PBM Protection, Control and Monitoring System
PBM Protection, Control and Monitoring System
PBM Protection, Control and Monitoring System
PBM B
base MODULE
Current measurement is obtained from the motor line through the From 0,8 up to 25 A with internal current transformers.
magnetic module without need of external current transformers. Over 25 A with external current transformers.
PBM-B1 PBM-B5
MODELS
PBM-B11 PBM-B12 PBM-B51 PBM-B52
Adjustment range Ib (A) 0,8-6A 0,8-6A 4-25A 4-25A
Auxiliary supply 110/230Vac-dc 24/48Vdc 110/230Vac-dc 24/48Vdc
Frequency 50/60/ variable (45-65) Hz
Maximum motor nominal voltage 1.000 Vac
CODE 17000 17002 17001 17003
For IN of the motor below the minimum setting IB Pass the cables several times (n) through the holes in the relay IB = n x IN
For IN of the motor above the maximum setting IB Use 3 CT .../5 and the relay PBM B and pass the secondary through the holes
OTHERS CHaracterIstics
Optional PBM-H display module HMI
Inputs 1 x PTC temperature sensor, 1 x Toroidal transformer (external earth fault), 1 x Digital input 24 Vdc
Outputs 2 x NO-NC contact
Short circuit withstand rating 5000 A to 0,5s (SCR 5000@0,5s)
Communication RS485 ModBus RTU
Signalling 5 signalling LEDs
Reset mode Manual, automatic and automatic time delayed
Test Specific test menu
Operating temperature - 10ºC + 60ºC
88
PBM H
This is an optional display module with an LCD screen for signalling, control and setting.
The LEDs can be configured and are identified by labels.
Access to menus is intuitive and direct, making protection system commissioning easier.
PBM B PBM H
108mm
Ø 10
98 mm
80
99
mm
78 17
,3
89