ABSA Piping
ABSA Piping
ABSA Piping
Rev.01
Additional requirements:
• Form AB-83 must be completed and kept by the owner/user for at least 5 years.
• Form AB-81 must be completed by the contractor upon completion of the project
and submitted to ABSA.
• Skid units:
o The CRN for a skid system is not transferable between jurisdictions, since
it is still linked to one particular installation.
o They must be registered in Alberta when they form part of a CRN-
registered system (over 0.5 cubic metres), even when their own volume is
less than 0.5 metres.
Exemptions: A piping system is exempt from registration when all of the following
conditions are met:
Size: Pipe nominal size is less than or equal to DN 50, and
Pressure: Design Pressure is less than or equal to 1035 kPa (150 PSI), and
Temperature: Design Temperature is between minus 29 degrees Celsius and
186 degrees Celsius (-20 < T < 366oF), and
Fluid: fluid must be either air, nitrogen, argon, carbon dioxide, steam or hot
water, and
Code Compliance: is constructed to the applicable ASME Code,
Please note that Section 35 of Regulation 49/2006 is still in force.2
Notes:
1. As an example of what this means: this statement excludes registration of a hydraulic system.
2. Section 35 in the Alberta Regulation 49/2006 touches on the owner’s duty to report to ABSA “any
unsafe condition, accident, or fire that occurs with respect to that pressure equipment.”
Key Design Engineering Please be reminded that this information has been supplied
55 Northfield Dr. E, Suite 194 as a starting guide, for general information purposes only.
Waterloo, ON N2K 3T6 Please contact Key Design Engineering with further
Ph: 520-265-3657 questions. The information contained here can be found on
http://www.keydesigneng.com/ various pages at www.absa.ca, by following the “Design
Registration” link.