Service Manual 30RAN PDF
Service Manual 30RAN PDF
Service Manual 30RAN PDF
AquaSnapTMLiquid Chillers
With ComfortLinkTM Controls
50/60 Hz
Installation Instructions
CONTENTS
ELECTRIC SHOCK HAZARD
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1 Open all remote disconnects before servicing
this equipment.
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-24
Step 1 — Rig and Place the Unit. . . . . . . . . . . . . . . . . . 1
• RIGGING INSTALLATION
• PLACING UNIT
• MOUNTING UNIT Step 1 — Rig and Place the Unit
Step 2 — Check Compressor Mounting . . . . . . . . . . 3 RIGGING — Preferred method is with spreader bars from
Step 3 — Cooler Fluid and Drain Piping above the unit. Use hooks in lifting holes. Rig at a single point
Connections (Units Without with 4 cables or use spreader bars. All panels must be in place
Hydronic Packages). . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 when rigging. See rigging label on unit for details concerning
• PREPARATION FOR YEAR-ROUND shipping weights, distance between lifting holes, center of
OPERATION gravity, and lifting ring dimensions. See Fig. 3.
• PREPARATION FOR WINTER SHUTDOWN
Step 4 — Cooler Fluid and Drain Piping If overhead rigging is not possible, place chiller on skid or
Connections (Units With Factory-Installed pad for rolling or dragging. When rolling, use a minimum of
Hydronic Packages). . . . . . . . . . . . . . . . . . . . . . . . . . . 12 3 rollers. When dragging, pull the pad. Do not apply force to
• WATER SYSTEM OVERVIEW the unit. When in final position, raise from above to lift unit
• AIR SEPARATION off pad.
• WATER CONNECTIONS
• WATER SYSTEM CLEANING
• SYSTEM PRESSURIZATION
• FILLING THE SYSTEM All panels must be in place when rigging.
Step 5 — Make Electrical Connections . . . . . . . . . . 18
• POWER SUPPLY PLACING UNIT — There must be at least 3 ft (.9 m) for ser-
• POWER WIRING vice and for unrestricted airflow on all non-coil sides of unit,
• FIELD CONNECTIONS and a minimum of 3.5 ft (1.1 m) clear air space on coil sides.
Step 6 — Install Accessories . . . . . . . . . . . . . . . . . . . . 18 For multiple units, allow 8 ft (2.48 m) separation between units
• ELECTRICAL for airflow and service.
Step 7 — Refrigerant Circuit. . . . . . . . . . . . . . . . . . . . . 24 MOUNTING UNIT — When unit is in proper location, use
• LEAK TESTING of mounting holes in base rails is recommended for securing
• DEHYDRATION unit to supporting structure, or for mounting unit on vibration
• REFRIGERANT CHARGE isolators if required. See Fig. 3. Fasteners for mounting unit are
APPENDIX A (Pressure Drop Curves, field supplied. Be sure unit is level to within 1/8 in. per foot for
30RA010-055) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25-27 proper oil return to compressor.
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning equip-
ment can be hazardous due to system pressures, electrical
components, and equipment location (roofs, elevated struc-
tures, etc.).
Only trained, qualified installers and service mechanics
should install, start up, and service this equipment (Fig. 1).
Untrained personnel can perform basic maintenance func-
tions such as cleaning coils. All other operations should be
performed by trained service personnel.
When working on the equipment, observe precautions in the
literature and on tags, stickers, and labels attached to the
equipment.
• Follow all safety codes.
• Wear safety glasses and work gloves.
• Keep quenching cloth and fire extinguisher nearby when
brazing.
• Use care in handling, rigging, and setting bulky
equipment. See Tables 1A-1D for Physical Data. Refer Fig. 1 — Typical 30RA Unit (010-018 Shown)
to Fig. 2 for unit weights.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 PC 903 Catalog No. 533-00045 Printed in U.S.A. Form 30RA-12SI Pg 1 7-02 Replaces: 30RA-1SI
Tab 5c
B A
CONTROL
BOX END
C D
60 Hz 50 Hz
STD UNITS (without hydronic package) STD UNITS (without hydronic package)
POUNDS — ALUMINUM POUNDS — COPPER POUNDS — ALUMINUM POUNDS — COPPER
30RA 30RA 30RA 30RA
SIZE Total SIZE Total SIZE Total SIZE Total
A B C D Weight A B C D Weight A B C D Weight A B C D Weight
010 182 210 255 299 946 010 194 231 274 326 1025 010 186 211 262 317 976 010 198 232 281 346 1057
015 197 245 291 335 1068 015 216 280 321 382 1199 015 190 242 456 304 1192 015 200 280 494 349 1323
018 206 268 377 358 1209 018 220 303 411 404 1338 018 205 268 378 358 1209 018 219 304 412 403 1338
022 336 451 381 355 1523 022 364 521 418 410 1713 022 340 453 388 374 1555 022 368 520 425 431 1744
025 350 464 395 380 1589 025 380 532 432 436 1780 025 354 468 410 398 1630 025 382 534 448 456 1820
030 378 518 409 400 1705 030 409 606 441 474 1930 032 746 641 604 848 2839 032 851 717 691 960 3219
035 748 642 604 850 2844 035 854 721 691 958 3224 035 768 652 620 911 2951 035 872 729 708 1022 3331
040 763 653 616 882 2914 040 869 731 702 992 3294 042 867 714 761 937 3279 042 968 795 851 1045 3659
045 860 709 746 903 3218 045 965 790 833 1011 3599 045 886 729 800 985 3400 045 1009 823 904 1115 3851
050 876 721 770 946 3313 050 978 805 859 1051 3693
055 977 753 831 954 3515 055 1096 857 931 1082 3966
KILOGRAMS — ALUMINUM KILOGRAMS — COPPER
30RA 30RA
SIZE Total SIZE Total
KILOGRAMS — ALUMINUM KILOGRAMS — COPPER A B C D Weight A B C D Weight
30RA 30RA
SIZE Total SIZE Total 010 84 96 119 144 443 010 90 105 127 157 479
A B C D Weight A B C D Weight
015 86 110 207 138 541 015 91 127 224 158 600
010 83 95 116 136 430 010 88 105 124 148 465 018 93 122 171 162 548 018 99 138 187 183 607
015 89 111 132 152 484 015 98 127 146 173 544 022 154 205 176 170 705 022 167 236 193 195 791
018 93 122 171 162 548 018 100 137 186 183 606 025 161 212 186 181 740 025 173 242 203 207 825
022 152 205 173 161 691 022 165 236 190 186 777 032 338 291 274 385 1288 032 386 325 313 435 1459
025 159 210 179 172 720 025 172 241 196 198 807 035 348 296 281 413 1338 035 396 331 321 464 1512
030 171 235 186 181 773 030 186 275 200 215 876 042 393 324 345 425 1487 042 439 361 386 474 1660
035 339 291 274 386 1290 035 387 327 313 435 1462 045 402 331 363 447 1543 045 458 373 410 506 1747
040 346 296 279 400 1321 040 394 332 318 450 1494
045 390 322 338 410 1460 045 438 358 378 459 1633
050 397 327 349 429 1502 050 444 365 390 477 1676 SINGLE PUMP UNITS
055 443 342 377 433 1595 055 497 389 422 491 1799
POUNDS — ALUMINUM POUNDS — COPPER
30RA 30RA
SIZE Total SIZE Total
SINGLE PUMP UNITS A B C D
Weight A B C D Weight
POUNDS — ALUMINUM POUNDS — COPPER 010 213 241 300 362 1116 010 225 262 319 391 1197
30RA 30RA 015 212 270 510 340 1332 015 222 308 548 385 1463
SIZE Total SIZE Total 018 229 299 422 399 1349 018 243 335 456 444 1478
A B C D A B C D
Weight Weight 022 371 494 423 408 1695 022 399 561 460 465 1884
010 209 241 293 343 1086 010 221 262 312 370 1165 025 384 508 445 432 1770 025 412 574 483 490 1960
015 223 277 329 379 1208 015 242 312 359 426 1339 032 799 686 647 908 3039 032 904 762 734 1020 3419
018 230 299 421 399 1349 018 244 334 455 445 1478 035 820 696 662 973 3151 035 924 773 750 1084 3531
022 367 492 416 388 1663 022 395 562 453 443 1853 042 920 758 807 994 3479 042 1021 839 897 1102 3859
025 381 505 430 413 1729 025 411 573 467 469 1920 045 938 772 847 1043 3600 045 1061 866 951 1173 4051
030 409 561 443 433 1845 030 440 649 475 507 2070
035 801 687 646 910 3044 035 907 766 733 1018 3424
040 815 698 658 943 3114 040 921 776 744 1053 3494 KILOGRAMS — ALUMINUM KILOGRAMS — COPPER
30RA 30RA
045 913 753 792 959 3418 045 1018 834 879 1067 3799 SIZE Total SIZE Total
A B C D Weight A B C D Weight
050 929 765 816 1003 3513 050 1031 849 905 1108 3893
055 1033 796 878 1008 3715 055 1152 900 978 1136 4166 010 96 110 136 165 507 010 102 119 144 178 543
015 96 123 231 154 604 015 101 140 248 174 663
KILOGRAMS — ALUMINUM KILOGRAMS — COPPER 018 104 136 191 181 612 018 110 152 207 202 671
30RA 30RA 022 168 223 192 185 768 022 181 254 209 210 854
SIZE Total SIZE Total 025 175 230 202 197 804 025 187 260 219 223 889
A B C D A B C D
Weight Weight 032 362 311 293 412 1378 032 410 345 332 462 1549
010 95 109 133 156 493 010 108 129 152 181 570 035 372 316 300 441 1429 035 420 351 340 492 1603
015 101 126 149 172 548 015 117 151 174 206 648 042 417 344 366 451 1578 042 463 381 407 500 1751
018 104 136 191 181 612 018 117 161 218 215 711 045 426 350 384 473 1633 045 482 392 431 532 1837
022 166 224 189 176 755 022 187 268 215 211 881
025 173 229 195 187 784 025 194 272 221 224 911
030 185 254 201 196 836 030 208 308 224 241 981 DUAL PUMP UNITS
035 363 311 293 413 1380 035 422 356 341 474 1593
040 370 316 298 427 1411 040 429 361 346 490 1626 POUNDS — ALUMINUM POUNDS — COPPER
30RA 30RA
045 414 342 359 435 1550 045 473 387 408 496 1764 SIZE Total SIZE Total
050 421 347 370 455 1593 050 479 394 421 514 1808 A B C D A B C D
Weight Weight
055 468 361 398 458 1685 055 533 417 453 527 1930 010 213 241 300 362 1116 010 241 282 342 421 1287
015 212 270 510 340 1332 015 235 329 580 410 1553
DUAL PUMP UNITS 018 229 299 422 399 1349 018 257 356 483 472 1568
022 371 494 423 408 1695 022 417 589 481 488 1974
POUNDS — ALUMINUM POUNDS — COPPER 025 384 508 445 432 1770 025 430 601 505 514 2050
30RA 30RA 032 799 686 647 908 3039 032 928 782 753 1046 3509
SIZE Total SIZE Total 035 820 696 662 973 3151 035 948 792 770 1111 3621
A B C D Weight A B C D Weight
042 920 758 807 994 3479 042 1045 858 918 1128 3949
010 226 262 316 372 1176 010 238 283 335 399 1255 045 938 772 847 1043 3600 045 1085 885 972 1199 4141
015 238 299 353 408 1298 015 257 334 383 455 1429
018 244 320 448 427 1439 018 258 355 482 473 1568
022 385 521 437 410 1753 022 413 591 474 465 1943 KILOGRAMS — ALUMINUM KILOGRAMS — COPPER
30RA 30RA
025 399 533 451 436 1819 025 429 601 488 492 2010 SIZE Total SIZE Total
A B C D Weight A B C D Weight
030 427 590 462 456 1935 030 458 678 494 530 2160
035 825 707 666 936 3134 035 931 786 753 1044 3514 010 96 110 136 165 507 010 110 128 155 191 584
040 840 717 678 969 3204 040 946 795 764 1079 3584 015 96 123 231 154 604 015 107 149 263 186 706
045 938 773 813 984 3508 045 1043 854 900 1092 3889 018 104 136 191 181 612 018 116 162 219 214 711
050 953 784 837 1029 3603 050 1055 868 926 1134 3983 022 168 223 192 185 768 022 189 267 218 221 895
055 1057 816 899 1033 3805 055 1176 920 999 1161 4256 025 175 230 202 197 804 025 195 273 229 233 930
032 362 311 293 412 1378 032 421 354 341 474 1590
KILOGRAMS — ALUMINUM KILOGRAMS — COPPER 035 372 316 300 441 1429 035 430 360 349 504 1643
30RA 30RA 042 417 344 366 451 1578 042 474 390 417 512 1793
SIZE Total SIZE Total 045 426 350 384 473 1633 045 492 401 441 544 1878
A B C D Weight A B C D Weight
010 103 119 144 169 535 010 108 129 152 181 570 LEGEND
015 108 135 160 185 588 015 117 151 174 206 648
018 110 146 203 194 653 018 117 161 218 215 711 Aluminum — Aluminum Condenser Coil Fins
022 174 237 198 186 795 022 187 268 215 211 881 Copper — Copper Condenser Coil Fins
025 181 241 204 198 824 025 194 272 221 224 911
030 193 268 210 207 878 030 208 308 224 241 981
035 374 320 302 425 1421 035 422 356 341 474 1593
040 381 325 307 440 1453 040 429 361 346 490 1626
045 425 351 368 447 1591 045 473 387 408 496 1764
050 432 356 380 466 1634 050 479 394 421 514 1808
055 479 370 408 469 1726 055 533 417 453 527 1930
2
Step 2 — Check Compressor Mounting — As fused disconnect. Identify disconnect as heat tape power source
shipped, each compressor is held down by 4 bolts. After unit is with a warning that power must not be turned off except when
installed, verify mounting bolt torque 12 to14 ft-lb. unit is being serviced.
Step 3 — Cooler Fluid and Drain Piping Con- The cooler drain connection is at the opposite end from the
compressor (see Fig. 4-9). Insulate the drain piping (in the
nections (Units Without Hydronic Packages) — same manner as the chilled water piping) for at least one ft
These chillers are supplied with factory-installed strainer (305 mm) from cooler.
(including blow-down valve) in the entering fluid piping and
flow switch in the leaving fluid piping. Flow switch wiring is PREPARATION FOR YEAR-ROUND OPERATION — If
factory installed. unit is in operation year-round, add sufficient inhibited ethyl-
ene glycol or other suitable inhibited antifreeze solution to
Piping connections are located on the left side of the chiller chilled water to prevent freezing under low-ambient operating
when facing the control panel for 010-030 sizes and at the end conditions. Consult local water treatment specialist on charac-
opposite the control panel for 032-055 sizes. See Fig. 4-9 teristics of water and recommended inhibitor.
depending on model.
PREPARATION FOR WINTER SHUTDOWN — Do not
All sizes have FPT connections as shown in the Physical shut off electrical disconnect during off-season shutdown. At
Data tables. Provide a means of venting air from the high point end of cooling season:
of the field-installed piping as required. Install field-supplied
drains in both the entering and leaving fluid connections. 1. Position LOCAL/OFF/REMOTE switch to OFF.
After field piping is complete, freeze-up protection is rec- 2. Drain water from system.
ommended using inhibited ethylene glycol or other suitable in- 3. Replace drain plug and put 2 gallons (8 liters) of inhibited
hibited antifreeze solution and electric heat tapes in areas ethylene glycol (or other suitable inhibited anti-freeze) in
where piping is exposed to low ambient temperatures (34 F cooler to prevent freezing of residual water.
[1 °C] or below). Heat tapes should possess a rating for area 4. At the beginning of the next cooling season, refill cooler
ambients and be covered with a suitable thickness of closed- and add recommended inhibitor.
cell insulation. Route power for heating tapes from a separately
3
Table 1A — Physical Data, 30RA — 60 Hz English
UNIT 30RA 010 015 018 022 025 030 035 040 045 050 055
REFRIGERANT TYPE R-22, TXV Controlled System
Refrigerant Charge (lb) Ckt A/Ckt B 18/— 27/— 36/— 37/— 38/— 48/— 44/30 45/30 44/44 45/45 55/55
COMPRESSORS Scroll, Hermetic
Quantity 1 1 2 2 2 2 3 3 4 4 4
Speed (Rpm) 3500
(Qty) Ckt A (1) SM115, (1) SM115, (1) SM125,
(1) SM125 (1) SM185 (2) SM110 (2) SM160 (2) SM185 (1) SM160 (2) SM160 (2) SM160 (2) SM185
(1) SM160 (1) SM160
(Qty) Ckt B (1) SM125,
— — — — — — (1) SM185 (1) SM185 (2) SM160 (2) SM185
(1) SM160
Oil Charge (Compressor/Pt) SM110/5.7, SM115/6.7, SM125/6.7, SM160/7.0, SM185/11.6
No. Capacity Steps
Standard 1 1 2 2 2 2 3 3 4 4 4
Optional (Maximum) 2 2 3 3 3 3 4 4 5 5 5
Minimum Capacity Step (%)
Standard 100 100 50 42 50 50 25 32 22 25 25
Optional 69 79 32 27 38 39 16 24 15 19 20
COOLER Welded, Direct-Expansion Plate Heat Exchanger
Net Fluid Volume (gal) 1.12 1.61 1.86 2.41 2.84 3.40 6.30 7.00 6.55 7.44 8.56
Maximum Refrigerant Pressure (psig) 450 450 450 450 450 450 450 450 450 450 450
Maximum Fluid Side Pressure 150 150 150 150 150 150 150 150 150 150 150
Without Pump(s) (psig)
Maximum Fluid Side Pressure 150 150 150 150 150 150 150 150 150 150 150
With Pump(s) (psig)
FLUID CONNECTIONS (in.)
Inlet and Outlet, FPT 2 2 2 2 2 2 21/2 21/2 21/2 21/2 21/2
Drain (NPT) 1/ 1/ 1/ 1/ 1/ 1/ 1/ 1/ 1/ 1/ 1/
2 2 2 2 2 2 2 2 2 2 2
CONDENSER FANS
Standard Low Noise Type
Fan Speed (Rpm) 1140/570 1140/570 1140/570 —/850 —/850 —/850 —/850 —/850 —/850 —/850 —/850
Standard/Low Noise
No. Blades...Diameter (in.) 11...30/ 11...30/ 11...30/ 11...30/ 11...30/
15...30/— 15...30/— 15...30/— 11...30/— 11...30/— 11...30/—
Ckt A/Ckt B 11...30 11...30 11...30 11...30 11...30
2...2.0 (A), 2...2.0 (A),
No. Fans...Total kW 1...1.8 1...1.8 1...1.8 2...2.0 2...2.0 2...2.0 4...4.0 4...4.0 4...4.0
1...1.8 (B) 1...1.8 (B)
Total Airflow (Cfm) 10,500 10,500 10,500 13,600 13,600 14,500 21,000 21,000 27,300 27,300 29,000
CONDENSER COILS
Quantity...No. Rows 1...2 1...3 1...3 1...3 1...3 1...3 2...3 2...3 2...3 2...3 2...3
Total Face Area (sq ft) 23 23 23 32 32 40 55 55 64 64 80
HYDRONIC MODULE (Optional)* Pump(s), Strainer W/Blowdown Valve, Expansion Tank, Pressure Gages, Drain and Vent Plugs, Flow Switch, and Balance Valve
Pump Single or Dual, Close-Coupled Centrifugal Pump(s), 3500 Rpm
Expansion Tank Volume (gal) 4.4 10.3
4
Table 1C — Physical Data, 30RA — 60 Hz SI
UNIT 30RA 010 015 018 022 025 030 035 040 045 050 055
REFRIGERANT TYPE R-22, TXV Controlled System
Refrigerant Charge (kg) Ckt A/Ckt B 8.2/— 12.2/— 16.3/— 16.8/— 17.2/— 21.8/— 20.0/13.6 20.4/13.6 20.0/20.0 20.4/20.4 25.0/25.0
COMPRESSORS Scroll, Hermetic
Quantity 1 1 2 2 2 2 3 3 4 4 4
Speed (r/s) 58.3
(1) SM115, (2) SM160 (2) SM185 (1)
(Qty) Ckt A SM115, (1) SM125,
(1) SM125 (1) SM185 (2) SM110 (2) SM160 (2) SM160 (2) SM185
(1) SM160 (1) SM160 (1) SM160
(Qty) Ckt B (1) SM125,
— — — — — — (1) SM185 (1) SM185 (2) SM160 (2) SM185
(1) SM160
Oil Charge (Compressor/L) SM110/2.7, SM115/3.2, SM125/3.2, SM160/3.3, SM185/5.5
No. Capacity Steps
Standard 1 1 2 2 2 2 3 3 4 4 4
Optional (Maximum) 2 2 3 3 3 3 4 4 5 5 5
Minimum Capacity Step (%)
Standard 100 100 50 42 50 50 25 32 22 25 25
Optional 69 79 32 27 38 39 16 24 15 19 20
COOLER Welded, Direct-Expansion Plate Heat Exchanger
Net Fluid Volume (L) 4.22 6.08 7.03 9.12 10.75 12.84 23.84 26.49 24.79 28.12 32.34
Maximum Refrigerant Pressure (kPa) 3103 3103 3103 3103 3103 3103 3103 3103 3103 3103 3103
Maximum Fluid Side Pressure 1034 1034 1034 1034 1034 1034 1034 1034 1034 1034 1034
Without Pump(s) (kPa)
Maximum Fluid Side Pressure 1034 1034 1034 1034 1034 1034 1034 1034 1034 1034 1034
With Pump(s) (kPa)
FLUID CONNECTIONS (mm)
Inlet and Outlet, FPT 50.8 50.8 50.8 50.8 50.8 50.8 63.5 63.5 63.5 63.5 63.5
Drain (NPT) 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7
CONDENSER FANS
Standard Low Noise Type
Fan Speed (r/s) 19/9.5 19/9.5 19/9.5 —/14.2 —/14.2 —/14.2 —/14.2 —/14.2 —/14.2 —/14.2 —/14.2
Standard/Low Noise
No. Blades...Diameter (mm) 11...762/ 11...762/ 11...762/ 11...762/ 11...762/
15...762/— 15...762/— 15...762/— 11...762/— 11...762/— 11...762/—
Ckt A/Ckt B 15...762 15...762 11...762 11...762 11...762
2...2.0 (A), 2...2.0 (A),
No. Fans...Total kW 1...1.8 1...1.8 1...1.8 2...2.0 2...2.0 2...2.0 4...4.0 4...4.0 4...4.0
1...1.8 (B) 1...1.8 (B)
Total Airflow (L/s) 4,955 4,955 4,955 6,419 6,419 6,843 9,595 9,595 12,884 12,884 13,687
CONDENSER COILS
Quantity...No. Rows 1...2 1...3 1...3 1...3 1...3 1...3 2...3 2...3 2...3 2...3 2...3
Total Face Area (sq m) 2.14 2.14 2.14 2.97 2.97 3.72 5.11 5.11 5.95 5.95 7.43
HYDRONIC MODULE (Optional)* Pump(s), Strainer W/Blowdown Valve, Expansion Tank, Pressure Gages, Drain and Vent Plugs, Flow Switch, and Balance Valve
Pump Single or Dual, Close-Coupled Centrifugal Pump(s), 58.3 r/s
Expansion Tank Volume (L) 16.5 39
5
NOTES:
1. Unit must have clearances for airflow as follows:
Top — Do not restrict in any way.
Coil Side — 31/2 ft [1067 mm] from solid surface side.
Ends — 3 ft [914 mm] from solid surface (for service
access).
2. Coil side clearance with accessory hail guard
installed is 3 ft [914 mm] to outside edge of hail guard
top panel.
3. Coil side clearance for multiple chiller installation is
6 ft [1981 mm].
4. Flow switch is factory installed in leaving fluid piping.
Strainer is factory installed for entering fluid piping.
6
Fig. 4 — Dimensions — 30RA010,015,018 AquaSnap™ Chiller
NOTES:
1. Unit must have clearances for airflow as
follows:
Top — Do not restrict in any way.
Coil Side — 31/2 ft [1067 mm] from solid
surface side.
Ends — 3 ft [914 mm] from solid surface
(for service access).
2. Coil side clearance with accessory hail
guard installed is 3 ft [914 mm] to outside
edge of hail guard top panel.
3. Coil side clearance for multiple chiller
installation is 6 ft [1981 mm].
4. Flow switch is factory installed in leaving
fluid piping. Strainer is factory installed
for entering fluid piping.
7
Fig. 5 — Dimensions — 30RA022,025 AquaSnap™ Chiller
NOTES:
1. Unit must have clearances for airflow as
follows:
Top — Do not restrict in any way.
Coil Side — 31/2 ft [1067 mm] from solid
surface side.
Ends — 3 ft [914 mm] from solid surface
(for service access).
2. Coil side clearance with accessory hail
guard installed is 3 ft [914 mm] to out-
side edge of hail guard top panel.
3. Coil side clearance for multiple chiller
installation is 6 ft [1981 mm].
4. Flow switch is factory installed in leaving
fluid piping. Strainer is factory installed
for entering fluid piping.
8
Fig. 6 — Dimensions — 30RA030 AquaSnap™ Chiller
NOTES:
1. Unit must have clearances for airflow as follows:
Top — Do not restrict in any way.
Coil Side — 31/2 ft [1067 mm] from solid surface side.
Ends — 3 ft [914 mm] from solid surface (for service
access).
2. Coil side clearance with accessory hail guard
installed is 3 ft [914 mm] to outside edge of hail guard
top panel.
3. Coil side clearance for multiple chiller installation is
6 ft [1981 mm].
4. Flow switch is factory installed in leaving fluid piping.
Strainer is factory installed for entering fluid piping.
9
Fig. 7 — Dimensions — 30RA032-040 AquaSnap™ Chiller
NOTES:
1. Unit must have clearances for airflow as follows:
Top — Do not restrict in any way.
Coil Side — 31/2 ft [1067 mm] from solid surface side.
Ends — 3 ft [914 mm] from solid surface (for service
access).
2. Coil side clearance with accessory hail guard
installed is 3 ft [914 mm] to outside edge of hail guard
top panel.
3. Coil side clearance for multiple chiller installation is
6 ft [1981 mm].
4. Flow switch is factory installed in leaving fluid piping.
Strainer is factory installed for entering fluid piping.
10
Fig. 8 — Dimensions — 30RA042-050 AquaSnap™ Chiller
NOTES:
1. Unit must have clearances for airflow as follows:
Top — Do not restrict in any way.
Coil Side — 31/2 ft [1067 mm] from solid surface side.
Ends — 3 ft [914 mm] from solid surface (for service
access).
2. Coil side clearance with accessory hail guard
installed is 3 ft [914 mm] to outside edge of hail guard
top panel.
3. Coil side clearance for multiple chiller installation is
6 ft [1981 mm].
4. Flow switch is factory installed in leaving fluid piping.
Strainer is factory installed for entering fluid piping.
11
Fig. 9 — Dimensions — 30RA055 AquaSnap™ Chiller
Step 4 — Cooler Fluid and Drain Piping Con-
nections (Units with Factory-Installed Hy- 3
dronic Packages)
WATER SYSTEM OVERVIEW — The 30RA chillers with
factory-installed hydronic packages are designed for use with
closed systems, meaning that there is no more than one water- 5
air interface in the water loop. Cooling tower loops, for
example, have two water-air interfaces (sump and nozzles) and
would thus be classified as open, whereas a correctly designed
chilled water loop with the only water-air interface being in the
expansion tank is closed. Since closed and open water systems
behave very differently, these instructions assume that the
chilled water loop is closed. A system installed incorrectly such
that air is not handled properly — pipe leaks, vent leaks, air in
pipes, etc. — may behave as an open system and thus have
unsatisfactory operation. Pump seal wear can also cause leaks
that cause poor system operation.
2 4
Proper closed system design and installation procedures
should be followed closely. The system must be constructed
with pressure tight components and thoroughly tested for 7
installation leaks. Factory-supplied hydronic systems are avail-
able with single or dual (for back-up) pumps. The factory-
installed system includes all of the components within the 1
dashed lines in Fig. 10.
Installation of water systems should follow sound engineer-
ing practice as well as applicable local and industry standards. 6
Improperly designed or installed systems may cause unsatis-
factory operation and/or system failure. Consult a water treat-
ment specialist or appropriate literature for information regard- LEGEND
ing filtration, water treatment, and control devices. Figure 10 1 — Strainer 5 — Flow Switch
shows a typical installation with components that might be in- 2 — Blow-Down Valve 6 — Field Connections
3 — Discharge Check Valve 7 — Heater
stalled with the hydronic package of the 30RA unit. Figure 11 (Dual Pumps Only)
illustrates a typical dual pump package for the 010-030 size 4 — Balancing Valve with Drain Plug
models.
NOTE: It is recommended that isolation (shut-off) valves be Fig. 11 — Typical Dual Pump Package
placed exterior to the unit to allow removal and service of
the entire pump assembly, if necessary. Also, if the unit is
isolated with valves, a properly sized pressure relief valve
should be installed in the piping between the unit and the
valves, following all applicable state and local codes.
2 6
14 7
LEGEND
5 1 — Strainer/Blow-Down Valve
12 11 3
2 — Expansion Tank
3 — Pump
4 — Electric Heater
5 — Air Vent Connection Port
1 6 — Pressure Gages/Petcocks
10 7 — Heat Exchanger
4
8 — Flow Switch
13 9 — Balancing Valve Balance
Valve/Drain Plug
10 — Pressure Relief
11 — Isolation Valves
12 — Flex Connections
13 — Pressure Reducing/Fill Valve
14 — Air Separator and Vent
6
FS
12 11 9
8
12
AIR SEPARATION — For proper system operation, it is 2. Be sure to use a cleaning agent that is compatible with all
essential that water loops be installed with proper means to system materials. Be especially careful if the system
manage air in the system. Free air in the system can cause contains any galvanized or aluminum components. Both
noise, reduce terminal output, stop flow, or even cause pump detergent-dispersant and alkaline-dispersant cleaning
failure due to pump cavitation. For closed systems, equipment agents are available.
should be provided to eliminate all air from the system. 3. It is a good idea to fill the system through a water meter.
The amount of air that water can hold in solution depends This provides a reference point for the future for loop
on the pressure and temperature of the water/air mixture. Air is volume readings, but it also establishes the correct
less soluble at higher temperatures and at lower pressures. quantity of cleaner needed in order to get the required
Therefore, separation can best be done at the point of highest concentration.
water temperature and lowest pressure. Typically, this point 4. Use a feeder/transfer pump to mix the solution and fill the
would be on the suction side of the pump as the water is return- system. Circulate the cleaning system for the length of
ing from the system or terminals. Generally speaking, this is time recommended by the cleaning agent manufacturer.
the best place to install an air separator, if possible. a. After cleaning, drain the cleaning fluid and flush the
1. Install automatic air vents at all high points in the system. system with fresh water.
(If the 30RA unit is located at the high point of the b. A slight amount of cleaning residue in the system can
system, a vent can be installed on the piping entering the help keep the desired, slightly alkaline, water pH of 8
heat exchanger on the ¼-in. NPT female port.) to 9. Avoid a pH greater than 10, since this will
2. Install an air separator in the water loop, at the place adversely affect pump seal components.
where the water is at higher temperatures and lower c. A side stream filter is recommended (see Fig. 14)
pressures — usually in the chilled water return piping. during the cleaning process. Filter side flow rate
On a primary-secondary system, the highest temperature should be enough to filter the entire water volume
water is normally in the secondary loop, close to the every 3 to 4 hours. Change filters as often as neces-
decoupler. Preference should be given to that point on the sary during the cleaning process.
system (see Fig. 12). In-line or centrifugal air separators d. Remove temporary bypass when cleaning is
are readily available in the field. complete.
It may not be possible to install air separators at the place of A strainer with a blow-down valve is standard on all 30RA
lowest pressure and highest temperature. In such cases, prefer- units, both with and without hydronic packages. The blow-
ence should be given to the points of highest temperature. It is down valve allows removal of particulates caught in the strain-
important that pipe be sized correctly so that free air can be er without complete removal of the screen. A female NPT
moved to the point of separation. Generally, a water velocity of connection is provided on the valve, allowing hose connection
at least 2 feet per second will keep free air entrained and for drainage outside the unit.
prevent it from forming air pockets.
The Carrier ComfortLink™ controls provided have a built-
Automatic vents should be installed at all physically elevat- in feature to remind building owners or operators to clean the
ed points in the system so that air can be eliminated during strainer by discharging the blow-down valve at a pre-set time
system operation. Provision should also be made for manual interval. Properly installed and cleaned systems will rarely
venting during the water loop fill. It is important that the need the strainer cleaned after the initial fill. This time interval
automatic vents be located in accessible locations for mainte- is user-configurable.
nance purposes, and that they be located where they can be
prevented from freezing. Table 2 — Water Quality Characteristics
WATER CONNECTIONS — The water connections are cop- and Limitations
per or brass FPT. Any connecting pipe to the 30RA pump
package must be of a material that will not cause any galvanic WATER CHARACTERISTIC QUALITY LIMITATION
corrosion. For this reason, galvanized steel pipe or other dis- Alkalinity (HCO3-) 70 – 300 ppm
similar metals must not be used unless joined by a dielectric Sulfate (SO42-) Less than 70 ppm
coupling. The connection sizes for the 30RA unit sizes 010- HCO3-/SO42- Greater than 1.0
030 are 2-in. FPT. Sizes 032-055 use 21/2-in. FPT. Electrical Conductivity 10 – 500 µS/cm
Follow the steps below when connecting pipe to the unit pH 7.5 – 9.0
water connections: Ammonium (NH3) Less than 2 ppm
Chorides (Cl-) Less than 300 ppm
1. Remove side panel(s) of unit to access the piping area. Free chlorine (Cl2) Less than 1 ppm
2. Remove access covers of pump box. Hydrogen Sulfide (H2S)* Less than 0.05 ppm
3. Use a backup wrench on internal water connections to Free (aggressive) Carbon Less than 5 ppm
prevent twisting of internal piping, using a good sealant Dioxide (CO2)†
that will also allow for disconnecting the pipes if needed. Total Hardness (dH) 4.0 – 8.5
4. After connection is made, replace access covers of pump Nitrate (NO3) Less than 100 ppm
box and side panels of unit. Iron (Fe) Less than 0.2 ppm
WATER SYSTEM CLEANING — Proper water system Aluminum (Al) Less than 0.2 ppm
cleaning is of vital importance. Excessive particulates in the Manganese (Mn) Less than 0.1 ppm
water system can cause excessive pump seal wear, reduce or *Sulfides in the water quickly oxidize when exposed to air, requiring that
stop flow, and cause damage of other components. Water no agitation occur as the sample is taken. Unless tested immediately
at the site, the sample will require stabilization with a few drops of one
quality should be maintained within the limits indicated in Molar zinc acetate solution, allowing accurate sulfide determination up
Table 2. to 24 hours after sampling. A low pH and high alkalinity cause system
problems, even when both values are within the ranges shown. The
1. Install a temporary bypass around the chiller to avoid cir- term pH refers to the acidity, basicity, or neutrality of the water supply.
culating dirty water and particulates into the pump pack- Below 7.0, the water is considered to be acidic. Above 7.0, water is
age and chiller during the flush. Use a temporary circulat- considered to be basic. Neutral water contains a pH of 7.0.
†Dissolved carbon dioxide can either be calculated from the pH and
ing pump during the cleaning process. Also, be sure that total alkalinity values, shown below, or measured on the site using a
there is capability to fully drain the system after cleaning. test kit. Dissolved Carbon Dioxide, PPM = TA x 2[(6.3-pH)/0.3] where TA
(See Fig 13.) = Total Alkalinity, PPM as CaCO3.
13
Distribution Pump
Chiller 1
Chiller 2
Zone 1
Zone 2
Zone 3
Decoupler Expansion
Tank(s)
Air Separator
with Vent
NOTE: Expansion tanks in the 30RA hydronic kits must be disconnected for chillers placed parallel in the primary water loop.
Fig. 12 — Typical Air Separator and Expansion Tank Location on Primary-Secondary Systems
SYSTEM SYSTEM
POT FEEDER AND POT FEEDER AND
TRANSFER PUMP TRANSFER PUMP
DILUTED DILUTED
CLEANING SIDE CLEANING
AGENT STREAM AGENT
FILTER
x x
TEMPORARY 30RA UNIT TEMPORARY 30RA UNIT
PUMP PUMP
x x
TEMPORARY TEMPORARY
BYPASS BYPASS
TO DRAIN TO DRAIN
Fig. 13 — Typical Set Up for Cleaning Process Fig. 14 — Cleaning Using a Side Stream Filter
SYSTEM PRESSURIZATION — A proper initial cold fill Table 3 — “X” Factor for Setting Tank Pressure
pressure must be established before the filling of the unit. The
initial cold fill pressure is the pressure applied at the filling ETHYLENE PROPYLENE
% GLYCOL GLYCOL GLYCOL
point to fill a system to its highest point, plus a minimum pres-
sure at the top of the system (4 psi minimum) to operate air 0 (pure water) 2.31 2.31
vents and positively pressurize the system. 10 2.36 2.33
20 2.38 2.36
The compression tank (sometimes called expansion tank) is
very important to system pressurization. The compression tank 30 2.40 2.38
actually serves several purposes: 40 2.43 2.38
50 2.47 2.40
1. Provide Net Positive Suction Head Required (NPSHR)
for the pump to operate satisfactorily. NOTE: If expansion tanks are placed elsewhere in the system this
method cannot be used since extra pressure drop between the tank
2. Set system pressure. and the pump must be accounted for.
3. Accommodate expansion/contraction of water due to
temperature changes. NOTE: If the system requires a pre-charge greater than
4. Acts as a pressure reference for the pump. 40 psig, increase pressure as described below.
The compression tank pressure must be set BEFORE the Expansion Tank Pre-Charge — To pre-charge the expansion
system is filled. The tanks are pre-charged at the factory to tank, do the following steps:
40 psig. If the 30RA unit with expansion tank is the high point 1. Check the tank air pressure at the pre-charge connection
in the system, tank pre-charge pressure of 40 psig will be with an accurate pressure gage. Adjust as needed.
adequate. If the 30RA unit with expansion tank is NOT at the 2. If additional pressure is required, charge the tank with oil-
high point in the system, then the minimum pre-charge free compressed air or nitrogen gas. Occasionally check
pressure for the water system must be determined using Table 3 the pressure as when filling a tire.
and the method below:
3. Check the air valve for leakage. If it leaks, relieve the
Tank Pressure = 4 + (height from tank to top of pressure and replace the core with a Schraeder type tire
system in feet/“X”) core. DO NOT depend on the valve cap to seal the leak.
For example, assuming a system containing a 20% concen- Once the system is pressurized, the pressure at the connec-
tration of ethylene glycol and 50 feet in height from the top of tion point of the expansion tank to water piping will not change
the system to the expansion tank, the minimum tank pre- unless the water loop volume changes (either due to addition/
charge pressure would be: subtraction of water or temperature expansion/contraction).
Tank Pressure = 4 + (50 ÷ 2.38) = 25.0 psig The pressure at this point remains the same regardless of
whether or not the pump is running.
14
Since the expansion tank acts as a reference point for the 3. Open the blow-down valve to flush the strainer.
pump, there cannot be two reference points (two expansion Normally, a closed system needs to be filled only once. The
tanks) in a system (unless manifolded together). If system actual filling process is generally a fairly simple procedure. All
volume or other design considerations warrant the placement air should be purged or vented from the system. Thorough
of another expansion tank somewhere in the system, the expan- venting at the high points and circulation at room temperature
sion tank in the 30RA hydronic package MUST be disconnect- for several hours is recommended.
ed from its hose and the end of the hose securely plugged.
NOTE: Local codes concerning backflow devices and other
This is also true for applications where two or more 30RA protection of the city water system should be consulted and
chillers are placed in parallel. There should not be more than followed to prevent contamination of the public water
one expansion tank in the system (unless manifolded together supply. This is especially important when anti-freeze is used
as seen in Fig. 12). The expansion tanks must be disconnected in the system.
from the 30RA hydronic package. It is permissible to install the
expansion tank(s) in a portion of the return water line that is Set Water Flow Rate — Once the system is cleaned, pressur-
common to all pumps, providing that the tank is properly sized ized, and filled, the flow rate through the chiller needs to be
for combined system volume. established. On units with the hydronic package, this can best
be done using the balancing valve.
If the application involves two or more chillers in a primary-
secondary system, a common place for mounting the In order to adjust the balancing valve, put a differential
expansion tank is in the chilled water return line, just before the pressure gage across the pressure taps on the valve. Make sure
decoupler. See Fig. 12 for placement of expansion tank in that all system isolation and control valves are open. Use
primary-secondary systems. Tables 4 and 5 or a Bell & Gossett balancing valve calculator to
determine GPM. To read Tables 4 and 5:
The expansion tank included in the 30RA hydronic package
is a diaphragm tank, meaning that a flexible diaphragm physi- 1. Measure the pressure drop across the balancing valve. If
cally separates the water/air interface. With this type of expan- the pressure reading is in psi, multiply psi x 2.31 to con-
sion tank, it is undesirable to have any air in the water loop. See vert to feet of water before using Tables 4 and 5.
the section on air separation on page 13 for instructions on 2. Go to the row in the chart corresponding to the setting on
providing air separation equipment. the valve, interpolating if necessary.
FILLING THE SYSTEM — The initial fill of the chilled 3. The GPM corresponding to the pressure drop measured is
water system must accomplish three purposes: the flow through the balancing valve.
1. The entire piping system must be filled with water. NOTE: Carrier recommends a differential pressure gage when
measuring pressures across the pumps or balancing valves.
2. The pressure at the top of the system must be high enough This provides for greater accuracy and reduces error build-up
to vent air from the system (usually 4 psig is adequate for
most vents). that often occurs when subtracting pressures made by different
gages.
3. The pressure at all points in the system must be high
enough to prevent flashing in the piping or cavitation in On primary/secondary systems, it is advisable to set the
the pump. 30RA balancing valve to maintain design flow plus 10%
through the chiller.
The pressure created by an operating pump affects system
pressure at all points except one — the connection of the A rough estimate of water flow can also be obtained from
the pressure gages across the 30RA heat exchanger.
compression tank to the system. This is the only location in the Figures 15A-16B show the relationship between GPM and
system where pump operation will not give erroneous pressure
indications during the fill. Therefore, the best location to install heat exchanger pressure drop. It should be noted that these
curves are for “clean” heat exchangers; they do not apply to
the fill connection is close to the expansion tank. An air vent heat exchangers with fouling. To read the chart, subtract the
should be installed close by to help eliminate air that enters
during the fill procedure. readings of the two pressure gages on the hydronic kit. This
number is the pressure drop across the heat exchanger. Adjust
Ensure the following when filling the system: the factory-installed balancing valve or external balancing
1. Remove temporary bypass piping and cleaning/flushing valve (units without hydronic package) until the correct pres-
equipment. sure drop is obtained for the required GPM.
2. Check to make sure all drain plugs are installed.
15
LEGEND LEGEND
1 — 30RA010 4 — 30RA022 7 — 30RA032, 30RA035 10 — 30RA050
2 — 30RA015 5 — 30RA025 8 — 30RA040 11 — 30RA055
3 — 30RA018 6 — 30RA030 9 — 30RA042, 30RA045
Fig. 15A — Heat Exchanger Pressure Drop — Fig. 16A — Heat Exchanger Pressure Drop —
30RA010-030 (English) 30RA032-055 (English)
1 2 3
Heat Exchanger Pressure Drop (KPa)
30 4 25
1
5
1 2 3 4 5 6 5 6 7 8 9 10
Flow Rate (L/S) Flow Rate (L/S)
LEGEND LEGEND
1 — 30RA010 4 — 30RA022 7 — 30RA032, 30RA035 10 — 30RA050
2 — 30RA015 5 — 30RA025 8 — 30RA040 11 — 30RA055
3 — 30RA018 6 — 30RA030 9 — 30RA042, 30RA045
Fig. 15B — Heat Exchanger Pressure Drop — Fig. 16B — Heat Exchanger Pressure Drop —
30RA010-030 (SI) 30RA032-055 (SI)
Minimum Loop Volume — The preferred minimum loop A properly baffled storage tank is available from the factory
volume is equal to twice the water flow rate per ton. (For as an accessory. These tanks are designed to physically fit
example, the preferred water volume for 2.4 GPM/ton would beneath the corresponding 30RA unit, taking up the same
be 2 x 2.4 = 4.8 gallons in the loop per ton of cooling.) In order footprint.
to obtain leaving water temperature stability for comfort cool- Available volumes are as follows:
ing applications, a minimum of 3 gallons per ton is required on
all other unit sizes. For process cooling applications, where • 30RA010-018 110 gallons
high stability is critical, the loop volume should be increased to • 30RA022-030 152 gallons
6 to 10 gallons per ton of cooling. • 30RA032-055 305 gallons
In order to achieve this volume, it may be necessary to add a Maximum Loop Volume — Since the minimum size of the
water storage tank to the water loop. (The compression/ expansion tank is dependent upon loop volume, units with the
expansion tank on the 30RA hydronic package is NOT a integrated hydronic kit must not exceed the maximum loop
storage tank. If a storage tank is added to the system, it should volume limits below (see Table 6). The limits are dependent on
be properly vented so that the tank can be completely filled and the maximum and minimum temperatures of the water, the
all air eliminated. Failure to do so could cause lack of pump maximum and minimum pressures seen by the expansion tank,
stability and poor system operation.) and the heat transfer fluid. Expansion tank and maximum loop
volume data is as follows.
NOTE: On systems with a high volume, check the section on
maximum loop volume. A different expansion tank may be 30RA010-030 30RA032-055
required on systems with very high loop volumes. Volume gal 4.4 10.3
Any storage tank that is placed in the water loop should Acceptance Volume gal 3.2 10.3
have internal baffles to allow thorough mixing of the fluid. See
Fig 17.
16
that has experience in this operation. Contact your local Carrier
representative for a recommended machine shop. After trim-
ming, the impeller MUST be balanced. Failure to balance
trimmed impellers can result in excessive vibration, noise, and
premature bearing failure.
Impeller trimming has the added benefit of maximum BHP
savings. It is very possible for power savings to pay for the
BAD GOOD trimming cost very quickly.
Freeze Protection — The 30RA units are provided with a
water strainer and a flow switch to protect against freezing situ-
ations that occur from no water flow. While the flow switch
(paddle-type) is helpful in preventing freezing during no-flow
situations, it does not protect the chiller in case of power fail-
ure, or in other cases where water temperature falls below the
freezing mark. Appropriate concentrations of inhibited ethyl-
ene glycol or other suitable inhibited antifreeze solution should
BAD GOOD be considered for chiller protection where ambient tempera-
tures are expected to fall below 32 F. Consult local water treat-
Fig. 17 — Tank Baffling ment specialist on characteristics of the system water and add a
recommended inhibitor to the chilled water.
1. If the pump will be subjected to freezing temperatures,
steps must be taken to prevent freeze damage. If the
pump will not be used during this time, it is recommend-
Table 6 — Maximum Loop Volume Limits ed to drain the pump and hydronic package and these
components back-flushed with inhibited glycol. Other-
MAX LOOP VOLUME IN GALLONS (LITERS) wise, a glycol-water solution should be considered as the
% Ethylene Glycol 30RA010-030 30RA032-055 heat transfer fluid. Drains are located on the balancing
0 (Pure Water) 310 (1173) 725 (2744) valves for units with hydronic kits. Units without hydron-
10 180 (681) 425 (1609) ic kits have a drain mounted on the piping leaving the
20 175 (662) 410 (1552) heat exchanger. Drain knockouts are located on the sheet
30 155 (587) 370 (1400) metal base of all units.
40 150 (568) 350 (1325) NOTE: Do not use automobile anti-freeze, or any other fluid
50 145 (549) 340 (1287) that is not approved for heat exchanger duty. Only use appro-
% Propylene Glycol 30RA010-030 30RA032-055 priately inhibited glycols, concentrated to provide adequate
10 175 (662) 410 (1552)
protection for the temperature considered.
20 150 (568) 350 (1325) 2. Use an electric tape heater for the internal piping (exclud-
30 128 (484) 300 (1136) ing those within the pump box) if unit will be exposed to
40 118 (447) 275 (1041)
freezing temperature.
3. Ensure that power is available to the chiller at all times,
NOTE: Max loop volume is based on typical system of 12 psi and
30 psi of min/max pressures, and 100 F mean temperature. If the even during the off-season, so that the pump and cooler
volume in the system is greater than the limits listed, then extra heaters have power. Also make sure that the piping tape
expansion tank volume must be added to the system. heaters also have power.
4. On units with pump packages, a heater is supplied in the
Pump Modification/Trimming — Since the pumps are pump box that will protect this section from freezing in
constant speed, the only way to obtain greater flow with a outdoor-air temperatures down to –20 F, except in case of
given pump/impeller is to decrease system head. This will a power failure. Carrier warranty does not cover damage
allow the pump to “ride” its curve to the right, resulting in due to freezing.
increased flow. If greater flow is necessary, look at opening the 5. Cooler heaters that will protect down to –20 F can be
balance valve. Also, verify that the strainer is clean, and that no installed as a factory option. Again, it should be noted
unnecessary system resistance is present, such as partially that these heaters will not protect the cooler from freezing
closed isolation valves. in the event of a power failure.
Increasing system resistance by closing the balancing valve Preparation for Winter Shutdown — Do not shut off power
will force the pump to “ride” its curve to the left, resulting in disconnect during off-season shutdown. At the end of the cool-
less flow. Although this does reduce power consumption ing season:
slightly, it may not be the desirable method of reducing the 1. Drain water from system.
flow, especially if a rather large reduction is needed.
2. Replace drain plug(s) and add sufficient inhibited ethyl-
The other method for reducing flow on a constant speed ene glycol (or other suitable inhibited antifreeze) to
pump is impeller trimming. The impellers in the pumps provid- cooler, pump and piping to prevent freezing of residual
ed in the 30RA hydronic kit are easily removable for this pur- water.
pose. Refer to the ITT literature packet supplied with the
hydronic package information on Seal Replacement in the 3. At the beginning of the next cooling season, refill cooler
Service Section, and follow its instructions for impeller remov- and add recommended inhibitor.
al. Trimming should only be done by a qualified machine shop
17
Step 5 — Make Electrical Connections block or non-fused disconnect. A field neutral is required for
380/415-3-50 units only. To comply with NEC Article 440-14,
ELECTRIC SHOCK HAZARD. the disconnect must be located within sight from and readily
accessible from unit. Refer to Fig. 18 and 19.
To avoid the possibility of electrical shock,
open and tag all disconnects before installing IMPORTANT: To ensure power to the heaters, make sure
this equipment. auxiliary power to unit is always on (except for servicing or
prolonged shutdown).
POWER SUPPLY — Electrical characteristics of available
power supply must agree with unit nameplate rating. Field wir-
ing size and supply voltage must be within limits shown in
Tables 7 and 8. See Tables 9-11 for component electrical data.
Proper rotation of condenser fan(s) MUST be verified
IMPORTANT: Operating unit on improper supply voltage before pumps or compressors are started. Consult the Con-
or with excessive phase imbalance constitutes abuse and trols, Start-Up and Operation manual provided with this
may affect Carrier warranty. chiller for correct procedure. Improper pump rotation can
cause permanent damage to pump impeller and housing. If
POWER WIRING — All power wiring must comply with pump(s) have been removed for trimming, verify that wir-
applicable local and national codes. Install field-supplied ing is reconnected in the original manner.
branch circuit fused disconnect per NEC (National Electric
Code, U.S.A.) of a type can be locked OFF or ON. Disconnect Control Power — Control power is obtained from the main
must be within sight from and readily accessible from unit in power supply and does NOT require a separate source. A
compliance with NEC Article 440-14. toggle switch (marked Emergency On-Off on the unit label
General Wiring Notes diagram and by the switch) allows the control circuit to be
manually disconnected when necessary. Cooler and pump
1. The control circuit does NOT require a separate power heaters (if installed) are in an operable state when this switch is
source. Control circuit power is obtained by a step-down in the Off position.
transformer from the main three-phase power supply. Up
to two terminal blocks are provided for field-wired Step 6 — Install Accessories
control devices. ELECTRICAL — A number of electrical accessories are
2. Cooler and pump heaters (if factory installed) are wired available to provide the following optional features (for details,
in the control circuit so they are operable as long as the refer to the Controls, Start-Up, Operation, Service, and
main power supply to the unit is ON. A factory-installed Troubleshooting book):
and set overload device protects them. Energy Management Module (Used for any of the following
NOTE: The field-supplied disconnect should never be off types of temperature reset, demand limit and ice features):
except when unit is being serviced or is to be down for a pro- • 4 to 20 mA leaving fluid temperature reset (requires
longed period, in which case cooler should be drained. field-supplied 4 to 20 mA generator)
3. Power entry is at one end only. • 4 to 20 mA cooling set point reset (requires field-
4. Maximum field wire sizes allowed by lugs on terminal supplied 4 to 20 mA generator)
block/non-fused disconnect are listed in Table 7. • Discrete inputs for 2-step demand limit (requires field-
supplied dry contacts)
5. Terminals for field power supply are suitable for • 4 to 20 mA demand limit (requires field-supplied 4 to
copper conductors. Insulation must be rated 167 F (75 C) 20 mA generator)
minimum. • Discrete input for Ice Done switch (requires field-
supplied dry contacts)
Table 7 — Recommended Field Wiring Sizes
Navigator Display — Provides hand-held, mobile capability
CONNECTION MAX WIRE
UNIT SIZE AND VOLTAGE
using easy to read 4-line display. Keypad function is the same
TYPE SIZE as the Scrolling Marquee module. Features magnet for ‘hands
TERMINAL #2/0 AWG 30RA010-030 (all voltages) free’ service of components.
BLOCK 350 kcmil 30RA035-055 (all voltages)
30RA010-055 (575-3-60) Low Ambient Operation — If outdoor ambient operating
30RA010-030 temperatures below 45 F (7.2 C) for 30RA010-018 units and
60/100 AMP (380-3-60, 460-3-60) 32 F (0.0° C) for 30RA022-055 units are expected, refer to sep-
NON-FUSED #1 AWG
DISCONNECT 30RA010-025 (380/415-3-50) arate installation instructions for low-ambient operation using
30RA010-018 (230-3-50, 230-3-60, accessory Motormaster® V control.
208/230-3-60)
30RA035-055 (380-3-60, 460-3-60) Minimum Load Accessory — If minimum load accessory is
250 AMP 30RA032-045 (380/415-3-50) required, refer to unit Price Pages or contact your local Carrier
NON-FUSED 350 kcmil 30RA022-045 (230-3-50) representative for more details. For installation details, refer to
DISCONNECT separate installation instructions supplied with the accessory
30RA022-055 (230-3-60, 208/230-
3-60) package.
AWG — American Wire Gage Miscellaneous Accessories — For applications requiring spe-
cial accessories, the following packages are available: Coil hail
FIELD CONNECTIONS guard, external vibration, enhanced display, temperature reset,
Main Power — Bring wires from the fused disconnect switch condenser coil grilles, storage tank and remote cooler. For
through hole in bottom of left front corner post (010-030 sizes) installation details, refer to separate installation instructions
or through hole in bottom center panel (032-055 sizes) of unit supplied with these accessory packages.
to bottom of control box and connect to terminals on terminal
18
Table 8 — Electrical Data
2.0/1.5 HP 2.0/1.5 HP
1.5/1.0 HP PUMP 3.0/2.0 HP PUMP 5.0/3.0 HP PUMP
(STD) PUMP (ALT) PUMP
UNIT VOLTAGE POWER NO HYDRONIC PACKAGE Pump Options Pump Options Pump Options
Pump Options Pump Options
UNIT SUPPLY ‘A’ or ‘F’ ‘D’ or ‘J’ ‘E’ or ‘K’
‘B’ or ‘G’ ‘C’ or ‘H’
30RA QTY.
Supplied REQD. MCA MOCP ICF Rec MCA MOCP Rec MCA MOCP Rec MCA MOCP Rec MCA MOCP Rec MCA MOCP Rec
V-Hz Fuse Fuse Fuse Fuse Fuse Fuse
(3 Ph) Min Max XL XL XL XL XL XL XL XL XL XL XL XL XL
Size Size Size Size Size Size
230-60 207 253 1 46.2 70 272.6 60 50.2 80 60 51.4 80 60 51.4 80 60 53.6 80 70 — — —
208/230-60 187 253 1 51.3 80 273.4 60 55.7 90 70 57.0 90 70 57.0 90 70 59.5 90 70 — — —
460-60 414 506 1 23.8 35 123.8 30 25.8 40 30 26.4 40 35 26.4 40 35 27.5 40 35 — — —
010 575-60 518 633 1 19.2 30 83.0 25 20.8 30 25 21.2 30 25 21.2 30 25 22.1 35 30 — — —
380-60 342 418 1 29.9 50 159.6 35 32.3 50 40 33.0 50 40 33.0 50 40 34.3 50 40 — — —
380/415-50 342 440 1 28.5 45 138.8 35 30.2 50 40 31.0 50 40 31.0 50 40 31.6 50 40 — — —
230-50 207 253 1 48.9 80 231.3 60 51.7 80 70 52.9 80 70 52.9 80 70 54.0 80 70 — — —
230-60 207 253 1 62.4 100 387.6 80 66.4 110 80 67.6 110 80 67.6 110 80 69.8 110 90 — — —
208/230-60 187 253 1 69.3 110 388.4 90 73.7 110 90 75.0 110 90 75.0 110 90 77.5 125 90 — — —
460-60 414 506 1 33.6 50 178.8 40 35.6 50 45 36.2 50 45 36.2 50 45 37.3 60 45 — — —
015 575-60 518 633 1 26.7 45 143.0 35 28.3 45 35 28.7 45 35 28.7 45 35 29.6 45 35 — — —
380-60 342 418 1 42.2 70 239.6 50 44.6 70 60 45.4 70 50 45.4 70 50 46.7 70 60 — — —
380/415-50 342 440 1 36.0 50 148.1 40 37.6 50 45 38.4 50 45 38.4 50 45 39.1 50 45 — — —
230-50 207 253 1 64.5 90 242.2 80 67.3 90 80 68.5 90 80 68.5 90 80 69.7 90 80 — — —
230-60 207 253 1 67.3 90 271.2 80 71.3 90 80 72.5 90 80 72.5 90 80 74.7 100 90 — — —
208/230-60 187 253 1 74.8 100 274.9 90 79.2 100 90 80.5 110 90 80.5 110 90 83.0 110 100 — — —
460-60 414 506 1 35.5 45 147.9 40 37.5 50 45 38.1 50 45 38.1 50 45 39.2 50 45 — — —
018 575-60 518 633 1 28.5 35 99.3 35 30.1 40 35 30.5 40 35 30.5 40 35 31.4 40 35 — — —
380-60 342 418 1 44.0 60 182.1 50 46.4 60 60 47.1 60 60 47.1 60 60 48.5 60 60 — — —
380/415-50 342 440 1 38.9 50 139.4 45 40.6 50 45 41.3 50 50 41.3 50 50 42.0 50 50 — — —
230-50 207 253 1 69.5 90 239.4 80 72.3 100 80 73.5 100 90 73.5 100 90 74.6 100 90 — — —
230-60 207 253 1 84.9 110 311.3 100 88.9 125 100 90.1 125 100 90.1 125 100 92.3 125 110 — — —
208/230-60 187 253 1 94.3 125 316.4 110 98.7 125 110 100.1 125 125 100.1 125 125 102.5 125 125 — — —
460-60 414 506 1 44.7 60 154.4 50 46.7 60 60 47.3 60 60 47.3 60 60 48.4 60 60 — — —
022 575-60 518 633 1 36.8 50 136.0 45 38.4 50 45 38.9 50 45 38.9 50 45 39.8 50 45 — — —
380-60 342 418 1 57.7 80 194.7 70 60.1 80 70 60.9 80 70 60.9 80 70 62.2 80 70 — — —
380/415-50 342 440 1 49.2 60 159.4 60 50.9 70 60 51.6 70 60 51.6 70 60 52.3 70 60 — — —
230-50 207 253 1 84.4 110 266.8 100 87.2 110 100 88.4 110 100 88.4 110 100 89.5 110 100 — — —
230-60 207 253 1 92.2 125 311.3 110 96.2 125 110 97.4 125 110 97.4 125 110 99.6 125 110 — — —
208/230-60 187 253 1 102.4 125 316.4 125 106.8 125 125 108.2 125 125 108.2 125 125 110.6 150 125 — — —
460-60 414 506 1 50.3 70 160.0 60 52.3 70 80 52.9 70 80 52.9 70 80 54.0 70 80 — — —
025 575-60 518 633 1 41.2 50 140.4 50 42.8 50 50 43.3 50 50 43.3 50 50 44.2 60 50 — — —
380-60 342 418 1 65.2 90 202.2 80 67.6 90 80 68.4 90 80 68.5 90 80 69.7 90 80 — — —
380/415-50 342 440 1 59.1 80 203.8 70 60.8 80 70 61.5 80 70 61.5 80 70 62.2 80 70 — — —
230-50 207 253 1 101.3 125 359.3 125 104.0 125 125 105.3 125 125 105.3 125 125 106.4 125 125 — — —
230-60 207 253 1 108.2 150 433.4 125 112.2 150 125 113.4 150 125 113.4 150 125 115.6 150 150 — — —
208/230-60 187 253 1 120.2 150 439.3 150 124.6 150 150 125.9 150 150 125.9 150 150 128.4 175 150 — — —
030 460-60 414 506 1 58.4 80 203.6 70 60.4 80 70 61.0 80 70 61.0 80 70 62.1 80 70 — — —
575-60 518 633 1 46.4 60 162.7 60 48.0 60 60 48.4 60 60 48.4 60 60 49.3 60 60 — — —
380-60 342 418 1 73.5 100 270.9 90 76.0 100 90 76.7 100 90 76.7 100 90 78.0 100 90 — — —
380/415-50 342 440 1 73.0 90 217.7 80 — — — 75.4 90 90 — — — 76.1 100 90 78.2 100 90
032 230-50 207 253 1 126.2 150 384.2 150 — — — 130.2 150 150 — — — 131.3 150 150 134.9 175 150
230-60 207 253 1 138.1 175 463.4 150 — — — 143.3 175 175 — — — 145.5 175 175 150.7 175 175
208/230-60 187 253 1 153.4 200 472.5 175 — — — 159.1 200 175 — — — 161.6 200 175 167.3 200 200
460-60 414 506 1 73.2 90 218.4 80 — — — 75.8 90 90 — — — 76.9 100 90 79.5 100 90
035 575-60 518 633 1 59.3 70 175.7 70 — — — 61.4 80 70 — — — 62.3 80 70 64.3 80 70
380-60 342 418 1 93.3 110 290.7 110 — — — 96.5 125 110 — — — 97.8 125 110 101.0 125 110
380/415-50 342 440 1 87.1 110 231.8 100 — — — 89.5 110 100 — — — 90.2 110 100 92.3 110 100
230-50 207 253 1 149.1 175 407.1 175 — — — 153.1 175 175 — — — 154.2 175 175 157.8 175 175
230-60 207 253 1 145.4 175 470.6 175 — — — 150.6 175 175 — — — 152.8 175 175 158.0 200 175
208/230-60 187 253 1 161.5 200 480.6 175 — — — 167.2 200 200 — — — 169.7 200 200 175.4 200 200
040 460-60 414 506 1 78.8 100 224.0 90 — — — 81.4 100 90 — — — 82.5 100 90 85.1 100 90
575-60 518 633 1 63.7 80 180.1 70 — — — 65.8 80 80 — — — 66.7 80 80 68.7 80 70
380-60 342 418 1 100.8 125 298.2 110 — — — 104.0 125 125 — — — 105.3 125 125 108.5 125 110
280/415-50 342 440 1 84.2 100 194.4 90 — — — 86.6 100 100 — — — 87.3 100 100 89.4 100 90
042 230-50 207 253 1 144.9 175 327.3 175 — — — 146.9 175 175 — — — 150.1 175 175 153.6 175 150
230-60 207 253 1 162.1 200 382.7 175 — — — 167.3 200 200 — — — 169.5 200 200 174.7 200 175
208/230-60 187 253 1 180.0 200 395.6 200 — — — 185.8 225 200 — — — 188.2 225 225 193.9 225 200
460-60 414 506 1 86.0 100 196.8 100 — — — 88.6 100 100 — — — 89.7 110 100 92.3 110 90
045 575-60 518 633 1 69.9 80 170.1 80 — — — 72.0 80 80 — — — 72.9 90 80 74.9 90 70
380-60 342 418 1 109.9 125 248.4 125 — — — 113.0 125 125 — — — 114.4 125 125 117.5 125 110
380/415-50 342 440 1 112.1 125 256.9 125 — — — 114.5 125 125 — — — 115.2 125 125 117.4 125 100
230-50 207 253 1 192.1 225 450.1 225 — — — 196.1 225 225 — — — 197.2 225 225 200.8 225 175
230-60 207 253 1 175.3 200 394.4 200 — — — 180.5 200 200 — — — 182.7 200 200 187.9 200 175
208/230-60 187 253 1 194.6 225 408.6 225 — — — 200.4 225 225 — — — 202.8 225 225 208.6 225 200
050 460-60 414 506 1 95.5 110 205.2 110 — — — 98.1 110 110 — — — 99.2 110 110 101.8 110 90
575-60 518 633 1 78.2 90 177.5 90 — — — 80.3 90 90 — — — 81.2 90 90 83.3 90 70
380-60 342 418 1 123.8 150 260.8 150 — — — 127.0 150 150 — — — 128.3 150 150 131.4 150 110
230-60 207 253 1 205.5 225 530.7 225 — — — 210.7 250 225 — — — 212.9 250 225 218.1 250 175
208/230-60 187 253 1 228.2 250 547.3 250 — — — 234.0 250 250 — — — 236.4 250 250 242.1 250 200
055 460-60 414 506 1 110.8 125 256.0 125 — — — 113.4 125 125 — — — 114.5 125 125 117.1 125 90
575-60 518 633 1 88.0 100 204.4 100 — — — 90.1 100 100 — — — 91.0 100 100 93.0 110 70
380-60 342 418 1 139.5 150 336.9 150 — — — 142.7 150 175 — — — 144.0 150 175 147.2 175 110
LEGEND 2. All units have single point primary power connection. The unit control circuit power
(24 v, single-phase) is supplied from the main power and does not require a separate
ICF — Instantaneous Current Flow MOCP — Maximum Overcurrent Protection power source.
MCA — Minimum Circuit Amps XL — Across-the-Line Start
3. Hydronic package and cooler heaters are wired into the control circuit so they are
NOTES: always operable as long as the power supply disconnect is on, even if any safety
device is open, and the unit ON/OFF switch is in the OFF position.
1. Units are suitable for use on electrical systems where voltage supplied to the unit
terminals is not below or above the listed minimum and maximum limits. Maximum 4. Power draw control circuits include cooler heaters (where used).
allowable phase imbalance is: voltage, 2%; amps 10%.
19
Table 9 — Fan Electrical Data Table 10 — Pump Electrical Data
UNIT VOLTAGE STANDARD CONDENSER FANS PUMP PUMP PUMP UNIT VOLTAGE FLA LRA
UNIT OPTION SIZE RPM (each) (each)
30RA Circuit A FLA Circuit B FLA V-Hz (3 Ph)
V-Hz (3 Ph) Quantity (each) Quantity (each) 3500 230-60 4.0 32.0
230-60 1 7.6 — — 3500 208/230-60 4.4 36.0
208/230-60 1 8.4 — — 1.5 HP 3500 460-60 2.0 16.0
460-60 1 3.8 — — ‘A’ or ‘F’ 3500 575-60 1.6 14.4
010 575-60 1 3.0 — — 3500 380-60 2.4 21.8
380-60 1 4.6 — — 2925 380/415-50 1.7 16.0
380/415-50 1 3.8 — — 1.0 HP
2925 230-50 2.8 32.0
230-50 1 6.3 — —
3490 230-60 5.2 42.0
230-60 1 7.6 — — 3490 208/230-60 5.8 47.0
208/230-60 1 8.4 — — 2.0 HP 3490 460-60 2.6 21.0
460-60 1 3.8 — — ‘B’, ‘C’ 3490 575-60 2.1 18.8
015 575-60 1 3.0 — — ‘G’ or ‘H’ 3490 380-60 3.1 28.4
380-60 1 4.6 — —
380/415-50 1 3.8 — — 1.5 HP 2910 380/415-50 2.4 21.5
230-50 1 6.3 — — 2910 230-50 4.0 42.0
230-60 1 7.6 — — 3480 230-60 7.4 53.0
208/230-60 1 8.4 — — 3480 208/230-60 8.2 58.0
460-60 1 3.8 — — 3.0 HP 3480 460-60 3.7 26.5
018 575-60 1 3.0 — — ‘D’ or ‘J’ 3480 575-60 3.0 25.6
380-60 1 4.6 — — 3480 380-60 4.5 38.7
380/415-50 1 3.8 — — 2900 380/415-50 3.1 29.0
230-50 1 6.3 — — 2.0 HP
2900 230-50 5.1 53.0
230-60 2 4.8 — — 3450 230-60 12.6 126.0
208/230-60 2 5.3 — — 3450 208/230-60 13.9 136.8
460-60 2 2.4 — — 5.0 HP 3450 460-60 6.3 63.0
022 575-60 2 1.9 — — ‘E’ or ‘K’ 3450 575-60 5.0 55.4
380-60 2 2.9 — — 3450 380-60 7.6 83.9
380/415-50 2 2.3 — —
230-50 2 3.8 — — 3.0 HP 2850 380/415-50 5.3 68.0
2850 230-50 8.7 126.0
230-60 2 4.8 — —
208/230-60 2 5.3 — — LEGEND
460-60 2 2.4 — — FLA — Full Load Amps
025 575-60 2 1.9 — — LRA — Locked Rotor Amps
380-60 2 2.9 — —
380/415-50 2 2.3 — —
230-50 2 3.8 — —
230-60 2 4.8 — —
208/230-60 2 5.3 — —
030 460-60 2 2.4 — —
575-60 2 1.9 — —
380-60 2 2.9 — —
380/415-50 2 2.3 1 3.8
032 230-50 2 3.8 1 6.3
230-60 2 4.8 1 7.6
208/230-60 2 5.3 1 8.4
460-60 2 2.4 1 3.8
035 575-60 2 1.9 1 3.0
380-60 2 2.9 1 4.6
380/415-50 2 2.3 1 3.8
230-50 2 3.8 1 6.3
230-60 2 4.8 1 7.6
208/230-60 2 5.3 1 8.4
040 460-60 2 2.4 1 3.8
575-60 2 1.9 1 3.0
380-60 2 2.9 1 4.6
380/415-50 2 2.3 2 2.3
042 230-50 2 3.8 2 3.8
230-60 2 4.8 2 4.8
208/230-60 2 5.3 2 5.3
460-60 2 2.4 2 2.4
045 575-60 2 1.9 2 1.9
380-60 2 2.9 2 2.9
380/415-50 2 2.3 2 2.3
230-50 2 3.8 2 3.8
230-60 2 4.8 2 4.8
208/230-60 2 5.3 2 5.3
050 460-60 2 2.4 2 2.4
575-60 2 1.9 2 1.9
380-60 2 2.9 2 2.9
230-60 2 4.8 2 4.8
208/230-60 2 5.3 2 5.3
055 460-60 2 2.4 2 2.4
575-60 2 1.9 2 1.9
380-60 2 2.9 2 2.9
LEGEND
FLA — Full Load Amps
20
Table 11 — Compressor Electrical Data
UNIT VOLTAGE COMPRESSOR
UNIT A1 A2 B1 B2
30RA V-Hz (3 Ph)
RLA LRA RLA LRA RLA LRA RLA LRA
230-60 30.9 265 — — — — — —
208/230-60 34.3 265 — — — — — —
460-60 16.0 120 — — — — — —
010 575-60 12.9 80 — — — — — —
380-60 20.2 155 — — — — — —
380/415-50 19.8 135 — — — — — —
230-50 34.1 225 — — — — — —
230-60 43.8 380 — — — — — —
208/230-60 48.7 380 — — — — — —
460-60 23.8 175 — — — — — —
015 575-60 18.9 140 — — — — — —
380-60 30.1 235 — — — — — —
380/415-50 14.3 130 14.3 130 — — — —
230-50 25.9 210 25.9 210 — — — —
230-60 26.6 237 26.6 237 — — — —
208/230-60 29.5 237 29.5 237 — — — —
460-60 14.1 130 14.1 130 — — — —
018 575-60 11.3 85 11.3 85 — — — —
380-60 17.5 160 17.5 160 — — — —
380/415-50 15.6 120 15.6 120 — — — —
230-50 28.1 205 28.1 205 — — — —
230-60 29.4 265 36.7 265 — — — —
208/230-60 32.7 265 40.8 265 — — — —
460-60 14.6 120 20.2 135 — — — —
022 575-60 12.2 80 16.6 120 — — — —
380-60 18.9 155 26.4 170 — — — —
380/415-50 19.8 135 19.8 135 — — — —
230-50 34.1 225 34.1 225 — — — —
230-60 36.7 265 36.7 265 — — — —
208/230-60 40.8 265 40.8 265 — — — —
460-60 20.2 135 20.2 135 — — — —
025 575-60 16.6 120 16.6 120 — — — —
380-60 26.4 170 26.4 170 — — — —
380/415-50 24.2 175 24.2 175 — — — —
230-50 41.6 310 41.6 310 — — — —
230-60 43.8 380 43.8 380 — — — —
208/230-60 48.7 380 48.7 380 — — — —
030 460-60 23.8 175 23.8 175 — — — —
575-60 18.9 140 18.9 140 — — — —
380-60 30.1 235 30.1 235 — — — —
380/415-50 14.5 120 19.8 135 24.2 175 — —
032 230-50 26.2 205 34.1 225 41.6 310 — —
230-60 29.4 265 36.7 265 43.8 380 — —
208/230-60 32.7 265 40.8 265 48.7 380 — —
460-60 14.6 120 20.2 135 23.8 175 — —
035 575-60 12.2 80 16.6 120 18.9 140 — —
380-60 18.9 155 26.4 170 30.1 235 — —
380/415-50 24.2 175 24.2 175 24.2 175 — —
230-50 41.6 310 41.6 310 41.6 310 — —
230-60 36.7 265 36.7 265 43.8 380 — —
208/230-60 40.8 265 40.8 265 48.7 380 — —
040 460-60 20.2 135 20.2 135 23.8 175 — —
575-60 16.6 120 16.6 120 18.9 140 — —
380-60 26.4 170 26.4 170 30.1 235 — —
380/415-50 19.8 135 19.8 135 19.8 135 19.8 135
042 230-50 34.1 225 34.1 225 34.1 225 34.1 225
230-60 30.9 265 36.7 265 30.9 265 36.7 265
208/230-60 34.3 265 40.8 265 34.3 265 40.8 265
460-60 16.0 120 20.2 135 16.0 120 20.2 135
045 575-60 12.9 80 16.6 120 12.9 80 16.6 120
380-60 20.2 155 26.4 170 20.2 155 26.4 170
380/415-50 24.2 175 24.2 175 24.2 175 24.2 175
230-50 41.6 310 41.6 310 41.6 310 41.6 310
230-60 36.7 265 36.7 265 36.7 265 36.7 265
208/230-60 40.8 265 40.8 265 40.8 265 40.8 265
050 460-60 20.2 135 20.2 135 20.2 135 20.2 135
575-60 16.6 120 16.6 120 16.6 120 16.6 120
380-60 26.4 170 26.4 170 26.4 170 26.4 170
230-60 43.8 380 43.8 380 43.8 380 43.8 380
208/230-60 48.7 380 48.7 380 48.7 380 48.7 380
055 460-60 23.8 175 23.8 175 23.8 175 23.8 175
575-60 18.9 140 18.9 140 18.9 140 18.9 140
380-60 30.1 235 30.1 235 30.1 235 30.1 235
LEGEND
LRA — Locked Rotor Amps
RLA — Rated Load Amps
21
LEGEND
A — Alarm TB — Terminal Block
CWP — Chilled Water Pump Field Power Wiring
CWPI — Chilled Water Pump Interlock Field Control Wiring
EMM — Energy Management Factory-Installed Wiring
SPT — Space Temperature
NOTES:
1. Factory wiring is in accordance with UL 1995 standards. Any field wiring modi-
fications or additions must be in compliance with all applicable codes.
2. Wiring for main field supply must be rated 75 C minimum. Use copper for all
units. Maximum incoming wire size for the terminal block is #2/0 AWG. Maxi-
mum incoming wire size for 60 and 100-amp non-fused disconnect is #1 AWG.
Maximum incoming wire size for 250-amp non-fused disconnect is 350 kcmil.
3. Terminals 9 and 10 of TB5 are for field external connections for remote on-off.
The contacts must be rated for dry circuit application capable of handling a
24-vac load up to 50 mA.
4. Terminals 1 and 2 of TB5 are connected to the factory-installed chilled water
flow switch (CWFS). To add chilled water pump interlock contacts, remove the
orange harness wire from TB5-1 and wire contacts in series as shown. The
contacts must be rated for dry circuit application capable of handling a 24-vac
load up to 50 mA.
5. Terminals 11 and 13 of TB5 are for control of Chilled Water Pump 1 (CWP1)
starter. Terminals 13 and 15 of TB5 are for control of Chilled Water Pump 2
(CWP2) starter. The maximum load allowed for the chilled water pump relay is
5 va sealed, 10 va inrush at 24 v. Field power supply is not required.
6. Terminals 12 and 13 of TB5 are for an alarm relay. The maximum load allowed
for the alarm relay is 5 va sealed, 10 va inrush at 24 v. Field power supply is
not required.
7. Make appropriate connections to TB6 as shown for Energy Management
Board options. The contacts for Demand Limit and Ice Done options must be
rated for dry circuit application capable of handling a 24-vac load up to 50 mA.
22
Fig. 18 — Main Power and Control Connections — 30RA010-030 Without Hydronic Package
LEGEND
A — Alarm EMM — Energy Management Field Power Wiring
CWP — Chilled Water Pump SPT — Suction Pressure Transducer Field Control Wiring
CWPI — Chilled Water Pump Interlock TB — Terminal Block Factory-Installed Wiring
NOTES:
1. Factory wiring is in accordance with UL 1995 standards. Any field wiring modifications or
additions must be in compliance with all applicable codes.
2. Wiring for main field supply must be rated 75 C minimum. Use copper for all units. Maxi-
mum incoming wire size for the terminal block is 350 kcmil. Maximum incoming wire size
for 100-amp non-fused disconnect is #1 AWG. Maximum incoming wire size for 250-amp
non-fused disconnect is 350 kcmil.
3. Terminals 9 and 10 of TB5 are for field external connections for remote on-off. The
contacts must be rated for dry circuit application capable of handling a 24-vac load up to
50 mA.
4. Terminals 1 and 2 of TB5 are connected to the factory-installed chilled water flow switch
(CWFS). To add chilled water pump interlock contacts, remove the orange harness wire
from TB5-1 and wire contacts in series as shown. The contacts must be rated for dry cir-
cuit application capable of handling a 24-vac load up to 50 mA.
5. Terminals 11 and 13 of TB5 are for control of Chilled Water Pump 1 (CWP1) starter. Termi-
nals 13 and 15 of TB5 are for control of Chilled Water Pump 2 (CWP2) starter. The
maximum load allowed for the chilled water pump relay is 75 va sealed, 360 va inrush at
115 v. Field power supply is not required.
6. Terminals 12 and 13 of TB5 are for an alarm relay. The maximum load allowed for the
alarm relay is 75 va sealed, 360 va inrush at 115 v. Field power supply is not required.
7. Make appropriate connections to TB6 as shown for Energy Management Board options.
The contacts for Demand Limit and Ice Done options must be rated for dry circuit applica-
tion capable of handling a 24-vac load up to 50 mA.
23
Fig. 19 — Main Power and Control Connections — 30RA032-055 Without Hydronic Package
Step 7 — Refrigerant Circuit If unit is equipped with a Motormaster® V control, the pres-
LEAK TESTING — Units are shipped with complete operat- sure transducer has to be removed from the liquid line Schrader
ing charge of R-22 (refer to Physical Data tables) and should be connection to allow for gauge access.
under sufficient pressure to conduct a leak test. Perform a leak The compressors are provided with a 1/4-in. Schrader fitting
test to ensure that leaks have not developed during unit for connecting to low-side system pressure. The location of the
shipment. Dehydration of the system is not required unless the suction access port is shown in Fig. 20.
entire refrigerant charge has been lost. Compressor oil equal-
ization line fittings use O-ring face seal fittings. If a leak is
detected at these fittings, tighten fitting 1/4 turn. If leak persists,
open system and inspect the O-ring surface for foreign material
or damage. Do not reuse O-rings. Repair any leak found using
good refrigeration practice.
DEHYDRATION — Refer to Carrier Standard Service Tech-
niques Manual, Chapter 1, Refrigerants, Sections 6 and 7 for
details. Do not use compressor to evacuate system.
REFRIGERANT CHARGE (Refer to Tables 1A-1D) —
Immediately ahead of filter drier in each circuit is a factory-
installed liquid line service valve. Each valve has a 1/4-in.
Schrader connection for charging liquid refrigerant.
.
24
APPENDIX A
PRESSURE DROP, WITHOUT PUMP UNITS, PRESSURE DROP, WITHOUT PUMP UNITS,
30RA032-055 30RA032-055
PRESSURE DROP, SINGLE PUMP UNITS, PRESSURE DROP, SINGLE PUMP UNITS,
30RA010-030 30RA010-030
Use the following formula to convert Feet of water to psi: Use the following formula to convert psi to Feet of water:
Ft of water (.4335) = psi Psi (2.306) = Ft of water
LEGEND
1 — 30RA010 3 — 30RA018 5 — 30RA025 7 — 30RA032, 30RA035 9 — 30RA042, 30RA045 11 — 30RA055
2 — 30RA015 4 — 30RA022 6 — 30RA030 8 — 30RA040 10 — 30RA050
25
APPENDIX A (cont)
PRESSURE DROP, DUAL PUMP UNITS, PRESSURE DROP, DUAL PUMP UNITS,
SIZES 30RA010-030 SIZES 30RA010-030
PRESSURE DROP, DUAL PUMP UNITS, PRESSURE DROP, DUAL PUMP UNITS,
SIZES 30RA032-055 SIZES 30RA032-055
Use the following formula to convert Feet of water to psi: Use the following formula to convert psi to Feet of water:
Ft of water (.4335) = psi Psi (2.306) = Ft of water
LEGEND
1 — 30RA010 3 — 30RA018 5 — 30RA025 7 — 30RA032, 30RA035 9 — 30RA042, 30RA045 11 — 30RA055
2 — 30RA015 4 — 30RA022 6 — 30RA030 8 — 30RA040 10 — 30RA050
26
APPENDIX A (cont)
100.0
30RA-900---010
PRESSURE DROP (ft wg)
10.0
30RA-900---001,009
1.0
0.1
1 10 100 1000
ACCESSORY TANK FLOW RATE (gpm)
100.0
30RA-900---010
PRESSURE DROP (kPa)
10.0
30RA-900---001,009
1.0
0.1
1.0 10.0
ACCESSORY TANK FLOW RATE (L/s)
27
Copyright 2002 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 PC 903 Catalog No. 533-00045 Printed in U.S.A. Form 30RA-12SI Pg 28 7-02 Replaces: 30RA-1SI
Tab 5c