50 TJ 016
50 TJ 016
50 TJ 016
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 PC 111 Catalog No. 565-135 Printed in U.S.A. Form 50TJ-14SI Pg 1 10-98 Replaces: 50TJ-13SI
Tab 1b
A B
UNIT
DEG. IN. DEG. IN.
2
3
Downloaded from www.Manualslib.com manuals search engine
STD UNIT ECONOMIZER CORNER CORNER CORNER CORNER
WEIGHT WEIGHT A B C D DIM A DIM B DIM C
UNIT
Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg ft-in. mm ft-in. mm ft-in. mm
50TJ016 1550 703 110 50 391 177 365 166 384 174 410 186 3-5 1041 3-6 1067 1-10 559
50TJ020 1650 748 110 50 399 181 384 174 402 182 439 199 3-4 1016 3-6 1067 1- 8 508
NOTES:
1. Refer to print for roof curb accessory dimensions.
2. Dimensions in ( ) are in millimeters.
3. Center of Gravity.
4. Direction of airflow.
5. Ductwork to be attached to accessory roof curb only.
6. Minimum clearance:
• Rear: 78-09 (2134) for coil removal. This dimension can be reduced to 48-09 (1219)
if conditions permit coil removal from the top.
• Left side: 48-09 (1219) for proper condenser coil airflow.
• Front: 48-09 (1219) for control box access.
• Right side: 48-09 (1219) for proper operation of damper and power exhaust if so
equipped.
• Top: 68-09 (1829) to assure proper condenser fan operation.
• Local codes or jurisdiction may prevail.
7. With the exception of clearance for the condenser coil and the damper/power ex-
haust as stated in Note #6, a removable fence or barricade requires no
clearance.
POWER EXHAUST/BAROMETRIC RELIEF
(ACCESSORY ONLY)
8. Dimensions are from outside of corner post. Allow 08-5⁄169 (8) on each side for top
cover drip edge.
9. See drawing 50TJ500352 for service option details.
4
NOTES:
1. Refer to print for roof curb accessory dimensions.
2. Dimensions in ( ) are in millimeters.
3. Center of Gravity.
4. Direction of airflow.
5. Ductwork to be attached to accessory roof curb only.
6. Minimum clearance:
• Rear: 78-09 (2134) for coil removal. This dimension can be reduced to 48-09 (1219)
if conditions permit coil removal from the top.
• Left side: 48-09 (1219) for proper condenser coil airflow.
• Front: 48-09 (1219) for control box access.
• Right side: 48-09 (1219) for proper operation of damper and power exhaust if so
equipped.
• Top: 68-09 (1829) to assure proper condenser fan operation.
• Local codes or jurisdiction may prevail.
7. With the exception of clearance for the condenser coil and the damper/power ex-
haust as stated in Note #6, a removable fence or barricade requires no
clearance.
POWER EXHAUST/BAROMETRIC RELIEF 8. Dimensions are from outside of corner post. Allow 08-5⁄169 (8) on each side for top
(ACCESSORY ONLY) cover drip edge.
9. See drawing 50TJ500352 for service option details.
5
LEGEND
Bhp — Brake Horsepower
TXV — Thermostatic Expansion Valve
*Circuit 1 uses the lower portion of the condenser coil and lower portion of the evaporator coils; and
Circuit 2 uses the upper portion of both coils.
†The 50TJ028 unit requires 2-in. industrial-grade filters capable of handling face velocities up to 625 ft/min
(such as American Air Filter no. 5700 or equivalent).
NOTE: The 50TJ016-028 units have a low-pressure switch (standard) located on the suction side.
6
Downloaded from www.Manualslib.com manuals search engine
Step 3 — Field Fabricate Ductwork — Secure all Step 4 — Make Unit Duct Connections — Unit
ducts to building structure. Use flexible duct connectors be- is shipped for through-the-bottom duct connections. Duct-
tween unit and ducts as required. Insulate and weatherproof work openings are shown in Fig. 6. Field-fabricated concen-
all external ductwork, joints, and roof openings with counter tric ductwork may be connected as shown in Fig. 7 and 8.
flashing and mastic in accordance with applicable codes. Attach all ductwork to roof curb and roof curb basepans.
Ducts passing through an unconditioned space must be Refer to installation instructions shipped with accessory roof
insulated and covered with a vapor barrier. curb for more information.
The 50TJ units with electric heat require a 1-in. clearance Step 5 — Trap Condensate Drain — See Fig. 4, 5,
for the first 24 in. of ductwork. and 9 for drain location. Plug is provided in drain hole and
Outlet grilles must not lie directly below unit discharge. must be removed when unit is operating. One 3⁄4-in. half-
NOTE: A 90-degree elblow must be provided in the duct- coupling is provided inside unit evaporator section for con-
work to comply with UL (Underwriters’ Laboratories) codes densate drain connection. An 81⁄2 in. x 3⁄4-in. diameter nipple
for use with electric heat. and a 2-in. x 3⁄4-in. diameter pipe nipple are coupled to stand-
ard 3⁄4-in. diameter elbows to provide a straight path down
through holes in unit base rails (see Fig. 10). A trap at least
4-in. deep must be used.
For vertical supply and return units, tools or parts could
drop into ductwork and cause an injury. Install a 90 de-
gree turn in the return ductwork between the unit and
the conditioned space. If a 90 degree elbow cannot be
installed, then a grille of sufficient strength and density
should be installed to prevent objects from falling into
the conditioned space. Due to electric heater, supply duct
will require 90 degree elbow.
7
Downloaded from www.Manualslib.com manuals search engine
IMPORTANT: If the supply voltage phase imbalance
is more than 2%, contact your local electric utility com-
pany immediately.
8
Downloaded from www.Manualslib.com manuals search engine
Table 2 — Electrical Data
NOMINAL VOLTAGE COMPRESSOR POWER ELECTRIC POWER
UNIT VOLTAGE RANGE OFM IFM
No. 1 No. 2 EXHAUST HEAT* SUPPLY
50TJ (3 Ph,
60 Hz) Min Max RLA LRA RLA LRA Qty Hp FLA (ea) Hp FLA FLA LRA kW FLA MCA MOCP*
— — — — 81/81 100/100
4.6 18.8 — — 85/86 110/110
— — 26/34 71/82 102/116 110/125
4.6 18.8 26/34 71/82 108/122 110/125
208/230 187 253 28.8 195 28.8 195 3 0.5 1.7 3.7 10.5/11.0
— — 42/56 117/135 159/149 175/175
4.6 18.8 42/56 117/135 165/155 175/175
— — 56/75** 156/180 169/194 200/225
4.6 18.8 56/75** 156/180 175/200 200/225
— — — — 43 50
2.3 6.0 — — 45 60
380 342 418 15.0 123 15.0 123 3 0.5 1.7 3.7 3.9 — — 20 30 43 50
2.3 6.0 20 30 46 60
016 — — 35 52 70 80
(15 Tons) 2.3 6.0 35 52 73 80
— — — — 40 50
2.3 6.0 — — 43 50
— — 32 39 55 60
2.3 6.0 32 39 58 60
460 414 508 14.7 95 14.7 95 3 0.5 0.8 3.7 4.8
— — 55 66 72 80
2.3 6.0 55 66 75 80
— — 80** 96 102 110
2.3 6.0 80** 96 105 110
— — — — 30 40
2.1 4.8 — — 32 40
575 518 633 10.8 80 10.8 80 3 0.5 0.75 3.0 3.9
— — 50** 48 67 70
2.1 4.8 50** 48 70 70
— — — — 87/87 110/110
4.6 18.8 — — 92/92 110/110
— — 26/34 71/82 109/122 110/125
4.6 18.8 26/34 71/82 114/128 125/150
208/230 187 253 30.1 225 28.8 195 3 0.5 1.7 5.0 15.8/15.8
— — 42/56 117/135 166/155 175/175
4.8 18.8 42/56 117/135 172/161 175/175
— — 56/75** 156/180 176/200 200/225
4.6 18.8 56/75** 156/180 182/206 200/225
020 — — — — 44 50
(18 Tons) 2.3 6.0 — — 47 60
— — 32 39 59 60
2.3 6.0 32 39 61 70
460 414 508 15.5 114 14.7 95 3 0.5 0.8 5.0 7.9
— — 55 66 76 90
2.3 6.0 55 66 79 90
— — 80** 96 106 125
2.3 6.0 80** 96 109 125
— — — — 34 40
575 518 633 12.1 80 10.8 80 3 0.5 0.75 5.0 6.0 2.1 4.8 — — 36 40
— — — — 116/116 150/150
4.6 18.8 — — 120/120 150/150
— — 26/34 71/82 120/134 150/150
4.6 18.8 26/34 71/82 126/140 150/150
208/230 187 253 37.8 239 30.1 225 2 1 6.6 7.5 25.0/25.0
— — 42/56 117/135 178/166 200/175
4.6 18.8 42/56 117/135 183/172 200/175
— — 56/75** 156/180 187/211 200/225
4.6 18.8 56/75** 156/180 193/217 200/225
— — — — 66 80
2.3 6.0 — — 68 80
— — 20 30 66 80
380 342 418 21.2 145 16.7 140 2 1 3.9 7.5 15.0 2.3 6.0 20 30 68 80
024
(20 Tons) — — 35 52 84 90
2.3 6.0 35 52 87 90
— — — — 57 70
2.3 6.0 — — 59 70
— — 32 39 65 70
2.3 6.0 32 39 68 70
460 414 508 17.2 125 15.5 114 2 1 3.3 7.5 13.0
— — 55 66 82 90
2.3 6.0 55 66 85 90
— — 80** 96 112 125
2.3 6.0 80** 96 115 125
— — — — 44 50
575 518 633 12.4 80 12.1 80 2 1 3.4 7.5 10.0 2.1 4.8 — — 46 50
9
Downloaded from www.Manualslib.com manuals search engine
Table 2 — Electrical Data (cont)
NOMINAL VOLTAGE COMPRESSOR POWER ELECTRIC POWER
UNIT VOLTAGE RANGE OFM IFM
No. 1 No. 2 EXHAUST HEAT* SUPPLY
50TJ (3 Ph,
60 Hz) Min Max RLA LRA RLA LRA Qty Hp FLA (ea) Hp FLA FLA LRA kW FLA MCA MOCP†
— — — — 130/130 150/150
4.6 18.8 — — 135/135 175/175
— — 26/34 71/82 130/138 150/150
4.6 18.8 26/34 71/82 135/143 175/175
208/230 187 253 41.0 350 37.8 239 2 1 6.6 10.0 28.0/28.0
— — 42/56 117/135 181/170 200/175
4.6 18.8 42/56 117/135 187/176 200/200
— − 56/75** 156/180 191/215 200/225
4.6 18.8 56/75** 156/180 197/221 200/225
— — — — 73 90
2.3 6.0 — — 76 90
380 342 418 21.8 151 21.2 145 2 1 3.9 10.0 17.0 — — 20 30 73 90
028 2.3 6.0 20 30 76 90
(25 Tons) — — 35 52 87 90
2.3 6.0 35 52 90 90
— — — — 66 80
2.3 6.0 — — 68 80
— — 32 39 67 80
2.3 6.0 32 39 70 80
460 414 508 21.8 158 17.2 125 2 1 2.8 10.0 14.6
— — 55 66 84 90
2.3 6.0 55 66 87 100
— — 80** 96 114 125
2.3 6.0 80** 96 117 125
575 518 633 17.3 125 12.4 80 2 1 3.4 10.0 13.0 — — — — 54 70
2.1 4.8 — — 56 70
LEGEND EXAMPLE: Supply voltage is 460-3-60.
FLA — Full Load Amps AB = 452 v
HACR — Heating, Air Conditioning and Refrigeration BC = 464 v
IFM — Indoor (Evaporator) Fan Motor AC = 455 v
LRA — Locked Rotor Amps 452 + 464 + 455
MCA — Minimum Circuit Amps Average Voltage =
MOCP — Maximum Overcurrent Protection 3
NEC — National Electrical Code 1371
=
OFM — Outdoor (Condenser) Fan Motor 3
RLA — Rated Load Amps
= 457
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v,
380 v, 480 v, and 575 v. Heaters are rated at 240 v, 380 v, 480 v, or Determine maximum deviation from average voltage.
600 v. If power distribution voltage to unit varies from rated heater volt- (AB) 457 − 452 = 5 v
age, heater kW will vary accordingly. (BC) 464 − 457 = 7 v
†Fuse or HACR circuit breaker. (AC) 457 − 455 = 2 v
**Heaters are field installed only. Maximum deviation is 7 v.
Determine percent of voltage imbalance.
NOTES:
1. In compliance with NEC requirements for multimotor and combination 7
load equipment (refer to NEC Articles 430 and 440), the overcurrent % Voltage Imbalance = 100 x
457
protective device for the unit shall be fuse or HACR breaker. The
Canadian units may be fuse or circuit breaker. = 1.53%
2. Unbalanced 3-Phase Supply Voltage This amount of phase imbalance is satisfactory as it is below the maxi-
Never operate a motor where a phase imbalance in supply voltage is mum allowable 2%.
greater than 2%. Use the following formula to determine the percent of
voltage imbalance.
IMPORTANT: If the supply voltage phase imbalance is more
% Voltage Imbalance = than 2%, contact your local electric utility company immediately.
max voltage deviation from average voltage
100 x
average voltage 3. MCA calculation for units with electric heaters over 50 kW
= (1.25 x IFM amps) + (1.00 x heater FLA).
10
Downloaded from www.Manualslib.com manuals search engine
Step 7 — Make Outdoor-Air Inlet Table 3 — Heat Anticipator Settings
Adjustments UNIT UNIT kW* STAGE 1 STAGE 2
MANUAL OUTDOOR-AIR DAMPER — All units 50TJ VOLTAGES
(except those equipped with a factory-installed economizer) 26/34 .40 .66
208/230-3-60 42/56 .66 .40
have a manual outdoor-air damper to provide ventilation air. 56/75 .66 .66
Damper can be preset to admit up to 25% outdoor air into 20 .40 .40
return-air compartment. To adjust, loosen securing screws 380-3-60
016-028 35 .40 .66
and move damper to desired setting. Then retighten screws 32 .40 .40
to secure damper (Fig. 13). 460-3-60 55 .40 .66
80 .66 .66
OPTIONAL ECONOMIZER 575-3-60 50 .66 .66
Economizer Motor Control Module (Fig. 14-16) — Set to
*Heater kW is based on heater voltage of 208 v, 240 v, 380 v, 480 v,
the ‘‘D’’ setting (Fig. 15). The control module is located on and 575 v.
the economizer motor. See Fig. 14 and 16.
Damper Vent Position Setting
1. Set fan switch at ON position (continuous fan operation)
and close night switch if used.
2. Set system selector switch to OFF position.
3. Turn adjustment screw slowly until dampers assume de-
sired vent position. Do not manually operate economizer
motor since damage to motor will result.
LEGEND
LED — Light-Emitting Diode
Fig. 15 — Economizer Control Module
Fig. 13 — 25% Outdoor-air Section Details (Part Number W7459A)
11
Downloaded from www.Manualslib.com manuals search engine
Step 8 — Install Outdoor-Air Hood — The same IMPORTANT: Be sure all seal strips and RTV sealant
type of factory-installed hood is used on units with 25% air are intact. A watertight seal to inside of unit must be
ventilation and units with an economizer. maintained.
NOTE: The hood top panel, upper and lower filter retain-
ers, hood drain pan, baffle (028), and filter support bracket DIFFERENTIAL ENTHALPY CONTROL
are secured opposite the condenser end of the unit. The screens,
hood side panels, remaining section of filter support bracket, NOTE: The accessory outdoor-air enthalpy sensor must be
seal strip, and all other hardware are in a package located installed BEFORE the economizer hoods are installed on the
inside the return-air filter access panel (Fig. 17). unit or hoods will have to be removed.
1. Attach seal strip to upper filter retainer. See Fig. 18. 1. Remove and discard the factory-installed jumper assem-
bly containing the 800-ohm resistor on the economizer
2. Assemble hood top panel and side panels, upper filter re- control module (between terminals SR and +. See
tainer, and hood drain pan (Fig. 19). Fig. 15.
3. Secure lower filter retainer and long section of filter sup- 2. Disconnect black wire from economizer control module
port bracket to unit. See Fig. 19. Leave screws loose on terminal SO and blue wire from the OAT (outdoor-air
028 units. thermostat).
4. Slide baffle (size 028 unit) behind lower filter retainer and 3. Remove OAT and black wire assembly containing the
tighten screws. 620-ohm resistor from the outside of the economizer (see
5. Loosen sheet metal screws for base unit top panel located Fig. 13).
above outdoor-air inlet opening, and remove screws for 4. Mount the outdoor-air enthalpy sensor (first sensor) to
hood side panels located on the sides of the outdoor-air the economizer on the outside of the unit (in the same
inlet opening. location from which the OAT was removed) using the 2
6. Match notches in hood top panel to unit top panel screws. screws provided. See Fig. 13.
Insert hood flange between unit top panel flange and unit. 5. Reconnect the blue wire removed in Step 2 to the en-
Tighten screws. thalpy sensor terminal +.
7. Hold hood side panel flanges flat against unit, and install 6. Cut the violet wire provided to desired length and ter-
screws removed in Step 5. minate with quick-connect terminal provided. Route the
8. Insert outdoor-air inlet screens and spacer in channel cre- violet wire from the enthalpy sensor terminal S, through
ated by lower filter retainer and filter support bracket. the snap bushing, and to the economizer control module
9. Attach remaining short section of filter support bracket. terminal SO.
7. Mount the second enthalpy sensor in the return-air duct
ENTHALPY CONTROL INSTALLATION (return-air sensor).
NOTE: The accessory outdoor-air enthalpy sensor must be 8. Route the blue wire (provided) from terminal + on the
installed BEFORE the economizer hoods are installed on the return-air enthalpy sensor to the economizer control mod-
unit or hoods will have to be removed. ule terminal +.
1. Remove and discard the factory-installed jumper assem- 9. Route the violet wire (provided) from terminal S on the
bly containing the 800-ohm resistor on the economizer return-air enthalpy sensor to the economizer control mod-
control module (between terminals SR and +). See ule terminal SR.
Fig. 15.
10. Turn changeover set point dial clockwise past the ‘‘D’’
2. Remove black wire assembly containing the 620-ohm re- setting, or the control will not operate on a differential.
sistor from between economizer control module terminal See Fig. 15.
SO and the outdoor-air thermostat (OAT). Place this wire
assembly (containing the 620-ohm resistor) between econo- 11. Reinstall economizer hood if removed.
mizer control module terminals SR and +, replacing the
jumper removed in Step 1. See Fig. 15. IMPORTANT: Be sure all seal strips and RTV sealant
3. Disconnect the blue wire from the OAT. are intact. A watertight seal to inside of unit must be
maintained.
4. Remove OAT from the outside of the economizer (see
Fig. 13).
Step 9 — Install All Accessories — After all the
5. Mount the enthalpy sensor (Fig. 20) to the economizer on factory-installed options have been adjusted, install all field-
the outside of the unit (in the same location from which installed accessories. Refer to the accessory installation in-
the OAT was removed) using the 2 screws provided. See structions included with each accessory.
Fig. 13.
6. Reconnect the blue wire removed in Step 3 to the en- MOTORMASTERt I CONTROL INSTALLATION (50TJ016
thalpy sensor terminal +. and 020 Only)
7. Cut the violet wire provided to desired length and ter- Install Field-Fabricated Wind Baffles — Wind baffles must
minate with quick-connect terminal provided. Route the be field-fabricated for all units to ensure proper cooling cycle
violet wire from the enthalpy sensor terminal S, through operation at low ambient temperatures. See Fig. 22 for baffle
the snap bushing, and to the economizer control module details. Use 20-gage, galvanized sheet metal, or similar
terminal SO . See Fig. 15. corrosion-resistant metal for baffles. Use field-supplied screws
to attach baffles to unit. Screws should be 1⁄4-in. diameter
8. Set changeover set point to the desired location. and 5⁄8-in. long. Drill required screw holes for mounting baffles.
See Fig. 21.
NOTE: For maximum benefit of outdoor air, set the en-
thalpy control to the ‘‘A’’ setting. At this setting, when
the relative humidity is 50% and the outdoor air is below To avoid damage to the refrigerant coils and electrical
74 F, the relay contacts on the sensor will be closed. components, use recommended screw sizes only. Use
care when drilling holes.
9. Reinstall economizer hoods if removed.
12
Downloaded from www.Manualslib.com manuals search engine
MOTORMASTER III CONTROL INSTALLATION
(50TJ024 and 028 Only)
Install Field-Fabricated Wind Baffles — Wind baffles must
be field-fabricated for all units to ensure proper cooling cycle
operation at low ambient temperatures. See Fig. 22 for baffle
details. Use 20-gage, galvanized sheet metal, or similar
corrosion-resistant metal for baffles. Use field-supplied screws
to attach baffles to unit. Screws should be 1⁄4-in. diameter
and 5⁄8-in. long. Drill required screw holes for mounting baffles.
BAFFLE (028 ONLY)
LOWER FILTER
RETAINER
FILTER SUPPORT
Fig. 17 — Outdoor-Air Hood Component Location BRACKET
HOOD SIDE
PANELS (2)
HOOD TOP
PANEL
BAFFLE
(028 ONLY)
LOWER
FILTER
RETAINER
13
Downloaded from www.Manualslib.com manuals search engine
CONTROL CONTROL POINT
(approx Deg)
CURVE AT 50% RH
A 73 To avoid damage to the refrigerant coils and electrical
B 68 components, use recommended screw sizes only. Use
C 63 care when drilling holes.
D 58
Replace Outdoor Motor — Replace outdoor fan motor no. 1
with motor included in accessory kit. Existing motor is not
Motormastert III compatible.
Install Motormaster III Controls — Only one Motor-
master III control is required per unit.
Sensor — Install the sensor for thermistor input control in
the location shown in Fig. 24. Connect sensor leads to the
purple and grey control signal leads on the Motormaster III
control.
Signal Selection Switch — Remove the cover of the Motor-
master III control. Set the switch to accept the thermistor
sensor input signal. Set the frequency to match the unit power
supply (60 Hz).
Motormaster III Control — Recommended mounting loca-
tion is beneath the control box, mounted to the partition that
separates the control box section from the indoor section.
NOTE: If unit power is supplied through the roof curb and
basepan of the unit, mount the Motormaster III control on
the corner post adjacent to the conduit running from the base-
pan to the bottom of the control box.
LEGEND
RH — Relative Humidity
Fig. 21 — Psychrometric Chart for Solid-State
Enthalpy Control
SENSOR SENSOR
LOCATION LOCATION
14
Downloaded from www.Manualslib.com manuals search engine
discharge line, and one on the liquid line. In addition Schrader-
type valves are located underneath the low-pressure switches.
Be sure that caps on the ports are tight.
Compressor Rotation — It is important to be certain
the compressors are rotating in the proper direction. To de-
termine whether or not compressors are rotating in the proper
direction:
1. Connect service gages to suction and discharge pressure
fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge pres-
sure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge
pressure does not rise to normal levels:
1. Note that the evaporator fan is probably also rotating in
the wrong direction.
2. Turn off power to the unit.
SENSOR SENSOR 3. Reverse any two of the incoming power leads.
LOCATION LOCATION 4. Turn on power to the compressor.
The suction and discharge pressure levels should now move
to their normal start-up levels.
NOTE: When compressors are rotating in the wrong direc-
tion, the unit will have increased noise levels and will not
provide heating and cooling.
After a few minutes of reverse operation, the scroll com-
pressor internal overload protection will open, which will
activate the unit’s lockout and requires a manual reset. Reset
is accomplished by turning the thermostat on and off.
HAIRPIN END HAIRPIN END Evaporator Fan — Fan belt and variable pulleys are
50TJ024 50TJ028 factory installed. Remove tape from the fan pulley. See
Table 4 for Air Quantity Limits. See Tables 5-7 for Fan
NOTE: All sensors are located on the eighth hairpin up from the Performance data. Be sure that fans rotate in the proper
bottom.
direction. See Tables 8 and 9 for Static Pressure infor-
Fig. 24 — MotormasterT III Sensor Locations mation for accessories and options. See Table 10 for fan rpm
at various fan motor pulley settings. To alter fan perfor-
mance, see Evaporator-Fan Performance Adjustment sec-
tion, page 21.
START-UP Table 4 — Air Quantity Limits
Use the following information and Start-Up Checklist on UNIT
page CL-1 to check out unit PRIOR to start-up. MINIMUM CFM MAXIMUM CFM
50TJ
016 4500 7,500
Unit Preparation — Check that unit has been installed 020 5400 9,000
in accordance with these installation instructions and all 024 6000 10,000
applicable codes. 028 7000 11,250
16
Downloaded from www.Manualslib.com manuals search engine
Table 6 — Fan Performance — 50TJ020 and 024
17
Downloaded from www.Manualslib.com manuals search engine
Table 7 — Fan Performance — 50TJ028
18
Downloaded from www.Manualslib.com manuals search engine
Table 8 — Accessory/FIOP Static Pressure (in. wg) — 50TJ016
CFM
COMPONENT
4500 5000 6000 7200 7500
Economizer 0.04 0.05 0.07 0.09 0.10
Glycol Coil 0.22 0.26 0.35 0.44 0.46
Electric Heat (kW)
22 0.06 0.07 0.09 0.11 0.12
26/34 0.06 0.07 0.09 0.11 0.12
32 0.06 0.07 0.09 0.11 0.12
37 0.07 0.08 0.12 0.15 0.17
42/56 0.07 0.08 0.12 0.16 0.17
50 0.09 0.10 0.15 0.20 0.21
55 0.07 0.08 0.12 0.15 0.17
56/75 0.09 0.10 0.15 0.20 0.21
80 0.09 0.10 0.15 0.20 0.21
LEGEND NOTES:
FIOP — Factory-Installed Option 1. The static pressure must be added to external static pressure. The
sum and the evaporator entering-air cfm should then be used in
conjunction with the Fan Performance tables to determine blower
rpm and watts.
2. Heaters are rated at 240 v, 480 v, and 600 v.
19
Downloaded from www.Manualslib.com manuals search engine
Base Unit Operation EVAPORATOR COIL — Clean as required with a commer-
cial coil cleaner.
COOLING, UNITS WITHOUT ECONOMIZER — When
thermostat calls for cooling, terminals G and Y1 are ener- NOTE: The 50TJ028 unit has a mist eliminator screen at-
gized. The indoor (evaporator) fan contactor (IFC), and com- tached to the evaporator coil to prevent condensate runoff at
pressor contactor no. 1 (C1) are energized and evaporator- high wet-bulb conditions. Check periodically and clean as
fan motor, compressor no. 1 and condenser fans start. The necessary.
condenser-fan motors run continuously while unit is cool- CONDENSER COIL — Clean condenser coil annually and
ing. If the thermostat calls for a second stage of cooling by as required by location and outdoor-air conditions. Inspect
energizing Y2, compressor contactor no. 2 (C2) is energized coil monthly — clean as required.
and compressor no. 2 starts.
CONDENSATE DRAIN — Check and clean each year at
HEATING, UNITS WITHOUT ECONOMIZER (If Acces- start of cooling season.
sory or Optional Heater is Installed) — Upon a call for heat-
ing through terminal W1, IFC and heater contactor no. 1 (HC1) FILTERS — Clean or replace at start of each heating and
are energized. On units equipped for 2 stages of heat, when cooling season, or more often if operating conditions re-
additional heat is needed, HC2 is energized through W2. quire. Refer to Table 1 for type and size.
COOLING, UNITS WITH ECONOMIZER — Upon a call NOTE: The 50TJ028 unit requires industrial grade throw-
for cooling, when outdoor ambient temperature is above the away filters capable of withstanding face velocities up to
outdoor-air temperature control setting, the evaporator and 625 fpm. Ensure that replacement filters for the 50TJ028 units
condenser fans and compressor energize. The economizer are rated for 625 fpm.
damper moves to VENT position. OUTDOOR-AIR INLET SCREENS — Clean screens with
Upon a first-stage call for cooling, when outdoor ambient steam or hot water and a mild detergent. Do not use throw-
temperature is below the temperature control setting, the evapo- away filters in place of screens.
rator fan starts and economizer damper modulates to main-
tain mixed-air temperature. The compressor(s) remains off. Lubrication
Upon a second-stage call for cooling, compressor no. 1 is COMPRESSORS — Each compressor is charged with the
energized and mechanical cooling is integrated with econo- correct amount of oil at the factory. Conventional white oil
mizer cooling. Compressor no. 2 is locked out. If the outdoor- (Sontext 200LT) is used. White oil is compatible with 3GS
air temperature is below 50 F, a cooling lockout switch pre- oil, and 3GS oil may be used if the addition of oil is re-
vents the compressor(s) from running. quired. See compressor nameplate for original oil charge. A
complete recharge should be four ounces less than the origi-
When supply-air temperature drops below a fixed set point, nal oil charge. When a compressor is exchanged in the field
the economizer damper modulates to maintain the tempera- it is possible that a major portion of the oil from the replaced
ture at the fixed set point. compressor may still be in the system. While this will not
FREEZE PROTECTION THERMOSTAT(S) — A freeze pro- affect the reliability of the replacement compressor, the ex-
tection thermostat (FPT) is located on the top and bottom of tra oil will add rotor drag and increase power usage. To re-
the evaporator coil. It detects frost build-up and turns off the move this excess oil, an access valve may be added to the
compressor, allowing the coil to clear. Once frost has melted, lower portion of the suction line at the inlet of the compres-
the compressor can be reenergized by resetting the compres- sor. The compressor should then be run for 10 minutes, shut
sor lockout. down, and the access valve opened until no oil flows. This
should be repeated twice to make sure the proper oil level
HEATING, UNITS WITH ECONOMIZER (If Accessory has been achieved.
or Optional Heater is Installed) — The outdoor air damper
stays at VENT position while the evaporator fan is operat- FAN SHAFT BEARINGS — For size 016 units, bearings
ing. Upon a call for heating through terminal W1, the indoor are permanently lubricated. No field lubrication is required.
(evaporator) fan contactor (IFC) and heater contactor no. 1 For size 020-028 units, the bearings are of the pillow block
(HC1) are energized. On units equipped for 2 stages of heat, type and have grease fittings. The bearing opposite the mo-
when additional heat is needed, HC2 is energized through tor end has an extended tube line so it can be lubricated from
W2. the motor side. Lubricate the bearings twice annually.
Typical lubricants are given below:
MANUFACTURER LUBRICANT
SERVICE Texaco Regal AFB-2*
Mobil Mobilplex EP No. 1
Sunoco Prestige 42
Texaco Multifak 2
Before performing service or maintenance operations on
unit, turn off main power switch to unit. Turn off ac- *Preferred lubricant because it contains rust and oxidation inhibitors.
cessory heater power switch if applicable. Electrical shock
could cause personal injury. CONDENSER AND EVAPORATOR-FAN MOTOR BEAR-
INGS — The condenser and evaporator-fan motors have
Cleaning — Inspect unit interior at beginning of each heat- permanently-sealed bearings, so no field lubrication is
ing and cooling season and as operating conditions require. necessary.
Remove unit top panel and/or side panels for access to unit
interior.
20
Downloaded from www.Manualslib.com manuals search engine
Evaporator Fan Performance Adjustment
(Fig. 25-27) — Fan motor pulleys are factory set for speed
shown in Table 1.
To change fan speeds:
1. Shut off unit power supply.
2. a. Size 016 Only: Loosen belt by loosening fan motor
mounting plate nuts.
b. Size 020-028 Only: Loosen nuts on the 2 carriage bolts
in the motor mounting base. Install jacking bolt and
plate under motor base (bolt and plate are shipped in
installer’s packet). See Fig. 27. Using bolt and plate,
raise motor to top of slide and remove belt. Secure
motor in this position by tightening the nuts on the
carriage bolts.
3. Loosen movable-pulley flange setscrew (see Fig. 25).
4. Screw movable flange toward fixed flange to increase speed
and away from fixed flange to decrease speed. Increasing
fan speed increases load on motor. Do not exceed maxi-
mum speed specified in Table 1.
See Table 4 for air quantity limits.
5. Set movable flange at nearest keyway of pulley hub and
tighten setscrew. (See Table 1 for speed change for each
full turn of pulley flange.)
6. Replace and tighten belts. See Belt Tension Adjustment
section on page 22.
To align fan and motor pulleys:
1. Loosen fan pulley setscrews.
Fig. 25 — Evaporator-Fan Pulley Alignment
2. Slide fan pulley along fan shaft. and Adjustment
3. Make angular alignment by loosening motor from mount-
ing plate.
Evaporator Fan Service and Replacement
50TJ016 UNITS (See Fig. 26)
NOTE: To remove belts only, follow Steps 1-6.
1. Remove filter and supply-air section panels.
2. Remove unit top panel.
3. Loosen carriage nuts A and B holding motor mount as-
sembly to fan scroll side plates.
4. Loosen screw C.
5. Rotate motor mount assembly (with motor attached) as
far as possible away from evaporator coil.
6. Remove belt.
7. Rotate motor mount assembly back past original posi-
tion toward evaporator coil.
8. Remove motor mounting nuts D and E (both sides).
9. Lift motor up through top of unit.
10. Reverse above procedure to reinstall motor.
11. Check and adjust belt tension as necessary.
50TJ020-028 UNITS (See Fig. 27) — The 50TJ020-028 units
use a fan motor mounting system that features a slide-out
motor mounting plate. To replace or service the motor, slide
out the bracket.
1. Remove the evaporator-fan access panel and the heat-
ing control access panel.
2. Remove the center post (located between the evaporator
fan and heating control access panels) and all screws
securing it.
3. Loosen nuts on the two carriage bolts in the motor mount-
ing base. Fig. 26 — 50TJ016 Evaporator-Fan
Motor Section
21
Downloaded from www.Manualslib.com manuals search engine
4. Using jacking bolt under motor base, raise motor to top Condenser-Fan Adjustment
of slide and remove belt. Secure motor in this position
by tightening the nuts on the carriage bolts. 50TJ016,020 UNITS (Fig. 28)
5. Remove the belt drive. 1. Shut off unit power supply.
6. Remove jacking bolt and tapped jacking bolt plate. 2. Remove access panel(s) closest to the fan to be adjusted.
7. Remove the 2 screws that secure the motor mounting 3. Loosen fan hub setscrews.
plate to the motor support channel. 4. Adjust fan height on shaft using a straightedge placed across
8. Remove the 3 screws from the end of the motor support the fan orifice.
channel that interfere with the motor slide path. 5. Tighten setscrews and replace panel(s).
9. Slide out the motor and motor mounting plate. 6. Turn on unit power.
10. Disconnect wiring connections and remove the 4 mount- 50TJ024,028 UNITS (Fig. 29)
ing bolts.
1. Shut off unit power supply.
11. Remove the motor.
2. Remove fan top-grille assembly and loosen fan hub screws.
12. To install the new motor, reverse Steps 1-11.
3. Adjust fan height on unit, using a straightedge placed across
the fan orifice.
4. Tighten setscrews and replace rubber hubcap to prevent
hub from rusting to motor shaft.
5. Fill hub recess with permagum if rubber hubcap is
missing.
NOTE: A 31⁄2-in. bolt and threaded plate are included in the installer’s
packet. They should be added to the motor support channel below
the motor mounting plate to aid in raising the motor. The plate part
number is 50DP503842. The adjustment bolt is 3⁄8 - 16 x 13⁄4-in. LG.
22
Downloaded from www.Manualslib.com manuals search engine
Table 11 — Economizer Checkout Procedures 9. Remove the jumper from around the contacts of the OAT
if installed in Step 6. Remove the jumper from termi-
TEST PROCEDURE RESULTS nals T and T1 installed in Step 7.
A. Disconnect power at 10. If the Cooling mode was simulated to operate the unit
TR and TR1.
Disconnect jumper in Step 4, remove the jumper and reconnect the ther-
between P and mostat wires to terminals Y1 and Y2.
P1. See Fig. 15.
B. Jumper TR to 1. Power Failure — Dampers have a spring return. In event
C. Jumper T1 to T. of power failure, dampers will return to fully closed position
D. Disconnect outdoor-air until power is restored. Do not manually operate damper
thermostat connections
from SO and +. motor.
Factory-installed
800 ohm resistor Refrigerant Charge — Amount of refrigerant charge
should remain connected is listed on unit nameplate and in Table 1. Refer to Carrier
to SR and +. GTAC II; Module 5; Charging, Recovery, Recycling, and Rec-
E. Reconnect power to
terminals TR and TR1. lamation section for charging methods and procedures. Unit
1. LED (light-emitting diode) panels must be in place when unit is operating during charg-
should be off. ing procedure.
2. Motor is in closed position.
NOTE: Do not use recycled refrigerant as it may contain
contaminants.
TEST PROCEDURE RESULTS
A. Disconnect
NO CHARGE — Use standard evacuating techniques. After
factory-installed evacuating system, weigh in the specified amount of refrig-
resistor from erant (refer to Table 1).
terminals SR and +.
1. LED (light-emitting diode) LOW CHARGE COOLING — Using cooling charging chart
should be on. (see Fig. 30), add or remove refrigerant until conditions of
2. Motor drives toward open. the chart are met. Note that charging chart is different from
those normally used. An accurate pressure gage and temperature-
Table 12 — High and Low Outdoor-Air sensing device is required. Charging is accomplished by en-
Temperature Simulation suring the proper amount of liquid sub-cooling. Measure liquid
line pressure at the liquid line service valve using pressure
TEST PROCEDURE RESULTS gage. Connect temperature sensing device to the liquid line
A. Reconnect factory- near the liquid ine service valve and insulate it so that out-
installed 800 ohm resis- door ambient temperature does not affect reading.
tor between terminals
SR and +. TO USE THE COOLING CHARGING CHART — Use the
B. Connect 1200 ohm above temperature and pressure readings, and find the in-
checkout resistor tersection point on the cooling charging chart. If intersection
between terminals point on chart is above line, add refrigerant. If intersection
SO and +.
C. Turn set point poten-
point on chart is below line, carefully recover some of the
tiometer to position A. charge. Recheck suction pressure as charge is adjusted.
Low outdoor-air temperature NOTE: Indoor-air CFM must be within normal operating range
test results:
1. LED (light-emitting diode)
of unit. All outdoor fans must be operating.
should be on. The TXV (thermostatic expansion valve) is set to main-
2. Motor drives toward open. tain between 15 and 20 degrees of superheat at the compres-
D. Turn set point poten- sors. The valves are factory set and should not require
tiometer to position D. re-adjustment.
E. Disconnect 1200 ohm
checkout resistor.
High outdoor-air temperature
BOTH CIRCUITS
test results:
ALL OUTDOOR FANS MUST BE OPERATING
1. LED should be off. 140
LIQUID TEMPERATURE AT LIQUID VALVE (DEG F)
120
ADD CHARGE IF ABOVE CURVE
5. Set the outdoor-air thermostat (OAT) located in the econo-
mizer section of the unit (see Fig. 14) to 75 F.
6. If the outdoor temperature is below 75 F, the econo- 100
mizer will control the mixed air with the mixed-air sen-
sor. If the outdoor air is above 75 F, place a jumper around
the contacts of the OAT. 80
7. Jumper terminal T to terminal T1 on the module (see
Fig. 15). The economizer will go to the full open po- REDUCE CHARGE IF BELOW CURVE
sition. The outdoor-air damper will go to the full open 60
position, and the return-air damper will go to the full
closed position.
8. Adjust mechanical linkage, if necessary, for correct po- 40
sitioning. It may be necessary to remove the filters to 50 100 150 200 250 300 350 400
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
adjust the linkage.
Fig. 30 — Cooling Charging Chart
23
Downloaded from www.Manualslib.com manuals search engine
Filter Drier — Replace whenever refrigerant system is EVAPORATOR FAN MOTOR PROTECTION — A manual
exposed to atmosphere. reset, calibrated trip, magnetic circuit breaker protects against
overcurrent. Do not bypass connections or increase the size
Protective Devices of the breaker to correct trouble. Determine the cause and
correct it before resetting the breaker.
COMPRESSOR PROTECTION
Overtemperature — Each compressor has an internal pro- CONDENSER-FAN MOTOR PROTECTION — Each
tector to protect it against excessively high discharge gas condenser-fan motor is internally protected against
temperatures. overtemperature.
Overcurrent — Each compressor has internal line break mo- HIGH- AND LOW-PRESSURE SWITCHES — If either
tor protection, except the circuit no. 1 on the 50TJ028 unit. switch trips, or if the compressor overtemperature switch ac-
Compressor no. 1 on the 50TJ028 unit uses an electronic tivates, that refrigerant circuit will be automatically locked
module located with the compressor junction box, to pro- out by the CLO. To reset, manually move the thermostat
vide motor protection. This electronic module monitors wind- setting.
ing and discharge temperatures. If these temperatures reach FREEZE PROTECTION THERMOSTAT (FPT) — An
the trip values, the module interrupts the control line and FPT is located on the top and bottom of the evaporator coil.
causes the compressor to switch off. It detects frost build-up and turns off the compressor, allow-
Crankcase Heater — Only the 50TJ028 unit is equipped with ing the coil to clear. Once the frost has melted, the com-
a 70-watt crankcase heater to prevent absorption of liquid pressor can be reenergized.
refrigerant by oil in the crankcase when the compressor is
idle. The crankcase heater is energized whenever there is a Relief Devices — All units have relief devices to pro-
main power to the unit and the compressor is not energized. tect against damage from excessive pressures (e.g., fire). These
devices protect the high and low side.
IMPORTANT: After prolonged shutdown or servic-
ing, energize the crankcase heaters for 24 hours before Control Circuit, 24-V — This control circuit is pro-
starting the compressors. tected against overcurrent by a 3.2-amp circuit breaker. Breaker
can be reset. If it trips, determine cause of trouble before
resetting.
Compressor Lockout — If any of the safeties (high-pressure,
low-pressure, freeze protection thermostat, compressor in- Replacement Parts — A complete list of replacement
ternal thermostat) trip, or if there is loss of power to the parts may be obtained from any Carrier distributor upon
compressors, the CLO (compressor lockout) will lock the request.
compressors off. To reset, manually move the thermostat
setting.
24
Downloaded from www.Manualslib.com manuals search engine
Fig. 31 — Typical Wiring Schematic (50TJ016, 460-v Shown)
25
Downloaded from www.Manualslib.com manuals search engine
Fig. 31 — Typical Wiring Schematic (50TJ016, 460-v Shown) (cont)
NOTES:
1. Compressor and fan motors thermally protected; 3-phase motors protected against
primary single-phasing conditions.
2. If any of the original wire furnished must be replaced, it must be replaced with
type 90 C wire or its equivalent.
3. Jumpers are omitted when unit is equipped with economizer.
4. The CLO locks out the compressor to prevent short cycling on compressor over-
load and safety devices. Before replacing CLO, check these devices.
5. Number(s) indicates the line location of used contacts. A bracket over (2) num-
bers signifies a single-pole, double-throw contact. An underlined number sig-
nifies a normally-closed contact. A plain (no line) number signifies a normally-
open contact.
26
Downloaded from www.Manualslib.com manuals search engine
Fig. 32 — Typical Component Arrangement (50TJ016 Shown)
27
Downloaded from www.Manualslib.com manuals search engine
TROUBLESHOOTING
Refer to Table 13 for troubleshooting details.
Table 13 — Cooling Service Analysis
PROBLEM CAUSE REMEDY
Compressor and Power failure. Call power company.
condenser fan Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker.
will not start.
Defective thermostat, contactor, transformer, or control Replace component.
relay.
Insufficient line voltage. Determine cause and correct.
Incorrect or faulty wiring. Check wiring diagram and rewire correctly.
Thermostat setting too high. Lower thermostat setting below room temperature.
Compressor will not start Faulty wiring or loose connections in compressor circuit. Check wiring and repair or replace.
but condenser fan runs. Compressor motor burned out, seized, or internal Determine cause. Replace compressor.
overload open.
Defective overload. Determine cause and replace.
Compressor locked out. Determine cause for safety trip and reset lockout.
One leg of 3-phase power dead. Replace fuse or reset circuit breaker.
Determine cause.
Compressor cycles Refrigerant overcharge or undercharge. Recover refrigerant, evacuate system, and recharge
(other than normally to nameplate.
satisfying thermostat). Defective compressor. Replace and determine cause.
Insufficient line voltage. Determine cause and correct.
Blocked condenser. Determine cause and correct.
Defective overload. Determine cause and replace.
Defective thermostat. Replace thermostat.
Faulty condenser-fan motor. Replace.
Restriction in refrigerant system. Locate restriction and remove.
Compressor operates Dirty air filter. Replace filter.
continuously. Unit undersized for load. Decrease load or increase unit size.
Thermostat set too low. Reset thermostat.
Low refrigerant charge. Locate leak, repair, and recharge.
Air in system. Recover refrigerant, evacuate system, and recharge.
Condenser coil dirty or restricted. Clean coil or remove restriction.
Excessive head pressure. Dirty air filter. Replace filter.
Dirty condenser coil. Clean coil.
Refrigerant overcharged. Recover excess refrigerant.
Faulty TXV. 1. Check TXV bulb mounting and secure tightly to
suction line.
2. Replace TXV if stuck open or closed.
Air in system. Recover refrigerant, evacuate system, and recharge.
Condenser air restricted or air short-cycling. Determine cause and correct.
Head pressure too low. Low refrigerant charge. Check for leaks, repair, and recharge.
Restriction in liquid tube. Remove restriction.
Excessive suction High heat load. Check for source and eliminate.
pressure. Faulty TXV. 1. Check TXV bulb mounting and secure tightly to
suction line.
2. Replace TXV if stuck open or closed.
Refrigerant overcharged. Recover excess refrigerant.
Suction pressure too low. Dirty air filter. Replace filter.
Low refrigerant charge. Check for leaks, repair, and recharge.
Metering device or low side restricted. Remove source of restriction.
Faulty TXV. 1. Check TXV bulb mounting and secure tightly to
suction line.
2. Replace TXV if stuck open or closed.
Insufficient evaporator airflow. Increase air quantity. Check filter and replace if
necessary.
Temperature too low in conditioned area. Reset thermostat.
Field-installed filter drier restricted. Replace.
Compressor no. 2 Unit in economizer mode. Proper operation; no remedy necessary.
will not run.
28
Downloaded from www.Manualslib.com manuals search engine
Downloaded from www.Manualslib.com manuals search engine
Copyright 1998 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 PC 111 Catalog No. 565-135 Printed in U.S.A. Form 50TJ-14SI Pg 30 10-98 Replaces: 50TJ-13SI
Tab 1b
Downloaded from www.Manualslib.com manuals search engine
Downloaded from www.Manualslib.com manuals search engine
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
START-UP CHECKLIST
PRE-START-UP:
START-UP:
ELECTRICAL
SUPPLY VOLTAGE L1-L2 L2-L3 L3-L1
TEMPERATURES
OUTDOOR-AIR TEMPERATURE F DB (Dry-Bulb)
RETURN-AIR TEMPERATURE F DB F WB (Wet-Bulb)
COOLING SUPPLY AIR F
ELECTRIC HEAT SUPPLY AIR (IF SO EQUIPPED) F
PRESSURES
REFRIGERANT SUCTION CIRCUIT NO. 1 PSIG CIRCUIT NO. 2 (020-028 ONLY) PSIG
REFRIGERANT DISCHARGE CIRCUIT NO. 1 PSIG CIRCUIT NO. 2 (020-028 ONLY) PSIG CUT ALONG DOTTED LINE
GENERAL
M ECONOMIZER MINIMUM VENT AND CHANGEOVER SETTINGS TO JOB REQUIREMENTS
M VERIFY INSTALLATION OF ALL OPTIONS AND ACCESSORIES
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 PC 111 Catalog No. 565-135 Printed in U.S.A. Form 50TJ-14SI Pg CL-1 10-98 Replaces: 50TJ-13SI
Tab 1b
Downloaded from www.Manualslib.com manuals search engine