Description Network Repeater


The ARCNET Repeater Module (RPT-E3) is an optional
component of the E3 Series® Expandable Emergency
Evacuation System. It allows the following remotable, E3
Series sub-assemblies to connect to the Broadband net-
work from remote locations:
• ILI-MB-E3
• NGA

The RPT-E3 is available for use in two versions:


• RPT-E3-FO
• RPT-E3-UTP RPT-E3

RPT-E3-UTP connects to the network using unshielded, Features


twisted-pair, copper wire only.
• Listed under UL Standard 864, 9th Edition
RPT-E3-FO communicates to the network using either • Provides the capability for remotable E3 Series
62.5/125 multi-mode fiber-optic cable or copper, sub-assemblies to connect in Styles 4 or 7
unshielded, twisted-pair wire.
configurations
• “FO” option allows either 62.5/125 fiber-optic cable or
Installation
copper, unshielded, twisted-pair wire
The RPT-E3 is adaptable for installation in standard E3 • “UTP” option available for unshielded, twisted-pair
Series System cabinets. Typically, the RPT-E3 module is copper wire only
mounted on standoffs on top of the right side of the ILI-MB- • 625K baud ARCNET Repeater
E3 module. Either unit can be easily connected to the
backbox or sub-assembly plate depending on the cabinet
model. Ordering Information
For instructions on installing the RPT-E3, refer to the E3
Model Description
Series® Expandable Emergency Evacuation Installation/
Operating Manual, Part Number: 9000-0574 or the RPT-E3 RPT-E3-UTP Network Repeaters, unshielded, twisted-pair
RPT-E3-FO Network Repeater, fiber-optic
Installation Instructions, Part Number: 9000-0580.

Specifications
Operating Voltage: 24 VDC FWR
(from PM-9 power supply)
Operating Current: 0.013 amp.
An ISO 9000-2000 Company
SIGNALING
Operating Temperature: 32° to 120° F (0° to 49° C)
Relative Humidity: 0 to 93%, non-condensing at FM City of

90° F (32° C) MEA Chicago


Approved
City of
Denver
APPROVED Approved
E3 Series® and NetSOLO® are registered trademarks of Honeywell International Inc.
Class 1 Approved
S1869 3025415 231-06-E 7165-0694:268 Class 2
7165-0694:269 High Rise

GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2007 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9020-0609 Rev. e1 page 1 of 1