GSK0400701S0201
GSK0400701S0201
GSK0400701S0201
1
System pro M
Warranty
We assume warranty in accordance with the Standard Sale and Delivery Terms, Complaints
shall be made in writing eight days following receipt of the goods.
Technical information and illustrations are not binding and subject to change without
notice.
2
Miniature Circuit Breakers
System pro M
Contents Page
Technical data
General ................................................................................................................ 4
Technical data .................................................................................................... 8
Tripping characteristics ...................................................................................... 14
Short-Circuit rupturing capacity ........................................................................ 15
Back-up protection ............................................................................................ 17
Tripping diagrams .............................................................................................. 18
Internal resistances ............................................................................................ 22
Max. permissible impedances of fault loops .................................................... 23
Short-circuit selectivity ....................................................................................... 24
Temperature influence ........................................................................................ 27
Application examples ......................................................................................... 28
Protection of lamps ............................................................................................ 28
Tripping diagrams, characteristics UC Range .................................................. 29
Supplementary devices ...................................................................................... 31
Mounting of supplementary devices ................................................................. 33
Mounting and operating instructions ................................................................ 35
Dimensions ......................................................................................................... 37
Busbars and busbar blocks ............................................................................... 39
Approvals and certifications .............................................................................. 41
Order specification
3
Miniature Circuit Breakers
System pro M
Delivered with open box terminals with captive screws and lower
dualfunction terminal ready for busbar connection.
4
Miniature Circuit Breakers
System pro M
Up to 5 conductors with cross sec- The lower terminal also allows cross-
tion 1.5 mm2 each can be connected wiring by solid round conductor.
safely and reliably.
SK 0116 B 94
5
Miniature Circuit Breakers
System pro M
STOTZ M.C.B’s of the System pro M are equiped with the Oscillogram of a rupturing process
for well proven STOTZ hammer head system and thus
offer current limiting to the highest degree.
They offer
SK 0130 Z 98
through ƒi2dt (current heating value).
Un = mains voltage
Unprotected pole (no trip mechanism) is force switched together with Contact position dependent on that of the M.C.B.
the M.C.B. The contacts are potential-free.
It can also be used as a normally open contact for signalling the contact
position of the M.C.B.
SK 0328 B 91
SK 0294 B 91
SK 0067 B 92
6
Miniature Circuit Breakers
System pro M
General
Brief description
Current limiting M.C.B.'s with undelayed magnetic and delayed thermal trips, with fixed
setting. Metal framed trip-free switching mechanism.
Task
Protection against overheating of electrical wires, cables and appliances in the case of
overcurrent due to overload, short-circuit or earth fault in compliance with DIN VDE 0100
part 430.
Protection against dangerous body currents in the case of too high touch voltage due to
insulation faults in compliance with DIN VDE 0100 part 410.
SK 0217 Z 00
Application
B, C, D
For installation, switching, regulation and metering systems of building installations in
commercial and industrial projects.
Accessories
The S2 ... range can be fitted subsequently with an auxiliary contact. The auxiliary contacts are
suitable for switching auxiliary circuits as a function of the M.C.B.’s contact position; with 2
or 3 galvanically separated contacts. The auxiliary contacts are trip-free due to their coupling
with the switching mechanism.
K The new characteristics acc. EN 60 898 are for line protection . They all have the same thermal
settings and differ only in their magnetic tripping values.
The higher magnetic settings of the C- or D-characteristics are for applications with start or
high inrush-currents.
K-Characteristic
Z-Characteristic
7
Miniature Circuit Breakers
System pro M
8
Miniature Circuit Breakers
System pro M
Specifications: DIN VDE 0641 part 11, IEC 898, EN 60 898, IEC 947-2
No. of poles: 1, 2, 3, 4, 1+NA, 3+NA
Tripping characteristics: B, C, K, Z
Rated current In: 0,5 ... 63 A
Rated voltage U n: single pole: 230 / 400 V
multipole 400 V
Max. operating voltage U Bmax : AC: Un + 10 %, acc. to UL 1077 and CSA 22.2: 480 V
DC: 1-pole 60 V ..., 2-pole 110 V ...
Min. operating voltage UBmin: 12 V , 12 V ...
Rated rupturing capacity
acc. to IEC 898, EN 60 898: see page 15
Selectivity class: S3
Short-circuit rupturing capacity: see page 15
Frequency: 50 ... 60 Hz, other frequencies see page 14
Insulation acc. DIN VDE 0110 part 1 and 2
- Overvoltage category: III
- Pollution degree: 2
- Surge voltage: 5 kV (1.2/50 µs)
- Surge alternating voltage: 3 kV (50/60 Hz)
Housing: Moulded plastic group I (CTI 600) to DIN IEC 112/VDE 303 part 1 RAL 7035
Switching lever: Moulded plastic group II (400 CTI 600) black, sealable
Degree of protection acc. to
DIN VDE 0100: IP 20, when built in into distribution board: IP 40
Depth of unit: 68 mm
Dimensions: acc. to DIN 43 880, size 1, see page 37
Mounting position: optional
Mounting: snap-on fixing on standard profile rails EN 50 022, 35 x 7.5 or screw fixing by means of
mounting plate (see accessories)
Connection: Box terminals on top and combi box terminals on bottom, safe against unintentional
touch acc. to DIN VDE 0106 part 100. Suitable for solid or flexible conductors from 0,75
mm² to 25 mm² (max.16 mm² when a max. 3 mm busbar is connected; from 0,75 mm²
with casing and from 1,5 mm² without)
Thigtening torque: 2 Nm
Mech. service life: 20 000 operations
Service life at rated load: In 32 A: 20 000 operations
In 32 A: 10 000 operations
Climate resistance acc. to
DIN VDE 50 015 and DIN 68 part 2-30: constant climatic conditions 23/83, 40/93, 55/20 [°C/RH]
variable climatic conditions 25/95 – 40/93 [°C/RH]
Storage temperature: Tmax + 70 °C, Tmin – 40 °C
Ambient temperature: Tmax + 55 °C, Tmin – 25 °C
Shock resistance acc. to DIN IEC 68-2-27
and DIN EN 60 068-2-27: 30 g minimum of 2 impacts duration of shock 13 ms
Vibration resistance acc. to DIN IEC 68-2-6
and DIN EN 60 068-2-6: 5 g, 20 cycles 5 ... 150 ... 5 Hz at 0.8 · I n
Weight: see selection tables
9
Miniature Circuit Breakers
System pro M
Specifications: DIN VDE 0641, DIN VDE 0660 Teil 1, BS 3871, IEC 898, EN 60 898, IEC 947-2
No. of poles: 1, 2, 3, 4, 1+NA, 3+NA
Tripping characteristics: B, C, K, Z, UC-B, UC-K, UC-Z
Rated current In: 0,2 ... 63 A
Rated voltage U n: single pole: 230 / 400 V
multipole 400 V
Max. operating voltage U Bmax: AC: Un + 10 %, acc. to UL 1077 and CSA 22.2: 480 V
DC: 1-pole 60 V ... S 280 UC: 220 V ...
2-pole 110 V ... S 280 UC: 440 V ...
Min. operating voltage UBmin: 12 V , 12 V ...
Rated rupturing capacity
acc. to IEC 898, EN 60 898: see page 16
Selectivity class: S3
Short-circuit rupturing capacity: see page 16
Frequency: 16 2/3 ... 60 Hz, other frequencies see page 14
Insulation acc. DIN VDE 0110 part 1 and 2
- Overvoltage category: III
- Pollution degree: 2
- Surge voltage: 5 kV (1.2/50 µs)
- Surge alternating voltage: 3 kV (50/60 Hz)
Housing: Moulded plastic group I (CTI 600) to DIN IEC 112/VDE 303 part 1 RAL 7035
Switching lever: Moulded plastic group II (400 CTI 600) black, sealable
Degree of protection acc. to
DIN VDE 0100: IP 20, when built in into distribution board: IP 40
Depth of unit: 68 mm
Dimensions: acc. to DIN 43 880, size 1, see page 37
Mounting position: optional
Mounting: snap-on fixing on standard profile rails EN 50 022, 35 x 7.5 or screw fixing by means of
mounting plate (see accessories)
Connection: Combi box terminals on top and bottom, safe against unintentional touch acc. to DIN
VDE 0106 part 100. Suitable for solid or flexible conductors from 0,75 mm2 to 35 mm2
(max. 25 mm2 when a max. 3 mm busbar is connected; from 0,75 mm2 with casing and
from 1,5 mm2 without)
Thigtening torque: 2 Nm
Mech. service life: 20 000 operations
Service life at rated load: In 32 A: 20 000 operations
In 32 A: 10 000 operations
Climate resistance acc. to
DIN VDE 50 015 and DIN 68 part 2-30: constant climatic conditions 23/83, 40/93, 55/20 [°C/RH]
variable climatic conditions 25/95 – 40/93 [°C/RH]
Storage temperature: Tmax + 70 °C, Tmin – 40 °C
Ambient temperature: Tmax + 55 °C, Tmin – 25 °C
Shock resistance acc. to DIN IEC 68-2-27
and DIN EN 60 068-2-27: 30 g minimum of 2 impacts duration of shock 13 ms
Vibration resistance acc. to DIN IEC 68-2-6
and DIN EN 60 068-2-6: 5 g, 20 cycles 5 ... 150 ... 5 Hz at 0.8 · I n
Contact position indicator: OUT = green, ON = red
Weight: see selection tables
10
Miniature Circuit Breakers
System pro M
11
Miniature Circuit Breakers
System pro M Supplementary devices
Auxiliary contact and Signal contact / Auxiliary contact (acc. DIN VDE 0660 part 200)
Ith = 10 A
Ue 60 V 24 V Ue 60 V 24 V Ue 60 V 24 V
DC 13 DC 13 DC 13
Ie 2A 4A Ie 2A 4A Ie 1A 4A
Auxiliary contact S2 – H ... KL Technical data Auxilary contact S 290-H and signal
(Low power) contact S 290-S
Ith = 0.5 A acc. to DIN VDE 0660 part 200/7. 92; EN 60 947-5 -1
Ith = 16 A
Ue 24 V 12 V Ui = 440 V
AC 12
Ie 5 mA 10 mA Min. operating voltage: 17 V DC
12
Miniature Circuit Breakers
System pro M Supplementary devices
Shunt trip S2 – A
Type: S2 – A 1 S2 – A 2
Operating voltages: 12 ... 60 V 110 ... 415 V AC and 110 ... 250 V DC
24 VA / W ... 600 VA / W 40 VA ... 570 VA and 40 W ... 207 W
13
Miniature Circuit Breakers
System pro M
Tripping characteristics
Thermal trips Electromagnetic trips
Influence of ambient temperature see below. The tripping values for the electromagnetic trip are valid for AC 50 ... 60 Hz.
For other frequencies see table below.
From warm operating condition (After I1 1 h resp. 2h)
acc. to IEC 947-2 K 0.2 up to 63 A 1.05 ⋅ In > 1h 10 ⋅ In > 0.1 s > 0.2 s
1.2 ⋅ In < 1h
14 ⋅ In 21 ⋅ In < 0.1 s < 0.2 s
acc. to IEC 947-2 Z 0.5 up to 63 A 1.05 ⋅ In > 1h 2 ⋅ In > 0.1 s > 0.2 s
1.2 ⋅ In < 1h 3 ⋅ In 5 ⋅ In < 0.1 s < 0.2 s
Influence of ambient temperature see below. The tripping values for the electromagnetic trip are valid for AC 50 ... 60 Hz.
For other frequencies see table below.
From warm operating condition (After I 1 1 h)
The tripping values of the thermal trips are independent of the frequency. The electromagnetic tripping is not dependent on temperature.
14
Miniature Circuit Breakers
System pro M
S 260 – B 6 63 A 100 A
10 ... 20 100 A 100 A 6000
25 ... 32 10/0.5 6/0.7 10/0.5 6/0.7 10/4 100 A 100 A
3
40 125 A 100 A
50 ... 63 160 A 100 A
3 ... 4 20 A –
6 40 A –
8 63 A 100 A 6000
10 ... 20 10/0.5 6/0.7 10/0.5 6/0.7 10/4 100 A 100 A
3
25 ... 32 100 A 100 A
40 125 A 100 A
50 ... 63 160 A 100 A
S 270 – B 6 63 A 100 A
10 ... 20 80 A 100 A
10 000
25 ... 32 10/0.5 10/0.5 10/0.5 10/0.5 10/4 100 A 100 A
40 125 A 100 A 3
50 ... 63 160 A 100 A
3 ... 4 20 A –
6 40 A –
8 63 A 100 A
10 000
10 ... 20 10/0.5 10/0.5 10/0.5 10/0.5 10/4 80 A 100 A
3
25 ... 32 100 A 100 A
40 125 A 100 A
50 ... 63 160 A 100 A
3 20 A –
4 25 A –
6 ... 10 63 A 100 A
6000
16 ... 20 10/0.5 6/0.7 10/0.5 6/0.7 10/4 80 A 100 A
25 ... 32 100 A 100 A
40 125 A 100 A
50 ... 63 160 A 100 A
3 ... 4 20 A –
6 35 A 100 A
8 40 A 100 A 6000
10 ... 16 10/0.5 6/0.7 10/0.5 6/0.7 10/4 63 A 100 A
20 ... 25 80 A 100 A
32 ... 40 100 A 100 A
50 ... 63 125 A 100 A
15
Miniature Circuit Breakers
System pro M
B6 ... 25 A 10 kA 10 kA 6 kA 10 kA 10 kA 10 kA 6 kA 100 A
K, Z 0.2 ... 2 A unlimited unlimited unlimited unlimited unlimited unlimited unlimited not neccessary
K, Z 3 ... 4 A 10 kA 10 kA 6 kA 10 kA 10 kA 10 kA 6 kA 35 A
K, Z 6 ... 8 A 10 kA 10 kA 6 kA 10 kA 10 kA 10 kA 6 kA 63 A
K, Z 10 ... 32 A 10 kA 10 kA 6 kA 10 kA 10 kA 10 kA 6 kA 100 A
K; Z 40 ... 63 A 6 kA 6 kA 4.5 kA 10 kA 6 kA 6 kA 4.5 kA 125 A
Back-up protection is only necessary when, at the point of installation the maximum rated short circuit rupturing capacity is expected
to be exceeded.
Z 0.5 A ... 2 A
16
Miniature Circuit Breakers
System pro M
3 – – 35 –
4 – – 50 –
6 63 100 63 100
SK 0043 Z 97
Determination of the smallest selective back-up device (main circuit breaker or fuse) to Examples
a STOTZ M.C.B.
Determine for a M.C.B. type B16 the
Smallest rated current of back-up device = rated current of M.C.B. x selective factor smallest selective back-up device.
B 6 – B 63 A 1.4 1.4 -
S 700 – Ksel
C 0.5 – C 6 A 5
C 8 – C 32 A 2.0 1.4 3.2 In S 700 E 16 · 1.4 = 22.4 A
C 40 – C 63 A 2.5 select: S 700 – K 25
D 0.5 – D 3 A 5
D 4 – D 16 A 2.8 1.4 4
D 25 – D 63 A 3.2
Fuse gL
K 0.5 – K 3 A 5
K 4 – K 20 A 2.4 1.2 2 IN fuse gL 16 x 2.0 = 32 A
K 25 – K 63 A 3.2 select: fuse gL 32 A
S 280
K 0.2 – K 16 A 5
K 20 – K 63 A 2.8 1.4 4
Z 0.5 – Z 10 A 2
Z 16 – Z 63 A 1.15 1.15 1.6
17
Miniature Circuit Breakers
System pro M
Tripping diagrams
SK 0126 Z 00
SK 0128 Z 00
SK 0134 Z 00
Tripping characteristic B Tripping characteristic C Tripping characteristic D
acc. to DIN VDE 0641 part 11 acc. to DIN VDE 0641 part 11 acc. to DIN VDE 0641 part 11
In = 6 ... 63 A In = 0.5 ... 63 A In = 0.5 ... 63 A
S 260, S 270, S 280 S 260, S 270, S 280 S 280
SK 0142 Z 00
SK 0144 Z 00
SK 0146 Z 00
18
Miniature Circuit Breakers
System pro M
SK 0052 Z 97
Pulse duration
19
Miniature Circuit Breakers
System pro M
Miniature circuit breakers S 260 B/C Miniature circuit breakers S 270 B/C
SK 0165 Z 97
SK 0167 Z 97
min. melting I 2t (pre-arcing), e.g. In = 80 A gL Let through value I2t reduce by
max. Let-through I 2t of M.C.B., e.g. B 20 A 127 V with factor 2.5 – 110 V with factor 3.0
20
Miniature Circuit Breakers
System pro M
SK 0156 Z 94
SK 0157 Z 94
Prospective short-circuit current ip / A Prospective short-circuit current ip / A
S 280 Z
SK 0158 Z 94
21
Miniature Circuit Breakers
System pro M
25 5.0 3.2 5.0 3.2 5.0 3.2 4.6 2.9 4.10 2.56
32 3.6 3.7 3.6 3.7 3.6 3.7 3.5 3.6 2.81 2.88
40 3.0 4.8 3.0 4.8 3.0 4.8 2.8 4.5 2.55 4.09
Rated S 280-D
current S 280 UC-B S 280-K/S 280 UC-K S 280-Z/S 280 UC-Z S 280-B and C
In m
W m
W m
W m
W
13 – – – – – – 13.3 2.3
16 9.7 2.5 8.1 2.07 10.9 2.80 9.7 2.5
22
Miniature Circuit Breakers
System pro M
In those cases where the measured impedances exceed these values an earth fault protection device in acc. with VDE
0664 should be provided as a rupturing device in TN or TT networks.
e.g. STOTZ Residual Current Circuit-Breakers F 372 and F 374 or RCBO multiSTOTZ F 270/6.
U0 = rated voltage to earthed conductors: for U0 = 240 V ZS · 1.04 applies;
for U0 = 127 V ZS · 0.55 applies ZS = RM.C.B. + Rlopp
The fault loop impedance can be measured with commercially available instruments such as e.g. ABB-
METRAWATT type PROFITEST C or PROFITEST 0100 S II.
23
Miniature Circuit Breakers
System pro M
Short-circuit selectivity
If the short-circuit current does not exceed the rupturing capacity of the M.C.B. selectivity is given up to the stated values.
SK 0041 Z 97 SK 0113 Z 93
to main circuit breakers S 700 to fuses, characteristic gL/gl
(DIN VDE 0636; IEC 269/3)
In
A 20 25 35 40 50 63 80 100 20 25 35 50 63 80 100 125 160
S 230-B 6 3,0 3,0 3,0 3,0 3,0 3,0 3,0 3,0
S 240-C 10 3,0 3,0 3,0 3,0 3,0 3,0 3,0 3,0
16 3,0 3,0 3,0 3,0 3,0 3,0 3,0
20 3,0 3,0 3,0 3,0 3,0 3,0
25 3,0 3,0 3,0 3,0 3,0 3,0
32 3,0 3,0 3,0 3,0
40 no selectivity 3,0 3,0 3,0 on request
S 260-B 2 > 15 > 15 > 15 > 15 > 15 > 15 > 15 > 15 1.2 4 > 15 > 15 > 15 > 15 > 15 > 15 > 15
S 240-C 3 6 6 6 6 6 6 6 6 0.7 1.2 4.6 6 6 6 6 6 6
4 6 6 6 6 6 6 6 6 0.6 0.9 2.8 6 6 6 6 6 6
6 6 6 6 6 6 6 6 6 0.5 0.8 2 3.3 5.5 6 6 6 6
8 6 6 6 6 6 6 6 6 0.4 0.7 1.7 2.8 4.5 6 6 6 6
10 6 6 6 6 6 6 6 6 0.4 0.7 1.5 2.5 3.5 5 6 6 6
13 6 6 6 6 6 6 6 6 0.7 1.5 2.5 3.5 5 6 6 6
16 6 6 6 6 6 6 6 1.3 2 2.9 4.1 6 6 6
20 6 6 6 6 6 6 1.8 2.6 3.5 5 6 6
25 6 6 6 6 6 6 1.8 2.6 3.5 5 6 6
32 6 6 6 6 2.2 3 4 6 6
40 6 6 6 2.5 4 6 6
50/63 no selectivity 6 6 no selectivity 3.5 5 6
S 260-D 2 > 15 > 15 > 15 > 15 > 15 > 15 > 15 > 15 > 15 > 15 > 15 > 15 > 15 > 15 > 15 > 15 > 15
3 6 6 6 6 6 6 6 6 0.7 1.2 4.6 6 6 6 6 6 6
4 6 6 6 6 6 6 6 6 0.6 0.9 2.8 6 6 6 6 6 6
6 6 6 6 6 6 6 6 6 0.7 1.7 3 5.9 6 6 6 6
8 6 6 6 6 6 6 6 1.3 2.2 3.6 6 6 6 6
10 6 6 6 6 6 6 1.7 2.5 4 6 6 6
13 6 6 6 6 6 1.6 2.2 3.1 4.6 6 6
16 6 6 6 6 2.2 3.1 4.6 6 6
20 6 6 6 3.1 4.6 6 6
25 6 6 2.6 3.5 6 6
32 6 3.5 6 6
40/50 5.5 6
63 no selectivity no selectivity
For the B-characteristic all values are valid, for the C-characteristic only the grey fields.
Smaller currents below 6 A are only valid for C-characteristic.
The current 8 A are only valid for C-characteristic.
24
Miniature Circuit Breakers
System pro M
Short-circuit selectivity
If the short-circuit current does not exceed the rupturing capacity of the M.C.B. selectivity is given up to the stated values.
In
A 20 25 35 40 50 63 80 100 20 25 35 50 63 80 100 125 160
S 270-B 2 > 15 > 15 > 15 > 15 > 15 > 15 > 15 > 15 1.2 4 > 15 > 15 > 15 > 15 > 15 > 15 > 15
S 240-C 3 10 10 10 10 10 10 10 10 0.7 1.2 4.6 10 10 10 10 10 10
4 10 10 10 10 10 10 10 10 0.6 0.9 2.8 7 10 10 10 10 10
6 10 10 10 10 10 10 10 10 0.5 0.8 1.7 3.1 7 10 10 10 10
10 10 10 10 10 10 10 10 10 0.4 0.7 1.4 2.3 3.4 4.8 7.5 10 10
13 10 10 10 10 10 10 10 10 0.7 1.4 2.3 3.4 4.8 7.5 10 10
16 10 10 10 10 10 10 10 1.3 2 2.9 4.2 6 9.5 10
20 10 10 10 10 10 10 1.9 2.7 3.8 5.6 8.5 10
25 10 10 10 10 10 10 1.8 2.6 3.6 5.4 8 10
32 10 10 10 10 2.4 3.2 4.2 6.8 10
40 10 10 10 3.2 4.2 6.8 9.5
50/63 no selectivity 10 10 no selectivity 3.8 5.7 8.5
S 270-K 2 > 15 > 15 > 15 > 15 > 15 > 15 > 15 > 15 1.2 4 > 15 > 15 > 15 > 15 > 15 > 15 > 15
3 6 6 6 6 6 6 6 6 0.7 1.2 4.6 6 6 6 6 6 6
4 6 6 6 6 6 6 6 6 0.6 0.9 2.8 6 6 6 6 6 6
6 6 6 6 6 6 6 6 6 0.7 1.7 3 5.9 6 6 6 6
8 6 6 6 6 6 6 6 6 1.3 2.2 3.6 6 6 6 6
10/13 6 6 6 6 6 6 6 1.7 2.5 4 6 6 6
16 6 6 6 6 6 2.2 3.1 4.6 6 6
20 6 6 6 6 3.1 4.6 6 6
25 6 6 6 2.6 3.5 6 6
32 6 6 3.5 6 6
40/50 6 5.5 6
63 no selectivity no selectivity 6
S 270-Z 2 > 15 > 15 > 15 > 15 > 15 > 15 > 15 > 15 > 15 > 15 > 15 > 15 > 15 > 15 > 15 > 15 > 15
3 6 6 6 6 6 6 6 6 0.7 1.8 6 6 6 6 6 6 6
4 6 6 6 6 6 6 6 6 0.6 1.3 6 6 6 6 6 6 6
6 6 6 6 6 6 6 6 6 0.5 0.9 2.7 6 6 6 6 6 6
8 6 6 6 6 6 6 6 6 0.5 0.6 1.7 3.8 6 6 6 6 6
10 6 6 6 6 6 6 6 6 0.4 0.6 1.3 2.4 4 6 6 6 6
16 6 6 6 6 6 6 6 6 0.5 1.1 1.7 3 4.5 6 6 6
20 6 6 6 6 6 6 6 0.9 1.5 2.3 3.5 5.2 6 6
25 6 6 6 6 6 6 1.4 2 3 4 6 6
32 6 6 6 6 6 1.4 2 3 4 6 6
40 6 6 6 6 2 3 4 6 6
50/63 no selectivity 6 6 6 no selectivity 2.2 3.5 5.8 6
For the B-characteristic all values are valid, for the C-characteristic only the grey fields.
Smaller currents below 6 A are only valid for C-characteristic.
25
Miniature Circuit Breakers
System pro M
Short-circuit selectivity
If the short-circuit current does not exceed the rupturing capacity of the M.C.B. selectivity is given up to the stated values.
In
A 20 25 35 40 50 63 80 100 20 25 35 50 63 80 100 125 160
S 280-B 2 > 15 > 15 > 15 > 15 > 15 > 15 > 15 > 15 1.2 4 > 15 > 15 > 15 > 15 > 15 > 15 > 15
S 240-C 3 10 10 10 10 10 10 10 10 0.7 1.2 4.6 10 10 10 10 10 10
4 10 10 10 10 10 10 10 10 0.6 0.9 2.8 7 10 10 10 10 10
6 10 10 10 10 10 10 10 10 0.5 0.8 1.7 3.1 7 10 10 10 10
10 10 10 10 10 10 10 10 10 0.4 0.7 1.4 2.3 3.4 4.8 7.5 10 10
13 10 10 10 10 10 10 10 10 0.7 1.4 2.3 3.4 4.8 7.5 10 10
16 10 10 10 10 10 10 10 1.3 2 2.9 4.2 6 9.5 10
20 10 10 10 10 10 10 1.9 2.7 3.8 5.6 8.5 10
25 10 10 10 10 10 10 1.8 2.6 3.6 5.4 8 10
32 10 10 10 10 2.4 3.2 4.2 6.8 10
40 10 10 10 3.2 4.2 6.8 9.5
50/63 no selectivity 10 10 no selectivity 3.8 5.7 8.5
S 280-D 2 > 15 > 15 > 15 > 15 > 15 > 15 > 15 > 15 1.2 4 > 15 > 15 > 15 > 15 > 15 > 15 > 15
S 280-K 3 10 10 10 10 10 10 10 10 0.7 1.2 4.6 10 10 10 10 10 10
4 10 10 10 10 10 10 10 10 0.6 0.9 2.8 7 10 10 10 10 10
6 10 10 10 10 10 10 10 10 0.7 1.7 3 5.9 10 10 10 10
8 10 10 10 10 10 10 10 10 1.3 2.2 3.6 6 10 10 10
10/13 10 10 10 10 10 10 10 1.7 2.5 4 6,5 10 10
16 10 10 10 10 10 2.2 3.1 4.6 10 10
20 10 10 10 10 3.1 4.6 10 10
25 10 10 10 2.6 3.5 6 10
32 10 10 3.5 6 10
40/50 10 5.5 9
63 no selectivity no selectivity 7.5
S 280-Z 2 > 15 > 15 > 15 > 15 > 15 > 15 > 15 > 15 1.2 4 > 15 > 15 > 15 > 15 > 15 > 15 > 15
3 10 10 10 10 10 10 10 10 0.7 1.8 10 10 10 10 10 10 10
4 10 10 10 10 10 10 10 10 0.6 1.3 7 10 10 10 10 10 10
6 10 10 10 10 10 10 10 10 0.5 0.9 2.7 6 10 10 10 10 10
8 10 10 10 10 10 10 10 10 0.5 0.6 1.7 3.8 8 10 10 10 10
10 10 10 10 10 10 10 10 10 0.4 0.6 1.3 2.4 4 7 10 10 10
16 10 10 10 10 10 10 10 10 0.5 1.1 1.7 3 4.5 7.5 10 10
20 10 10 10 10 10 10 10 0.9 1.5 2.3 3.5 5.2 9.5 10
25 10 10 10 10 10 10 1.4 2 3 4 7 10
32 10 10 10 10 10 1.4 2 3 4 7 10
40 10 10 10 10 2 3 4 7 10
50/63 no selectivity 10 10 10 no selectivity 2.2 3.5 5.8 10
For the B-characteristic all values are valid, for the C-characteristic only the grey fields.
Smaller currents below 6 A are only valid for C-characteristic.
26
Miniature Circuit Breakers
System pro M
SK 0109 Z 94
SK 0232 Z 95
MCB’s mounted in a row side by side MCB’s mounted with a separating distance X
8 mm distance
with filler piece FST
SK 0080 Z 93
SK 0078 Z 93
27
Miniature Circuit Breakers
System pro M
The making time of a contactor type B 9 is 9 ... 17 ms. If this time is The M.C.B. S 270-K 0.5 is especially suitable for the monitoring of
not sufficient, a delay-on energisation timer (0.1 ... 40 s) may be fuses, since, due to its high internal resistance it has an unlimited
snapped onto the contactor without problems. switching capacity.
The resistor Rx has to be selected according to the requirements (see In case of planned switching, e.g. withdrawl of the fuse cartridges
determination of Rx ). or opening of the disconnector it must be ensured that the M.C.B.
also is switched off.
SK 0112 Z 94
SK 0209 Z 95
Determination of RX:
RX 1.1 Un
IH
Un = Mains voltage
IH = electromagn. non tripping current of S 271-K (8 x In) see table
on page 14
Protection of lamps
10 27 23 15 32 32 20 18 18 8
16 43 37 24 51 51 33 26 26 12
20 53 46 30 64 64 41 33 33 15
25 66 58 37 82 82 53 42 42 19
1 Version with 2 tubes, swiched together
KVG: conventional ballast
EVG: electronic ballast
28
High rupturing capacity M.C.B.’s
System pro M S 280 UC Range
Thermal trips
Electromagnetic trips
3 A 6 A 9 A 15 A
4 A 8 A 12 A 19 A
6 A 12 A 18 A 29 A
8 A 16 A 24 A 38 A
10 A 20 A 30 A 48 A
16 A 32 A 48 A 77 A
20 A 40 A 60 A 96 A
25 A 50 A 75 A 120 A
32 A 64 A 96 A 153 A
40 A 80 A 120 A 192 A
50 A 100 A 150 A 240 A
63 A 126 A 189 A 120 A
In the short circuit range must be additional balanced the I2t value of the
S 281-Z 25 at the short-circuit current X with the I2t value of the electronic load
disconnecting relay (10 ms-value).
29
High rupturing capacity M.C.B.’s
System pro M S 280 UC Range
The M.C.B.’s type S 280 UC can be used up to 220 V ... for single pole It is not permitted to use a larger number of M.C.B.’s with less poles
M.C.B.’s or up to 440 V ... for 2 pole or for 4 pole M.C.B.’s with series in place of a smaller number of M.C.B.’s with more poles i.e. separate
connection of 2 poles. single pole M.C.B.’s in place of a 2 or 4 pole M.C.B. are not allowed.
The S 280 UC version differs from the standard S 280 M.C.B. in that
In the case of DC voltages up to 60 V ... or by series connection up to
it is fitted with a permanent magnet which assists in the forced
110 V ... the standard S 280 M.C.B. can be used.
extinguishing of the arc. It is therefore important that care is taken to
observe the correct polarity and current flow direction when connect-
ing these M.C.B.’s.
If voltages of over 220 V ... to earth are to be switched then for single
pole switching a 2 pole M.C.B. S 280 UC and for all pole switching a
4 pole M.C.B. S 280 should be used.
Example for max. permissible voltages between leads in relation to the number of poles and switching:
max. voltage
between the 220 V ... 440 V ... 440 V ... 440 V ... 440 V ... (voltage reversal)
leads
max. voltage
between leads 220 V ... 220 V ... 440 V ... 220 V ... 220 V ...
and earth
M.C.B. 1 pole 2 pole 2 pole 2 pole 4 pole
S 281 UC S 282 UC S 282 UC S 282 UC S 284 UC
Supply-input
below
SK 0114 Z 94
Supply-input
above
SK 0115 Z 94
Examples for various high voltages between a connecting lead and earth with equal voltages between the leads:
max. voltage
between the 440 V ... 440 V ... 440 V ...
leads All pole switching All pole switching All pole switching
30
Miniature Circuit Breakers
System pro M
SK 0063 Z 98
SK 0062 Z 98
SK 0154 Z 94
Auxiliary contact H.. or Signal contact or Shunt trip or undervoltage Hand operated neutral
combined signal contact/ undervoltage release UA release and auxiliary contact
auxiliary contact S/H or or combined signal contact/
signal contacts aux. contact or signal contact
The switching position of the auxiliary contact depends on the position of the M.C.B. (ON-OFF).
SK 0328 B 91
SK 0329 B 91
Because of coupling to the switching mechanism of the M.C.B. the auxiliary contact offers a
trip free feature.
The auxiliary contact can be delivered either with screw- or plug in connections, the auxiliary
contact with 3 potential free contacts only in screw-in connection.
S 2-H 11 S 2-H 11X
Signal contact S 2 – S
It signals the tripping caused by overload earth fault or short circuit current however there is
no signal when the M.C.B. is switched OFF manually. With a red handle which allows resetting
of the trip signal without the M.C.B. being switched on. It has also a test button for checking
the control circuit without interrupturing the main circuit.
SK 0330 B 91
Undervoltage release S 2 – UA ..
S 2-A... For remote tripping of the M.C.B. Only in case of substained voltage the relay allows to switch
on the M.C.B. The undervoltage release trips the M.C.B. if the supply voltage is interrupted or
switched off (suitable for emergency off circuits).
Shunt trip S 2 – A .
For remote tripping of the M.C.B. by applying a control voltage. The shunt trip contains a relay
with an integrated contact, that opens after the M.C.B. has tripped and interrupts the control
voltage of the relays, this prevents the flow of current in case of substained control voltage.
SK 0331 B 91
31
Miniature Circuit Breaker
System pro M Supplementary devices
The combined signal contact/auxiliary contact can easily be built-on subsequently to M.C.B.’s
of the range S 260/S 270/S 280.
The signal unit and the auxiliary unit have a potential free changeover contact.
Switching
lever of The contacts are trip free.
signal contact
SK 0332 B 91
Test button
The signal contact
The multipurpose function of the combined signal
signals the tripping caused by overload contact/auxiliary contact S2-H is excellent.
earth fault or short circuit current however Testing the main Testing the signal
there is no signal when the M.C.B. is circuit without circuit without
signalling service interruption
switched OFF manually.
SK 0333 B 91
SK 0334 B 91
circuit without interrupturing the main cir-
cuit.
Signal
contact
SK 0150 Z 91
signals a trip caused by overload, earth
Auxiliary
contact fault and short circuit current as well as the
manual switching OFF of the M.C.B.
SK 0022 Z 95 After short circuit or overload,
resetting of the signal
Arrangement of function
Applications
for testing purposes of the control circuit. Press red signal contact handle
to the top position
The signal contact is switched OFF of by
pressing the test button ”T” and can be
reset by operating the red toggle, the main
Terminal arrangement
circuit will not be interrupted.
SK 0151 Z 91
Switching diagram
32
Miniature Circuit Breaker
System pro M Mounting instruction for supplementary devices
The M.C.B.’s S 260/S 270/S 280 range can subsequently be fitted with The auxiliary contact blocks are supplied with the contact arrangement
an auxiliary contact, signal contact or combined signal contact/auxil- 1 NO + 1 NC, 2 NO or 2 NC.
iary contact.
The combined signal contact/auxiliary contact have each a potential
Ordering details see selection table. free changeover contact.
SK 0122 Z 98
Bring the M.C.B.’s handle Break out the opening Place the auxiliary ... and fix it with spring clamps
to the ON position at the M.C.B. contact to the M.C.B. ...
SK 0123 Z 98
Bring the M.C.B.’s handle Break out the opening Place the signal contact ... and fix it with spring clamps
to the OFF position at the M.C.B. to the M.C.B. ...
SK 0243 Z 99
Bring the M.C.B.’s handle Break out the opening Bring the handle to the ON ... and fix it with spring clamps
to the ON position at the M.C.B. position; bring the metal pin in
and remove the window position as marked with an
arrow, place the signal contact/
auxiliary contact to the M.C.B. ...
33
Miniature Circuit Breaker
System pro M Mounting instruction for supplementary devices
Shunt trip
The M.C.B.’s S 260, S 270 and S 280 range can be subsequently be fitted with a shunt trip.
If auxiliary contacts or the combined signal contact/auxiliary contact are to be fitted these must be fitted
on left hand side of the shunt trip.
SK 0122 Z 94
SK 0125 Z 98
Bring the M.C.B.'s handle to the OFF Bring the shunt trip's handle in the OFF ... and fix it with spring clamps
position and remove the cover at the position, place the shunt trip to the
M.C.B. M.C.B. ...
The possible fitting of an auxiliary contact or combined signal contact/auxiliary contact is described on page 32.
SK 0126 Z 98
Bring the undervoltage relais and Fit the connection Place the undervoltage ... fix it with spring clamps and
M.C.B.'s handle in OFF position and lever in the release to the M.C.B. ... install the switch lever.
remove the covers. housing of the M.C.B.
34
Miniature Circuit Breaker
System pro M Mounting and operating instruction
Mounting
Arbitrary mounting position using snap-on fixing to standard mounting rail EN 50 022 35 x 7.5
mm. The slide bolt located on the bottom side of the M.C.B. engaged in the external position.
The engagement is triggered off by pressure on the middle part of the slide bolt conly S 280 (see
Fig. 3).
SK 0134 Z 94
Separate mounting by means of:
Mounting rail with 2 screw fixing holes.
Mounting kit with terminal covers.
Mounting kit for flange mounting with special terminals for rear connection.
Operation
The M.C.B.’s are switched on by operation of the switch toggle to the upper position i.e. towards
the type label in the position ”I” ON is visible on the switch toggle. At the S 280 the contact
position indicator turns from red to green.
SK 0133 Z 94
If the M.C.B. can be reclosed soon after a trip it can be assumed that the reason for tripping was
an overload. If the M.C.B. trips instantly again when reclosed after a trip, wait for a while
and try again. A repeated instant trip indicates a short-circuit or earthfault in the circuit.
No attempt should be made to continually reclose on to an existing short-circuit or earth fault.
The M.C.B.’s are fitted with a trip free mechanism i.e. they even trip under fault conditions also
when the switch handle is held to the "I" (ON) position by force.
Cleaning
M.C.B.’s which may have become soiled during assembly work in the switchboard can be cleaned
Fig. 2 Removal with a damp and soapy cloth. On no account corrosive or similar solvents should be used.
Maintenance
STOTZ M.C.B.'s are maintenance free.
In case of opening the M.C.B, the right to claim under guarantee expires.
Connection diagrams
Input optional from top or bottom. Terminal markings acc. EN 50 005.
SK 0105 Z 93
SK 0149 Z 91
SK 0030 Z 92
Fig. 3
35
Miniature Circuit Breaker
System pro M Mounting and operating instruction S 290
Mounting
Arbitrary mounting position using snap-on fixing to standard mounting rail EN 50 022 35 x 7.5
mm.
SK 0202 Z 95
Connection
When connecting cables it must be ensured that the cable is rigidly fixed and is not likely to be
moved by other components or is subject to excessive vibration.
Max. tightening torque 4.5 Nm for main terminals, and 0.5 Nm for auxiliary terminals.
Fig. 1 Mounting
Operation
The M.C.B.’s are switched on by operation of the switch toggle to the upper position i.e. towards
the type label in the position ”I”. The contact position indicator turns from red to green.
If the M.C.B. can be reclosed soon after a trip it can be assumed that the reason for tripping was
an overload. If the M.C.B. trips instantly again when reclosed after a trip, wait for a while
and try again. A repeated instant trip indicates a short-circuit or earthfault in the circuit.
No attempt should be made to continually reclose on to an existing short-circuit or earth fault.
The M.C.B.’s are fitted with a trip free mechanism i.e. they even trip under fault conditions also
when the switch handle is held to the "I" position.
SK 0203 Z 95
Cleaning
M.C.B.’s which may have become soiled during assembly work in the switchboard can be cleaned
with a damp and soapy cloth. On no account corrosive or similar solvents should be used.
Maintenance
STOTZ M.C.B.'s are maintenance free.
Fig. 2 Removal
In case of opening the M.C.B, the right to claim under guarantee expires.
Connection diagrams
Input optional from top or bottom. Terminal markings acc. EN 50 005.
SK 0090 Z 95
36
Miniature Circuit Breaker
System pro M Dimensions
Miniature Circuit Breaker S 230, S 260, S 270, S 280 and S 290 Dimensions in mm
SK 0025 Z 95
SK 0132 Z 94
SK 0109 Z 97
S 231 S 232 S 233 S 234 H.. S/H AL NT
S 230/S 260/ S 261 S 231-NA S 263 S 233-NA S UA
S 270 S 271 S 262 S 273 S 264 EST
S 281 S 261-NA S 283 S 263-NA
S 272 S 274
Dimensions without guarantee. We re-
S 271-NA S 273-NA
serve the right to make technical modi-
S 282 S 284
fications.
S 281-NA S 283-NA
SK 0017 Z 94
SK 0083 Z 95
SK 0084 Z 95
S 280
Terminal covers
Busbar adapter
Enclosure of moulded plastic
SK 0149 Z 94
SK 0150 Z 94
SK 0078 Z 98
SA 11 SA 12 QES 4/3 N
37
Miniature Circuit Breaker
System pro M Dimensions
Dimensions in mm
On type DSW 1
the two fixing
holes are
SK 0093 Z 98
vertically arranged
SK 0150 Z 93
Drill holes
SK 0131 Z 94
S 500 - ME
38
Miniature Circuit Breaker
System pro M Comb-busbars and busbar blocks
Technical Data
max. supply current Is / Phase A 100 110 – 150*) 170*) 220*) 110 – 130*) – – –
Connection cross section mm2 25 35 – 2 x 25 2 x 25 2 x 35 25 – 35
a
SK 0062 Z 91
SK 0063 Z 91
*) If supply connection is at the centre via the M.C.B.-terminals, care has to be taken that the max. current for each supply point does not exceed
the values as stated by the manufacturers. For example: for STOTZ-M.C.B.’s of ranges S 240, S 260 and S 270: max. 110 A, for M.C.B.’s S
280 range: max. 140 A.
Further care has to be taken that the sum of each branch currents a1 ... an does not exceed the max. busbar load Is / Phase, mentioned in above
table.
39
Miniature Circuit Breaker
System pro M Comb-busbars and busbar blocks
Dimensions in mm
SK 0032 Z 98 SK 0319 Z 98
SK 0019 Z 98 SK 0022 Z 98
SK 0008 Z 98 SK 0030 Z 98
SK 0211 Z 99 SK 0260 Z 98
SK 0028 Z 99
SK 0209 Z 99
40
Approvals and certifications by classification societies
Miniature Circuit Breakers
System pro M
Symbol SEV DEMKO NEMKO SEMKO EL. CSA KEMA ÖVE CEBEC UTE VDE BBJ EZU GOST BV GL LRS DNV
inspect.
S 230
S 270, B, C
1 + 3pol. + NA
S 270, K
1 - 3pol
S 277/480 V AC, K, Z
S 280, B, C
1 + 3pol. + NA
S 280, K, 2-3pol.
S 280, K
1 - 4 pol. 440 V, 50+60 Hz
S 280, Z
1 - 4pol. S 277/480 V AC
S 280, K, 2-3pol.
S 280 UC, K, Z
1 + 2 pol. 440 V, 50+60 Hz
S 280 UC - B
1 + 2 pol.
S 290, C on request
41
Approved Submitted for approval / planned to be submitted Approved variants on request Approval not required
B/C
acc. to
Miniature Circuit Breakers
System pro M
EN 60 898
S 230-B type for cable
protection
Selection table
No. of Rated Ordering details bbn Price Price Weight Pack.
poles current 40 16779 1 piece group 1 piece unit
In A Type No. Order code EAN DM kg pcs.
Selection table
No. of Rated Ordering details bbn Price Price Weight Pack.
poles current 40 16779 1 piece group 1 piece unit
In A Type No. Order code EAN DM kg pcs.
42
B
acc. to
Miniature Circuit Breakers
System pro M
EN 60 898
for cable
S 260-B type protection
Selection table
No. of Rated Ordering details bbn Price Price Weight Pack.
poles current 40 12233 1 piece group 1 piece unit
In A Type No. Order code EAN DM kg pcs.
43
B
acc. to
Miniature Circuit Breakers
System pro M
EN 60 898
for cable
S 260-B type protection
44
C
acc. to
Miniature Circuit Breakers
System pro M
EN 60 898
for cable
S 260-C type protection
Selection table
No. of Rated Ordering details bbn Price Price Weight Pack.
poles current 40 12233 1 piece group 1 piece unit
In A Type No. Order code EAN DM kg pcs.
45
C
acc. to
Miniature Circuit Breakers
System pro M
EN 60 898
for cable
S 260-C type protection
46
D
acc. to
Miniature Circuit Breakers
System pro M
EN 60 898
for cable
S 260-D type protection
Selection table
No. of Rated Ordering details bbn Price Price Weight Pack.
poles current 40 12233 1 piece group 1 piece unit
In A Type No. Order code EAN DM kg pcs.
47
System pro M
Miniature Circuit Breakers
S 260-D type D
Selection table
No. of Rated Ordering details bbn Price Price Weight Pack.
poles current 40 12233 1 piece group 1 piece unit
In A Type No. Order code EAN DM kg pcs.
48
with reference to IEC94741
System pro M
Miniature Circuit Breakers
S 270-K type K for the protection of devices as
motors, transformers, lamps
etc. and for cable protection
Selection table
No. of Rated Ordering details bbn Price Price Weight Pack.
poles current 40 12233 1 piece group 1 piece unit
In A Type No. Order code EAN DM kg pcs.
49
K
with reference to IEC 947-4-1
Miniature Circuit Breakers
System pro M
for the protection of devices as
motors, transformers, lamps etc.
S 270-K type and for cable protection
Selection table
No. of Rated Ordering details bbn Price Price Weight Pack.
poles current 40 12233 1 piece group 1 piece unit
In A Type No. Order code EAN DM kg pcs.
50
KS
acc. to DIN VDE 0660 part 101
Miniature Circuit Breakers
System pro M
for the protection of devices such
as motors, transformers, lamps
S 270-KS type etc. and for cable protection
UL 1077, CSA, C22.2 No. 235, Report No. LR 98793-9
Selection table
No. of Rated Ordering details bbn Price Price Weight Pack.
poles current 40 12233 1 piece group 1 piece unit
In A Type No. Order code EAN DM kg pcs.
Z
with reference to IEC 947 for
Miniature Circuit Breakers
System pro M
the protection of semiconductor
S 270-Z type devices and voltage transformer
circuits
Selection table
No. of Rated Ordering details bbn Price Price Weight Pack.
poles current 40 12233 1 piece group 1 piece unit
In A Type No. Order code EAN DM kg pcs.
System pro M
Miniature Circuit Breakers
S 270-Z type Z the protection of semiconductor
devices and voltage transformer
circuits
Selection table
No. of Rated Ordering details bbn Price Price Weight Pack.
poles current 40 12233 1 piece group 1 piece unit
In A Type No. Order code EAN DM kg pcs.
52
acc. to
Selection table
No. of Rated Ordering details bbn Price Price Weight Pack.
poles current 40 12233 1 piece group 1 piece unit
In A Type No. Order code EAN DM kg pcs.
53
acc. to
System pro M
Miniature Circuit Breakers
S 270-B type B EN 60 898
for cable
protection
Selection table
54
acc. to
System pro M
Miniature Circuit Breakers
S 270-C type C EN 60 898
for cable
protection
Selection table
No. of Rated Ordering details bbn Price Price Weight Pack.
poles current 40 12233 1 piece group 1 piece unit
In A Type No. Order code EAN DM kg pcs.
55
acc. to
System pro M
Miniature Circuit Breakers
S 270-C type C EN 60 898
for cable
protection
56
Miniature Circuit Breakers
B
acc. to DIN VDE
System pro M
0641part 11 for
S 280-B type cable protection
25 000
Selection table
No. of Rated Ordering details bbn Price Price Weight Pack.
poles current 40 12233 1 piece group 1 piece unit
In A Type No. Order code EAN DM kg pcs.
125 V ...
63 S 284-B 63 GH S284 0001 R0635 48150 7
57
acc. to DIN VDE
System pro M
Miniature Circuit Breakers
S 280-B type B
25 000
0641 part 11 for
cable protection
Selection table
No. of Rated Ordering details bbn Price Price Weight Pack.
poles current 40 12233 1 piece group 1 piece unit
In A Type No. Order code EAN DM kg pcs.
58
acc. to DIN VDE
System pro M
Miniature Circuit Breakers
S 280-C type C
25 000
0641 part 11 for
cable protection
Selection table
No. of Rated Ordering details bbn Price Price Weight Pack.
poles current 40 12233 1 piece group 1 piece unit
In A Type No. Order code EAN DM kg pcs.
59
acc. to DIN VDE
System pro M
Miniature Circuit Breakers
S 280-C type C
25 000
0641 part 11 for
cable protection
60
acc. to
System pro M
Miniature Circuit Breakers
S 280-D type D25 000
EN 60 898
for cable
protection
Selection table
No. of Rated Ordering details bbn Price Price Weight Pack.
poles current 40 12233 1 piece group 1 piece unit
In A Type No. Order code EAN DM kg pcs.
61
acc. to
System pro M
Miniature Circuit Breakers
S 280-D type D25 000
EN 60 898
for cable
protection
62
K
acc. to DIN VDE 0660 part
Miniature Circuit Breakers
System pro M
101 for the protection of
devices such as motors,
S 280-K type transformers, lamps etc.
25 000 and for cable protection
Selection table
No. of Rated Ordering details bbn Price Price Weight Pack.
poles current 40 12233 1 piece group 1 piece unit
In A Type No. Order code EAN DM kg pcs.
63
K
acc. to DIN VDE 0660 part
Miniature Circuit Breakers
System pro M
101 for the protection of
S 280-K type devices such as motors,
transformers, lamps etc.
25 000 and for cable protection
Selection table
No. of Rated Ordering details bbn Price Price Weight Pack.
poles current 40 12233 1 piece group 1 piece unit
In A Type No. Order code EAN DM kg pcs.
UBmax 125 V ... with 2 poles connected in series max. rated rupturing capacity of the range
64
Z
acc. to DIN VDE
Miniature Circuit Breakers
System pro M
0660 part 11
S 280-Z type
25 000
Selection table
No. of Rated Ordering details bbn Price Price Weight Pack.
poles current 40 12233 1 piece group 1 piece unit
In A Type No. Order code EAN DM kg pcs.
65
acc. to DIN VDE
System pro M
Miniature Circuit Breakers
S 280-Z type Z
25 000
066 part 11
Selection table
No. of Rated Ordering details bbn Price Price Weight Pack.
poles current 40 12233 1 piece group 1 piece unit
In A Type No. Order code EAN DM kg pcs.
66
System pro M
High rupturing capacity M.C.B.’s
S 280 UC Range B/K
Selection table
B No. of
poles
Rated
current
In A
6
Ordering details
Type No.
S 281 UC-B 6
Order code
16230 2
Price
1 piece
DM
Price
group
Weight
1 piece
kg
0.130
Pack.
unit
pcs.
10
1
acc. to DIN VDE 0641 part 11 10 S 281 UC-B 10 GH S281 0164 R0105 16240 1
U Bmax 16 S 281 UC-B 16 GH S281 0164 R0165 16230 0
440 V 20 S 281 UC-B 20 GH S281 0164 R0205 16260 9
220 V ... 25 S 281 UC-B 25 GH S281 0164 R0255 16270 8
Selection table
67
acc. to VDE 0660 part 101
High rupturing capacity M.C.B.’s
System pro M S 280 UC Range K for the protection of
devices such as motors,
transformers, lamps etc.
and for cable protection.
Selection table
No. of Rated Ordering details bbn Price Price Weight Pack.
poles current 40 12233 1 piece group 1 piece unit
In A Type No. Order code EAN DM kg pcs.
3 0.2 S 283 UC-K 0.2 GH S283 0164 R0087 73810 6 0.390 3/12
0.3 S 283 UC-K 0.3 GH S283 0164 R0117 73820 5
0.5 S 283 UC-K 0.5 GH S283 0164 R0157 73830 4
68
acc. to VDE 0660
System pro M
High rupturing capacity M.C.B.’s
S 280 UC Range Z part 104 for protection
of semiconductors
Selection table
No. of Rated Ordering details bbn Price Price Weight Pack.
poles current 40 12233 1 piece group 1 piece unit
In A Type No. Order code EAN DM kg pcs.
69
Miniature Circuit Breakers
System pro M Supplementary devices
Auxiliary contact
Screw connection
1 NO + 1 NC S 2-H 11 GH S270 1916 R0001 61500 1 0.04 1
2 NO S 2-H 20 GH S270 1916 R0002 61510 0 0.04 1
SK 0009 B 95
Screw connection
2 NO + 1 NC S 2-H 21 GH S270 1936 R0001 01370 3 0.05 1
1 NO + 2 NC S 2-H 12 GH S270 1936 R0002 01380 2 0.05 1
3 NO S 2-H 30 GH S270 1936 R0003 01390 1 0.05 1
3 NC S 2-H 03 GH S270 1936 R0004 01400 7 0.05 1
Signalcontact
S 2-S/H ...
Signal contact S 2-S GH S280 1902 R0008 42920 2 0.05 1
Undervoltage release
12 V DC S 2-UA 12 GH S280 1911 R0001 42970 7 0,07 1
24 V AC/DC S 2-UA 24 GH S280 1911 R0002 42980 6 0,07 1
48 V AC/DC S 2-UA 48 GH S280 1911 R0003 79360 0 0,07 1
110 V AC/DC S 2-UA 110 GH S280 1911 R0004 43000 0 0,07 1
S 2-A ...
220 V AC/DC S 2-UA 220 GH S280 1911 R0005 43010 9 0,07 1
380 V AC S 2-UA 380 GH S280 1911 R0006 79370 9 0,07 1
Shunt trip
12 ... 60 V ... S 2-A 1 GH S280 1909 R0001 42930 1 0.145 1
110 ... 415 V ... S 2-A 2 GH S280 1909 R0002 42940 0 0.145 1
and
110 ... 250 V ...
SK 0331 B 91
S 2-NT
Removable base for S 280 max. I n = 32 A
S 2-EST GH S280 1925 R0001 127707 0.07 1
bbn 40 16779
70
Miniature Circuit Breakers
System pro M S 290 Range
Selection table
No. of Rated Ordering details bbn Price Price Weight Pack.
C
acc. to DIN VDE
poles current 40 16779 1 piece group 1 piece unit
0641 part 11 for In A Type No. Order code EAN DM kg pcs.
cable protection
1 80 S 291-C 80 GH S291 1001 R0804 11960 3 0.26 6
10 000 U Bmax 100 S 291-C 100 GHS 291 1001 R0824 11970 2
440 V AC 125 S 291-C 125 GHS 291 1001 R0844 11980 1
60 V AC
440 V AC
Selection table
acc. to
D
EN 60 898
for cable
protection
No. of
poles
1
Rated
current
In A
80
Ordering details
Type No.
S 291-D 80
Order code
EAN
12080 7
Price
40 16779 1 piece
DM
Price Weight
group 1 piece
kg
0,26
Pack.
unit
pcs.
6
U Bmax 100 S 291-D 100 GHS 291 1001 R0821 12090 6
440 V AC 125 S 291-D 125 GHS 291 1001 R0841 12330 3
60 V AC
71
System pro M
Miniature Circuit Breakers
S 290 Range
and supplementary devices
K
Selection table
acc. to DIN VDE No. of Rated Ordering details bbn Price Price Weight Pack.
K 10 000
0660 part 101 for
the protection of
devices such as
motors, transfo-
poles
1
U Bmax
current
In A
80
100
Type No.
S 291-K 80
S 291-K 100
Order code
30880 9
30890 8
DM
group 1 piece
kg
0,26
unit
pcs.
rmers, lamps etc. 440 V AC 125 S 291-K 125 GHS 291 1001 R0847 30900 4
and for cable 60 V AC
Selection table
Description Ordering details bbn Price Price Weight Pack.
40 16779 1 piece group 1 piece unit
Type No. Order code EAN DM kg pcs.
Auxiliary contact
SK 0039 B 95
Signal contact
Signal contact S 290-S G HS 290 1902 R0008 12210 8 0,05 1
Shunt trip
AC 110 - 415V S 290-A1 G HS 290 1909 R0001 30030 8 0,09 1
DC 24 - 48V S 290-A2 G HS 290 1909 R0002 30040 7 0,09 1
SK 0040 B 95
Untervoltage release
72
Miniature Circuit Breakers
System pro M Accessories
SK 0100 Z 98
Filler piece
Width 8.75 mm for us as heat conductor for M.C.B.’s mounted in a row. Two different heights, with break-off sections,
for rails acc. to EN 50 022, 35 x 7.5 mm
SZ-FST 2 SZ-FST-2 GH L530 1908 R0002 06070 2 0.01 25
SK 0103 B 91
Spring part
SZ-FDT 2
Carrier for equipment covers, various heights (in combination with filler piece FST-2)
SZ-FDT 2 GH L530 1908 R0001 06080 1 0.002 25
SK 0105 B 91
Filler plate
Material thickness 1 mm, light grey,
to compensate possible tolerances of adjacent M.C.B.’s
SZ-FST-2 + SZ-FDT-2
SZ-FW GH L530 1901 R0001 06030 6 0.001 25
SK 0090 B 00
End clamp
to prevent the units moving sideways along mounting rails to EN 50 022, 35 mm
END
END GJ I100 1814 R0001 59090 2 0.02 50
DSW 1 ... 6
73
Miniature Circuit Breakers
System pro M Accessories
Label mats,
à 40 labels labelled or unlabelled. The unlabelled can be labelled by water-resistant and permanent marker or by means
of computer-controlled labelling systems (plotter).
numbering 4 x 1-10
Label SZ-KZS/10 GH S210 1946 R0014 39060 6 30
numbering 4 x 11-20
bbn-No.: 40 16779
SZ-KZS ...
SK 0004 Z 94
SK 0162 Z 93
SK 0163 Z 93
SK 0202 B 93
SK 0164 Z 93
SK 0165 Z 93
SK 0166 Z 93
74
Miniature Circuit Breakers
System pro M Accessories
Labelling accessories
SK 0187 B 91
for protection against unauthorized or unsafe actuation on the operating lever. An adapter permits blocking of the
operating lever both in the OFF positions of the switch. The locking ensures by means of a padlock with a shackles
diameters of max. 3 or 6 mm. For multipole breakers/switches it is possible to provide each pole with a padlock.
The padlock adapter is suitable for all MCBs of series S 190, S 230, S 240, S 260, S 270, S 280 as well ass for the switches
SA 1 + SA 2 E 220 and isolators E 240/270.
Terminal cover KA 27
as a protection against accidental contact with live parts by occassional handling (e.g. in switch-boards) according to the
accident prevention regulations (e.g. VBG 4); comprising side pieces 475 mm long = 27 modules each 17.5 mm which can
be cut to the required size end pieces; can be snapped onto mounting rail EN 50 022, 35 mm. Side and end pieces must
be separately ordered.
SK 0077 B 96
Accessories
PCD 2 N PCD 4 N
Earth bar for
subsequent
mounting ES GH S270 1912 R0001 36660 6 0.08 10
Blanking plate BP GH S270 1913 R0001 36670 5 0.005 10
1 Module = 17.5 mm
Division: ½ module
SK 0078 B 96
PCD 6 N
75
Miniature Circuit Breakers
System pro M Accessories
Supplementary devices
Description Ordering details bbn Price Price Weight Pack.
40 12233 1 piece group 1 piece unit
Type No. Order code EAN DM kg pcs.
SK 0184 B 91
Push-on terminals
SK 0023 Z 95 for 2 connectors 2.8 mm without insulation (max. 8 A), push-on terminals HSTF also
for 1 connector 6.3 mm with insulation (max. 20 A)
HSTF
for main poles
2 x 2.8 – 0.5 or
1 x 6.3 – 0.5 HSTF GH S210 4555 P0001 65880 0 0.002 50
E430-AP
bbn-Nr.: 40 16779
S 2-EST
bbn-No. 40 13614
76
Miniature Circuit Breakers
System pro M Comb-busbars and busbar blocks
Selection table
M.C.B. Busbar connection Cross Length Poles Ordering details bbn Price Weight Pack.
section 40 12233 1 piece 1 piece unit
mm2 mm No. Type No. Order code EAN DM kg pcs.
* bbn-Nr. 401677 9
* bbn-Nr. 401677 9
77
Miniature Circuit Breakers
System pro M Comb-busbars and busbar blocks
Selection table
M.C.B. Busbar connection Cross Length Poles Ordering details bbn Price Weight Pack.
section 4012233 1 piece 1 piece unit
mm2 mm No. Type No. Order code EAN DM kg pcs.
Busbars for M.C.B.’s with aux. contact H... or combined signal contact/aux. contact S/H
for single pole M.C.B.’s with H... or S/H
SK 0095 Z 96
13 x 3 SZ-PSB 46 N
SK 0096 Z 96
-
SK 0099 Z 96
SK 0191 Z 97
SK 0097 Z 96
78
Miniature Circuit Breakers
System pro M S 280
79
ABB STOTZ-KONTAKT, the Heidelberg-based company, The new plug-in connection technology for the devices and
develops, manufactures and sells highly modern, modular apparatus rack ensures quick and reliable installations:
systems for electrical building installations. assembly, connection of the devices and cross wiring are
System pro M
It offers complete installation ranges for a wide variety of
applications:
carried out time-effectively in one single step.
If need be, component sets may still be changed quickly and
flexibly right until transfer takes place; devices may also be
exchanged easily at some later date, and economically in
System pro M terms of both money and time, at that.
The entire System Connect was developed by ABB STOTZ-
For classic installation applications KONTAKT and Striebel & John, within the framework of their
The modular System pro M for installation on DIN rails in- successful system partnership.
corporates Europe’s best-selling miniature circuit-breakers
and residual-current-operated circuit-breakers as well as a
complete range of built-in devices. EIB Installation Systems
The system components have been designed with various
functions and performance capabilities and are therefore to For intelligent Building Installation
able optimally cover the complete range of applications in Highly modern, programmable installation systems with
building installation: bus technology based on the European EIB standard.
conventional domestic electrical installations
industrial and commercial installations ABB i-bus EIB
protection and switch functions System with special 2-core bus cable, primarily for new
checking and monitoring tasks buildings.
control and time-dependent tasks etc.
ABB Powernet EIB
System pro M compact System for retrofitting in existing buildings. Transfer of
information via the existing network.
The extension of System pro M for targeted use in domestic
electrical installations stands out due to its compact and Security Systems
easily comprehensible range of miniature circuit-breakers,
residual-current-operated circuit-breakers and cross wiring
tools as well as an optimised installation technology taking All-in-one Protection
into account the special circumstances and requirements Wide range of security systems and components: intruder
of domestic electrical installations. and fire alarm systems, radio-controlled alarm systems, door
locking system and signalling components.