to provide trend curves and forecasts
Alarm history
EpIn
EpOut 45 kWh
Control
Maintenance
based on this data. They will provide a basis for load shedding and reconnection
operations used to adjust consumption to the subscribed power.
ESC 1/3
A-18
www.schneider-electric.com
Functions and characteristics
Power Meter functions
Micrologic A/E/P control unit with COM option (BCM ULP)
and COM Ethernet gateway
PB104831_ME.eps
PB106351A13.eps
PB111801-32_r_1.eps
A
PB104842.eps
PB119233.eps
Micrologic A/E/P integrated Power Meter functions Type Display
A/E P Micrologic FDM display
LCD
Display of protection settings
Pick-ups (A) and All settings can be displayed Ir, tr, Isd, tsd, Ii, Ig, tg A/E P -
delays
Measurements
Instantaneous rms measurements
Currents (A) Phases and neutral I1, I2, I3, IN A/E P
Average of phases Iavg = (I1 + I2 + I3) / 3 A/E P -
Highest current of the 3 phases Imax of I1, I2, I3, IN A/E P
and neutral
Ground fault (Micrologic 6) % Ig (pick-up setting) A/E P
Current unbalance between % Iavg - /E P -
phases
Voltages (V) Phase-to-phase V12, V23, V31 - /E P
Phase-to-neutral V1N, V2N, V3N - /E P
Average of phase-to-phase Vavg = (V12 + V23 + V31) / 3 - /E P -
voltages
Average of phase-to-neutral Vavg = (V1N + V2N + V3N) / - /E P -
voltages 3
Ph-Ph and Ph-N voltage % Vavg and % Vavg - /E P -
unbalance
Phase sequence 1-2-3, 1-3-2 -/- P [3]
Maximeters / minimeters
Associated with instantaneous Reset via FDM display unit A/E P
rms measurements and Micrologic keypad
Energy metering
Energy Active (kW), reactive (kVARh), Total since last reset - /E P
apparent (kVAh)
Demand and maximum demand values
Demand current Phases and neutral Present value on the - /E P
(A) selected window
Maximum demand since last - /E P [2]
reset
Demand power Active (kWh), reactive (kVAR), Present value on the - /E P
apparent (kVA) selected window
Maximum demand since last - /E P [2]
reset
Calculation window Sliding, fixed or Adjustable from 5 to 60 - /E P - -
com-synchronised minutes in 1 minute steps [1]
[1] Available via the communication system only.
[2] Available for Micrologic P only.
[3] FDM121 only.
A-19
Functions and characteristics www.schneider-electric.com
Operating-assistance functions
Micrologic A/E/P control unit with COM option (BCM ULP)
Histories
b Trip indications in clear text in a number of user-selectable languages.
b Time-stamping: date and time of trip.
Maintenance indicators
Micrologic control unit have indicators for, among others, the number of operating
cycles, contact wear P, load profile and operating times (operating hours counter) of
the MasterPact circuit breaker.
It is possible to assign an alarm to the operating cycle counter to plan maintenance.
The various indicators can be used together with the trip histories to analyse the
level of stresses the device has been subjected to.
Micrologic measurement capabilities come into full play with the FDM121 switchboard display. It connects to COM
option (BCM ULP) via a breaker ULP cord and displays Micrologic information. The result is a true integrated unit
combining a circuit breaker and a Power Meter. Additional operating assistance functions can also be displayed. A
PB119233.eps
b low priority: no display on the screen.
All faults resulting in a trip automatically produce a high-priority alarm, without any special settings required. In all
cases, the alarm history is updated. Micrologic saves the information in its non-volatile memory in the event of an
FDM121 power failure.
Status indications and remote control
When the circuit breaker is equipped with the Breaker Status Module, the FDM121 display can also be used to
view circuit breaker status conditions:
b O/F: ON/OFF FDM121 display.
b SD: trip indication
b SDE: Fault-trip indication (overload, short-circuit, ground fault).
When the circuit breaker system is equipped with the I/O application module, the FDM121 can monitor and control:
b craddle management
b circuit breaker operation
PB103807-32.eps
Switchboard-display functions
Micrologic A/E/P control unit with COM option (BCM ULP)
A
The Micrologic connects to the internal communication terminal block on the MasterPact via the breaker ULP
cord. Connection to one of the RJ45 connectors on the FDM121 automatically establishes communication
FDM121
I 1/11
DB432521.eps
I1 225 A I2 225 A
186 179 between the Micrologic and the FDM121 and supplies power to the Micrologic measurement functions.
A A
When the second connector is not used, it must be fitted with a line terminator.
I3 225 A IN 225 A
184 10 Navigation
A A
888 Five buttons are used for intuitive and fast navigation.
The “Context” button may be used to select the type of display (digital, bargraph, analogue).
The user can select the display language (Chinese, English, French, German, Italian, Portuguese, Spanish, etc.).
Screens
1 2 3 4 5 6
Main menu
1 escape
When powered up, the FDM121 screen automatically displays the ON/OFF status of the device.
2 down
3 ok Quick view Alarms Metering Services Control
4 up When not in use, the screen is not backlit. Backlighting can be activated by pressing one of the buttons. It goes off
5 context after 3 minutes.
6 alarm LED
Fast access to essential information
Product ID
FDM121
2/8
b "Quick view" provides access to five screens that display a summary of essential operating information (I, U, f,
P, E, THD, circuit breaker On / Off).
DB432522.eps
Maintenance
Module Access to detailed information
SN
PN
3N114850015
TRV00911
b "Metering" can be used to display the measurement data (I, U-V, f, P, Q, S, E, THD, PF) with the corresponding
Version V1.0.9 min/max values.
b Alarms displays active alarms and the alarm history.
b Services provides access to the operation counters, energy and maximeter reset
b function, maintenance indicators, identification of modules connected to the internal bus and FDM121 internal
Product identification. settings (language, contrast, etc.).
FDM121
Communication components and FDM121 connections
Energy 7/8 24 V DC 24 V DC
DB432520.eps
Ep 15 kwh A Ethernet
DB432530.eps
Eq 12 kVArh B
Es 20 kVAh
IFM D
Metering: meter. D
IFE lin'X
IFE
Ener
FDM121
Metering Test
DB432523.eps
02
LV4340
V L-L V L-N E OR
PQS E
E C F
F PF COS F
OK C
Red Black White Blue Red Black White Blue
Metering: sub-menu.
E1 E2 E3 E4 E5 E6 E1 E2 E3 E4 E5 E6
B / Tx+ D1
A’ / Rx- D0
B’ / Rx+ D1
B / Tx+ D1
A’ / Rx- D0
B’ / Rx+ D1
24 V
0V
A / Tx- D0
24 V
0V
A / Tx- D0
FDM121
Load Profile
DB432524.eps
0...49% 19466Hours
50..79% 0Hours
80..89% 0Hours
Customer terminal block Customer terminal block
90.100% 0Hours
A-22
www.schneider-electric.com
Functions and characteristics
Switchboard-display functions
Micrologic A/E/P control unit with COM Ethernet gateway
Micrologic measurement capabilities come into full play with the FDM128 switchboard display. It connects to Ethernet
communication via RJ45 port and displays Micrologic information. The result is a true integrated unit combining a
circuit breaker and a Power Meter. Additional operating assistance functions can also be displayed. A
A-23
Functions and characteristics www.schneider-electric.com
Switchboard-display functions
Micrologic A/E/P control unit with COM Ethernet gateway
Navigation
A 20.12.2011
S1-1 - Lighting/Level1
12:00:05
DB414407.eps
20.12.2011
S1-1 - Lighting/Level1
12:00:05
Touch screen is used for intuitive and fast navigation.
The user can select the display language (Chinese, English, French, German,
Quick view Product ID Information Reset all Quick view Energy
Metering Maintenance.
DB414408.eps
20.12.2011 12:00:05
Control
S1-1 - Lighting/Level1
Alarm history
0 to 49%
50 to 79%
Control
80 to 89%
Maintenance 90 to 100%
ESC 2/3 When not in use, the screen is automatically shifted to low back-lighting.
Fast access to essential information
Services. b “Quick view” provides access to five screens that display a summary of essential
operating information (I, U, f, P, E, THD, circuit breaker On / Off).
Access to detailed information
b "Metering" can be used to display the measurement data (I, U-V, f, P, Q, S, E,
THD, PF) with the corresponding min/max values.
b Alarms displays the trip history.
b Services provides access to the operation counters, energy and maximeter reset
function, maintenance indicators, identification of modules connected to the internal
bus and FDM128 internal settings (language, contrast, etc.).
A-24
www.schneider-electric.com
Functions and characteristics
Protection of distribution systems
Micrologic control units for ComPact NS630b to 3200
External sensors
External sensor for earth-fault and neutral protection A
DB128050.eps
The sensors, used with the 3P circuit breakers, are installed on the neutral conductor
for:
b neutral protection (with Micrologic P)
b residual type earth-fault protection (with Micrologic A, E and P).
The rating of the sensor (CT) must be compatible with the rating of the circuit
breaker:
b NS630b to 1600 A - 400/1600 CT External sensor (CT).
b NS1600b to 3200 A - 1000/4000 CT.
Rectangular sensor for earth-leakage protection
The sensor is installed around the busbars (phases + neutral) to detect the zero-
059476_SE.eps
phase sequence current required for the earth-leakage protection. Rectangular
sensors are available in two sizes.
Inside dimensions (mm)
b 280 x 115 up to 1600 A for ComPact NS630b to 1600 A (L1)
b 470 x 160 up to 3200 A for ComPact NS1600b to 3200 A (L2).
External sensor for source ground return protection
The sensor is installed around the connection of the transformer neutral point to
earth and connects to the Micrologic 6.0 control unit via an MDGF module to provide External sensor for earth leakage protection.
the source ground return (SGR) protection.
Long-time rating plug
Four interchangeable plugs may be used to limit the long-time threshold setting
range for higher accuracy.
PB100773-32.eps
The time delay settings indicated on the plugs are for an overload of 6 Ir (for further
details, see the characteristics on page A-13 and page A-17).
As standard, control units are equipped with the 0.4 to 1 plug.
Setting ranges
Standard Ir = In x… 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1 Long-time rating plug.
Low-setting option Ir = In x… 0.4 0.45 0.50 0.55 0.60 0.65 0.70 0.75 0.8
High-setting option Ir = In x… 0.80 0.82 0.85 0.88 0.90 0.92 0.95 0.98 1
Off plug No long-time protection (Ir = In for Isd setting)
Important: long-time rating plugs must always be removed before carrying out insulation or
dielectric withstand tests.
Battery module
The battery module maintains display operation and communication with the
supervisor if the power supply to the Micrologic control unit is interrupted.
It is installed in series between the Micrologic control unit and the AD module.
Characteristics
b Battery run-time: 4 hours (approximately).
b Mounted on vertical backplate or symmetrical rail.
PB100771-24.eps
Spare parts
Lead-seal covers
A lead-seal cover controls access to the adjustment dials. Battery module.
When the cover is closed:
b it is impossible to modify settings using the keypad unless the settings lockout pin
PB100775-32.eps
A-25
Functions and characteristics www.schneider-electric.com
Power supplies
Test equipment
A Hand-held test kit
The hand-held mini test kit may be used to:
b check operation of the control unit and the tripping and pole-opening system by
sending a signal simulating a short-circuit
b supply power to the control units for settings via the keypad when the circuit
breaker is open (Micrologic P control units).
PB100837-68.eps
Characteristics
b Power supply AC-to-DC or DC-to-DC
b Output voltage: 24 V DC ±5 %.
b Output current: 1 A.
b DIN rail or platine Fixing with Acti9 form factor
b Conducted emissions power line: class B per EN 61000-6-3.
A-26
www.schneider-electric.com
Functions and characteristics
Power supplies
PF106349SE_ABL8RPS24050.eps
be connected phase-to-neutral or phase-to-phase.
They deliver a voltage that is precise to 3 %, whatever the load and whatever the
value of the AC supply, within the ranges 85 to 132 V AC and 170 to 550 V AC.
The Universal Phaseo ABL8 powers:
b circuit breaker communication module and interface.
Characteristics
b Power supply AC-to-DC.
b Network frequency: 50/60 Hz (±5 %).
b Output voltage: 24 V DC ±3%.
b Output current: 3 or 5 A. ABL8 RPS power supply
b DIN rail or platine Fixing.
b Conducted emissions power line: class B per EN 61000-6-3.
To assist cooling there must be sufficient clearance around the Universal range
Phaseo power supplies:
b 50 mm above and below
b 10 mm on the side.
ABL8RPSpppp Module AD
Over Voltage Category Cat I per VDE 0106-1 Cat IV per IEC 62477-1 (AC
model)
Cat III per IEC 62477-1 (DC
model)
Cat III per UL 61010-1
Degree of pollution 2 3
as per IEC 60664-1
Input supply voltage AC 100…120 V AC and 110/130 or 200/240 V AC
200…500 V AC
Input supply voltage DC N/A 24/30 or 48/60
or 100/125 V DC
Dielectric Input/Output 4 kV rms -1 mn. 3 kV rms - 1 mn.
(110/130 V AC and
200/240 V AC model)
3 kV rms - 1 mn.
(110/125 V DC model)
2 kV rms - 1 mn. (24/30 V DC
and 48/60 V DC model)
Input/Ground 3.5 kV rms -1 mn. 3 kV rms - 1 mn.
Ouput /Ground 0,5 kV rms - 1 mn. 1.5 kV rms - 1 mn.
Temperature b 50 °C 70°C
b 60 °C with 80 % of
the rated current
maximum
Output current 3 A (ABL8RPS24030) 1A
5 A (ABL8RPS24050)
Inrush current for 2 ms < 30 A < 20 A
Ripple 200 mV peak-peak 200 mV peak-peak
Output voltage limits 24 to 28.8 V DC 22.8 to 25.2 V DC
A-27
Functions and characteristics www.schneider-electric.com
Ethernet has become the universal link between switchboards, computers and
Enerlin'X communication system provides communication devices inside the building. The large amount of information which
DB406689-55.eps
Main switchboard
Module SL
E E
E E
F D
ComPact NS
+ Micrologic F
logic
ComPact + Micro
H
B
Internet
Ethernet
A
Energy Server
DB406688-302.eps
H
Ethernet
Modbus
ULP
Hard wired
Sigle Wireless IEEE 802.15.4
A-28
www.schneider-electric.com
Functions and characteristics
Enerlin’X communication system
Products overview
A Com'X 510
24 V DC + PoE
Energy server +
Ethernet Gateway
Zigbee
(to wireless
32 Modbus
devices +
- EBX510
E
I/O Input/Output ULP ULP 6 binary 3 LV434063
application 1 analog
F
module (PT100 sensor)
for circuit breaker
G
wireless Modbus slave & Wireless to
devices PowerTag
H
functions
Ethernet Gateway or Interface: routes an internal traffic (ULP or other protocole) to the Internet, the outgoing messages are coded
with Modbus TCPIP protocol.
Server (Switchboard, Energy): routes the internal traffic to the Internet. Other complementary functions such as data logging and storage.
Provides devices status and energy trends on internal web pages...
A-29
Functions and characteristics www.schneider-electric.com
Communication
Communication wiring system
A The wiring system is designed for low-voltage power switchboards. Installation requires no tools or special skills.
The prefabricated wiring ensures both data transmission (Modbus protocol) and 24 V DC power distribution for
the communications modules on the Micrologic control units.
PB119237.eps
G
A
E
C F
Q
H
I P
L
K P L N D
A BCM ULP: Breaker Communication Module with ULP port L IFE: Ethernet interface LV434001 or LV434002
M External 24 V DC power supply module
B Micrologic control unit
0.35 m LV434195 N IFM: Modbus-SL interface LV434000
C Breaker ULP cord
1.3 m LV434196 O Com'X 210
3m LV434197 ULP cable 0.3 m TRV00803
5m LV434198
P
0.6 m TRV00806
D Modbus cable 1m TRV00810
Ethernet cable 2m TRV00820
E
3m TRV00830
F FDM121: Front Display Module TRV00121
5m TRV00850
G FDM128: Front Display Module LV434128
Q NSX cord 0.35 m LV434200
H Smartlink A9XMSB11 1.3 m LV434201
Acti9 3m LV434202
I Ethernet
J ULP line terminators TRV00880 Modbus
K I/O (Input/Output) application module LV434063 ULP
24 V DC
A-30
www.schneider-electric.com
Functions and characteristics
Communication
Overview of functions
PB104863.eps
Switch- Circuit
disconnectors breaker
Status indications
ON/OFF (O/F) S A E P
Spring charged CH S A E P
Ready to close S A E P
Fault-trip SDE S A E P
Connected / disconnected / test position S A E P
CE/CD/CT (I/O application module only) S A E P
Controls
MX open release S A E P
Closing release S A E P
Measurements
Instantaneous measurement information A E P
Averaged measurement information E P
Maximeter / minimeter A E P
Energy metering E P
Demand for current and power E P
Power quality
Operating assistance
Protection and alarm settings A E P
Histories A E P
Time stamped event tables A E P
Maintenance indicators A E P
S: Micrologic without measurement.
Modbus principle A: Micrologic with ammeter
The Modbus RS 485 (RTU protocol) system is an open bus on which communicating Modbus
devices (ComPact NS with Modbus COM, Power Meter PM700, PM800, Sepam, Vigilohm, E: Micrologic "Energy"
ComPact NSX, etc.) are installed. All types of PLCs and microcomputers may be connected to P: Micrologic "Power"
the bus.
Note: see the description of the Micrologic control units for
Addresses further details on protection and alarms, measurements,
The Modbus communication parameters (address, baud rate, parity) are entered using the waveform capture, histories, logs and maintenance
keypad on the Micrologic A, E, P, H. For a switch-disconnector, it is necessary to use the indicators.
Electrical Asset Manager or RSU (Remote Setting Utility) Micrologic utility.
Number of devices
The maximum number of devices that may be connected to the Modbus bus depends on the
type of device (ComPact with Modbus COM, PM700, PM800, Sepam, Vigilohm, ComPact
NSX, etc.), the baud rate (19200 is recommended), the volume of data exchanged and the
desired response time. The RS 485 physical layer offers up to 32 connection points on the bus
(1 master, 31 slaves).
A fixed device requires only one connection point (communication module on the device). A
drawout device uses two connection points (communication modules on the device and on the
chassis).
The number must never exceed 31 fixed devices or 15 drawout devices.
Length of bus
The maximum recommended length for the Modbus bus is 1200 meters.
Bus power source
A 24 V DC power supply is required (less than 20 % ripple, insulation class II).
Ethernet principle
Ethernet is a data link and physical layer protocol defined by IEEE 802 10 and 100 Mbps
specifications that connects computer or other Ethernet devices. Ethernet is an asynchronous
Carrier Sense Multiple Access with Collision detection (referred as CSMA/CD) protocol. Carrier
Sense means that the hosts can detect whether the medium (coaxial cable) is idle or busy.
Multiple Access means that multiple hosts can be connected to the common medium. Collision
Detection means a host detects whether its transmission has collided with the transmission of
another host (or hosts).
IFE Ethernet interface can be connected to a PC or a laptop over Ethernet. The maximum
length of Ethernet cable is 100 meters. IFE Ethernet interface + gateway provides a Modbus
TCP/IP gateway over Ethernet to enable Modbus TCP communication from a Modbus TCP
master to any Modbus slave devices connected to it. The maximum active Modbus TCP client
connection is twelve.
IFE Ethernet interface has an embedded web server (web page).
The Modbus RS 485 (RTU protocol) system is an open bus on which communicating Modbus
devices (ComPact NS with Modbus COM, Power Meter PM700, PM800, Sepam, Vigilohm,
ComPact NSX, etc.) are installed. All types of PLCs and microcomputers may be connected to
the bus.
A-31
Functions and characteristics www.schneider-electric.com
Communication
COM option in ComPact
All the ComPact devices can be fitted with the communication function thanks to the COM option. ComPact uses the
A Ethernet or Modbus communications protocol for full compatibility with the supervision management systems.
Eco COM is limited to the transmission of metering data and status. It is not used to communicate controls.
its set of sensors (OF, SDE, PF and CH micro switches) its kit for connection to
communicating voltage releases and its COM terminal block (inputs E1 to E6).
b IFM, this module required for connection to the network, contains the Modbus
address (1 to 99) declared by the user via the two dials in front. It automatically
adapts (baud rate, parity) to the Modbus network in which it is installed.
Or
b IFE, the Ethernet interface for LV circuit breaker enables an intelligent modular
unit (IMU), for example a ComPact NS circuit breaker to be connected to an Ethernet
network. Each circuit breaker has its own IFE and a corresponding IP address.
BCM ULP. b I/O (Input/Output) application module for LV breaker, the I/O application module is
delivered with withdrawable devices ordered with the COM option, for cradle
management. It must be installed on a DIN rail near the device. It must be connected
to the ULP system and to the position contacts (CD, CT, CE) that transmit the
position of the device in the cradle.
BCM ULP module
PB119234.eps
This module is independent of the control unit. It receives and transmits information
on the communication network. An infra-red link transmits data between the control
unit and the communication module.
Consumption: 30 mA, 24 V.
XF and MX1 communicating voltage releases
The XF and MX1 communicating voltage releases are equipped for connection to
the “device” communication module.
The remote-tripping function (MX2 or MN) are independent of the communication
option. They are not equipped for connection to the “device” communication module.
A-32
www.schneider-electric.com
Functions and characteristics
Communication
Communication architecture
Electrical operated
Fixed device
Ethernet Modbus
Drawout devices
Ethernet Modbus Ethernet Modbus A
DB424563.eps
DB432533.eps
DB432532.eps
J K J K
I J
IFE IFE
in'X IFE in'X
Enerl in'X Enerl
Enerl
02 02
LV4340 02 LV4340
LV4340
Test
Test
Test
or or
or
ULP system C
I6
I4
I5
C
I6
I5 C
I4 I3
C I2
I3 C
I2 I1
C
I1 + C
+ 24VD
C
24VD
A1
A1
O1
O1 I1
I1 O2
O2 I2
I2 O3
O3 I3
I3 APP
APP
I4
I4 I5
I5
I6
I6
G
4063
4063 LV43
LV43
IO IO
I I
A1
A1 T2
O3 T1
T2
O3 T1 34
O2 33
34
O2 33 24
O1 23
24
O1 23 14
14 13
13
H H
G G
B E E
A D1 C C B
B F
A A D2
Manually operated fixed device Manually operated withdrawable device Electrically operated withdrawable device
A-33
Functions and characteristics www.schneider-electric.com
General characteristics
A
DB419230.eps
Environmental characteristics
24VDC
DB425732_1.eps
Immunity to surges Conforming to IEC/EN 61000-4-5
Consumption 120 mA at 24 V input ETH1 ETH2
Physical characteristics
Dimensions 72 x 105 x 71 mm (2.83 x 4.13 x 2.79 in.)
Mounting DIN rail Enerlin'X IFE
IFE-XX.YY.ZZ (factory set)
C
Weight 182.5 g (0.41 lb) ETH1 LK/10-100/ACT
Degree of protection of the installed b On the front panel (wall mounted ETH2 LK/10-100/ACT
Module Status
D
IO enclosure): IP4x Modbus-SL
Network Status
b Connectors: IP2x T E
LV434001
Function
A IFM - Modbus communication interface - is required for connecting
MasterPact or ComPact NS and NSX to Modbus network whenever the circuit
breaker has an ULP port (Universal Logic Plug). The port is available
on BCM ULP for MasterPact range and BSCM module for ComPact range.
Note: IFM is defined as an IMU (Intelligent Modular Unit) in the ULP connection System
documentation.
PB119111.eps
Once connected to IFM, the circuit breaker is considered as a slave by the Modbus
master. Its electrical values, alarm status, open/close signals car be monitored
or controlled by a Programmable Logic Controller or any other system.
Characteristics
ULP port
2 RJ45 sockets, internal parallel wiring.
b Connection of a single circuit breaker (eventually via its I/O application module).
IFM Modbus communication interface. b An ULP line terminator or FDM121 display unit must be connected
Ref.: LV434000. to the second RJ45 ULP socket.
The RJ45 sockets deliver a 24 V DC supply fed from the Modbus socket.
Built-in test function, for checking the correct connection to the circuit breaker
and FDM121 display unit.
Modbus slave port
b Modbus SL RJ45 port - RJ45 connector ensures fast and reliable wiring.
b Lateral socket, for Din-rail stackable connector.
Both top and lateral sockets are internally parallel wired.
b Multiple IFM can be stacked, thus sharing a common power supply and Modbus
line without individual wiring.
b On the front face:
v Modbus address setting (1 to 99): 2 coded rotary switches
v Modbus locking pad: enables or disable the circuit breaker remote control
and modification of IFM parameters.
b Self adjusting communication format (Baud rate, parity).
24 V DC power supply
b Screw clamp terminal block
v High electrical insulation between Modbus and 24 V DC connectors + separated
lines ensure improved communication robustness.
A B
DB424558.eps
Mo
dbu
s
0V
24V
C
5 6
4 7
3 8
x10
2 9
1 0
5 6
4 7
3 8
x1
D
2 9
1 0
COM
E
1
COM
F
G
J I H
A-36
www.schneider-electric.com
Functions and characteristics
IFM Modbus communication interface
Technical characteristics
IFM Modbus communication interface
A
Dimensions 18 x 73 x 90 mm
Maximum number of stacked IFM 12
Degree of protection Part projecting beyond IP4x
of the installed the escutcheon
module Other module parts IP3x
Connectors IP2x
Operating -25...+70 °C
temperature
Power supply 24 V DC -20 %/+10 % (19.2...26.4 V
voltage DC)
Consumption Typical 21 mA/24 V DC at 20 °C
Maximum 30 mA/19.2 V DC at 60 °C
Certification
CE IEC/EN 60947-1
UL UL 508 - Industrial Control Equipment
CSA No. 142-M1987 - Process Control
Equipment
b CAN/CSA C22.2 No. 0-M91 -
General requirements - Canadian
Electrical Code Part
b CAN/CSA C22.2 No. 14-05 -
Industrial Control Equipment
DB424559.eps
Test
Test
Test
Test Test
Test Test
Test Test
IFE
lin'X
Ener
002
LV434
A-37
Functions and characteristics www.schneider-electric.com
Connect the IFE to a fixed manual operated Connect the IFE to a drawout ComPact NS or circuit breaker using
ComPact NS or circuit breaker using the the breaker ULP cord
A breaker ULP cord
Ethernet Ethernet
DB432534.eps
DB424557.eps
24 Vdc 24 Vdc
I6
C
I5
I4
C
I3
I2
C
I1
+ C
24VD
IFE IFE
A1
lin'X lin'X
Ener Ener O1
K
I1
O2
I2
O3
I3
APP
I4
I5
I6
02 02
LV4340 LV4340
63
LV4340
A A IO
33
O3
34
T1
A1
T2
O2
24
O1 23
14
13
B
B
J
I
D H
D
E
E
G
A IFE Ethernet interface for LV circuit breaker A IFE Ethernet interface for LV circuit breaker
B Breaker ULP cord B ULP cable
C Fixed terminal block C Breaker ULP cord
D BCM ULP communication module D Circuit breaker disconnected position contact (CD)
E Fixed electrically operated circuit breaker E Circuit breaker cradle
F BCM ULP communication module
G Drawout circuit breaker
H Drawout terminal block
I Circuit breaker connected position contact (CE)
J Circuit breaker test position contact (CT)
K I/O (Input/Output) application module for LV circuit breaker
A-38
www.schneider-electric.com
Functions and characteristics
Connection of the IFM to a fixed or drawout ComPact NS
DB424564.eps
This module, required for connection to the network, contains the Modbus address
(1 to 99) declared by the user via the two dials in front. It automatically adapts (baud
rate, parity) to the Modbus network in which it is installed.
It is equipped with a lock-out switch to enable or disable operations involving writing 6
B
5
4 7
3 8
x10
to Micrologic, i.e. reset, counter reset, setting modifications, device opening and
2 9
1 0
C
5 6
4 7
3 8
x1
2 9
1 0
COM
D Test
There is a built-in test function to check the connections of the Modbus interface Test
E
Test
F
Mounting G
The module is mounted on a DIN rail. A number of modules may be clipped one next
to the other. For this, a stacking accessory is available for fast clip-connection of both A Five-point Modbus and 24 V DC connector
the Modbus link and the 24 V DC supply. B Two Modbus address dials (1 to 99)
The Modbus interface module supplies 24 V DC to the corresponding Micrologic, C Modbus traffic LED
FDM121 display and BSCM module. Module consumption is 60 mA / 24 V DC. D Lock-out to disable writing to the NSX
E Test LED
F Test button
DB424568.eps
Connect the IFM to a fixed manual operated Connect the IFM to a drawout ComPact NS or circuit breaker using
ComPact NS or circuit breaker using the the breaker ULP cord
breaker ULP cord Modbus
Modbus
DB432535.eps
DB425864.eps
I6
C
I5
I4
C
I3
I2
C
I1
+ C
24VD
A1
O1
I1
O2
K
I2
O3
I3
APP
I4
I5
I6
63
LV4340
IO
A1
T2
O3 T1
34
A
O2 33
24
O1 23
14
Test
13
A
Test
B
C
J
I
D H
E
D
F
E G
A IFM Ethernet interface for LV circuit breaker F BCM ULP communication module
B ULP cable G Drawout circuit breaker
A IFM Ethernet interface for LV circuit breaker
C Breaker ULP cord H Drawout terminal block
B Breaker ULP cord
D ircuit breaker disconnected position
C I Circuit breaker connected position contact (CE)
C Fixed terminal block J
contact (CD) Circuit breaker test position contact (CT)
D CM ULP communication module
B K I/O (Input/Output) application module for LV
E E Circuit breaker cradle
Fixed electrically operated circuit breaker circuit breaker
A-39
Functions and characteristics www.schneider-electric.com
The I/O application module is compliant with the ULP system specifications.
Two I/O application module can be connected in the same ULP network.
The ranges of LV circuit breakers enhanced by the I/O application module are:
b MasterPact
b ComPact NS1600b-3200
b ComPact NS630b-1600
b ComPact NSX100-630 A.
I/O application module
Pre-defined applications
Pre-defined application adds new functions to the IMU in a simple way:
b selection by the application rotary switch on the I/O application module, defining
5 the application with pre-defined input/output assignment and wiring diagram.
4 6
b no additional setting with the Ecoreach software required.
DB419578.eps
3 7 The resources not assigned to the pre-defined application are free for additional
2 8 user-defined applications:
1 9 b cradle management
APP b breaker operation
b light and load control
b custom.
DB419579.eps
DB419580.eps
User-defined applications
User-defined applications are processed by the I/O application module in addition to
the pre-defined application selected.
The user-defined applications are available depending on:
b the pre-defined application selected
b the I/O application module resources (inputs and outputs) not used by the
application.
The resources required by user-defined applications are assigned using the
Ecoreach software:
b protection
b control
b energy management
b monitoring.
Mounting
The I/O application module is a DIN rail mounting device.
A-40
www.schneider-electric.com
Functions and characteristics
I/O application module
General characteristics
Environmental characteristics
Conforming to standards UL 508, UL 60950, IED 60950, 60947-6-2
A
DB419233.eps
Certification cUIUs, GOST, FCC, CE
Ambient temperature -20 to +70 °C (-4 to +158 °F)
Relative humidity 5–85 %
Level of pollution Level 3 I1 C I2 I3 C I4 I5 C I6
DB432536.eps
Immunity to surges Conforming to IEC/EN 61000-4-5 24VDC I1 C I2 I3 C I4 I5 C I6
Consumption 165 mA
Physical characteristics C
Dimensions 71.7 x 116 x 70.6 mm (2.83 x 4.56 x 2.78 in.) M 3
4 5 6
7 I1
AI
D
Mounting DIN rail
2 8
1 9 I2
L E
APP
I3 O1
K
O3
Degree of protection of the On the front panel (wall mounted enclosure): IP4x T
I6
F
installed I/O application IO parts: IP3x J IO LV434063 G
module Connectors: IP2x
Connections Screw type terminal blocks
Technical characteristics - 24 V DC power supply 13
O1
14 23
O2
24 33
O3
34 T1
A1
T2
Digital input type Self powered digital input with current limitations as
per
IEC 61131-2 type 2 standards (7 mA) 1
2
Introduction
A Electrical Asset Manager is a software application that helps the user to manage a
project as part of designing, testing, site commissioning, and maintenance of the
project life cycle.
It enables the user to prepare the settings of the devices offline (without connecting
to the device) and configure them when connected with the devices.
Also it provides lot of other value added features for the user to manage the project
Capture1b.eps
such as, safe repository in cloud, attach artifacts to each device or at the project
level, organize devices in switchboard wise, manage a hierarchical structure of the
installation etc.
References:
Electrical Asset Manager software package can be downloaded from our website
www.schneider-electric.com.
Features
Capture3b.eps
b generate and print device settings report and communication test report
b manage multiple devices with electrical and communication hierarchy model
b manage artifacts (project documents)
b check consistency in settings between devices on a communication network
b compare configuration settings between PC and device (online)
b download latest firmware.
Electrical Asset Manager enables the user to avail the advanced features of the
software once the project is saved in Schneider Electric cloud.
A-42
www.schneider-electric.com
Functions and characteristics
Electrical Asset Manager Configuration Engineering tool
Functions
Offline Mode A
A project can be built in offline mode through 2 different ways:
b through BOM file import
b through Device Selection.
Capture5b.eps
Additionally, the user can open an existing project and modify the settings offline.
The user can do the selectivity curve check and firmware compatibility check for
devices in the project.
Online Mode
A project can be built in online mode through device discovery also other than the
methods possible through offline method.
Once the project is built, the following functions can be performed in addition to the
functions available in offline mode:
b compare the device parameters with project parameters
b load parameters from project to the device and vice versa
Capture6b.eps
b firmware downloads to the device
b monitor the measurement, maintenance, device status and I/O status
b control functions.
User Interface
Electrical Asset Manager software provides fast direct access to the project and the
devices in the project through different tabs.
b Project: to provide the project information including customer details, project
references and to add project artifacts (documents related to the project).
b Configuration: to build up the tree structure of the project architecture ; to have a
table view of the devices added in the project ; to set the parameters of the devices ;
to transfer the device settings ; to view the tripping curves; to attach device artifacts
Capture7b.eps
and to download the latest firmware, to do the communication test for all the devices
and generate the test report.
b Monitoring: this allows the user to monitor the real time values of different devices
through different sub tabs namely Monitoring, Logs and Control.
b Reports: report tab allows you to generate and print a report of the project settings
from the report tab. The user details and project characteristics are automatically
filled with the details entered in the Project page.
Capture8b.eps
A-43
Functions and characteristics www.schneider-electric.com
Motor protection
Overview of solutions
The circuit breakers presented here provide protection against short circuits and are suitable for isolation as defined by
A standard IEC 60947-2. For complete protection of the motor and its control device, overload protection may be provided
by either the circuit breaker or a separate Schneider Electric thermal relay. The control device may be of the direct on-
line type (with or without reversing) or of the “star-delta” type. Combinations are governed by standard IEC 60947-4.1.
Breaking N 50
capacity (kA rms) H 70
380/415 V L 150
A-44
www.schneider-electric.com
Functions and characteristics
Earth-leakage protection
Overview of solutions
PB104831_ME.eps
PB104845_ME.eps
A-45
Functions and characteristics www.schneider-electric.com
A
DB425818.eps
Final
distribution
enclosure
for
commercial
applications
LV devices
Acti 9 NG125 EasyPact ComPact NS MasterPact MTZ1 Micrologic ComPact INS ComPact INV FuPact INF
ComPact ComPact ComPact MasterPact MTZ2 MasterPact ComPact Source-changeover FuPact FuPact
NSX NSX DC NS NW DC INS/INV ISFT ISFL
A-46
www.schneider-electric.com
Functions and characteristics
Control and isolation
Overview of solutions
ComPact switch-disconnectors are used to control and isolate electrical distribution circuits. In addition to these basic
functions, other functions for safety, remote control and convenience include:
b earth-leakage protection A
b auxiliary MN/MX releases
b remote operation.
ComPact switch-disconnectors may be interlocked with another ComPact switch-disconnector or circuit breaker to
constitute a source-changeover system.
PB104837.eps
A-47
Functions and characteristics www.schneider-electric.com
A
ComPact switch-disconnectors
Number of poles
PB104837_1.eps
A-48
www.schneider-electric.com
Functions and characteristics
Control and disconnection
ComPact NS630bNA to 1600NA switch-disconnectors
A
NS630bNA NS800NA NS1000NA NS1250NA NS1600NA
3, 4 3, 4 3, 4 3, 4 3, 4
25 25 25 25 25
4 4 4 4 4
3 3 3 3 3
A-49
Functions and characteristics www.schneider-electric.com
Installation standards require upstream protection. However, ComPact NS1600b to 3200NA switch-disconnectors
ComPact switch-disconnectors
Number of poles
Control manual toggle
direct or extended rotary handle
electric
Connections fixed front connection
rear connection
withdrawable (on chassis) front connection
rear connection
Electrical characteristics as per IEC 60947-3 and EN 60947-3
Conventional thermal current (A) Ith 60 °C
PB104838.eps
A-50
www.schneider-electric.com
Functions and characteristics
Control and disconnection
ComPact NS1600bNA to 3200NA switch-disconnectors
A
NS1600bNA NS2000NA NS2500NA NS3200NA
3, 4 3, 4 3, 4 3, 4
- - - -
- - - -
- - - -
- - - -
- - - -
3 3 3 3
A-51
Functions and characteristics www.schneider-electric.com
Source-changeover systems
Presentation
Some installations use two supply sources to counter the temporary loss of the main
supply.
PB191613-50.eps
A-52
www.schneider-electric.com
Functions and characteristics
Source-changeover systems
Manual source-changeover systems
A manual source-changeover system can be installed on two to three manually-operated circuit breakers or switch-
disconnectors. Interlocking is mechanical. Interlocks prevent connection to both sources at the same time, even
momentarily. A
PB113831.eps
The mechanism inhibits the two devices being closed at the same time, but does
allow for both to be open (OFF) at the same time.
Combinations of "Normal" and "Replacement" devices
All ComPact NS630b to 1600 circuit breakers and switch-disconnectors with rotary
handles can be interlocked.
Interlocking of a ComPact NS630b with a ComPact NS630b to 1600 is not possible.
Interlocking of a number of devices using keylocks
(captive keys)
Interlocking with keylocks.
Interlocking uses two identical keylocks with a single key. This solution enables
interlocking between two devices that are physically distant or that have significantly
different characteristics, for example between a low and a medium-voltage device,
or between ComPact NS circuit breakers and switch-disconnectors.
PB113832.eps
A system of wall-mounted units with captive keys makes possible a large number
of combinations between many devices.
Combinations of Normal and Replacement devices
All ComPact NS630b to 1600 circuit breakers and switch-disconnectors with rotary
handles or motor mechanisms can be interlocked.
Interlocking of two ComPact NS630b to 1600 devices using
connecting rods
The two devices must be mounted one above the other (either 2 fixed or 2
withdrawable/drawout devices). Interlocking of two devices with rotary handles.
Installation
This function requires:
b an adaptation fixture on the right side of each circuit breaker or switch-disconnector
b a set of connecting rods with no-slip adjustments.
DB128465.eps
DB417641.eps
The adaptation fixtures, connecting rods and circuit breakers or switch-
disconnectors are supplied separately, ready for assembly by the customer. O
FFO
h sup
O
FFO
h sup
The maximum vertical distance between the fixing planes is 900 mm.
NO h
I I
NO h
sup sup
FFO
O FFO
O
degr degr
ahcs ahcs
id id
I
O
FFO
hsup
side-by-side.
NO h NO h
sup sup
FFO
O FFO
O
degr degr
ahcs ahcs
id id
The interlocked devices may be fixed or drawout, three-pole or four-pole, and have
different ratings and sizes.
Installation Interlocking with Interlocking with cables.
This function requires: connecting rods.
b an adaptation fixture on the right side of each device
b a set of cables with no-slip adjustments.
The maximum distance between the fixing planes (vertical or horizontal) is 2000 mm.
A-53
Functions and characteristics www.schneider-electric.com
Electrical interlocking
IVE unit
Electrical interlocking is used with a mechanical interlocking system. Morover, the relays controlling the closing order
A to the "S1" and "S2" circuit breakers must be mechanically and/or electrically interlocked to prevent them from giving
simultaneous closing commands.
PB119174_48.eps
IVE unit.
For ComPact NS630b to NS1600, each circuit breaker must be
equipped with:
b a motor mechanism
b an available OF contact
b a CE connected-position contact (carriage switch) on withdrawable circuit breakers
b an SDE contact.
Standard configuration for ComPact NS
Types of mechanical Possible Typical electrical Diagram
interlocking combinations diagrams no.
2 devices
QN QR ComPact NS630b to
1600:
DB424569.eps
0 0 b electrical interlocking
with lockout after fault:
0 1 v Permanent replacement 51201183 [1]
source (with IVE)
0 1 v with emergency off 51201184 [1]
by shunt release MX
v with emergency off by 51201185 [1]
undervoltage release MN
[1] See catalogue "Source changeover systems", ref. LVPED211022EN.
A-54
www.schneider-electric.com
Functions and characteristics
Electrical interlocking
Remote-operated systems
DB128465.eps
DB417641.eps
PB100857_16_SE.eps
O
FFO
O
h sup FFO
h sup
NO h
I I
NO h
sup sup
FFO
O FFO
O
degr degr
ahcs ahcs
id id
DB403810R.eps
A B
NO h
I I
NO h
sup sup
A-55
Functions and characteristics www.schneider-electric.com
Source-changeover systems
Associated controllers
A possible to automatically control source transfer according to user-selected sequences. These controllers can be
used on source-changeover systems comprising 2 circuit breakers. For source-changeover systems comprising 3
circuit breakers, the automatic control diagram must be prepared by the installer as a complement to to diagrams
provided in the “electrical diagrams” section of this catalogue.
Controller BA UA
DB403809.eps
4-position switch
Compatible circuit breaker All ComPact NS circuit breaker
Automatic operation
Forced operation on "Normal" source
Forced operation on "Replacement" source
Stop (both Normal and Replacement sources OFF)
Automatic operation
Monitoring of the "Normal" source
and automatic transfer
Generator set startup control
BA controller. Delayed shutdown (adjustable) of engine generator set
Load shedding and reconnection of non-priority circuits
Transfer to the “Replacement” source if one of the phases
DB403810.eps
Test
By opening the P25M circuit breaker supplying
the controller
By pressing the test button on the front of the controller
Indications
Circuit breaker status indication on the front
of the controller: on, off, fault trip
Automatic mode indication contact
Other functions
UA controller
Selection of type of "Normal" source
[1] For example, 220 V single-phase or 220 V three-phase. (single-phase or three-phase) [1]
[2] The controller is powered by the ACP control plate. The Voluntary transfer to "Replacement" source
same voltage must be used for the ACP plate, the IVE unit
(e.g. energy-management commands)
and the operating mechanisms. If this voltage is the same
as the source voltage, then the "Normal" and "Replacement" During peak-tariff periods (energy-management
sources can be used directly for the power supply. If not, an commands) forced operation on "Normal" source if
isolation transformer must be used. "Replacement" source not operational
A-56
www.schneider-electric.com
Functions and characteristics
Source-changeover systems
Associated controllers
Controller BA UA
IP degree of protection (EN 60529) and IK degree of protection
against external mechanical imPacts (EN 50102)
Front IP40
Side IP30
Connectors IP20
Front IK07
Characteristics of output contacts (dry, volt-free contacts)
Rated thermal current (A) 8
Minimum load 10 mA at 12 V
Output contacts:
Position of the Auto/Stop switch
Load shedding and reconnection order
Generator set start order
AC DC
Utilisation category (IEC 60947-5-1) AC12 AC13 AC14 AC15 DC12 DC13
Operational current (A) 24 V 8 7 5 6 8 2
48 V 8 7 5 5 2 -
110 V 8 6 4 4 0.6 -
220/240 V 8 6 4 3 - -
250 V - - - - 0.4 -
380/415 V 5 - - - - -
440 V 4 - - - - -
660/690 V - - - - - -
A-57
Functions and characteristics www.schneider-electric.com
A B D
A2 D1
A
A1 A3
B C
DB432537.eps
C1 D2
C2
E
E1
E2
5.0 E
Micr ologic
I ON
push
O OFF
push
H
NS 1200Uimp 12kV
Ui 1000V
8kV
Uimp Icu
arged Ue (kA)
disch 100 % (V) 100
40 85
220/2
90
O OFF 480/6
100%
Icu
40 % Ics =
menu
E3
alar m
tim e tr 8 12
long
(s) 4 16
Ir .8 .9
.7 2 20
.95
.6 1 24
.98 .5 at 6 Ir eous
.5 1 instantan
.4 x In Ii 8 10
6 12
tsd .4 .4 .3
e
t tim
shor
.2 4 15
(s)
Isd3 4 5 .3 .1 3 off
6 2
2.5
.2 0 x In
8 .1 2
2 I t
10 on
1.5 delay
x Ir
53
setting
012
B B F
I H G
G1 G2 G3
I1 H1
I on
ed
tripp
t
r es e
0 OFF
'X IFE
Enerlin
tripped
reset
4002
LV43
Test
I2 H2
I on
tripp
r es e
ed
t
G4 G5
0 OFF
A-58
www.schneider-electric.com
Functions and characteristics
Electrical and mechanical accessories
ComPact NS630b to 1600 (withdrawable version)
A D E
A2 D1 D2 D3
A
DB432538.eps
E1
A1 A3
Enerlin
'X IFE
E2
4002
LV43
Test
B C
C1
E3
C2 D4 D5
5.0 E
Micr ologic
5.0 E
Micr ologic
I
push
ON H
O NS 1200Uimp 12kV
push
OFF H Ui 1000V
NS 1200Uimp 12kV Uimp
8kV
Icu
Ui 1000V Ue (kA)
Uimp
8kV 100 % (V) 100
Icu 40 85
220/2
Ue (kA) 90
100 %
480/6
arged (V) 100 Icu
disch 40 85 100%
220/2
90 40 % Ics =
480/6
O OFF
Icu
100%
40 % Ics =
947-2 UNE NEMA
IEC CEI
BS
UTE VDE
947-2 UNE NEMA
IEC CEI
UTE VDE BS menu
alar m
menu tim e tr 8 12
long
(s) 4 16
Ir .8 .9
alar m .7 2 20
.95
.6 1 24
tim e tr 8 12 .98 .5 at 6 Ir eous
long
(s) 4 16 .5 1 instantan
Ir .8 .9 .4 x In
.7 2 20 Ii 8 10
.95 6 12
tsd .4 .4 .3
1 24 t tim
e
.6 .98 4
.5
.5 at 6 Ir
instantan
eous shor
(s) .2 15
1 Isd3 4 5
.4 x In Ii 8 10 .3 .1 3
2
off
6
6 12 .2 x In
tsd .4 .4 .3
e 2.5 8 0
shor
t tim
.2 4 15 2
.1 2
I t
(s) on
10
Isd3 4 5 .3 .1 3 off 1.5 delay
6
.2 2 x Ir
2.5 8 0 x In setting
2
.1 2
I t
10 on
1.5 delay
x Ir
setting
53
012
G F F2
F3
F1 I on
ed
tripp
t
r es e
F
0 OF
I on
ed
tripp
t
r es e
F
0 OF
tripped
reset
A-59
Functions and characteristics www.schneider-electric.com
A b extract and/or rapidly replace the circuit breaker without having to touch connections;
b allow for the addition of future circuits at a later date.
Installation
PB106360r-50_1.eps
PB104831_ME_1.eps
Fixed configuration
ComPact NS630b to 1600 circuit breakers may be installed vertically, horizontally or
flat on their back.
DB128063.eps
DB128064.eps
Manually operated fixed Electrically operated fixed
ComPact NS800. ComPact NS1600.
Withdrawable configuration
ComPact NS630b to 1600 circuit breakers should be installed vertically only.
DB128065.eps
DB128066.eps
059782N_I_50_SE_ME_1.eps
DB128068.eps
A-60
www.schneider-electric.com
Functions and characteristics
Electrical and mechanical accessories
ComPact NS630b to 1600
C
D
E
F
G
A H
I
J
B
A Mismatch protection
B Door interlock
C Racking interlock
D Keylock locking
E Padlock locking
F Position indicator
G Chassis front plate (accessible with cubicle door closed)
H Crank entry
I Reset button
J Crank storage
A-61
Functions and characteristics www.schneider-electric.com
A
Types of connection
Fixed device
Front connections (N, L) Connection by:
bars bare cables (except L) cables with lugs(except L)
DB128077.eps
DB128072.eps
DB128073.eps
DB128074.eps
DB128075.eps
DB128076.eps
Rear connections (N, L, LB) Connection by:
Horizontal: Vertical: bars cables with lugs
(except L,LB)
DB128078.eps
DB128079.eps
DB128072.eps
DB128074.eps
DB128080.eps
DB128082.eps
DB128072.eps
DB128073.eps
DB128074.eps
DB128075.eps
DB128076.eps
Withdrawable device
Front connections Connection by:
bars cables with lugs
DB128083.eps
DB128072.eps
DB128074.eps
DB128076.eps
DB128072.eps
DB128074.eps
DB128080.eps
A-62
www.schneider-electric.com
Functions and characteristics
To ensure performance and isolation, depending on the type of circuit breaker (N, H, L, LB) and type of connection,
certain isolation accessories are mandatory.
A
Connections accessories
Type of accessories For ComPact NS630b to NS1600
Fixed: Withdrawable:
Front connection Rear connection Front connection Rear connection
Vertical-connection N, H - N, H, L, LB -
adapters
DB128085.eps
[1]
Set of bare-cable N, H - - -
connectors and terminal
DB128086.eps
[1]
Interphase barriers N, H, L, LB N, H, L, LB - N, H, L, LB
DB128088.eps
DB425866.eps
[2] [3]
Spreaders N, H N, H N, H, L, LB N, H, L, LB
DB128089.eps
[1]
Connection shield N, H, L - - -
DB128090.eps
by padlocks (IP20)
[4]
[1] Spreaders, vertical connection adapters and cable lugs adapters are not compatible with voltages u 500 V.
[2] Mandatory for voltages u 500 V unless using the bare-cable connector + terminal shield kit.
[3] Mandatory for fixed devices with L and LB performance levels, whatever the voltage.
[4] Mandatory for fixed front-connection versions with vertical connection adapters oriented towards the front.
A-63
Functions and characteristics www.schneider-electric.com
If the vertical connection adapters are front oriented, then it is mandatory to install
the arc chute screen in order to comply with the safety clearances.
DB128098.eps
DB128100.eps
DB128099.eps
Spreaders.
DB128101.eps
DB128102.eps
DB128097.eps
Vertical-connection
adapters.
Bare cables
Special sets of connectors and terminal shields may be used to connect up to four
240 mm2 copper or aluminium cables for each phase. Bare cable connection is
DB128095.eps
DB128104.eps
DB128096.eps
4-cable connectors.
Cables with lugs
Cable lug adapters are combined with the vertical-connection adapters.
One to four cables with crimped lugs (y 300 mm2) may be connected.
To ensure stability, spacers must be positioned between the terminal extensions.
If the cable lug adapters are installed over the top of the arc chute chambers, then it is
mandatory to install the arc chute screen in order to comply with the safety clearances.
DB128105.eps
DB403911.eps
DB128107.eps
A-64
www.schneider-electric.com
Functions and characteristics
Electrical and mechanical accessories
ComPact NS630b to 1600
DB128109.eps
DB403912.eps
Fixed, rear-connection ComPact NS630b to 1600 devices equipped with horizontal
or vertical connectors may be directly connected to flat or edgewise bars, depending
on the position of the connectors.
Spreaders are available to increase the pole pitch to 95 mm.
DB128100.eps
Spreaders.
DB128110.eps
DB128111.eps
DB128112.eps
DB128096.eps
DB128105.eps
DB128114.eps
A-65
Functions and characteristics www.schneider-electric.com
DB128094.eps
pitch to 95 mm.
DB128097.eps
DB128100.eps
Vertical-connection adapters. Spreaders.
DB128116.eps
DB128115.eps
DB128117.eps
Cables with lugs
Cable lug adapters enable connection of one to four cables with crimped lugs
(y 300 mm2).
To ensure stability, spacers must be positioned between the terminal extensions.
DB128096.eps
DB128105.eps
DB128119.eps
A-66
www.schneider-electric.com
Functions and characteristics
Electrical and mechanical accessories
ComPact NS630b to 1600
DB128121.eps
DB128094.eps
depending on the position of the connectors.
Spreaders are available to increase the pole pitch to 95 mm.
DB128100.eps
Spreaders.
DB128122.eps
DB128123.eps
DB128124.eps
DB128096.eps
DB128105.eps
DB128126.eps
A-67
Functions and characteristics www.schneider-electric.com
DB128127.eps
Connection shield.
Interphase barriers
These barriers are flexible insulated partitions used to reinforce isolation of
connection points in installations with busbars, whether insulated or not.
Barriers are installed vertically between front or rear connection terminals.
They are mandatory for voltages u 500 V for both fixed and withdrawable products
and for L and LB types, whatever the voltage.
DB128128.eps
DB128129.eps
DB128130.eps
ComPact NS equipped with connection
shield.
Interphase barriers for Interphase barriers for fixed Interphase barriers for
fixed device, front device, rear connection. withdrawable device, rear
connection. connection.
Safety shutters (standard)
Mounted on the chassis, the safety shutters automatically block access to the
disconnecting contact cluster when the device is in the disconnected or test positions
(degree of protection IP20). When the device is removed from its chassis, no live
parts are accessible.
The shutters can be padlocked (padlock not supplied) to:
b prevent connection of the device
b lock the shutters in the closed position.
DB128131.eps
Safety shutters.
A-68
www.schneider-electric.com
Functions and characteristics
Electrical and mechanical accessories
ComPact NS630b to 1600
DB424573.eps
CAO1
Connections are made directly to the auxiliaries once the front has been removed. CAO2
Wires exit the circuit breaker through a knock-out in the top.
OF1
OF2
OF3
DB424579.eps
SD
MN or MX
SDE
COM
Manually operated device.
Withdrawable devices
Auxiliary circuits are connected to terminal blocks located in the top part of the
chassis.
DB424572.eps
The auxiliary terminal block is made up of a fixed and moving part. The two parts are
in contact when the device is in the test and connected positions. SDE
OF3
OF2
DB424570.eps
OF1
MN or MX
COM
CT1
DB424571.eps
CE3
CE2
CE1
CD2
CD1
Withdrawable device.
A-69
Functions and characteristics www.schneider-electric.com
All the auxiliary contacts opposite are also available in "low-level" versions capable of switching very low loads (e.g.
Indication contacts
Contacts installed in the device
054549-18.eps
Changeover contacts are used to remote circuit breaker status information and can
thus be used for indications, electrical locking, relaying, etc.
They comply with the IEC 60947-5 international recommendation.
Functions
b OF (ON/OFF) - indicates the position of the main circuit breaker contacts
b SD (trip indication) - indicates that the circuit breaker has tripped due to:
v an overload
OF, SD and SDE changeover contacts. v a short-circuit
v an earth-leakage fault.
v operation of a voltage release
v operation of the "push to trip" button
v disconnection when the device is ON.
Returns to de-energised state when the circuit breaker is reset.
b SDE (fault indication) - indicates that the circuit breaker has tripped due to:
v an overload
v a short-circuit
v an earth-leakage fault.
Returns to de-energised state when the circuit breaker is reset.
b CAF / CAO (early-make or early-break function) - indicates the position of the
rotary handle. Used in particular for advanced opening of safety trip devices (early
break) or to energise a control device prior to circuit breaker closing (early make).
Installation
b OF, SD and SDE functions - a single type of contact provides all these different
indication functions, depending on where it is inserted in the device. The contacts
clip into slots behind the front cover of the circuit breaker
b CAF / CAO function - the contact fits into the rotary-handle unit (direct or extended).
Electrical characteristics of the OF/SD/SDE/CAF/CAO
auxiliary contacts
Contacts Standard Low level
Rated thermal current (A) 6 5
Minimum load 100 mA at 24 V 1 mA at 4 V
Utilisation cat. (IEC 60947-5-1) AC12 AC15 DC12 DC14 AC12 AC15 DC12 DC14
Operational 24 V 6 6 6 1 5 3 5 1
current (A) 48 V 6 6 2.5 0.2 5 3 2.5 0.2
110 V 6 5 0.6 0.05 5 2.5 0.6 0.05
220/240 V 6 4 - - 5 2 - -
250 V - - 0.3 0.03 5 - 0.3 0.03
380/440 V 6 2 - - 5 1.5 - -
480 V 6 1.5 - - 5 1 - -
660/690 V 6 0.1 - - - - - -
Connected, disconnected, test position carriage switches
A single type of changeover contact can be mounted optionally on the chassis to
indicate, depending on the slot where it is installed:
b the connected (CE) position
b the disconnected (CD) position. This position is indicated when the required
clearance for isolation of the power and auxiliary circuits is reached
b the test (CT) position. In this position, the power circuits are disconnected and the
056456.eps
A-70
www.schneider-electric.com
Functions and characteristics
Electrical and mechanical accessories
ComPact NS630b to 1600
Rotary handles
PB104828_1.eps
There are two types of rotary handle:
b direct rotary handle
b extended rotary handle.
There are two models:
b standard with a black handle
b VDE with a red handle and yellow front for machine-tool control.
A-71
Functions and characteristics www.schneider-electric.com
Manually operated circuit breakers may be equipped with an MX shunt release, an MN undervoltage release or a delayed
Remote tripping
This function opens the circuit breaker via an electrical order. It is made up of:
b a shunt release (2nd MX)
PB106360r-50_1.eps
b or an undervoltage release MN
b or a delayed undervoltage release MN + delay unit.
These releases (2nd MX or MN) cannot be operated by the communication bus.
The delay unit, installed outside the circuit breaker, may be disabled by an emergency OFF button to obtain
instantaneous opening of the circuit breaker.
Wiring diagram for the remote-tripping function
DB128139.eps
Opening Opening Delayed
DB128138.eps
DB128137.eps
MX MN MN
D1
C1 D1
The MX release locks the circuit breaker in OFF position if the order is maintained (except for MX "communicating"
releases).
Characteristics
Power supply V AC 50/60 Hz 24 - 48 - 100/130 - 200/250 - 277 - 380/480
V DC 12 - 24/30 - 48/60 - 100/130 - 200/250
Operating threshold 0.7 to 1.1 Un
Permanent locking function 0.85 to 1.1 Un
Consumption (VA or W) pick-up: 200 (200 ms) hold: 4.5
Circuit breaker response time at Un 50 ms ±10
Instantaneous voltage releases MN
The MN release instantaneously opens the circuit breaker when its supply voltage drops to a value between 35 %
and 70 % of its rated voltage. If there is no supply on the release, it is impossible to close the circuit breaker, either
Fixed ComPact NS1600. manually or electrically. Any attempt to close the circuit breaker has no effect on the main contacts. Circuit breaker
closing is enabled again when the supply voltage of the release returns to 85 % of its rated value.
Characteristics
Power supply V AC 50/60 Hz 24 - 48 - 100/130 - 200/250 - 380/480
V DC 24/30 - 48/60 - 100/130 - 200/250
Operating opening 0.35 to 0.7 Un
threshold closing 0.85 Un
Consumption (VA or W) pick-up: 200 (200 ms) hold: 4.5
MN consumption with delay unit (VA or W) pick-up: 400 (200 ms) hold: 4.5
Circuit breaker response time at Un 90 ms ±5
MN delay units
To eliminate circuit breaker nuisance tripping during short voltage dips, operation of the MN release can be
delayed. This function is achieved by adding an external delay unit in the MN voltage-release circuit. Two versions
056421.eps
A-72
www.schneider-electric.com
Functions and characteristics
Electrical and mechanical accessories
ComPact NS630b to 1600
Electrically operated circuit breakers are equipped as standard with a motor mechanism module. Two solutions are
available for electrical operation:
b a point-to-point solution A
b a bus solution with the COM communication option.
PB104831_ME_1.eps
Operating threshold 0.85 to 1.1 Un
Consumption (VA or W) 180
Motor overcurrent 2 to 3 In for 0.1 second
Charging time maximum 4 seconds
Operating frequency maximum 3 cycles per minute
Electrical closing order
The release remotely closes the circuit breaker if the spring mechanism is charged.
Release electrical characteristics are identical to those of an MX release (see
above), the operating threshold is from 0.85 to 1.1 Un and the circuit breaker
response time at Un is 60 ms ±10.
The ComPact NS electrical operation function can be used to implement a synchro-
coupling system.
Electrical opening order
The release instantaneously opens the circuit breaker when energised. The supply
can be impulse-type or maintained.
Release electrical characteristics are identical to those of an MX release (see above).
Note: whether the operating order is maintened or automatically disconnected (pulse-type), Electrically operated ComPact NS circuit breaker.
"communicating" releases ("bus" solution with "COM" communication option) always have an
impulse-type action (see diagram).
Wiring diagram of a point-to-point electrical operation solution Wiring diagram of a bus-type electrical
operation solution
DB424577.eps
DB424578.eps
A1 81 11 A1
COM
DB424576.eps
200 ms
min. Supervisor
for MX OF
SDE
A-73
Functions and characteristics www.schneider-electric.com
accessories
Toggle lock in
b OFF position padlock removable device
b OFF or ON position padlock fixed device
Direct rotary handle lock in
Toggle locked by removable padlocking device. b OFF position padlock
b OFF or ON position keylock locking
device + keylock
PB104828_ME_r_1.eps
ed
B
harg
disc
O OFF
F
G
53
012
H
Pushbutton locking VBP
The transparent cover blocks access to the pushbuttons used to open and close the
PB100810A-32.eps
device.
It is possible to independently lock the opening OFF button and the closing ON
PB100811A-32.eps
button.
The pushbuttons may be locked using either:
b padlocks (not supplied), 5 to 8 mm
b lead seal
b two screws.
Device locking in the OFF position
Access to pushbuttons Pushbutton locking using VCPO by padlocks, VSPO by keylocks
protected by transparent a padlock. The circuit breaker is locked in the OFF position by physically maintaining the
cover. opening pushbutton pressed down:
b using padlocks in standard (one to three padlocks, not supplied)
b using a keylock (supplied).
PB100812A-32.eps
Keys may be removed only when locking is effective (Profalux or Ronis type locks).
The keylocks are available in any of the following configurations:
b one keylock
b one keylock mounted on the device + one identical keylock supplied separately for
PB104365A-32.eps
A-74
www.schneider-electric.com
Functions and characteristics
Electrical and mechanical accessories
ComPact NS630b to 1600
Chassis locking
A ismatch protection
m
A
B door interlock
DB128071.eps
C racking interlock
D keylock locking
C E padlock locking
F position indicator
D
G chassis front plate
E (accessible with
F cubicle door closed)
H crank entry
G I reset button
A H J crank storage
I
J
B
PB104366A32.eps
PB104367A34.eps
(standard) or keylocks (VSPD option)
Mounted on the chassis and accessible with the door closed, these devices lock the
circuit breaker in the disconnected position in two manners:
b using padlocks (standard), up to three padlocks (not supplied)
b using keylocks (optional), one or two different keylocks are available.
Profalux and Ronis keylocks are available in different options:
b one keylock
b one keylock mounted on the device + one identical keylock supplied separately,
using the same key, for interlocking with another device
b one (or two) keylocks mounted on the device + one (or two) identical keylocks
supplied separately, for interlocking with another device.
A locking kit (without locks) is available for installation of one or two keylocks (Ronis, "Disconnected" position "Disconnected" position
Profalux, Kirk or Castell). locking by padlocks. locking by keylocks.
“Connected”, “disconnected” and “test” position locking
The connected, disconnected and test positions are shown by an indicator and are
PB104352A32.eps
mechanically indexed.
The racking crank blocks when the exact position is obtained.
A release button is used to free it.
As standard, the circuit breaker can be locked only in "disconnected position". On
request, the locking system may be modified to lock the circuit breaker in any of the
three positions: "connected", "disconnected" or "test".
Door interlock catch VPEC
Mounted on the right or left-hand side of the chassis, this device inhibits opening of
the cubicle door when the circuit breaker is in connected or test position. It the Door interlock.
breaker is put in the connected position with the door open, the door may be closed
without having to disconnect the circuit breaker.
PB104368A32.eps
Mismatch protection.
A-75
Functions and characteristics www.schneider-electric.com
Other accessories
A PB104740-32.eps
front panel. This option is mandatory for Source-changeover systems and only
compatible with electrically operated devices.
Escutcheon (CDP)
Optional equipment mounted on the door of the cubicle, the escutcheon increases
the degree of protection to IP40. It is available in fixed and withdrawable versions.
Operation counter.
Transparent cover (CCP) for escutcheon
Optional equipment mounted on the escutcheon, the cover is hinged and secured by
a screw. It increases the degree of protection to IP54 and the degree of protection
DB128144.eps
against mechanical imPacts to IK10. It may be used for withdrawable devices only.
Blanking plate (OP) for escutcheon
Used with the escutcheon, this option closes off the door cutout of a cubicle not yet
equipped with a device. It may be used with the escutcheon for both fixed and
withdrawable devices.
Escutcheon.
DB128145.eps
Transparent cover.
DB128146.eps
Blanking plate.
A-76
www.schneider-electric.com
Functions and characteristics
Electrical and mechanical accessories
ComPact NS1600b to 3200 (fixed version)
B A
A2
A
DB432539.eps
C
C1
C2
C3
E
ic 5.0
Microlog
OFF
100 % OFF
40 %
menu
alarm
long
time tr 8 12
(s) 4 16
Ir .8 .9
.7 2 20
.95
.6 1 24
.98 .5 at 6 Ir aneous
.5 1 instant
.4 x In Ii 8 10
6 12
time tsd .4 .4 .3 4
short
(s) .2 15
Isd3 4 5 .3 .1 3 off
6 2
2.5
.2 0 x In
8 .1 2
2 I t
10 on
1.5 delay
x Ir
setting
E
ic 5.0
Microlog
OFF
OFF
Circuit breaker
100 %
40 %
menu
alarm
NS1600b / 2500
D
long
time tr 8 12
(s) 4 16
Ir .8 .9
.7 2 20
.95
.6 1 24
.98 .5 at 6 Ir aneous
.5 1 instant
.4 x In Ii 8 10
6 12
time tsd .4 .4 .3 4
short
(s) .2 15
Isd3 4 5 .3 .1 3 off
6 2
2.5
.2 0 x In
8 .1 2
2 I t
10 on
1.5 delay
x Ir
setting
A
Circuit breaker
NS3200
E
E1 E2 E3 E4 E5
'X IFE
Enerlin
4002
LV43
Test
A-77
Functions and characteristics www.schneider-electric.com
A
Installation
PB106366_L81.eps
DB128151.eps
OFF
OFF
Mounting on rails.
Connection
Fixed ComPact NS.
Front connection
NS1600 to 2500 NS3200
DB128153.eps
DB128154.eps
DB128069.eps
OFF
OFF
OFF
OFF
Bars
DB128155.eps
OFF
OFF
DB128159.eps
DB128157.eps
OFF
OFF
OFF
OFF
A-78
www.schneider-electric.com
Functions and characteristics
Electrical and mechanical accessories
ComPact NS1600b to 3200
All the auxiliary contacts opposite are also available in "low-level" versions capable of switching very low loads
(e.g. for the control of PLCs or electronic circuits).
A
Indication contacts
Contacts installed in the device
Changeover contacts are used to remote circuit breaker status information and can
054549-18.eps
thus be used for indications, electrical locking, relaying, etc.
They comply with the IEC 60947-5 international recommendation.
Functions
b OF (ON/OFF) - indicates the position of the main circuit breaker contacts
b SD (trip indication) - indicates that the circuit breaker has tripped due to:
v an overload
v a short-circuit
v an earth-leakage fault OF, SD and SDE changeover contacts.
v operation of a voltage release
v operation of the "push to trip" button
b Returns to de-energised state when the circuit breaker is reset.
SDE (fault indication) - indicates that the circuit breaker has tripped due to:
v an overload
v a short-circuit
v an earth-leakage fault.
Returns to de-energised state when the circuit breaker is reset.
Installation
b OF, SD and SDE functions - a single type of contact provides all these different
indication functions, depending on the position where it is inserted in the device.
The contacts clip into slots behind the front cover of the circuit breaker.
Electrical characteristics of the OF/SD/SDE auxiliary contacts
Contacts Standard Low level
Rated thermal current (A) 6 5
Minimum load 100 mA at 24 V 1 mA at 4 V
Utilisation cat. (IEC 60947-5-1) AC12 AC15 DC12 DC14 AC12 AC15 DC12 DC14
Operational 24 V 6 6 6 1 5 3 5 1
current (A) 48 V 6 6 2.5 0.2 5 3 2.5 0.2
110 V 6 5 0.6 0.05 5 2.5 0.6 0.05
220/240 V 6 4 - - 5 2 - -
250 V - - 0.3 0.03 5 - 0.3 0.03
380/440 V 6 2 - - 5 1.5 - -
480 V 6 1.5 - - 5 1 - -
660/690 V 6 0.1 - - - - - -
A-79
Functions and characteristics www.schneider-electric.com
ComPact NS1600b to 3200 circuit breakers may be equipped with an MX shunt release, an MN undervoltage release
Remote tripping
This function opens the circuit breaker via an electrical order. It is made up of:
056421.eps
DB128139.eps
DB128137.eps
C2 D2 Instantaneous
opening D2
order
MX MN MN
C1 D1 D1
A-80
www.schneider-electric.com
Functions and characteristics
Electrical and mechanical accessories
ComPact NS1600b to 3200
A
Device locking
PB104836_ME_1.eps
Locking in the OFF position guarantees isolation as per IEC 60947-2.
Padlocking systems can receive up to three padlocks with shackle diameters
ranging from 5 to 8 mm (padlocks not supplied).
Control device Function Means Required
accessories
Toggle lock in OFF position padlock removable
device
lock in OFF or ON padlock fixed device
position
Interphase barriers
These barriers are flexible insulated partitions used to reinforce isolation of ComPact NS with toggle locked using a fixed device
connection points in installations with busbars, whether insulated or not. and padlocks.
Barriers are installed vertically between front connection terminals.
PB104835_ME_1.eps
Escutcheon CDP
Optional equipment mounted on the door of the cubicle, the escutcheon increases
the degree of protection to IP40.
Interphase barriers.
DB128161.eps
Escutcheon.
A-81
ComPact NS630b to 3200 www.schneider-electric.com
Installation recommendations
B-1
Installation recommendations www.schneider-electric.com
Operating conditions
ComPact circuit breakers have been tested for operation in industrial atmospheres.
It is recommended that the equipment be cooled or heated to the proper operating temperature and kept free of
excessive vibration and dust.
Altitude derating
B Altitude does not significantly affect circuit-breaker characteristics up to 2000 m.
DB419120.eps
Above this altitude, it is necessary to take into account the decrease in the dielectric
strength and cooling capacity of air.
The following table gives the corrections to be applied for altitudes above
2000 metres. The breaking capacities remain unchanged.
ComPact NS630b to 3200
Altitude (m) 2000 3000 4000 5000
Impulse withstand voltage Uimp (kV) 8 7.1 6.4 5.6
Rated insulation voltage (Ui) 800 710 635 560
Maximum rated operationnal voltage 50/60 690 690 635 560
Hz Ue (V)
Rated current 40 °C 1 x In 0.99 0.96 0.94
x In x In x In
Intermediate values may be obtained by interpolation.
Vibrations
ComPact NS devices resist electromagnetic or mechanical vibrations.
DB419119.eps
Tests are carried out in compliance with standard IEC 60068-2-6 for the levels
required by merchant-marine inspection organisations (Veritas, Lloyd’s, etc.):
b 2 V 13.2 Hz: amplitude ±1 mm
b 13.2 V 100 Hz: constant acceleration 0.7 g.
Excessive vibration may cause tripping, breaks in connections or damage to
mechanical parts.
Electromagnetic disturbances
ComPact NS devices are protected against:
DB419121.eps
B-2
www.schneider-electric.com
Installation recommendations
Installation in switchboards
Power supply and weights
Power supply
ComPact NS circuit breakers can be supplied from either the top or the bottom
without any reduction in performance. This capability facilitates connection when B
installed in a switchboard.
Weights
Circuit Chassis
DB424588.eps
breaker
NS630b to 1600 manual operation 3P 14 14
4P 18 18
NS630b to 1600 electrical operation 3P 14 16
4P 18 21
NS1600b to 3200 3P 24 -
4P 36 -
The table above presents the weights (in kg) of the circuit breakers and the main accesories,
which must be summed to obtain the total weight of complete configurations.
B-3
Installation recommendations www.schneider-electric.com
Installation in switchboards
Safety clearances and minimum distances
General rules
When installing a circuit breaker, minimum distances (safety clearances) must be
maintained between the device and panels, bars and other protection devices
installed nearby. These distances, which depend on the ultimate breaking capacity,
are defined by tests carried out in accordance with standard IEC 60947-2.
If installation conformity is not checked by type tests, it is also necessary to:
b use insulated bars for circuit-breaker connections
B b block off the busbars using insulating screens.
ComPact NS630b to 3200 (fixed devices)
A (*) B A (*) B
DB424587.eps
DB424582.eps
146.5
F
[1] An overhead clearance of 50 mm is
required to remove the arc chutes.
DB424585.eps
40
180
F
B-4
www.schneider-electric.com
Installation recommendations
Installation in switchboards
Installation example
Painted sheetmetal
DB424583.eps
B-5
Installation recommendations www.schneider-electric.com
Mounted on the left or right-hand side of the chassis, this locking device prevents opening of the door if the circuit
breaker is in the connected or test positions. If the circuit breaker was connected with the door open, the door may
be closed without having to disconnect the circuit breaker.
B
DB424581.eps
61
11.5
(1) (2)
2
Dimensions (mm)
Type (1) (2)
NS630b to 1600 (3P) 135 168
NS630b to 1600 (4P) 205 168
Device in the connected or test positions
Door locked
Door
DB424591.eps
F
5
23
Note: The door interlock may be mounted on either the left or right-hand side of the chassis.
F Datum
B-6
www.schneider-electric.com
Installation recommendations
Control wiring
24 V DC power-supply module
External 24 V DC power-supply module for Micrologic (F1-, F2+)
b It is recommended to use the AD power supply due to its low stray primary-secondary capacitance. Good operation
of the Micrologic Trip Unit in noisy environment is not guaranteed with other power supplies.
b The dedicated AD power supplies shall be used only for the Micrologic trip units. If the COM option is used, a second
dedicated power supply shall be used.
b The consumption of a Micrologic Trip Unit is approximately 100mA.
b For Micrologics control units alone, a number of 10 devices can be connected to the same AD power supply. Add
other AD power supply for more than 10 Micrologics.
b If the installation is shared between several panels, one AD power supply shall be added for each panel.
b AD power supply dedicated to Micrologics trip units shall not be connected to earth. (F1-, F2+).
External 24 V DC power supply for Communication bus
b A dedicated 24 V DC power supply shall be used for the communication devices.
b Do not connect the positive terminal (E1) to earth.
b The negative terminal (E2) can be connected to earth.
b A number of communication modules (BCM, IFE, IFM, I/O, FDM…) can be connected to the same 24 V DC
power supply. Refer bellow the devices consumption table to avoid exceeding the maximum current delivered by
the
24 V DC power supply.
ULP module consumption
The table below lists the ULP module consumption.
Module Typical Consumption Maximum Consumption
(24 V DC at 20 °C / 68 °F) (19.2 V DC at 60 °C / 140 °F)
BCM ULP for MasterPact and ComPact 40 mA 65 mA
NS
Micrologic 5 or 6 trip unit for 30 mA 55 mA
ComPact NSX circuit breakers
BSCM for ComPact NSX circuit breakers 9 mA 15 mA
2-wire RS 485 isolated repeater 15 mA 19 mA
FDM121 display for LV circuit breaker 21 mA 30 mA
IFM Modbus-SL interface for LV circuit 21 mA 30 mA
breaker
IFE Ethernet interface for LV circuit 120 mA 3 A (with gateway)
breaker
I/O input/output interface module for LV 165 mA 420 mA
circuit breaker
Maintenance module 0 mA (the maintenance module has 0 mA (the maintenance module
its own power supply) has its own power supply)
Installation recommendation
b The 24 V DC wires (output of the 24 V DC power supply) shall be twist together.
b The 24 V DC wires (output of the 24 V DC power supply) must cross all power cables perpendicularly.
b The technical characteristics of the external 24 V DC power-supply module for Micrologic control units are
indicated on page A-28.
Note: wiring of ZSI: it is recommended to use twisted shielded cable. The shield must be connected to earth at both ends.
B-7
Installation recommendations www.schneider-electric.com
Temperature derating
ComPact NS devices equipped with electronic trip units
ComPact circuit breakers have been tested for operation in industrial atmospheres.
It is recommended that the equipment be cooled or heated to the proper operating temperature and kept free of
excessive vibration and dust.
B For mixed connections, use the same derating values as for horizontal connections.
Version Fixed device
Connection Front or horizontal rear Vertical rear
temp. Ti [2] 40 45 50 55 60 65 70 40 45 50 55 60 65 70
NS630b N/L 630 630 630 630 630 630 630 630 630 630 630 630 630 630
NS800 N/L 800 800 800 800 800 800 800 800 800 800 800 800 800 800
NS1000 N/L 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
NS1250 N 1250 1250 1250 1250 1250 1240 1090 1250 1250 1250 1250 1250 1250 1180
NS1600 N 1600 1600 1560 1510 1470 1420 1360 1600 1600 1600 1600 1600 1510 1460
B-8
www.schneider-electric.com
Installation recommendations
Power dissipation / Resistance
ComPact NS devices equipped with electronic trip units
Version Withdrawable
device
N L LB
R/pole P/pole R/pole P/pole R/pole P/pole
NS630b 0.038 19 0.072 34 0.086 34
NS800 0.038 30 0.072 40 0.086 40
NS1000 0.038 50 0.072 77
NS1250 0.036 84
NS1600 0.036 154
B-9
ComPact NS630b to 3200 www.schneider-electric.com
C-1
Dimensions and connection www.schneider-electric.com
Manual control
Front connection (N, L)
(1)
DB424678.eps
DB424677.eps
254
163.5
X 327 X
508 200
100
C
107.5 99.5 (3P)
99.5
169.5 (4P)
205 Y
F
Z [1] Terminal shields are optional.
DB424675.eps
188
94
105 123
X X
234 210
113
92.5 117 123
F
107.5 35
140.5 70
146.5 Y
205 14
Z
Electrical control
Front and rear connection (N, L, LB)
105 (3P)
175 (4P) 105
DB424674.eps
DB424684.eps
188
94
123
105
X X
210 234 200
117 100
123
107.5 35 F : Datum.
175.5 70 Note: Dimensions for front and rear
182 99.5 (3P) connection on electrically operated
99.5
F 169.5 (4P) devices are identical to those for
Z Y
manually operated devices.
C-2
www.schneider-electric.com
Dimensions and connection
ComPact NS630b to 1600 (fixed version)
Mounting
Front connection
On backplate On rails
Y
Y 4 Ø6.5
DB424673.eps
DB424672.eps
4 Ø6.5
X X
200 200
100 100
C
99.5 (3P)
99.5
169.5 (4P)
99.5 (3P)
99.5
169.5 (4P)
Rear connection
On backplate On rails
Y
Y 4 Ø6.5 (3P)
DB424593.eps
DB424592.eps
6 Ø6.5 (4P)
4 Ø5.5
4 R30
60 107
75
X 200 X 234
75
60 100 107 117
70 70
200 (3P) (4P)
270 (4P)
Toggle control
Door cutout
(A) 124 mini
DB424671.eps
(B)
(1) (2) A Y
B Y
(C) 150 194 mini (3P) 194 mini (3P)
(2) 194 mini 194 mini
DB424635.eps
DB424634.eps
264 mini (4P) 264 mini (4P)
201(1)
X X 216 (1) X
266 (2)
C 108 (1)
133 (2)
100.5 (1)
90.5 (1)
107.5 194 (1) 97 (1) 181 (1)
140.5 244 (2) 122 (2)
146.5
F
Z
F : Datum. Y
[1] Without escutcheon. 194 mini (3P) 194 mini
DB424633.eps
95.5 (1)
108 (2)
35.5 (1)
71 (1) 60.5 (2)
121 (2)
Electrical control
Door cutout A
Y
(A) 150 mini 194 mini (3P)
(1) (2) 194 mini
DB424632.eps
DB424635.eps
X X 216 (1)
266 (2)
108 (1)
133 (2)
F : Datum.
[1] Without escutcheon.
[2] With escutcheon.
C-4
www.schneider-electric.com
Dimensions and connection
ComPact NS630b to 1600 (fixed version)
Rotary handle
DB424631.eps
DB424683.eps
60°
R80
X X
195
C
24
60°
107.5 25
140.5
146.6
175.5
229.5
F
Z
Door cutout
A B D
Y Y Y
194 mini (3P) 194 mini (3P)
194 mini 194 mini 194 mini
DB424635.eps
DB424630.eps
DB424629.eps
201 (1)
216 (1) 201 (1)
X X X
266 (2)
108 (1)
133 (2)
90.5 (1) 90.5 (1)
194 (1) 97 (1)
181 (1) 130 (1)
244 (2) 122 (2)
DB424626.eps
DB424627.eps
60°
R100
X X
X
24
60°
212.5 25
231.5 mini
605.5 maxi F
Z
F : Datum. Note: X and Y are the symmetry planes for a 3-pole device Z is the back plane of the device.
C-5
Dimensions and connection www.schneider-electric.com
Dimensions
Manual control Electrical control
127.5 (3P)
160.5
210 210 197.5 (4P)
DB424624.eps
DB424623.eps
DB424625.eps
70 (*) 46 [1]
199
C X X X
45.5
69 123
5 5
90 (3P)
60 mini 60 mini 160 (4P)
90
F F Y
Mounting
Bottom mounting on base plate or rails Vertical on uprights or backplate
Y
Y
DB424622.eps
DB424621.eps
DB424620.eps
X
24 25
100
216
231
F
F
Cutouts
Door cutout Rear panel cutout
Y
170 mini (3P) 230 mini
DB424619.eps
DB424618.eps
[1]
259 [2]
X 303 X 234
117
109[1] [2]
130.8 102.5 (3P)
161[2][1]
102.5
183 172.5 (4P)
259 [1]
307 [2]
C-6
www.schneider-electric.com
Dimensions and connection
ComPact NS630b to 1600 (withdrawable version)
Rotary handle
DB424616.eps
DB424617.eps
Y
[1]
136
60°
R80
93
X
24
X
C
60°
5
Door cutout
170 mini (3P)
230 mini
240 mini (4P)
Y
DB424611.eps
259 [1]
[2]
303
X
109[1]
130.8 [2]
161 [1]
259[1] 183 [2] [1] Without escutcheon.
307[2] [2] With escutcheon.
DB424609.eps
DB424608.eps
60°
E47966A
R200
X X X
24
60°
207 mini 17 25
447 maxi
F
Dimensions
(A) 132 mini Y
(B)
DB424606.eps
DB424607.eps
(C)
165
X X
330
C
18.5
38.5
132
162.5
168.5
222.5
F
368
Z
DB424604.eps
X 216 (1) X
267 (2) 201
108 (1) 100.5
133.5 (2)
173 (1)
198.5 (2) 166
346 (1) 332
397 (2)
C Mounting on rails
Y Y
DB424603.eps
DB424602.eps
4 Ø12
X
X 150
119
75
95.9
73 195 (3P)
310 (4P) 195
146
F : Datum.
[1] Without escutcheon.
[2] With escutcheon. Note: X and Y are the symmetry planes for a 3-pole device.
C-8
www.schneider-electric.com
Dimensions and connection
ComPact NS630b to 3200
External modules
DB128217.eps
DB424601.eps
8
S : 0.6 mm²
S : 2.5 mm²
Ø3.5
Only one wire per terminal.
82
90
G4
G3 N
L
ply
er sup
Pow
AC /DC
444
LVA454 /240V
t: 200
Inpu
0.25A Output
50/60Hz DC
ut: 24V
Outp
1A
ge
volta C4)
Overlevel (OV
High
67.5 108
60
61
73
112
75
++ 90
Network
45
Réseau
us
modb
CCM
shield
Fault
A A
B B
A’ A’
B’ B’
Com.
Breaker
Disjoncteur
ss
Addre
+
.
sync
CE
CD
CT
58
54
C-9
Dimensions and connection www.schneider-electric.com
DB416700.eps
24VDC I1 C I2 I3 C I4 I5 C I6
4 5 6
3 7 I1
AI
2 8
1 9 I2
APP
I3 O1
45 92
I4 O2
I5
O3
I6
T 84.8 115
IO LV434063
O1 O2 O3 A1
13 14 23 24 33 34 T1 T2
C 72 63.6
71
DB425703.eps
45 109
90
66
18 73
DB416698.eps
ETH1 ETH2
Enerlin'X IFE
IFE-XX.YY.ZZ (factory set)
ETH1 LK/10-100/ACT
45 92
ETH2 LK/10-100/ACT
Module Status
84.8 105
Modbus-SL
Network Status
T LV434002
72 63.6
71
Com’X 210/510
DB432541.eps
DB417077.eps
Com’X 210
90 45 85 106
144 63
69
C-10
www.schneider-electric.com
Dimensions and connection
ComPact NS630b to 3200
External modules
35 76
177
208
127
44
44 174 44
295
Installation
400/1600 (NS630b to NS1600) 1000/4000 A (NS1600b to NS3200)
DB128230.eps
DB128231.eps
C-11
Dimensions and connection www.schneider-electric.com
DB128233.eps
DB128232.eps
197
233
115 216
280 71
362
381
C 8 Ø9
470 x 160 mm window
DB128235.eps
DB128234.eps
242 281
146
160 263
456 72
470
552
572
Busbars path
280 x 115 mm window 470 x 160 mm window
Busbars spaced 70 mm centre-to-centre Busbars spaced 115 mm centre-to-centre
M1 M2 M3
DB128237.eps
DB128236.eps
C-12
www.schneider-electric.com
Dimensions and connection
FDM121 switchboard display
Dimensions
FDM121
DB432542.eps
DB432543.eps
96
X
96
Y
Mounting
Through panel
C
DB432544.eps
DB424612.eps
DB424679.eps
+ 0.8
X 92 0
X
+ 0.8
10.6 92 0
20.7 23
Y
Z
On panel
2 Ø22.5
DB432545.eps
DB424681.eps
DB432546.eps
DB115270.eps
16.5
X 99.3
+0.5 X
-
32
19
+
- 0.3
15 37 20 13 2 Ø22.5
+1.5
-
33
Z
17
Connector (optional).
99.3
Y
C-13
Dimensions and connection www.schneider-electric.com
Dimensions
DB416703.eps
DB424615.eps
129
X
C
163
Mounting
On panel
1.5...6
DB416704.eps
DB424614.eps
DB416738.eps
100
X
30.6
17.5
39
+0
Ø 22,5 -0,30
DB416739.eps
DB424613.eps
100
100 100
100
+0
30 -0,20
C-14
www.schneider-electric.com
Dimensions and connection
Accessories NS630b to 3200
Escutcheon
NS630b to NS1600 (fixed control)
A C
(A)
Y
DB424599.eps
DB424598.eps
DB424600.eps
(C)
Y
X X X
275 154
27
C
27 27
131
27
253
DB424596.eps
X X 313
27
27 13 27
317
DB424594.eps
27
X 275 X
137.5
27 202.5
405
C-15
Dimensions and connection www.schneider-electric.com
DB424716.eps
DB424719.eps
DB128247.eps
15
123
E47904A
67.5 N Y
X
67.5 44
25 9.5 12.5
DB128249.eps
123
15 60
C F
31
2 Ø11
12.5
DB424715.eps
DB424718.eps
View A
97
X
N Y
97
60
12.5
DB128252.eps
12.5 9.5
31
44
F
Z
25
2 Ø11
View A detail.
Front connection
70 70 70
30
DB128253.eps
DB432101.eps
DB424713.eps
163.5
129
N Y
X View A
15
16.5 15
15 25
9.5
F 2 screws M10 44
Z
View A detail.
F : Datum.
Note: Recommended connection screws: M10 class 8.8. Tightening torque: 50 Nm with contact washer.
C-16
www.schneider-electric.com
Dimensions and connection
ComPact NS630b to 1600 (fixed version)
Bars
DB424712.eps
DB424711.eps
DB128257.eps
196
181
15
Y
View A
X
95 95 95
70 70 70
DB424710.eps
181
196 12.5 12.5
C
N Y 15
31.5 View A
F
Z
DB424709.eps
DB424708.eps
123
15
82.5
X
15 52.5
Y
123
95 95 95
70 70 70
DB424707.eps
83
F 12.5 12.5
Z
N
Y
Spreader detail
Middle left or middle right Middle spreader for 3P Left or right spreader for 4P Left or right spreader for 3P
spreader for 4P
DB128266.eps
DB128268.eps
DB128267.eps
DB128265.eps
View A detail.
F : Datum.
C-17
Dimensions and connection www.schneider-electric.com
DB424706.eps
DB424717.eps
View A
200
X N
430 Y
200
DB128271.eps
C
10
62.5
F
Z View A detail.
F : Datum.
Note: [1] two mounting possibilities for vertical-connection adapters (pitch 21 mm).
Recommended connection screws: M10 class 8.8.
Tightening torque: 50 Nm with contact washer.
C-18
www.schneider-electric.com
Dimensions and connection
ComPact NS630b to 1600 (fixed version)
Cables with lugs and bare cables
DB424705.eps
DB424704.eps
View A
250
200
N Y
15
X 530
200
C
250
DB128275.eps
15
10
150
View A detail.
F
Z
Lugs
Ø20.5 : 240 mm²
Ø23 : 300 mm²
DB128276.eps
DB128277.eps
DB128278.eps
89.5
Ø10
11.5
25
31
DB424703.eps
DB424702.eps
199 206.5
N
Y
X
398 413
199 206.5
DB128282.eps
16.5
35
61
F
Z
F : Datum.
C-19
Dimensions and connection www.schneider-electric.com
DB424701.eps
DB424700.eps
DB128283.eps
15
67.5
X
228
N
67.5 Y
114
44
25 9.5 12.5
DB128249.eps
267.5 15
C F
12.5
60
2 Ø11
DB424699.eps
DB424698.eps
View A
97
X
97 N
Y
60
267.5 12.5
DB128252.eps
F 12.5 9.5
44
25
2 Ø11
View A detail.
Front connection
15 12.5 View A
70 70 70
DB424697.eps
DB424696.eps
DB128291.eps
171
N Y
X 336 Top terminal Bottom terminal
140
DB128294.eps
235 12.5
F
View A detail.
F : Datum.
Note: Recommended connection screws: M10 class 8.8. Tightening torque: 50 Nm with contact washer.
C-20
www.schneider-electric.com
Dimensions and connection
ComPact NS630b to 1600 (withdrawable versions)
Bars
DB424695.eps
DB424694.eps
DB128295.eps
238
223
X Y
95 95 95
207 70 70 70
DB424693.eps
192 View A
12.5 12.5
C
250
F
N Y
Spreader detail
Middle left or middle Middle spreader for 3P Left or right spreader for 4P Left or right spreader for 3P
right spreader for 4P
DB128265.eps
DB128266.eps
DB128267.eps
DB128268.eps
View A detail.
F : Datum.
C-21
Dimensions and connection www.schneider-electric.com
DB424692.eps
DB424691.eps
DB128303.eps
50
71
292
21 N
Y 15
171
X 583
DB128275.eps
C 140
21
261
71
View A detail.
50
193.5 15
F
Lugs
Ø20.5 : 240 mm²
Ø23 : 300 mm²
DB128276.eps
DB128277.eps
DB128278.eps
89.5
Ø10
11.5
25
31
F : Datum.
Note: X and Y are the symmetry planes for a 3-pole device.
Recommended connection screws: M10 class 8.8.
Tightening torque: 50 Nm with contact washer.
C-22
www.schneider-electric.com
Dimensions and connection
ComPact NS1600b to 3200 (fixed version)
DB424690.eps
DB424689.eps
165
150
X Y
N
View A
150
OFF
OFF
165
DB128313.eps
20
F C
Z
View A detail.
DB424688.eps
DB424685.eps
230
142.5
X Y
N
View A
142.5
OFF
OFF
230
DB128317.eps
25
F
40
Z
View A detail.
DB424687.eps
DB424686.eps
230
142.5
N Y
X View A
OFF
142.5
DB128317.eps
OFF
230
25
F
40
Z
View A detail.
F : Datum.
Note: Recommended connection screws: M10 class 8.8.
Tightening torque: 50 Nm with contact washer.
C-23
Dimensions and connection www.schneider-electric.com
DB128324.eps
DB128325.eps
DB128322.eps
Middle left or middle Middle spreader Left or right Left or right spreader
right spreader for 4P for 3P spreader for 4P for 3P
44
25 9.5 12.5
DB128327.eps
DB128328.eps
DB128329.eps
DB128330.eps
DB128326.eps
C 60
12.5
2 Ø11
DB128333.eps
DB128334.eps
DB128335.eps
DB128331.eps
60
12.5
DB128336.eps
12.5 9.5
44
25
2 Ø11
DB128324.eps
DB128325.eps
DB128322.eps
DB128342.eps
15 25 15
2 M10 screws 9.5
44
C-24
www.schneider-electric.com
Dimensions and connection
Power connections for ComPact NS1600b to 3200
Recommended drilling dimensions
DB128325.eps
DB128322.eps
DB128346.eps
C
Front connection with vertical-connection adapter (NS1600b to 2500)
DB128348.eps
DB128349.eps
DB128347.eps
DB128350.eps
DB128351.eps
DB128350.eps
DB128351.eps
C-25
Dimensions and connection www.schneider-electric.com
DB128357.eps
E E
Connection of bars
B Bars must be adjusted to ensure correct positioning on the terminals before bolting (B).
Bars must rest on a support firmly attached to the switchboard frame, such that the
DB424721.eps
Electrodynamic forces
The first spacer between bars must be positioned within a maximum distance (see
table below) of the connection point to the circuit breaker. This distance is calculated
to resist the electrodynamic stresses exerted between the bars of each phase during
a short-circuit.
B C
DB128359.eps
DB424720.eps
C-26
www.schneider-electric.com
Dimensions and connection
Power connections for ComPact NS630b to 3200
Connections
The quality of bar connections depends, among other things, on the tightening
torques used for the nuts and bolts. Over-tightening may have the same 1 2 3 4 5
consequences as under-tightening.
DB128361.eps
The correct tightening torques for the connection of bars to the circuit breaker
terminals are indicated in the table below.
The values below are for copper bars (Cu ETP-NFA51-100) and steel nuts and bolts
(class 8.8).
The same values apply to AGS-T52 quality aluminium bars
(French standard NFA 02-104 and American National Standard H-35-1).
Examples of bar connections
DB128362.eps
DB128363.eps
DB128364.eps
6
Tightening torque for bars 1 terminal screws, factory tightened to 13 Nm
2 circuit breaker terminal
Rated diameter Drilling (mm) Tightening torque Tightening torque (Nm) 3 bars
(mm) diameter (Nm) with flat or with contact or split 4 bolt
grower washers washers 5 washer
10 11 37.5 50 6z nut
Bar drilling
Examples
DB128365.eps
DB128366.eps
DB128367.eps
Insulation distance
DB128368.eps
Dimensions (mm)
Utilisation voltage X minimum
Ui y 600 V 8 mm
Ui y 1000 V 14 mm
Bar bending
Bars must be bent according to the table below. A tighter bend may cause cracks.
DB128369.eps
Dimensions (mm)
e Radius r
Minimum Recommended
5 5 7.5
10 15 18 to 20
C-27
Dimensions and connection www.schneider-electric.com
Note: The values presented in the tables are the result of trials and theoretical calculations on the basis of the assumptions
mentioned above. These tables are intended as an aid in designing connections, however, the actual values must be confirmed
by tests on the installation.
Front or horizontal rear connections
DB128370.eps
C-28
www.schneider-electric.com
Dimensions and connection
Power connections for ComPact NS630b to 3200
Sizing of bars
C
ComPact Maximum Ti: 40 °C Ti: 50 °C Ti: 60 °C
service Number of bars Number of bars Number of bars
current 5 mm 10 mm 5 mm 10 mm 5 mm 10 mm
thick thick thick thick thick thick
NS630b 400 2b.30 x 5 1b.30 x 10 2b.30 x 5 1b.30 x 10 2b.30 x 5 1b.30 x 10
NS630b 630 2b.40 x 5 1b.40 x 10 2b.40 x 5 1b.40 x 10 2b.40 x 5 1b.40 x 10
NS800 800 2b.50 x 5 1b.50 x 10 2b.50 x 5 1b.50 x 10 2b.50 x 5 1b.50 x 10
NS1000 1000 2b.50 x 5 1b.50 x 10 2b.50 x 5 1b.50 x 10 2b.63 x 5 1b.63 x 10
NS1250 1250 2b.63 x 5 1b.63 x 10 3b.50 x 5 2b.40 x 10 3b.50 x 5 2b.40 x 10
NS1600 1400 2b.80 x 5 1b.80 x 10 2b.80 x 5 2b.50 x 10 3b.63 x 5 2b.50 x 10
NS1600 1600 3b.63 x 5 2b.50 x 10 3b.63 x 5 2b.50 x 10 3b.80 x 5 2b.63 x 10
NS2000 2000 3b.100 x 5 2b.63 x 10 3b.100 x 5 2b.63 x 10 3b.100 x 5 2b.80 x 10
NS2500 2500 4b.100 x 5 2b.80 x 10 4b.100 x 5 2b.80 x 10 4b.100 x 5 3b.80 x 10
NS3200 3200 6b.100 x 5 3b.100 x 10 6b.100 x 5 3b.100 x 10 4b.100 x 10
C-29
ComPact NS630b to 3200 www.schneider-electric.com
Electrical diagrams
D-1
Electrical diagrams www.schneider-electric.com
The diagram is shown with circuits de-energised, all devices open, connected and charged and relays
in the normal position.
DB424738.eps
Z1
Z2
Z3
Z4
Z5
Z1
Z2
Z3
Z4
Z5
AT BPO BPF
D2
C2
B4
A4
A2
VN
Z1
Z2
Z3
Z4
Z5
Q
MN MX Motor-mechanism
module
Micrologic
D D1 or
A1
C1
F2+
M1
M2
T2
T3
T1/M3
T4/F1
24 V DC
E : energy
A : digital ammeter.
P : A + power meter + additional protection.
Motor-mechanism
module
A1
CN2 a - 440/480 V
D-2
www.schneider-electric.com
Electrical diagrams
ComPact NS630b to 1600
Fixed circuit breakers
Yellow
Brown
White
Black
Blue
Red
DB128375.eps
DB424737.eps
Open Closed Fault Fault Closed Open
E6 E5 E4 E3 E2 E1
MN/MX
OF1
11 12 14
M1M2M3 F1 F2 D1/C1
542
544
532
534
524
522
514
512
Z1 Z2 Z3 Z4 Z5 T1 T2 T3 T4
32
34
22
24
12
14
82
84
92
94
D2/C2 OF2
21 22 24
OF3
31 32 34
SD
OF3 OF2 OF1 CAO2 CAO1 91 92 94
SDE SD CAF2 CAF1
D
541
531
521
511
31
21
11
81
91
Black
Blue
Red
DB424736.eps
81 31 21 11
82 32 22 12
84 34 24 14
B4 A4 A2 A1
D-3
Electrical diagrams www.schneider-electric.com
The diagram is shown with circuits de-energised, all devices open, connected and charged and relays
in the normal position.
DB424734.eps
Z1
Z2
Z3
Z4
Z5
Z1
Z2
Z3
Z4
Z5
AT BPO BPF
VN
D2
C2
B4
Z1
Z2
Z3
Z4
Z5
A4
A2
Q
Motor-mechanism
MN MX module
Micrologic
D or
F2+
M1
M2
T2
T3
T1/M3
D1
C1
A1
T4/F1
24 V DC
Terminal-block marking
Control unit Remote operation
Com UC1 UC2 UC3 CAF2 MN / MX MT2 MT1
/
E5 E6 Z5 M1 M2 M3 F2+ 544 D2 C2 A4 A2
E3 E4 Z3 Z4 T3 T4 VN 542 B4
/
E1 E2 Z1 Z2 T1 T2 F1 – 541 D1 C1 A1
D-4
www.schneider-electric.com
Electrical diagrams
ComPact NS630b to 1600
Withdrawable circuit breakers
DB128150.eps
DB128382.eps
DB128188.eps
Open Closed Fault Fault Closed Open Disconnected Connected Test
822
824
812
814
332
334
322
324
312
314
542
544
532
534
524
522
514
512
914
912
32
34
22
24
12
14
82
84
92
94
331
321
311
821
811
911
541
531
521
511
31
21
11
81
91
544 534 84 94 524 514 34 24 14 824 814 334 324 314 914
542 532 82 92 522 512 32 22 12 822 812 332 322 312 912
541 531 81 91 521 511 31 21 11 821 811 331 321 311 911
Legend
Connected (only one wire per connection point).
D-5
Electrical diagrams www.schneider-electric.com
The diagram is shown with circuits de-energised, all devices open, connected and charged and relays
in the normal position.
DB424728.eps
Z1
Z2
Z3
Z4
Z5
Z1
Z2
Z3
Z4
Z5
AT
D2
C2
Z1
Z2
Z3
Z4
Z5
Q
MN MX
Micrologic
D D1 or
C1
F2+
M1
M2
T2
T3
T1/M3
T4/F1
24 V DC
D-6
www.schneider-electric.com
Electrical diagrams
ComPact NS1600b to 3200
Fixed circuit breakers
E6 E5 E4 E3 E2 E1
MN/MX
DB128392.eps
DB424727.eps
OF1
Open Closed Fault Fault 11 12 14
M1M2M3 F1 F2 D1/C1
Z1 Z2 Z3 Z4 Z5 T1 T2 T3 T4
D2/C2 OF2
21 22 24
32
34
22
24
12
14
82
84
92
94
OF3
31 32 34
SD
91 92 94
D
31
21
11
81
91
81
82
84
SDE
Indication contacts
OF3 / OF2 / OF1: ON / OFF indication contacts
D-7
Electrical diagrams www.schneider-electric.com
DB424726.eps
ComPact equipped with a Micrologic 6 A/E/P [1]:
b shielded cable with 2 twisted pairs
b T1 twisted with T2
b maximum length 4 meters
b cable cross-sectional area 0.4 to 1.5 mm2
b recommended cable: Belden 9552 or equivalent.
For proper wiring of neutral CT, refer to instruction
Bulletin 48041-082-03 shipped with it.
Do not remove Micrologic factory-installed jumper
between T1 and T2 unless neutral CT is connected.
If supply is via the top, follow the shematics.
If supply is via the bottom, control wiring is identical; for
the power wiring, H1 is connected to the source side,
H2 to the load side.
For four-pole versions, for residual earth-fault
protection, the current transformer for the external Shield Drain
Micrologic 6
F2+
T1/M3
M1
M2
T2
T3
T4/F1
12 5 6 7 10 11
H1 X1
1 MiDGF module 9
H2 X2 3 8
PE 13 14
D-8
www.schneider-electric.com
Electrical diagrams
ComPact NS630b to 3200
Earth-fault and earth-leakage protection
Neutral protection Zone selective interlocking
Earth-leakage protection
N L1 L2 L3
Connection of the rectangular-sensor
secondary circuit
DB424731.eps
ComPact equipped with a Micrologic 7 A/P:
Z1
Z2
Z3
Z4
Z5
use the cable shipped with the rectangular sensor.
Q
I
Micrologic 7
U
F2+
T1/M3
M1
M2
T2
T3
T4/F1
M1
M2
M3 D
Neutral protection
b three pole circuit breaker:
v neutral protection is impossible with Micrologic A,E
v with Micrologic P, an external neutral transformer is necessary; the connection diagram is the same as for residual earth-fault protection.
b four pole circuit breaker:
v ComPact equipped with Micrologic A,E,P
v the current transformer for external neutral is not necessary.
tsd = 0.3
shortening the time required to clear faults, while
maintaining time selectivity between the various
devices.
A pilot wire interconnects a number of circuit breakers
equipped with Micrologic A/E/P control units, as
Fault 1
illustrated in the diagram above.
The control unit detecting a fault sends a signal
upstream and checks for a signal arriving from
downstream. If there is a signal from downstream, the
circuit breaker remains closed for the full duration of its B
tripping delay. If there is no signal from downstream, the tsd = 0.2
circuit breaker opens immediately, regardless of the
tripping-delay setting.
Fault 1.
Only circuit breaker A detects the fault. Because it Fault 2
receives no signal from downstream, it immediately
opens in spite of its tripping delay set to 0.3.
Fault 2.
Downstream
Circuit breakers A and B detect the fault. Circuit breaker circuit break
A receives a signal from B and remains closed for the full
duration of its tripping delay set to 0.3. Circuit breaker B
does not receive a signal from downstream and opens
immediately, in spite of its tripping delay set to 0.2.
Wiring
b Maximum impedance: 2.7 Ω / 300 m.
b Capacity of connectors: 0.4 to 2.5 mm2.
b Wires: single or multicore.
b Maximum lenght: 3000 m.
b Limits to device interconnection:
v the common ZSI - OUT (Z1) and the output ZSI - OUT
(Z2) can be connected to a maximum of 10 upstream
device
v a maximum of 100 downstream devices may be
connected to the common ZSI - IN (Z3) and to an input
ZSI - IN CR ( Z4) or GF (Z5).
D-9
Electrical diagrams www.schneider-electric.com
Ethernet
J
24 V DC
Modbus
A A A
24 V DC
B
24 V DC
I I I
K
C
C D
IFE
lin'X
Ener
K Test
Test
02
LV4340
D Ener
lin'X
IFE
Ener
lin 'X IF
E
L
I I I
01
LV4340
I6
C
I5
I4
C
I3
I2
C
I1
+
DC
24V
A1
K
K APP
I1
I2
I3
O1
O2
O3
I4
K
I5
I6
E
63
LV4340
IO
A1
T2
O3 T1
34
O2 33
I6
C 24
I5 23
I4 O1
C 14
I3 13
I2
C
I1
+
DC
24V
I6
C
I5
I4
C
I3
I2
C
I1
+
DC
24V
A1
O1
I1
O2
I2
O3
I3
A1 APP I4
I5
O1
I1 I6
O2
I2
O3
I3
APP 63
I4 LV4340
I5
I6
IO
A1
T2
63 O3 T1
LV4340 33
34
O2
24
23
IO
O1
14
13
A1
T2
O3 T1
34
O2 33
24
O1 23
14
13
F
L L L M M
F G H H
F1
F2
F3
F4
CH
PF F1
XF F2
N/ X1 F3
X2 A01
DE1 A02
2C C3 SD
DE2 C4 T1
es N/ T2
C2 X
C1
AF1
C2
K ULP cable
L Breaker ULP cord
A FDM121 (TRV00121) E I/O application module (LV434063) I ULP termination (TRV00880) M NSX cord
N Modbus Termination
[1]
C IFE (LV434001) G ComPact NS630b-3200 Modbus
(VW3A8306DRC)
D IFM (LV434000) H ComPact NSX
[1] Modbus termination is mandatory, see ULP system user guide TRV99101.
D-10
www.schneider-electric.com
Electrical diagrams
Fixed, electrically operated ComPact NS630b to 3200
Connection to the communication interface module
DB432548.eps
Color
Red E1 24 V
Black E2 0V
White E5 H
Blue E6 L
Breaker ULP
cord
E1 E2 E3 E4 E5 E6
D
B / Tx+ D1
A’ / Rx- D0
B’ / Rx+ D1
24 V
0V
A / Tx- D0
24 V DC 24 V DC
Ethernet
IFM
IFE IFE
in'X
Enerl
Test
4002
LV43
ULP Termination
ULP Termination
OR
D-11
Electrical diagrams www.schneider-electric.com
I6
C
I5
I4
C
I3
I2
C
I1
+
DC
24V
I/O A1
application
O1
I1
O2
I2
O3
I3
APP I4
module
I5
I6
63
LV4340
IO
A1
T2
O3 T1
34
O2 33
24
O1 23
14
13
Color
Red E1 24 V
Black E2 0V ULP cable
Breaker
White E5 H
ULP cord
Blue E6 L
E1 E2 E3 E4 E5 E6
24 V
A / Tx- D0
B / Tx+ D1
A’ / Rx- D0
B’ / Rx+ D1
0V
D
Customer terminal block
24 V DC
24 V DC
Ethernet
02
LV4340
Test
ULP Termination
ULP Termination
OR
D-12
www.schneider-electric.com
Electrical diagrams
ComPact NS630b to 3200
24 V DC external power supply AD module
DB432611.eps
v to keep available the display and the energy metering, even if Current < 20 % In.
v to use the display even if the circuit breaker is open or not supplied (for the exact
conditions of use, see the “electrical diagrams” part of this catalogue)
v to display fault currents after tripping
v to modify settings when the circuit breaker is open (OFF position).
b The same 24 V DC external power supply can be used for the micrologic control
unit and the communication devices (IFE, IFM, I/O, FDM).
b The 24 V DC external power supply (AD module) for the Micrologic control unit
(F1- F2+) is not required for basic protections LSIG.
b The 24 V DC external power supply for the BCM ULP communication module
(E1-E2) is required. The same 24 V DC external power supply can be used for the
communication devices (IFE, IFM, I/O, FDM).
b If the 24 V DC external power supply (AD module) is used to supply Micrologic
control unit, this power supply shall be used only for supplying Micrologic control unit
and M2C.
b The dedicated AD power supply shall be used only for the Micrologic trip unit. If the
COM option is used, a second dedicated 24 V DC external power supply shall be
used.
Note: case of using the 24 V DC external power supply (AD module), maximum cable length
between 24 V DC (G1, G2) and the control unit (F1-, F2+) must not exceed 10 meters.
D
The internal voltage taps are connected to the bottom side of the circuit breaker.
An external voltage taps are possible using the PTE option:
b With this option, the internal voltage taps are disconnected and the voltage taps are
connected to terminals VN, V1, V2, V3.
b The PTE option is required for voltages less than 220 V and greater than 690 V (in which
case a voltage transformer is compulsory). For three-pole devices, the system is supplied with
terminal VN connected only to the control unit.
b When the PTE option is implemented, the voltage measurement input must be protected 110/240 V AC
against short-circuits. 24/125 V DC
Installed as close as possible to the busbars, this protection function is ensured by a P25M
circuit breaker (1 A rating) with an auxiliary contact (cat. no. 21104 and 21117).
b This voltage measurement input is reserved exclusively for the control unit and must not
ever be used to supply other circuits outside the switchboard.
Connection
The maximum length for each conductor supplying power to the trip unit module is
10 m.
Do not ground F2+, F1-, or power supply output:
b the positive terminal (F2+) on the trip unit must not be connected to earth ground
b the negative terminal (F1-) on the trip unit must not be connected to earth ground
b the output terminals (- and +) of the 24 V DC power supply must not be grounded.
D-13
ComPact NS630b to 3200 www.schneider-electric.com
Additional characteristics
Tripping curves
ComPact NS630b to 3200.............................................................................................E-2
E-1
Additional characteristics www.schneider-electric.com
Tripping curves
ComPact NS630b to 3200
DB424743.eps
I²t ON
0.4
0.3
0.2
I²t OFF 0.1
0
[1]
Ig = In x… A B C D E F G H J
In < 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
400 A y In y 1200 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
In > 1200 A 500 640 720 800 880 960 1040 1120 1200
E-2
www.schneider-electric.com
Additional characteristics
Current-limiting curves
The limiting capacity of a circuit breaker is its aptitude to limit short-circuit currents.
DB424741.eps
forces created by fault currents in devices.
Prospective
The result is a major increase in breaking performance. In particular, the service current
breaking capacity Ics is equal to 100 % of Icu for limitor circuit breaker.
The Ics value, defined by IEC standard 60947-2, is guaranteed by tests comprising Prospective
the following operations: Isc
b break three times consecutively a fault current equal to 100 % of Icu
b check that the device continues to function normally: Limited Isc
peak
v it conducts the rated current without abnormal temperature rise Actual
v protection functions perform within the limits specified by the standard current
v suitability for isolation is not impaired. Limited
Isc
Longer service life of electrical installations
Current-limiting circuit breakers greatly reduce the negative effects of short-circuits (t)
on installations. The exceptional limiting capacity of the ComPact NS
Thermal effects range is due to the rotating double-break technique (very
rapid natural repulsion of contacts and the appearance of
Less temperature rise in conductors, therefore longer service life for cables.
two arc voltages in-series with a very steep wave front).
Mechanical effects
Reduced electrodynamic forces, therefore less risk of electrical contacts or busbars
being deformed or broken.
Electromagnetic effects
Less disturbances for measuring devices located near electrical circuits.
Economy by means of cascading E
Cascading is a technique directly derived from current limiting. Circuit breakers with
breaking capacities less than the prospective short-circuit current may be installed
downstream of a limiting circuit breaker. The breaking capacity is reinforced by the
limiting capacity of the upstream device.
It follows that substantial savings can be made on downstream equipment and
enclosures.
Current-limiting curves
The current-limiting capacity of a circuit breaker is expressed by two curves which
are a function of the prospective short-circuit current (the current which would flow if
no protection devices were installed):
b the actual peak current (limited current),
b thermal stress (A2s), i.e. the energy dissipated by the short-circuit in a conductor
with a resistance of 1 Ω.
Example
What is the real value of a 200 kA rms prospective short-circuit (i.e. 440 kA peak)
limited by an NS630bLB upstream ?
Answer: 70 kA peak (see next page).
E-3
Additional characteristics www.schneider-electric.com
Current-limiting curves
Current-limiting curves
Voltage 400/440 V AC (1) Voltage 660/690 V AC
Limited short-circuit current (k peak) Limited short-circuit current (k peak)
NS630bH
DB424739.eps
DB424740.eps
NS800H
NS1000H NS1600bN
NS630bH NS2000N
NS1250H NS800H
NS630bN NS1600H NS2500N
NS1000H NS3200N
NS800N NS1250H
NS1000N NS630bL NS630bN NS1600H
NS1250N NS800L NS630bLB NS800N
NS1600N NS1000L NS800LB NS1000N
NS1250N NS630bLB
R NS1600N NS800LB
HB2
L NSX630 NSX630
S NS630bL
H NSX400 R NSX400
N NS800L L HB1
k F R k NS1000L S
L HB2 NSX250
S NSX250 H R
H NSX100 NSX100
N NSX160 HB1
F F, N L NSX160
B S
N, H
F
E Rated short-circuit current (kA rms) Rated short-circuit current (kA rms)
Thermal-stress curves
Voltage 400/440 V AC [1] Voltage 660/690 V AC
Limited energy Limited energy
DB419931.eps
DB419932.eps
NS630bH NS1600bN
NS630bN NS800H NS630bH NS2000N
NS800N NS1000H NS800H NS2500N
NS1000N NS1250H NS1000H NS3200N
NS1250N NS1600H NS1250H
NS1600N NS1600H
NS630bN
NS800N
NS1000N
NS1000L NS1250N
NS630bL NS1600N
NS800L NS630bLB
NS630bLB NS630bL NS800LB
NS800LB NS800L
NS1000L L NSX630
S L NSX630 S
F N H H NSX400
R
NSX400
R HB1 HB2
F, N HB2
R NSX250
L
F N H S L R S NSX100
B NSX250 N, H HB1 NSX160
NSX100 F
NSX160
Rated short-circuit current (kA rms) Rated short-circuit current (kA rms)
F-1
Catalogue numbers www.schneider-electric.com
F NS1600
ComPact NS type L
33569 33571
F-2
www.schneider-electric.com
Catalogue numbers
NS630b to NS1600 fixed manually operated
Complete device
Note: select in addition the connection accessories, device accessories and auxiliaries, control-unit accessories and communications option, as required.
F-3
Catalogue numbers www.schneider-electric.com
"ammeter" A
3P/4P
Micrologic 2.0 A basic protection 33505
Micrologic 5.0 A selective protection 33512
Micrologic 6.0 A selective + earth-fault protection 33513
Micrologic 7.0 A selective + earth-leakage protection 33514
"energy" E [1]
3P/4P
F Micrologic 2.0 E
Micrologic 5.0 E
Micrologic 6.0 E
basic protection
selective protection
selective + earth-fault protection
33535
33537
33539
Basic switch-disconnector
ComPact NS type NA
3P 4P
DB128408.eps
O OFF
Icu = 70 kA at 220/415 V 3P 4P
NS630b 33271 33275
NS800 33281 33285
NS1000 33291 33295
NS1250 33301 33305
Note: the characteristics of the motor mechanism module NS1600 33311 33315
for electrical operation are specified separately by selecting ComPact NS type L
a part number from the table at the bottom of this page. Icu = 150 kA at 220/415V 3P 4P
NS630b 33272 33276
NS800 33282 33286
NS1000 33292 33296
Micrologic control units
Without "measurement"
3P/4P
Micrologic 2.0 basic protection 33504
Micrologic 5.0 selective protection 33511
Micrologic 6.0 selective + earth-fault protection 33515
"ammeter" A
3P/4P
Micrologic 2.0 A basic protection 33505
Micrologic 5.0 A selective protection 33512
Micrologic 6.0 A selective + earth-fault protection 33513
Micrologic 7.0 A selective + earth-leakage protection 33514
"energy" E [1]
3P/4P
Micrologic 2.0 E basic protection 33535
Micrologic 5.0 E selective protection 33537
Micrologic 6.0 E selective + earth-fault protection 33539
"power meter" P [1]
3P/4P
[1] In case of an installation 3P + Neutral, please add ENVT Micrologic 5.0 P selective protection 65290
device ref. 65317 (see page F-13). Micrologic 6.0 P selective + earth-fault protection 65291
Basic switch-disconnector
Micrologic 7.0 P selective + earth-leakage protection 65292
F
ComPact NS type NA
3P 4P
DB424752.eps
d
discharge
Note: the characteristics of the motor mechanism module for electrical operation are specified
O OFF
separately by selecting a part number from the table at the bottom of this page.
Basic switch-disconnector
ComPact NS type NA
3P 4P
DB424750.eps
F-6
www.schneider-electric.com
Catalogue numbers
NS630b to NS1600 electrically
operated withdrawable devices
Device based on separate components
Basic circuit breaker
ComPact NS type N
Icu = 50 kA at 220/415 V 3P 4P
DB424749.eps
d
discharge
O OFF
Icu = 70 kA at 220/415 V 3P 4P
NS630b 33371 33375
NS800 33381 33385
NS1000 33391 33395
Note: the characteristics of the motor mechanism module for NS1250 33401 33405
electrical operation are specified separately by selecting a part NS1600 33411 33415
number from the table at the bottom of this page. ComPact NS type L
Icu = 150 kA at 220/415 V 3P 4P
NS630b 33372 33376
NS800 33382 33386
NS1000 33392 33396
Micrologic control units
Without "measurement"
3P/4P
Micrologic 2.0 basic protection 33504
Micrologic 5.0 selective protection 33511
Micrologic 6.0 selective + earth-fault protection 33515
"ammeter" A
3P/4P
Micrologic 2.0 A basic protection 33525
Micrologic 5.0 A selective protection 33532
Micrologic 6.0 A selective + earth-fault protection 33533
Micrologic 7.0 A selective + earth-leakage protection 33534
"energy" E [1]
3P/4P
Micrologic 2.0 E basic protection 33536
Micrologic 5.0 E selective protection 33538
Micrologic 6.0 E selective + earth-fault protection 33540
"power meter" P [1]
3P/4P
F
Micrologic 5.0 P selective protection 65293
[1] In case of an installation 3P + Neutral, please add ENVT Micrologic 6.0 P selective + earth-fault protection 65294
device ref. 65316 (see page F-13). Micrologic 7.0 P selective + earth-leakage protection 65295
Basic switch-disconnector
ComPact NS type NA
3P 4P
DB424748.eps
O OFF
separately by selecting a part number from the table at the bottom of this page.
Chassis and connections
Chassis
3P 4P
DB128415.eps
100/130 V [2]
33827 33834 [2]
48/60 V 33831 [2]
33838 [2]
220/240 V [2]
33828 33835 [2]
100/130 V 33832 [2]
33839 [2]
380/415 V [2]
33829 33836 [2]
200/250 V 33833 [2]
33840 [2]
F-7
Catalogue numbers www.schneider-electric.com
4P (4 parts) 33641
4P 33629
Vertical-connection adapters
3P (3 parts) 33642
DB128422.eps
4P (4 parts) 33643
DB128446.eps
4P 33623 33623
Electrical auxiliaries
Indication contacts
6 A - 240 V Low level
DB128428.eps
12 V DC 33658
24/30 V DC, 24 V AC 33659 33668
48/60 V DC, 48 V AC 33660 33669 48/60 V AC/DC 33680
100/130 V AC/DC 33661 33670 100/130 V AC/DC 33684 33681
200/250 V AC/DC 33662 33671 200/250 V AC/DC 33685 33682
277 V AC 33663
380/480 V AC 33664 33673 380/480 V AC/DC 33683
Installation accessories
Escutcheon (small cut-out) for manually operated device with toggle 33717
DB128430.eps
DB128431.eps
F-8
www.schneider-electric.com
Catalogue numbers
Accessories for NS630b to NS1600 withdrawable
devices
4P (4 parts) 33643
Spreaders
3P (3 parts) 33622 33622
DB128427.eps
Chassis accessories
Auxiliary terminal shield (CB)
3P 33763
DB128434.eps
4P 33764
F
Electrical auxiliaries
OF ON/OFF indication contacts
6 A - 240 V Low level
OF, ON/OFF indication contacts 33801 33804
DB128436.eps
SD, trip indication contact for manually operated devices 33800 33803
SDE, fault indication contact operated devices 33799 33802
Up to 3 OF, 1 SD and 1 SDE can be connected (the SDE contact is standard for electrically operated devices)
CE, CD, CT carriage switches
6 A - 240 V Low level
Connected position NO/NC contact (up to 3 CE) 33751 33754
Disconnected position NO/NC (up to 2 CD) 33753 33756
DB128437.eps
12 V DC 33809
24/30 V DC, 24 V AC 33810 33819
48/60 V DC, 48 V AC 33811 33820 48/60 V AC/DC 33680
100/130 V AC/DC 33812 33821 100/130 V AC/DC 33684 33681
200/250 V AC/DC 33813 33822 200/250 V AC/DC 33685 33682
277 V AC 33814
380/480 V AC 33815 33824 380/480 V AC/DC 33683
Auxiliary terminals for chassis alone
3 wire terminal (30 parts) 47071
6 wire terminal (10 parts) 47072
Jumpers (10 parts) 47900
F-9
Catalogue numbers www.schneider-electric.com
Chassis locking
Keylocking in disconnected position
By Profalux keylocks
Profalux 1 lock with 1 key + adaptation kit 64909
DB424747.eps
By Ronis keylocks
Ronis 1 lock with 1 key + adaptation kit 64912
2 locks 1 key + adaptation kit 64913
2 locks 2 different keys + adaptation kit 64914
1 keylock Ronis (without adaptation kit):
identical key not identified combination 33189
identical key identified EL24135 combination 33190
identical key identified EL24153 combination 33191
identical key identified EL24315 combination 33192
Optional disconnected/test/connected position locking 33779
Adaptation kit (without keylock):
adaptation kit Profalux 33769
adaptation kit Ronis 33770
adaptation kit Castell 33771
adaptation kit Kirk 33772
Door interlock
Right side of chassis (VPECD) 33786
Left side of chassis (VPECG) 33787
DB424746.eps
F
DB424745.eps
Installation accessories
Escutcheon
33857
DB128430.eps
Blanking plate
33858
DB128432.eps
F-10
www.schneider-electric.com
Catalogue numbers
Accessories for NS630b to NS1600 fixed and
withdrawable devices
I on
tripp
ed
Conversion accessory CNOMO 33866
Locking by keylocks Ronis Profalux
reset
0 OFF
tripp
reset
ed
Telescopic (for chassis-mounted devices) 33880
0 OFF
I
ON
tripped
reset
OFF
0
9
0039
F-11
Catalogue numbers www.schneider-electric.com
O
FFO
h sup
I
NO h
sup
FFO
O
degr
ahcs
id
O
FFO
hsup
I
NO h
sup
FFO
O
degr
ahcs
id
FFO
O
degr
ahcs
id
O
FFO
hsup
I
NO h
sup
FFO
O
degr
ahcs
id
F-12
www.schneider-electric.com
Catalogue numbers
Communication option for NS630b to NS1600 fixed
and withdrawable devices
Communication options
IFE Ethernet interface LV434001
DB425868.eps
for LV breaker
Ethernet interface LV434002
for LV breakers and gateway
X IFE
Enerlin'
002
LV434
Test
I6
C
I5
I4
C
I3
I2
C
I1
+
24VDC
A1
O1
I1
O2
I2
O3
I3
APP I4
I5
I6
63
LV4340
IO
A1
T2
O3 T1
34
O2 33
24
O1 23
14
13
time 8 12
33543
tr
48/60 V DC LV454441
G4
100/125 V DC LV454442
110/130 V AC LV454443
G3 N
L
Outp
ut
200/240 V AC LV454444
Test equipment
Mini test kit
Hand held test kit (HHTK) 33594
DB128463.eps
F-13
Catalogue numbers www.schneider-electric.com
Circuit breaker
ComPact NS type N
Icu = 85/70 kA to 220/415 V 3P 4P
DB128467.eps
Switch-disconnector
ComPact NS type NA
3P 4P
DB128468.eps
F
OFF
OFF
Electrical auxiliaries
Indication contacts
6 A - 240 V Low level
OF, ON/OFF indication contacts 33108 33109
DB128428.eps
SD, trip indication contact for manually operated devices 33004 33008
SDE, fault indication contact operated devices 33011 33012
Up to 3 OF, 1 SD and 1 SDE can be connected
Instantaneous voltage releases
MX MN
Delay unit R (non-adjustable) Rr (adjustable)
DB128429.eps
12 V DC 33658
24/30 V DC, 24 V AC 33659 33668
48/60 V DC, 48 V AC 33660 33669 48/60 V AC/DC 33680
100/130 V AC/DC 33661 33670 100/130 V AC/DC 33684 33681
200/250 V AC/DC 33662 33671 200/250 V AC/DC 33685 33682
277 V AC 33663
380/480 V AC 33664 33673 380/480 V AC/DC 33683
Locking
Removable toggle locking system
Locking by 3 padlocks 33996
DB128448.eps
F-14
www.schneider-electric.com
Catalogue numbers
Accessories for NS1600b to NS3200
Communication option
IFE Ethernet interface LV434001
for LV breaker
DB424755.eps
long
time tr 8 12
(s) 4 16
Ir .8 .9
.7 2 20
.95
1 24
.6 .98 .5 Ir
33544
@6
48/60 V DC LV454441
G3
L
G4
N
100/125 V DC LV454442
110/130 V AC LV454443
Outp
ut
200/240 V AC LV454444
Test equipment
Mini test kit
Hand held test kit (HHTK) 33594
DB128463.eps
Installation accessories
Escutcheon
33929
DB128444.eps
F-15
Catalogue numbers www.schneider-electric.com
Connection accessories
Bare-cable connectors + 1 connector shield for 4 cables (240 mm²)
3P 33640
DB128420.eps
4P 33641
Installation manual 33148
4P 33629
4P 33643
Installation manual 33148
4P 33645
Installation manual 33148
Rear connection
DB128425.eps
4P 33597
Installation manual 33148
Brackets for mounting on a horizontal surface (2 parts)
3P/4P 64908
DB101032.eps
4P 33623
Installation manual 33148
Cable lug kits / Replacement kit (6 or 8 parts)
240 mm² 3P (6 lug kit) 33013
4P (8 lug kit) 33014
DB128424.eps
F-16
www.schneider-electric.com
Catalogue numbers
Spare parts: NS630b to NS1600 fixed circuit breaker
Electrical auxiliaries and installation accessories
Electrical auxiliaries
Indication contact / 1 part
6 A - 240 V Low level
OF, ON/OFF indication contacts 29450 29452
DB128428.eps
12 V DC 33658
24/30 V DC, 24 V AC 33659 33668
48/60 V DC, 48 V AC 33660 33669 48/60 V AC/DC 33680
100/130 V AC/DC 33661 33670 100/130 V AC/DC 33684 33681
200/250 V AC/DC 33662 33671 200/250 V AC/DC 33685 33682
277 V AC 33663
380/480 V AC 33664 33673 380/480 V AC/DC 33683
Installation manual 33149
F-17
Catalogue numbers www.schneider-electric.com
.7 .95
1 24
.6 .98 .5 Ir
.5 1 @6
Battery + cover
Battery (1 part) 33593
Cover (1 part) For Micrologic A, E 33592
DB128353.eps
Communication option
IFE Ethernet interface for LV breaker LV434001
Ethernet interface for LV breakers and gateway LV434002
DB417415.eps
I6
C
I5
I4
C
I3
I2
C
I1
+
24VDC
A1
O1
I1
O2
I2
O3
I3
APP I4
I5
I6
63
LV4340
IO
A1
T2
F
O3 T1
34
O2 33
24
O1 23
14
13
Rectangular sensors
Inside dimensions (mm) Ie (A)
280 x 115 1600 33573
DB126100.eps
48-60 V DC LV454441
G3
G4
N
100-125 V DC LV454442
LV454443
L
110-130 V AC
Outp
ut
200-240 V AC LV454444
F-18
www.schneider-electric.com
Catalogue numbers
Spare parts: NS630b to NS1600 fixed circuit breaker
Locking and accessories
By Ronis keylocks
Ronis 1 lock with 1 key + adaptation kit 33903
2 locks 1 key + adaptation kit 33905
1 keylock Ronis (without adaptation kit):
identical key not identified combination 33189
identical key identified EL24135 combination 33190
identical key identified EL24153 combination 33191
identical key identified EL24315 combination 33192
Adaptation kit (without keylock):
adaptation kit Profalux 33898
adaptation kit Ronis 33899
adaptation kit Kirk 47517
adaptation kit Castell 47518
Installation manual 47103
Operation counter CDM / 1 part
Operation counter CDM 33895
DB128456.eps
9
0039
Installation manual 47103
F-19
Catalogue numbers www.schneider-electric.com
O
FFO
h sup
I
NO h
sup
FFO
O
degr
ahcs
id
O
FFO
hsup
I
NO h
sup
FFO
O
degr
ahcs
id
I
NO h
sup
FFO
O
degr
ahcs
id
O
FFO
hsup
I
NO h
sup
FFO
O
degr
ahcs
id
F-20
www.schneider-electric.com
Catalogue numbers
Spare parts: NS630b to NS1600
withdrawable circuit breaker
Connection
Connection
3P 4P
Front connection / Replacement kit (6 or 8 parts)
DB128416.eps
Connection accessories
Vertical connection adapters for front-connected chassis / Replacement kit (3 or 4 parts)
3P 33642
DB128422.eps
4P 33643
Installation manual 33149
4P 33645
Installation manual 33149
4P 33623
Installation manual 33149
300 mm²
4P (8 lug kit)
3P (6 lug kit)
4P (8 lug kit)
33014
33015
33016
F
Installation manual 33149
Chassis accessories
Auxiliary terminal shield (CB) / 1 part
3P 33763
DB128434.eps
4P 33764
Installation manual 33149
Clusters
1 disconnecting contact cluster for chassis (see table below) (1 part) 64906
DB401446.eps
DB418007.eps
F-21
Catalogue numbers www.schneider-electric.com
12 V DC 33658
24/30 V DC, 24 V AC 33659 33668
48/60 V DC, 48 V AC 33660 33669 48/60 V AC/DC 33680
100/130 V AC/DC 33661 33670 100/130 V AC/DC 33684 33681
200/250 V AC/DC 33662 33671 200/250 V AC/DC 33685 33682
277 V AC 33663
380/480 V AC 33664 33673 380/480 V AC/DC 33683
Installation manual 47103
Auxiliaries terminal for chassis
3 wire terminal block (1 part) 33098
6 wire terminal block (1 part) 33099
Jumpers (10 parts) 47900
DB401448.eps
DB128354.eps
3 wires. 6 wires.
F-22
www.schneider-electric.com
Catalogue numbers
Spare parts: NS630b to NS1600
withdrawable circuit breaker
Installation accessories
Installation accessories
Escutcheon / 1 part
33857
DB128430.eps
F-23
Catalogue numbers www.schneider-electric.com
alarm
Communication option
IFE Ethernet interface for LV breaker LV434001
Ethernet interface for LV breakers and gateway LV434002
DB425868.eps
X IFE
Enerlin'
002
LV434
Test
I6
C
I5
I4
C
I3
I2
C
I1
+
24VDC
A1
O1
I1
O2
I2
O3
I3
APP I4
I5
I6
63
LV4340
IO
A1
T2
O3 T1
34
O2 33
24
O1 23
14
13
F External sensors
User guide I/O application module DOCA0055EN-00
Rectangular sensors
Inside dimensions (mm) Ie (A)
280 x 115 1600 33573
DB126100.eps
48-60 V DC LV454441
G3
L
G4
N
100-125 V DC LV454442
110-130 V AC LV454443
Outp
ut
200-240 V AC LV454444
F-24
www.schneider-electric.com
Catalogue numbers
Spare parts: NS630b to NS1600
withdrawable circuit breaker
Locking and accessories
Locking for manually operated devices
Removable toggle locking system / 1 part
Locking by 3 padlocks 44936
DB128448.eps
By Ronis keylocks
Ronis 1 lock with 1 key + adaptation kit 33903
2 locks 1 key + adaptation kit 33905
1 keylock Ronis (without adaptation kit):
identical key not identified combination 33189
identical key identified EL24135 combination 33190
identical key identified EL24153 combination 33191
identical key identified EL24315 combination 33192
Adaptation kit (without keylock):
adaptation kit Profalux 33898
adaptation kit Ronis 33899
adaptation kit Kirk 47517
adaptation kit Castell 47518
Installation manual 47103
Operation counter CDM / 1 part
Operation counter CDM / 1 part 33895
DB128456.eps
9
0039
Installation manual 47103
F-25
Catalogue numbers www.schneider-electric.com
devices
Note: the installation manual is enclosed.
O
FFO
h sup
I
NO h
sup
FFO
O
degr
ahcs
id
O
FFO
hsup
I
NO h
sup
FFO
O
degr
ahcs
id
I
NO h
sup
FFO
O
degr
ahcs
id
O
FFO
hsup
I
NO h
sup
FFO
O
degr
ahcs
id
F-26
www.schneider-electric.com
Catalogue numbers
Spare parts: NS630b to NS1600 fixed
or withdrawable circuit breaker
Instructions
Instructions
Chassis accessories 47104
Circuit breaker accessories Manual 33148
Electrical 33149
Fixed and drawout circuit breaker Manual 33148
Electrical 33149
NS630b user manual French 33159
English 33160
Micrologic user manual 20/50 (French) 33076
20/50 (English) 33077
2A/7A (French) 33079
2A/7A (English) 33080
2E/6E (French) 33079
2E/6E (English) 33080
5P/7P (French) 33082
5P/7P (English) 33083
Modbus communication notice for manual 33088
F-27
Catalogue numbers www.schneider-electric.com
Communication options
IFE Ethernet interface for LV breaker LV434001
DB425868.eps
Test
I6
C
I5
I4
C
I3
I2
C
I1
+
24VDC
A1
O1
I1
O2
I2
O3
I3
APP I4
I5
I6
63
LV4340
IO
A1
T2
O3 T1
34
O2 33
24
O1 23
14
13
mm)
F
DB127985.eps
F-28
www.schneider-electric.com
Catalogue numbers
Spare parts: ComPact NS1600b to 3200
Connection, locking and installation accessories
Electrical auxiliaries
Indication contacts (1 part)
OF, SD, SDE 6 A - 240 V 29450
DB128428.eps
12 V DC 33658
24/30 V DC, 24 V AC 33659 33668
48/60 V DC, 48 V AC 33660 33669 48/60 V AC/DC 33680
100/130 V AC/DC 33661 33670 100/130 V AC/DC 33684 33681
200/250 V AC/DC 33662 33671 200/250 V AC/DC 33685 33682
277 V AC 33663
380/480 V AC 33664 33673 380/480 V AC/DC 33683
Installation manual 33969
Locking
Removable toggle locking system / 1 part
Locking by 3 padlocks 33996
DB128448.eps
Installation accessories F
Escutcheon / 1 part
33929
DB128444.eps
F-29
Catalogue numbers www.schneider-electric.com
alarm
External sensors
External sensor for neutral + earth-fault protection (TCE) / 1 part
CT rating: 1000/4000 A 34036
DB128459.eps
Rectangular sensors
Inside dimensions (mm) Ie (A)
470 x 160 3200 33574
DB126100.eps
48-60 V DC LV454441
G3
L
G4
N
100-125 V DC LV454442
110-130 V AC LV454443
Outp
ut
200-240 V AC LV454444
F-30
www.schneider-electric.com
Order form
Order form: ComPact NS630b to NS3200
Circuit breakers and switch-disconnectors
Communication
LT OFF
VCPO - by padlocks
VSPO - by keylocks:
Keylock kit (w/o keylock) Profalux Ronis
F
COM module 1 keylock Profalux Ronis
Device with Ethernet interface Cradle 2 identical keylocks, 1 key Profalux Ronis
(BCM-ULP) management with Chassis locking in "disconnected" position:
with Ethernet interface + I/O application VSPD - by keylocks Keylock kit (w/o keylock) Profalux Ronis
Gateway module (Chassis) Kirk Castell
with Modbus interface 1 keylock Profalux Ronis
2 identical keylocks, 1 key Profalux Ronis
2 keylocks, different keys Profalux Ronis
Eco COM module Optional connected/disconnected/test position locking
Device with Ethernet interface VPEC - door interlock On right-hand side of
(BCM-ULP) chassis
with Ethernet interface + On left-hand side of chassis
Gateway VPOC - racking interlock
with Modbus interface VDC - mismatch protection
Accessories
Front Display Module Mounting accessories
(FDM121) VO - safety shutters on chassis NS - withdrawable as standard
Breaker ULP L = 0.35 m CDM - mechanical operation counter
Cord L = 1.3 m CDP - escutcheon
L=3m CP - transparent cover for escutcheon
L=5m OP - blanking plate for escutcheon
NS630b/1600 connection Mounting brackets for fixed NS for mounting on horizontal plane
Test kits Mini test kit Portable test kit
Horizontal rear connections Top Bottom
Vertical rear connections Top Bottom
Front connections Top Bottom
4 x 240 bare cable connectors + shields NS - FC fixed
v Micrologic control unit functions:
Long connection shields NS - FC fixed 2.0: basic protection (long time + inst.)
Vertical-connection adapters NS - FC fixed, 5.0: selective protection (long time + short time + inst.)
withdr. 6.0: selective + earth-fault protection
Cable-lug adapters NS - FC fixed, (long time + short time + inst. + earth-fault)
withdr. 7.0: selective + earth-leakage protection
Arc chute screen NS - FC fixed (long time + short time + inst. + earth-leakage)
Interphase barriers NS - FC fixed, withdrawable
Spreaders NS - FC fixed, withdrawable
NS1600b/3200 connection
Front connections NS - FC fixed
Vertical connection adaptor optional for NS1600b/2500
(standard for NS3200)
F-31
Schneider Electric Industries SAS
12-2019
ART. 960551
© 2018 - Schneider Electric. All Rights Reserved.
All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. This document has been
Document reference: LVPED211021EN printed on recycled paper