Controllers and Final Control Elements: 24/12/2016 Dr. Arkan Jasim Hadi 1
Controllers and Final Control Elements: 24/12/2016 Dr. Arkan Jasim Hadi 1
Controllers and Final Control Elements: 24/12/2016 Dr. Arkan Jasim Hadi 1
For the mathematical analysis of control systems, it is sufficient to regard the controller as a simple computer. For
example, a proportional controller may be thought of as a device that receives the error signal and puts out a signal
proportional to it. Similarly, the final control element may be regarded as a device that produces corrective
action on the process. The corrective action is regarded as mathematically related to the output signal from the
controller. However, it is desirable to have some appreciation of the actual physical mechanisms used to accomplish
this. For this reason, we begin this chapter with a physical description of a pneumatic control valve and a simplified
description of a proportional controller.
In general, the flow rate of fluid through the valve depends upon the upstream and downstream fluid pressures and the size of the
opening through the valve. The plug and seat (or orifice) can be shaped so that various relationships between stem position and
size of opening (hence, flow rate) are obtained. In our example, we assume for simplicity that at steady state the flow (for fixed
upstream and downstream fluid pressures) is proportional to the valve-top pneumatic pressure. A valve having this relation is
called a linear valve. A more complete discussion of control valves is presented in Chap. 19.
Controller
The control hardware required to control the temperature of a stream leaving a heat exchanger is shown in Fig. 9–2 .
This hardware consists of the following components listed here along with their respective conversions:
1. Transducer (temperature-to-current)
2. Computer/ Controller (current-to-current)
3. Converter (current-to-pressure)
4. Control valve (pressure-to-flow rate)
We assume that the valve is linear and is the air-to-open type. The external power (120 V) needed for each component is also
shown in Fig. 9–2 . Electricity is needed for the transducer, computer/controller, and converter. A source of 20 psig air is also
needed for the converter.
From this qualitative description, we see that the flow of signals from one component to the next is such that the
outlet temperature of the heat exchanger should return toward the set point. An equivalent P&ID (piping and
instrumentation diagram) for this control system is shown in Fig. 9–3 (for other P&ID symbols, see App. 9A).
where Kv is the steady-state gain, i.e., the constant of proportionality between the steady state flow rate and the
valve-top pressure, and 𝜏v is the time constant of the valve.
In many practical systems, the time constant of the valve is very small when compared with the time constants of
other components of the control system, and the transfer function of the valve can be approximated by a constant.
Under these conditions, the valve is said to contribute negligible dynamic lag.
The units of the set point and the measured variable must be the same
In a controller having adjustable gain, the value of the gain Kc can be varied by entering it into the controller,
usually by means of a keypad (or a knob on older equipment).
The value of ps is the value of the output signal when 𝜀 is zero, and in most controllers ps can be adjusted to obtain
the required output signal when the control system is at steady state and 𝜀 = 0.
To obtain the transfer function of Eq. (9.3), we first introduce the deviation variable
Taking the transform of Eq. (9.4) gives the transfer function of an ideal proportional controller.
The actual behavior of a proportional controller is depicted in Fig. 9–6 . The controller output will saturate (level out) at
pmax =15 psig or 20 mA at the upper end and at pmin = 3 psig or 4 mA at the lower end of the output. The ideal transfer
function Eq. (9.5) does not predict this saturation phenomenon.
FIGURE 9–6
Proportional controller output as
a function of error input to the
controller. (a) Ideal behavior;
(b) actual behavior.
Now assume that the gain of the controller is changed to 0.4 psi/ oF. Find the error in temperature that will cause
the control valve to go from fully closed to fully open.
At this level of gain, the valve will be fully open if the error signal reaches 30 oF. The gain Kc has the units of psi per
unit of measured variable. [Regarding the units on controller gain, if the actual controller of Fig. 9–4 is considered,
both the input and the output units are in milliamperes. In this case the gain will be dimensionless (i.e., mA/mA).]
PROPORTIONAL-INTEGRAL (PI) CONTROL. If we cannot tolerate any residual error, we will have to introduce an
additional control mode: integral control. If we add integral control to our proportional controller, we have what is
termed PI, or proportional-integral control. The integral mode ultimately drives the error to zero. This controller has
two adjustable parameters for which we select values, the gain and the integral time. Thus it is a bit more complicated
than a proportional controller, but in exchange for the additional complexity, we reap the advantage of no error at
steady state.
PI control is described by the relationship
In this case, we have added to the proportional action term 𝐾𝑐 𝜀 another term that is proportional to the integral of
the error. The values of Kc and 𝜏𝐼 are both adjustable.
Some manufacturers prefer to use the term reset rate, which is defined as the reciprocal of 𝜏𝐼 . The integral
adjustment on a controller may be denoted by integral time or reset rate (carefully check the specific controller to
be sure which value to enter). The calibration of the proportional and integral action is often checked by observing
the jump and slope of a step response, as shown in Fig. 9–8 .
To obtain the transfer function of Eq. (9.9), we again introduce the deviation variable P = p- ps into Eq. (9.9) and then
take the transform to obtain
PROPORTIONAL-INTEGRAL-DERIVATIVE (PID) CONTROL. This mode of control is a combination of the previous modes
and is given by the expression
In this case, all three values Kc , 𝜏𝐷 , and 𝜏𝐼 can be adjusted in the controller. The transfer function for this controller
can be obtained from the Laplace transform of Eq. (9.11); thus
The selection among the control systems whose responses are shown in Fig. 9–10 depends on the particular
application. If an offset of about 20 percent is tolerable, proportional action would likely be selected. If no offset were
tolerable, integral action would be added. If excessive oscillations had to be eliminated, derivative action might
be added. The addition of each mode means, as we will see in later chapters, more difficult controller adjustment.
CONTROL VALVES
Two basic types of control valves are air-to-close
and air-to-open. The air pressure (pneumatic) signal
is usually 3 to 15 psig. The dynamics of the valves
are adequately modeled as first-order systems. The
time constant is on the order of 1 s.
For more control systems we can see appendix 9A and the lectures for control examples
Table 9A.1 shows some common conventions used for identifying process instrumentation and control on
process drawings. Figure 9A–1 shows an example of a level control loop for a process tank.