SR1
Catalog
File 8501
03
CONTENTS
Description Page
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Overview of Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Wiring Diagrams and Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Zelio-Logic™ Relay
Overview
Overview
The Zelio-Logic™ relay is more than a typical relay. It will accept inputs, and has relay outputs like a programmable controller, but can not be connected to a network. Because
it has timers, counters and clocks that can be programmed, this product is ideal for applications where a typical relay, timer or time clock isn’t enough, but a PLC is not justified.
SR1-E
5. U/RUN: operating LED
Steady : power on, Stop mode, 5
Flashing : Run mode U/Run
3
10/03 © 2001-2003 Schneider Electric All Rights Reserved
Zelio-Logic™ Relay
Overview
13
N.O.
SPSTNO
Ix ▲ the contact connected to the input of
the module.
14
Contact
21
N.C.
SPSTNC
ix ▲ of the contact connected to the input
of the module.
22
The coil is energized when the
A1
Standard Coil Qx contacts to which it is connected are
closed.
A2
contacts re-open.
Example:
STOP START
M
L1 M1
L1
L2
L2
I1 I2 Q1 i1 I2 Q1
Q1 Q1
OR
4
© 2001-2003 Schneider Electric All Rights Reserved 10/03
Zelio-Logic™ Relay
Overview of Functions
Overview of Functions
TT1 A
RT . On-Delay
T. t
O t = 0 0 . 0 0 S
TT1 a
RT .
T. t On-Delay (with momentary input)
O t = 0 0 . 0 0 S
TT1 C
RT .
T. Off-Delay
t
O t = 0 0 . 0 0 S
TT1 B
RT .
T. One Shot
t
O t = 0 0 . 0 0 S
TT1 W
RT .
T. One Shot (when input is removed)
t
O t = 0 0 . 0 0 S
TT1 D
RT .
T. Repeat Cycle (with maintained input)
t
O t = 0 0 . 0 0 S
TT1 d
RT .
T. Repeat Cycle (with momentary input)
t
O t = 0 0 . 0 0 S
TT1 1 2 T
RT . Totalizing Timer with Reset
T.
O∑ t = 0 0 . 0 0 S
Each timer function has a preset time in one of four timing ranges:
The time setting on each timer can be locked. A password is required to unlock the timer.
For more information on these timers and counters, refer to the User’s Manual #SR1MAN01EN.
5
10/03 © 2001-2003 Schneider Electric All Rights Reserved
Zelio-Logic™ Relay
Overview of Functions
Arrow Keys (4) on the Front of the Relay can be used as Inputs
— They can be used as push buttons in the program.
I B ≤ Ref
Contact A1 is closed when the value of analog input IB does not exceed the reference voltage entered in the
A1 A n a l o g 1 reference field, 4.9 V in this example.
O R e f = 4.9 V
I B ≥ Ref
Contact A1 is closed when the value of analog input IB equals or exceeds the reference voltage entered in the
A1 A n a l o g 2 reference field, 4.9 V in this example.
O R e f = 4.9 V
I C ≤ Ref
Contact A1 is closed when the value of analog input IC does not exceed the reference voltage entered in the
A1 A n a l o g 3 reference field, 4.9 V in this example.
O R e f = 4 .9 V
I C ≥ Ref
Contact A1 is closed when the value of analog input IC equals or exceeds the reference voltage entered in the
A1 A n a l o g 4 reference field, 4.9 V in this example.
O R e f = 4 .9 V
I B ≤ I C
Contact A1 is closed when the value of analog input IB does not exceed the value of
A1 A n a l o g 5 analog input IC.
O
I B ≥ I C
Contact A1 is closed when the value of analog input IB equals or exceeds the value of
A1 A n a l o g 6 analog input IC.
O
I C - H ≤ I B ≤ I C + H
Contact A1 is closed when the value of analog input IB is between IC-H and IC+H.
A1 A n a l o g 7 H (the hysteresis) is entered in the H field, 4.9 V in this example.
O H = 4.9V
Text messages can be entered using the Zelio-Soft™ software and then displayed on the relay.
6
© 2001-2003 Schneider Electric All Rights Reserved 10/03
Zelio-Logic™ Relay
Overview of Functions
“ZELIO-SOFT™”: SOFTWARE
“Zelio-Soft™” software enables:
— the entering of control wiring diagrams
— the monitoring of applications, using its test feature
— the programming of messages for display on the “Zelio-Logic™”
— simplification of setting-up
Set-Up Simulation
The Zelio-Soft™ simulator enables testing of all the programs, i.e.:
— activating the discrete inputs and their N.O. or N.C. contact modes (momentary or maintained)
— indicating the output states
— varying the voltage of the analog inputs IB and IC
— activating the pushbuttons
— simulating the application program in real time and accelerated time
— dynamically indicating in red the various active elements of the program
7
10/03 © 2001-2003 Schneider Electric All Rights Reserved
Zelio-Logic™ Relay
Overview of Functions
L N I1 I2 I3 I4 I5 I6
Del. Ins.line
z1
z4 z2
z3
Esc. Sel./OK
O1 O2 O3 O4
+ – I1 I2 I3 I4 I5 I6 IB IC
O1 O2 O3 O4 L N I1 I2 I3 I4 I5 I6 I7 I8 I9 IA IB IC
Del. Ins.line
z1
z4 z2
z3
Esc. Sel./OK
O1 O2 O3 O4 O5 O6 O7 O8
The Pocket PC therefore avoids having to move the PC or smart relays for transfer and debugging of applications.
It is particularly useful for setting up smart relays which do not have a display or buttons.
Program Test with Smart The software can be quickly installed in the Pocket PC, via a PC, using a special installation CD (ref: SR1-SFT02).
Relay Connected Exchange of files between the Pocket PC and PC is achieved by means of the Active Sync software (version V3.1 or greater)
Supervision Mode supplied with the Pocket PC.
After the software has been installed, the Pocket PC can be used independently, as the only programming and adjustment tool for
Zelio Logic smart.
(1) Likely to change as Pocket PC manufacturers develop their ranges. Please consult your usual supplier.
(2) Only with module versions greater than or equal to V1.7.
Configuration of a Time
Delay Function Block
8
© 2001-2003 Schneider Electric All Rights Reserved 10/03
Zelio-Logic™ Relay
Application Data
Application Data
Environmental Characteristics
File E164866 CCN NRAQ
File E164866 CNN NRAQ7
Product Certifications
CSA File LR203359 Guide 2252 01
CE C-Tick, GL
Degree of Protection IP 20
32 °F to 131°F (0 °C to 55 °C) conforming to IEC 60068-2-1
Operation
Temperature and 60068-2-2
Storage -13 °F to 158 °F (-25 °C to 70 °C) conforming to IEC 61131-2
Maximum Relative Humidity 95% without condensation or dripping water
Altitude 0 to 6500 ft (0 to 2000 m)
Immunity to vibration Conforming to standard IEC 60068-2-6, test Fc
Mechanical Resistance
Immunity to mechanical shock Conforming to standard IEC 60068-2-27, test Ea
Resistance to Electrostatic Discharges Immunity to electrostatic discharges Conforming to standard IEC 61000-4-2, level 3 ▼
Immunity to electromagnetic radiated fields Conforming to standard IEC 61000-4-3, level 3 ▼
Immunity to rapid, pulsed, transients Conforming to standard IEC 61000-4-4, level 3 ▼
Resistance to HF Interference
Immunity to surges Conforming to standard IEC 61000-4-5
Immunity to damped oscillatory waves Conforming to standard IEC 61000-4-12
9
10/03 © 2001-2003 Schneider Electric All Rights Reserved
Zelio-Logic™ Relay
Application Data
AC Input Characteristics
Smart Relay Type SR1-pp01FU SR1-pp01B
Connection Screw terminals Screw terminals
Voltage V 100…240 24
mA 0.65 (U = 115 V)
Nominal value of inputs Current 3 (U = 24 V)
1.3 (U = 240 V)
Frequency Hz 47…63 47…63
Voltage V ≥ 79 ≥ 12
At state 1
Current mA ≥ 0.4 (U = 240 V) ≥ 1.5
Input switching limit values
Voltage V < 40 <5
At state 0
Current mA < 0.3 < 0.6
45…50 (U = 110 V),
State 0 to 1 50/60 Hz ms 18…22
85…90 (U = 240 V)
Response time
45…50 (U = 110 V),
State 1 to 0 50/60 Hz ms 23…25
18…22 (U = 240 V)
Between supply and inputs None None
Isolation
Between inputs None None
Maximum counting frequency Hz 10 10
10
© 2001-2003 Schneider Electric All Rights Reserved 10/03
Zelio-Logic™ Relay
Application Data
Processing Characteristics
Smart Relay Type SR1 A1pppp, B1pppp A2pppp, B2pppp
Number of control scheme
60 80
lines
Maximum cycle time ms 6 8
12 to 24
14 to 26 (SR1-p201BD)
(SR1-B121JD and p1ppBD)
Response time (2) ms 22 to 42
20 to 40
(SR1-p201FU and p201B)
(SR1-p101FU and p101B)
Day/time h ≥ 150 at 40 °C only applicable to SR1-B and SR1-E (4)
Back-up time in case of
Program and adjustments For life, internal EEPROM
power failure
Current values and states (3) For life, internal EEPROM on smart relays SR1B/SR1E only (4)
Program memory checking At each power-up
Clock drift s y 6 per month
Time delay block accuracy ± 12 ms ± 0.5 % of the time displayed
(1) Minimum level under test conditions defined by the standards.
(2) Time between change of state of an input and change of state of an output directly linked by the program in the same cycle
(3) The values and states to be saved must be configured in the remanence menu (retains last known value of timers, counters,
latching relays, and internal logic relays).
(4) As from product version V1.7.
11
10/03 © 2001-2003 Schneider Electric All Rights Reserved
Zelio-Logic™ Relay
Application Data
OPERATING CURVES
3.0
1.4
L/R = 10 ms 48 V
Millions of Operating Cycles
0.0 0.0
0 0.5 1 1.5 2 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Current (A) Current (A)
AC Loads
AC-13 (3) ♣ AC-14 (4) ♣
3.0 2.5
Millions of Operating Cycles
Millions of Operating Cycles
2.5 2.0
24 V 110 V
2.0
1.5
48 V
230 V
1.5
110 V 1.0 48 V
SR1
1.0 • 101FU 230 V 24 V
0.5
0.5
0.0 0.0
0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5 0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2
Current (A) Current (A)
AC-15 (5) ♣
1.0
0.9
Millions of Operating Cycles
0.8
110 V
0.7
0.6 230 V 48 V
0.5
0.4
0.3
0.2
0.1
0.0
0.5 0.7 0.9 1.1 1.3 1.5 1.7 1.9
Current (A)
(1) DC-12: switching resistive loads and photo-coupler isolated solid state loads, L/R ≤ 1 ms.
(2) DC-13: switching electromagnets, L/R ≤ 2 x (Ue x Ie) in ms, Ue: rated operational voltage, Ie: rated operational current
(with protection diode on load, use the DC-12 curves and apply a coefficient of 0.9 to the million of operating cycles value).
(3) AC-12: switching resistive loads and photo-coupler isolated solid state loads, cos ≥ 0.9.
(4) AC-14: switching electromagnetic loads whose power drawn with the electromagnet closed is ≤ 72 VA,
making: cos = 0.3, breaking: cos = 0.3.
(5) AC-15: switching electromagnetic loads whose power drawn with the electromagnet closed is > 72 VA,
making: cos = 0.7, breaking: cos = 0.4.
♣ The product life expressed above is based on average usage and normal operating conditions. Actual operating life will vary with
conditions. The above statements are not intended to, nor shall they create any expressed or implied warranties as to product
operation or life. For information on the listed warranty offered on this product, refer to the Square D terms and conditions of sale
found in the Square D Digest.
12
© 2001-2003 Schneider Electric All Rights Reserved 10/03
Zelio-Logic™ Relay
Ordering Information
Ordering Information
Relays
Supply Voltage Inputs Outputs Blind Version With Clock Catalog Number Weight lb (kg)
12 Vdc 8 - 12 Vdc 4 Relay No Yes SRIB121JD 0.64 lb (0.290 kg)
6 - 24 Vdc 4 Relay No No SR1A101BD 0.64 lb (0.290 kg)
6 - 24 Vdc 4 Relay Yes No SR1D101BD 0.64 lb (0.290 kg)
8 - 24 Vdc ▲ 4 Relay No Yes SR1B121BD 0.64 lb (0.290 kg)
24 Vdc 8 - 24 Vdc ▲ 4 Relay Yes Yes SR1E121BD 0.64 lb (0.290 kg)
8 - 24 Vdc ▲ 4 Transistor No Yes SR1B122BD 0.64 lb (0.290 kg)
12 - 24 Vdc 8 Relay No No SR1A201BD 0.77 lb (0.350 kg)
12 - 24 Vdc ▲ 8 Relay No Yes SR1B201BD 0.77 lb (0.350 kg)
6 - 24 Vac 4 Relay No Yes SRIB101B 0.64 lb (0.290 kg)
SR1• 121BD 24 Vac
12 - 24 Vac 8 Relay No Yes SRIB201B 0.64 lb (0.290 kg)
6 - 100/240 Vac 4 Relay No No SR1A101FU 0.64 lb (0.290 kg)
6 - 100/240 Vac 4 Relay No Yes SR1B101FU 0.64 lb (0.290 kg)
6 - 100/240 Vac 4 Relay Yes No SR1D101FU 0.64 lb (0.290 kg)
100 - 240 Vac
6 - 100/240 Vac 4 Relay Yes Yes SR1E101FU 0.64 lb (0.290 kg)
12 - 100/240 Vac 8 Relay No No SR1A201FU 0.77 lb (0.350 kg)
12 - 100/240 Vac 8 Relay No Yes SR1B201FU 0.77 lb (0.350 kg)
Separate Accessories
Catalog Weight
Description
Number lb (kg)
Relay to PC interconnecting cable - 1.8 m length SR1CBL01 0.77 lb (0.350 kg)
EEPROM memory cartridge (1 k bytes) SR1MEM01 0.002 lb (0.001 kg)
Zelio-Soft™ Software SR1SFT01 0.33 lb (0.150 kg)
SR1• 101FU
Zelio Soft™ Software for Pocket PC
Catalog Weight
Description
Number lb (kg)
Connecting cable between Sub-D-9 connector on the Pocket PC and the smart relay SR1-CBL02 0.77 lb (0.350 kg)
Programming software for Pocket PC (also contains Zelio Soft™ multi-language software) SR1-SFT02 0.33 lb (0.150 kg)
Promotional Kits
Catalog Weight
Description
Number lb (kg)
CD-ROM, and cable SR1KIT01 1.1 lb (0.500 kg)
SR1B121BD and SR1KIT01 SR1PACKBD 1.74 lb (0.790 kg)
SR1B101FU and SR1KIT01 SR1PACKFU 1.74 lb (0.790 kg)
Documentation
Catalog Weight
Description Language
Number lb (kg)
English SR1MAN01EN 0.0022 lb (0.001kg)
French SR1MAN01FR 0.0022 lb (0.001kg)
Users guide German SR1MAN01DE 0.0022 lb (0.001kg)
Italian SR1MAN01IT 0.0022 lb (0.001kg)
Spanish SR1MAN01ES 0.0022 lb (0.001kg)
ABL-7RM2401
13
10/03 © 2001-2003 Schneider Electric All Rights Reserved
Zelio-Logic™ Relay
Wiring Diagrams and Dimensions
Wiring Diagrams and Dimensions
DIMENSIONS
4.33
3.54
3.94
110
100
90
2.34 2.36
59.5 60
A
Catalog Number A
SR1A101BD
SR1B101B
SR1B121BD
SR1B121JD
SR1D101BD
SR1E121BD 2.83 " (72 mm)
SR1A101FU
SR1B101FU
SR1D101FU
SR1E101FU
SR1B122BD
SR1A201BD
SR1B201B
SR1B201BD 4.96 " (126 mm)
SR1A201FU
SR1B201FU Dual Dimensions inches
mm
WIRING DIAGRAMS
3-wire Sensor on: Analog Inputs on: Analog Inputs on:
SR1A101BD SR1B121BD SR1B201BD
SR1B121BD SR1E121BD
SR1B122BD SR1B122BD
SR1D101BD SR1B121JD
SR1E121BD
SR1A201BD
SR1B201BD
SR1B121JD
(1) 0-10 Vdc Analog 0-10 Vdc Analog
+
24 Vdc Ca / Ta Ca / Ta Ca / Ta Ca / Ta
1 2
– (1)
1 2
(1)
+ +
24 Vdc 24 Vdc
BL BN BL BN – –
BK BK
+ - I1 I2 I3 I4 I5 I6 IB IC
+- I1 I2 I3 I4 I5 I6 I8 I9 IA IB IC --
24 Vdc +- I1 I2 I3 I4 I5 I6 IC I7
IB
24 Vdc
24 Vdc
1 Q1 2 1 Q2 2 1 Q3 2 1 Q4 2 1 Q5 2 1 Q6 2 1 Q7 2 1 Q8 2
1 Q1 2 1 Q2 2 1 Q3 2 1 Q4 2 1 Q1 2 1 Q2 2 1 Q3 2 1 Q4 2
14
© 2001-2003 Schneider Electric All Rights Reserved 10/03
Zelio-Logic™ Relay
Wiring Diagrams and Dimensions
N/- N/-
+- I1 I2 I3 I4 I5 I6 IB IC + - I1 I2 I3 I4 I5 I6 I7 I8 I9 IA IB IC --
24 Vdc 24 Vdc
1 Q1 2 1 Q2 2 1 Q3 2 1 Q4 2 1 Q1 2 1 Q2 2 1 Q3 2 1 Q4 2 1 Q5 2 1 Q6 2 1 Q7 2 1 Q8 2
U (4) U (4)
L (1)
100-240 Vac
50 / 60 Hz
L (1)
+ (1) N
100-240 Vac
50 / 60 Hz
24 V L N I1 I2 I3 I4 I5 I6 I7 I8 I9 IA IB IC
N
L N I1 I2 I3 I4 I5 I6 100-240 Vac
+ I1 I2 I3 I4 I5 I6 IB IC
100-240 Vac
24 V
1 Q1 2 1 Q2 2 1 Q3 2 1 Q4 2 1 Q5 2 1 Q6 2 1 Q7 2 1 Q8 2
1 Q1 2 1 Q2 2 1 Q3 2 1 Q4 2
+ Q1 Q2 Q3 Q4
U (4)
U (4)
12-125 Vdc
12-125 Vdc
15
10/03 © 2001-2003 Schneider Electric All Rights Reserved
Schneider Electric Schneider Canada Inc.
8001 Highway 64 East 19 Waterman Avenue,
Knightdale, NC 27545 M4B 1 Y2
1-888-SquareD Toronto, Ontario
(1-888-778-2733) 1-800-565-6699 Catalog No. 8501CT0001R1/03 October 2003 © 2001–2003 Schneider Electric All Rights Reserved