K1704 Manual
K1704 Manual
K1704 Manual
TeamTec Incinerator
OG400 CAIS
2451
Ship name : N/B Hyundai Mipo Ulsan 2452
Date : 09.12.2013
OG200/400C
Rev 0 04.02.2011 KK
OG200/400C 3
OG200/400C
4 OG200/400C
ADDENDUMS, CORRECTIONS AND NOTES
All TeamTec incinerators are made according to EC Type-Examination Certificate MED-B, and are
found to comply with the requirements in the following regulations/standards:
Annex A.1, item NO. A1/2.7 and Annex B, Module B in the Directive. Marpol 73/78 as amended, Annex
VI Regulation 16(2)(a), IMO Res. MEPC.76 (40).
Generally, for a design or type approval certificate, it is allowed to make minor modifications to the
equipment. Minor modifications are changes that will not affect the incinerators function or design. The
incinerator type is still the same, and all main functions are identical to the type approved unit and will be
covered by the certificates. The type stamped on the incinerator is the same as we have on the certificate,
but some of the drawings might have letter codes to describe the extra equipment (minor modification) on
your incinerator. All possible letter codes are:
OG200/400C 5
ADDENDUMS, CORRECTIONS AND NOTES
6 OG200/400C
TABLE OF CONTENTS
Table of contents
ADDENDUMS, CORRECTIONS AND NOTES .................................................................................... 5
ACRONYMS AND TERMS .................................................................................................................... 13
THE INCINERATOR “10 COMMANDMENTS” ................................................................................ 15
GARBAGE MANAGEMENT ................................................................................................................. 17
INCINERATION OF SOLID AND LIQUID WASTE ............................................................................................... 17
SOLID AND LIQUID WASTE THAT IS PROHIBITED TO BE BURNED................................................................... 17
SOLID WASTE HANDLING ............................................................................................................................ 18
BATCH LOADING ......................................................................................................................................... 18
SLUICE FEEDING .......................................................................................................................................... 18
SLUDGE CAPACITY...................................................................................................................................... 18
INTRODUCTION .................................................................................................................................... 19
INSTRUCTION MANUAL, PURPOSE AND SCOPE.............................................................................................. 19
SERVICE NETWORK FOR TEAMTEC INCINERATORS. ..................................................................................... 19
MAIN DATA ............................................................................................................................................ 21
PERFORMANCE DATA .................................................................................................................................. 21
Incinerator (combustion chamber)......................................................................................................... 21
Burner (fixed on combustion chamber) .................................................................................................. 22
Diesel oil booster pump (optional) ........................................................................................................ 22
Flue gas fan (bulkhead mounted) ........................................................................................................... 23
Flue gas damper .................................................................................................................................... 23
Sludge tank ............................................................................................................................................. 24
Water tank (Optional) ............................................................................................................................ 24
Sludge circulating pump (installed on sludge tank) ............................................................................... 24
Sludge filling pump (if dual sludge tank system)(Optional) ................................................................... 24
Sludge transfer pump (optional on dual sludge tank system)(Optional) ................................................ 24
Sludge dosing pump (fixed on combustion chamber) ............................................................................. 24
Water dosage pump (Optional) .............................................................................................................. 25
Diesel oil preheater (fixed on combustion chamber) ............................................................................. 25
Electrical control panel incinerator (fixed on combustion chamber) .................................................... 26
Frequency inverter for flue gas fan (Optional) ...................................................................................... 26
SHIPS SYSTEM INTERFACE REQUIREMENT.................................................................................................... 27
Electrical ................................................................................................................................................ 27
Diesel oil ................................................................................................................................................ 27
Flue gas duct .......................................................................................................................................... 27
Sludge and Steam or Air ........................................................................................................................ 27
Water and Steam or Air (Optional) ........................................................................................................ 28
Sludge tank (1100L / 1700L / 2000L / 3000L option) ............................................................................ 28
Water tank (435 l) (Optional) ................................................................................................................ 28
TECHNICAL DESCRIPTION ............................................................................................................... 29
OVERALL SYSTEM FUNCTION DESCRIPTION ................................................................................................. 29
Water injection (Optional) ..................................................................................................................... 29
Combustion chamber ............................................................................................................................. 29
Flue gas fan............................................................................................................................................ 30
Sludge service tank with heater.............................................................................................................. 30
Sludge settling tank with heater (optional). ........................................................................................... 30
Water tank (Optional). ........................................................................................................................... 30
SLUDGE CONTROL ....................................................................................................................................... 31
Introduction............................................................................................................................................ 31
Temperature limits ................................................................................................................................. 31
Burner stage ........................................................................................................................................... 31
Control ................................................................................................................................................... 32
OPERATOR PANEL ............................................................................................................................... 33
OG200/400C 7
TABLE OF CONTENTS
8 OG200/400C
TABLE OF CONTENTS
OG200/400C 9
TABLE OF CONTENTS
10 OG200/400C
TABLE OF CONTENTS
Faults that can be reset with the automatic restart function, after the cause has disappeared
(continued) ........................................................................................................................................... 150
Faults that can be reset as soon as their cause disappears ................................................................. 151
APPENDIX G: SLUDGE BURNER .................................................................................................... 152
CLEANING OF SLUDGE BURNER ................................................................................................................. 152
PROCEDURE FOR ADJUSTING THE SLUDGE BURNER ................................................................................... 152
APPENDIX H: SLUDGE DOSAGE PUMP ....................................................................................... 154
DIMENSION ............................................................................................................................................... 154
DISMANTLING AND ASSEMBLY DIAGRAM, ................................................................................................. 155
Exploded view ...................................................................................................................................... 155
MOTOR FOR PUMP. .................................................................................................................................... 155
PARTS LIST ART. NO. 2007672 .......................................................................................................... 156
INSTALLATION .......................................................................................................................................... 157
Installation and Safety Recommendations ........................................................................................... 157
General ................................................................................................................................................ 157
STORAGE ................................................................................................................................................... 157
Short-term storage ............................................................................................................................... 157
Long-term storage ................................................................................................................................ 157
IMMEDIATELY PRIOR TO INSTALLATION AND STARTING. ........................................................................... 157
ELECTRICAL .............................................................................................................................................. 158
IMPORTANT ............................................................................................................................................... 158
General safety ...................................................................................................................................... 158
Start-up procedure ............................................................................................................................... 158
DRYRUNNING ............................................................................................................................................ 158
Mechanical seals, all pumps. ............................................................................................................... 159
Guards ................................................................................................................................................. 159
Warning/control device ........................................................................................................................ 159
Pump operating temperature ............................................................................................................... 159
MAINTENANCE OF WEARING COMPONENTS ............................................................................................... 159
Rotor and stator ................................................................................................................................................ 159
DIAGNOSTIC CHART .................................................................................................................................. 160
APPENDIX I: SLUDGE VALVE. ....................................................................................................... 162
A 6324/1101/7003. 0-1 bar. G 3/4"...................................................................................................... 162
Valve .................................................................................................................................................... 163
APPENDIX J: SLUDGE CIRCULATION PUMP.............................................................................. 164
GENERAL INFORMATION ........................................................................................................................... 164
Noise level ............................................................................................................................................ 164
DRAWING .................................................................................................................................................. 165
PARTS LIST ................................................................................................................................................ 165
COMMISSIONING ....................................................................................................................................... 165
MAINTENANCE .......................................................................................................................................... 166
Maintenance instructions following a prolonged shutdown ................................................................ 166
Removing the pump .............................................................................................................................. 166
Dismantling and assembly instructions of the mechanical seal ........................................................... 167
Dismantling ...................................................................................................................................................... 167
Assembly .......................................................................................................................................................... 167
Fitting of stationary ring ................................................................................................................................... 168
APPENDIX K: WATER DOSAGE PUMP.......................................................................................... 170
DIMENSION ............................................................................................................................................... 170
DISMANTLING AND ASSEMBLY DIAGRAM, ................................................................................................. 171
MOTOR FOR PUMP. .................................................................................................................................... 171
PARTS LIST ART. NO. 2007740 .......................................................................................................... 172
INSTALLATION .......................................................................................................................................... 173
Installation and Safety Recommendations ........................................................................................... 173
General ................................................................................................................................................ 173
STORAGE ................................................................................................................................................... 173
OG200/400C 11
TABLE OF CONTENTS
12 OG200/400C
ACRONYMS AND TERMS
OG200/400C 13
ACRONYMS AND TERMS
14 OG200/400C
THE INCINERATOR “ 10 COMMANDMENTS”
Keep the incinerator chamber inlet outlet and burner parts clean. Inspect daily before start
in the morning, and clean as required.
Do never throttle the air/steam needle valve more than ¾ turn closed. If the pressure
increases above green area, clean the sludge burner nozzle.
Do never turn off the main power before the chamber temperature is down below 170°C.
If experiencing any problem with high temperature in combustion chamber, flue gas or
control of sludge dosing, replace the dosing pump stator.
Do not transfer sludge to the service tank during sludge burning in a single tank system
(can damage the refractory).
As a minimum, heat the sludge over night, without starting the circulating pump. Next
morning drain off the free water and start the sludge program.
Never load glass, lithium batteries or large quantities of spray cans in the incinerator –
nor large quantities of oily rags or filter cartridges. This may damage the flue gas fan.
Inspect the cooling jacket every 6 months (open the cover plates) and clean as required
with steam or hot water.
Read the instruction manual, and never change any settings unless instructed by
TeamTec, Norway
OG200/400C 15
THE INCINERATOR “ 10 COMMANDMENTS”
16 OG200/400C
GARBAGE MANAGEMENT
Garbage management
TeamTec recommend working out guidelines for an onboard garbage management plan.
Personnel responsible for operation of the incinerator shall be trained and capable of
implementing the guidance follows by the instruction manual.
Waste incineration on board sea going ships and offshore platforms is world wide regulated by
IMO MARPOL 73/78, RESOLUTION MEPC 76(40), STANDARD SPECIFICATION FOR
SHIPBOARD INCINERATORS, adopted on 25.september 1997, and IMO MARPOL ANNEX
VI REGULATION 16 and APPENDIX IV adopted on 26. September 1997.
MERCURY
LEAD
NICKEL
VANADIUM
ZINC
OG200/400C 17
GARBAGE MANAGEMENT
Class 2 refuse, consists of approximately even mixture of rubbish and garbage by weight. This
type of waste is common to passenger ships occupancy, consisting of up to 50% moisture, 7%
incombustible solids and has a heating value of about 10.000 kJ/kg as fired.
Be aware that plastics has high calorific value, about 36.000 kJ/kg and must only be incinerated
in small amounts at the same time.
Batch loading
Do not attempt to clean the combustion chamber without activating the slagging mode on the
touch screen display, to prevent injury to personnel due to insufficient ventilation.
Each morning, providing that the combustion chamber temperature is lower that 170°C, slag
and ashes should be removed. Partly burnt garbage shall remain in the chamber. This garbage
will be fully incinerated at the next sequence of incineration. The air inlet openings in the
bottom of the combustion chamber must be regularly cleaned. This is important in order to let
the combustion air come into the chamber.
Load the combustion chamber with garbage of type IMO class 2. If high calorific garbage is
loaded, a smaller quantity must be loaded per charge.
Sluice feeding
If sluice is installed, solid waste can be fed into the 55 litre sluice at temperatures between
700°C and 1050°. Fill the trash in a garbage paper bag, open the sluice lid/sluice door and put
the bag into the sluice. Do not jam the trash bag into the sluice or overfill it. Close the lid /
sluice door and rotate the sluice by the handle on the sluice. The recommended waiting time
between each time the sluice can be operated is 210 seconds. After the waiting time has elapsed,
the sluice is ready for a new load.
Sludge Capacity
The incinerator is certified according to MEPC 76(40) which determines the sludge to contain
20% water.
A high water content up to 50% water content will result in a higher capacity than what is
mentioned in the certificate. As an example, the sludge with 40% water content will have lower
calorific value than IMO sludge, hence higher hydraulic capacity.
A water content higher than 50% requires a pilot burner (support burner). This reduces the
available capacity for burning of sludge
.
18 OG200/400C
INTRODUCTION
Introduction
Instruction manual, purpose and scope
This user manual is made according to guidelines in the Norwegian Standard NS 5820
The manual will guide the reader/user gradually to an understanding required for safe operation
and maintenance of the incinerator system.
It is important for the user to have a good understanding of the incinerator function, to avoid
malfunction caused by operational errors.
The guarantee will be invalid if problems and/or caused by operational errors or mistreatment.
Tel.: +(47) 37 19 98 00
Telefax: +(47) 37 19 98 90
E-mail: office@teamtec.no
Please note that our main strategy is to offer our customers the best service and quality
spare parts wherever and whenever they need them. To reach this goal we have
established a stock of spare parts and trained service personnel in major ports throughout
the world.
OG200/400C 19
INTRODUCTION
20 OG200/400C
MAIN DATA
Main data
Performance data
70 l/h IMO sludge oil (w. water injection) IMO sludge (20% water)
127 l/h Water consumption (w. water injection) From Bilge water tank
Corresponding to: 53 l/h IMO sludge oil (without water injection) IMO sludge (20% water)
Solid waste max. 400 litre per charge or 55 IMO class 02 waste
l/charge continuous feeding
81 l/h IMO sludge oil (w. water injection) IMO sludge (20% water)
140 l/h Water consumption (w. water injection) From Bilge water tank
Corresponding to: 74 l/h IMO sludge oil (without water injection) IMO sludge (20% water)
Solid waste max. 400 litre per charge or 55 IMO class 02 waste
l/charge continuous feeding
OG200/400C 21
MAIN DATA
Weight (each): 30 kg
Connections: 1/4"
Weight: 12 kg.
22 OG200/400C
MAIN DATA
OG200C: DN 300 H2
Designed to withstand
Type: OG400C: DN 350 H2 max temperature of
450°C
One stage centrifugal fan.
Weight: 326 kg
OG 200C: DN 300/400
Size:
OG 400C: DN 350/400
Weight: 68/71 kg
Dimension between
300 mm See dimension drawing.
flanges:
OG200/400C 23
MAIN DATA
Sludge tank
Flange rating: NP 16
Flange rating: NP 16
Weight: 424 Kg
24 OG200/400C
MAIN DATA
OG200/400C 25
MAIN DATA
Enclosure rating IP 55
Weight: 56 kg
Enclosure rating IP 54
Weight: 22 kg.
26 OG200/400C
MAIN DATA
Electrical
Refer to Cable Arrangement drawing.
Diesel oil
DN 15 flange, max
Diesel oil return line Connection.
pressure 1.5 bar
Connection DN 15 flange
OG200/400C 27
MAIN DATA
Connection DN 15 flange
Steam /air supply line Pressure 6 - 8 bar
for water injection
atomising. Consumption: Steam approx. 20kg/h
Compressed air approx. 20kg/h
Connection DN 15 flange
Consumption 2 m³/h
Heating: Thermal oil
Max. pressure 10 bar
Max. temperature 180°C
Detailed information regarding the system is found on the Piping & Instrument Diagram given in the
Drawings section.
28 OG200/400C
TECHNICAL DESCRIPTION
Technical description
Overall system function description
The TeamTec Incinerator type OG200/400C is designed for on board incineration of ship's waste oil, solid
refuse and destruction of bilge water. The system consists of 5 main parts:
Combustion chamber with diesel oil burner, sludge burner, pilot fuel heater and electric control panel.
Flue gas fan with flue gas damper or frequency inverter (Optional).
Sludge service tank with circulating pump and heater.
Sludge settling tank with filling pump and heater (Optional).
Water injection (Optional).
When burning sludge with injected water, the sludge burning capacity increases, NOx in flue gas duct reduces
and it is an easy way to get rid of problem water. Dumping oily water directly into the sea can harm marine
life, and is illegal. Various ports are facing new local regulations on ship emissions, including discharges of
ballast water, grey water, bilge water, and deck runoff, among others. Disposal of the contaminated water in the
incinerator is an easy and effective solution to a complex problem.
Combustion chamber
The combustion chamber consists of a cylindrical chamber. The trash is ignited by burner in the chamber. The
combustion chamber is equipped with an inspection, which can be opened only while the incinerator is not
burning. The control system will prevent the door from being opened before the set temperature for cooling is
reached.
The flue gas outlet is located at the top of the left chamber for most efficient use of the flames. The flames
from the burners follow a corkscrew pattern towards the bottom and continue rotation upwards in the centre of
the combustion chamber. Remnants of particulate matters in the gas flow are neutralised by the burner, making
the combustion ecologically safe. As the fumes exits the chamber, cooling air drawn from the lower part of the
casing is mixed with the flue gas to bring the temperature down to approx. 330°C before it pulled out by the
flue gas fan and blown out the stack to atmosphere.
The burning process is monitored by the PLC and scanned by a photo resistor in the burner. The temperatures
are also monitored/regulated automatically by the PLC control system.
Two sight glasses are equipped, for the operator to be able to inspect the amount of trash in the chamber and
the function of the system.
The combustion chamber is of steel construction, lined with specially designed refractory blocks. Between the
steel and refraction there is a 50mm layer of insulation. The refractory material is made of a low cement/high
alumina quality being slag resistant and having very good thermal shock resistance. A double steel casing with
a cooling air jacket forms the outside of the combustion chamber.
The combustion chamber is equipped with a, three-stage diesel oil burner and a steam/air atomising nozzle for
sludge burning. Under the burner assembly, a bracket/drip tray for sludge burning equipment is mounted.
The Diesel Oil burner has 3 stages, automatically controlled by the PLC. In addition there are four stages for
sludge burning, using steam or compressed air for atomising. The sludge burner allows particles up to 4 mm to
pass through. The D.O. burner is monitored by the PLC and has a built in primary air fan and diesel oil pump.
The main electrical control panel is normally fitted on the incinerator and it contains circuit breakers, starters,
frequency inverters, PLC and operator panel. A separate frequency inverter for flue gas fan control is optional,
and are to be installed close to the fan. The electric panels are built according to international standards for
marine equipment. The operator panel, which is located at the side of the control panel, has a LCD display
touch screen for selecting burner program modes and for monitoring the burning process.
OG200/400C 29
TECHNICAL DESCRIPTION
Drain valves (sample points) are mounted on the tank to check the sludge level in the tank. The lowest one is
meant to use for draining off the water. A level transmitter on the tank provides PLC to generate a tank level
readout on operator panel (display on incinerator control panel).
A filling pump is mounted on the tank. The pump transports the sludge to the sludge service tank. A low level
switch on the tank will stop the filling pump and heating when the level has reached a minimum. It is not
possible to transfer sludge to the service tank during sludge burning
An indicating light for heating is placed on the junction box on the tank.
The water tank has filling, overflow and ventilation connection. The incinerator has frequency controlled water
dosing pump unit, with suction lift at 3500mm. The water is connected to the incinerator with DN 15 flange
connection.
The water tank has two level switches. A high level switch to stop the filling pump and a low level switch, with
dual contact set, to start the filling pump and to stop the water injection if switch is activated for more than two
minutes. This is to prevent the water dosage pump to run dry. A suitable tank is available from TeamTec.
30 OG200/400C
TECHNICAL DESCRIPTION
Sludge control
Introduction
The automatic sludge control logic is designed for burning a maximum amount of sludge, consuming a
minimum amount of diesel, and maintaining a combustion chamber temperature above 870°C (CCT stop
burner diesel oil), see operator panel - settings sludge program page 2/4. Sludge quality is an important factor
for the sludge burning process. The system is capable to handling sludge with a high content of water, but this
might however result in a higher consumption of diesel oil.
Temperature limits
680°C Start sludge burner.
640°C Temperature decrease to this level stop sludge burner and increase sludge quality
counter with 2.
660°C Temperature decrease to this level, after temperature have been above 690°C,
decrease the sludge dosage pump rpm with 50 and increase sludge quality counter
with 2.
690°C Temperature increase to this level increase the sludge dosage pump rpm with 70.
700°C Alarm level for low combustion chamber temperature, if combustion chamber
temperature has been above 850°C.
840°C Starts a diesel support burner in addition to the condition at 870°C and increase the
sludge quality counter with 2. Decrease the sludge dosage pump rpm with 140.
870°C Temperature allowing burning sludge alone. Temperature increase to this level the
increase the sludge dosage pump rpm with 140.
890°C Above this temperature the sludge quality counter will step down one every minute.
900°C Sluice is available in Sludge/Solid waste program.
1000°C Temperature increase to this level and above, decrease the sludge dosage pump rpm
with 4 every 30 second if Sludge/Solid waste program is running.
1050°C Water injection starts.
1150°C Temperature increase to this level and above, decrease the sludge dosage pump rpm
with 4 every 30 second. Water injection control temperature. Water amount injected
to combustion chamber will increase if CCT is above this level, and decrease if CCT
below this level.
Burner stage
STAGE NO 3 Diesel oil nozzles no. 1 + 2.
OG200/400C 31
TECHNICAL DESCRIPTION
Control
At first start up a sludge burner program, the sludge burner start when combustion chamber temperature rise
above 680°C, the operator panel will indicate burner stage 5, the sludge dosage pump will be given start speed
190 rpm, and will run at this speed for 60 seconds. During the 60 seconds, burner step 5 will be fixed.
Assuming the sludge is of a good quality the temperature will start to rise. If the temperature raise is >=0°C
over 30 seconds, the sludge dosing pump increase 2 rpm. There will be a sampling of temperature each 30 sec.
and provided there is a temperature raise, a new step of 2 rpm will take place.
If the sludge quality is still good, the sludge dosing pump will be given a new step increase of 70 rpm when
temperature rises above 690°C. The burner stage will be 4. When temperature raise above 870°C the sludge
dosing pump will again be given a new step increase 60 rpm and the burner stage will be 7.
If the sludge contain too much water or chemicals, the temperature is likely to fall below 640°C and the sludge
dosing pump stop. Burner will change to stage 3, and the sludge quality counter will increase with 2 (after an
attempt to stage 5). When temperature rises above 680°C the sludge burner will start again. The burner stage
will then depend of sludge quality number. The sludge quality number is an indication of the quality of the
sludge. A high sludge quality number indicates a sludge with high water content, and burner will use more
diesel oil.
The low temperature alarm, 700°C, will first be activated if temperature has been above 870°C.
32 OG200/400C
OPERATOR PANEL
Operator Panel
General
The operator panel is a touch sensitive screen enabling the operator to enter information to the incinerator
control system. The screen is also displaying information from the control system to the operator. The panel is
connected to A PLC, controlling the combustion process. A description of the screens follows. The main
picture is displayed at start up and is possible to access by pressing “main” from most other screens. The screen
will display equipment according to scope of delivery from TeamTec AS
The Main picture has animated feedback to
the operator. The pumps and fans turn green 1
when running. The level switches are 2
animated up or down according to the level.
A level indication is animated at the sludge 3
tanks. There are written numbers displaying
4
actual measured values positioned
approximately according to physical
position at the incinerator. In addition to the
buttons at the lower part of the panel, it is
possible to press on an item on the screen to
5
open a different screen or dialogue box. The
list below describes the possible options: 6
10
11
12
(The appearance of the screen may differ based on the choice of optional equipment)
OG200/400C 33
OPERATOR PANEL
Structure
Logic control system consists of an “Overview” screen and several sub-screens in the order as described below:
Main
Select/start
programs
Setup Burner
Sludge I/O
Solid waste
Information
The control system Pop-up
will activate these SW Sludge
screens. Service
Pop-up
Sludge and Water
Login
Restore
Factory
Burn-in Settings
Display backlight
Date time
Prog. info
Water tank
Hour
General: From all screens it is possible to stop the incinerator by pressing “Stop” It is also possible to access
“Main”, Setup” and “Alarm from all screens.
34 OG200/400C
OPERATOR PANEL
Information pop-up
An information pop-up gives information to
the user about irregularities between user
actions and incinerator status. Read the
message and press “Ack”.
The following messages may appear as
information messages:
Not possible to start sludge filling pump low level in sludge settling tank
Not possible to start sludge filling pump high level in sludge service tank
Not possible to start sludge filling pump when sludge program is running
OG200/400C 35
OPERATOR PANEL
Not possible to start sludge circulation pump low level in sludge service tank
Not possible to start sludge program - low level sludge service tank
Not possible to start sludge with water program - low level sludge service tank
Not possible to start solid waste - sludge program - low level sludge service tank
Not possible to start program - Door not closed - please close door
Heating of refractory is finished. Let the incinerator cool down for 10 Hours1
Burner
Display actual values and status on motors,
actuators and sensors. No adjustments or
settings on this screen – view only.
Setting tanks
Displays tanks physical attributes and sludge
mass for correct sludge consumption.
1
Program revision A or later
36 OG200/400C
OPERATOR PANEL
Hour counters
Display last run and total hours. Press “Next”
button to access screen “Hour counters 2”
Setup
Some functions require the operator to login in
order to access a screen or to alter a value in
the setup. This normally indicates that the
operator needs training in order to be aware of
the consequences of his actions.
Select the setup screen you want to access. If
not logged in as user “usr”, values on different
setup screens are “view only”.
OG200/400C 37
OPERATOR PANEL
Login
Pressing “Setup” will give access to “Login”.
Change values
Plot the value that should be changed. A numeric pop-up will appear:
The present value is displayed on the line. Type in a new value and press return to
accept, or press “ESC” to cancel.
38 OG200/400C
OPERATOR PANEL
Settings burner
If not logged in as user “usr”, values on
different setup screens are “view only”.
Buttons “Prev.” and “Next” is used in a
circular shift function between a number of
setting screens.
Text Description
OG200/400C 39
OPERATOR PANEL
Settings alarms
If not logged in as user “usr”, values on
different setup screens are “view only”.
Text Description
Alarm max time dieselheater The maximum time the dieselheater is activated the first time after
start start incinerator. The dieselheater requires extra time at start-up.
Alarm max time dieselheater The maximum time the dieselheater is activated during
run incinerating.
40 OG200/400C
OPERATOR PANEL
Text Description
Set burning time2 Set total burning time for sludge program
CCT low hysteresis – stop Maximum drop combustion chamber temperature (CCT) – stop
sludge. sludge dosage system.
2
Can be changed by user
3
Can be changed by user
OG200/400C 41
OPERATOR PANEL
Text Description
CCT inc between adjust – inc The minimum increase in combustion chamber temperature (CCT)
sludge needed at time check before making adjustment to process.
Hys max. CCT – stop dec Maximum drop combustion chamber temperature (CCT) before
sludge stop reducing sludge.
Set min CCP for Minimum set point for Combustion Chamber Pressure (CCP) as
temp.regulating long as the Combustion Chamber Temperature is above 800°C
42 OG200/400C
OPERATOR PANEL
Text Description
Hys max. FGT – stop adjust Maximum drop flue gas temperature (FGT) before stop decreasing
CCP combustion chamber pressure (CCP)
Max. FGT – start adjust SDP Maximum flue gas temperature (FGT) decrease sludge dosage
RPM pump (SDP) RPM.
Hys FGT – stop adjust SDP Minimum drop flue gas temperature (FGT) before stop decreasing
RPM sludge dosage pump (SDP) RPM.
Min. CCT scale CCP run Minimum combustion chamber temperature (CCT) in scaling
sludge range for adjusting combustion chamber pressure (CCP)
Max. CCT scale CCP run Maximum combustion chamber temperature (CCT) in scaling
sludge range for adjusting combustion chamber pressure (CCP)
SDP comp. decrease diesel oil Increasing sludge when changing burner step from 5 to 4, or 6 to 5.
SDP comp. stop diesel oil Increasing sludge when changing burner step from 4 to 7.
OG200/400C 43
OPERATOR PANEL
Text Description
Purging start sludge Time for purging sludge nozzle before opening sludge.
Purging stop sludge – CCT Minimum combustion chamber temperature (CCT) for stop
below purging sludge nozzle.
Setpoint heat tracing Setpoint for heat tracing temperature on sludge line.
Hystersis heat tracing Hysteresis for setpoint, heat tracing temperature on sludge line.
Alarm low level Sludge service Activate if alarm is needed when sludge service tank low level
tank switch is activated.
44 OG200/400C
OPERATOR PANEL
Text Description
Set burning time4 On, makes it possible to program a fixed burning time
CCP start-up solid waste Minimum combustion chamber pressure (CCP) before start burner
program at start solid waste program
4
Can be changed by user
OG200/400C 45
OPERATOR PANEL
Text Description
Max. FGT start adjustment Maximum flue gas temperature (FGT) before start adjusting
CCP combustion chamber pressure (CCP).
Hysteresis FGT stop adjusting Minimum drop flus gas temperature (FGT) before stop adjusting
CCP combustion chamber pressure (CCP)
CCP inc when FGT above Value for increasing combustion chamber pressure (CCP) when
setpoint flue gas temperature (FGT) is above set point
CCP dec when FGT below Value for decrease combustion chamber pressure (CCP) when flue
setpoint gas temperature (FGT) is below set point
Max. FGT start adjust burner Maximum flue gas temperature (FGT) before start adjusting
step burner step.
Hysteresis FGT stop adjust Minimum drop flue gas temperature (FGT) before stop adjusting
burner step burner step.
Time check FGT adjust burner Time between reading flue gas temperature (FGT) before making
step adjustment to burner step.
46 OG200/400C
OPERATOR PANEL
Text Description
Hysteresis max. CCT SW & Minimum drop combustion chamber temperature (CCT) – stop
sludge reducing sludge when running solid waste and sludge program.
OG200/400C 47
OPERATOR PANEL
Text Description
48 OG200/400C
OPERATOR PANEL
Text Description
FGF RPM when CCT below Set point for flue gas fan (FGF) speed when running below “Stop”,
stop5 combustion chamber temperature (CCT) – Loading/slagging speed.
Off – After emergency stop the flue gas fan needs to be restarted by
pushing “STOP” button on display.
Auto start of FGF after stop6
On – After emergency stop the flue gas fan automatically starts if
temperature is above 220°C.
5
Only visible if frequency controlled flue gas fan is installed.
6
Can be changed by user.
OG200/400C 49
OPERATOR PANEL
Burn-in
If not logged in as user “usr”, values on
different setup screens are “view only”.
Burn-in program is used for burning in
refractory after long storage periods or
refractory replacement. It runs automatically
for 10 hours, increasing CCT from 100°C to
600°C. A message will appear when refractory
is ready.
Text Description
Hys. chang. burner step Hysteresis for temperature setpoint, when changing burner step.
50 OG200/400C
OPERATOR PANEL
Incinerator configuration
The button “Restore factory settings” can be
used to restore settings to factory
specifications.
Backlight
No user name and password required.
OG200/400C 51
OPERATOR PANEL
Program information
Values are view only. If assistance from
TeamTec is required, you might be asked for
the type and version listed on the screen.
Consumption
Display consumption for this run, last run and
total. Press “Setup consumption” to access
setup screen.
Consumption setup
If not logged in as user “usr”, values on
different setup screens are “view only”.
52 OG200/400C
OPERATOR PANEL
Alarm system
If the control system encounters any irregularities the system will give an alarm and shut down the incinerator.
When an alarm occurs, the internal audible alarm activates and the alarm signal is given to ships alarm system.
The "ALARM" screen will pop-up at the operator panel display and the most recent alarm(s) will be displayed
at the top of the list. The “ALARM” screen will display active alarms as well as the alarm history. A total of
128 alarms (active and history) can be displayed. When additional alarms occur, the oldest alarms will be
deleted from the alarm history list.
Alarms Status:
Symbols indicating alarm status
Symbol Status
*! Active Accepted
Double arrow up Move the line (alarm) selection to top of list or screen.
Move the line (alarm) selection down one line. If the alarm list contains
Arrow down more alarms than can be displayed on the screen, the list will move one
line at a time each time the button is pressed.
Switch off audible alarm. The audiable alarm will not reengage until all
Audio Off
the alarms have been inactive and an new alarm appears
OG200/400C 53
OPERATOR PANEL
Alarm List
The Alarm-list contains information about which alarms that are available. The reference refers to electrical
drawings.
Diesel oil press. Low 11 bar Running +2S1 Diesel oil pump press low.
7
Only visible if frequency controlled flue gas fan is installed
8
Only visible if water injection is installed
9
See motor rating
54 OG200/400C
OPERATOR PANEL
Sludge temperature low 50°C Sl. prog. -U3 Sludge temperature low.
Sludge temperature high 95°C All time -U3 Sludge temperature high.
Sludge
Steam/air press. - water Steam / air pressure water
1,5/4,5 bar w/water +25 S4/S5
low/high11 low/high.
Prog.
Low level sludge service Sl. Prog. Sludge below low level switch
~ +3A-S1
tank in more than 5 sec.
10
sludge tank w/el. heater
11
Only visible if water injection is installed
12
Program revision B or later
OG200/400C 55
OPERATOR PANEL
Setting list
50Hz 60Hz
Settings burner 50Hz 60Hz
Sluice Sluice
Burner damper burner step 1 18 % 18 % 18 % 15 %
Burner damper burner step 2 28 % 28 % 25 % 25 %
Burner damper burner step 3 37 % 37% 30 % 30 %
Burner damper burner step 4 28 % 28 % 25 % 25 %
Burner damper burner step 5 37 % 37 % 35 % 35 %
Burner damper burner step 6 100 % 100 % 100 % 100 %
Burner damper burner step 7 55 % 55 % 40 % 40 %
Factor CCP burner damper reg. 0.150
Factor SDP burner damper reg. 0.050
Settings alarms
Alarm max time dieselheater start 600 Sec.
Alarm max time dieselheater run 480 Sec.
Alarm max CCT 1200 °C
Min.operating CCT 850 °C
Alarm CCT below min. oper. 150 °C
Alarm max FGT 375 °C
Alarm min CCP (Draught failure) -5 mmWC
Settings sludge
Sludge alone Yes
CCP start sludge -28 mmWC
Max. CCP run sludge -28 mmWC
Min CCP run sludge -12 mmWC
Min. sludge temp run sludge 80 °C
Alarm sludge temp. low, below normal 30 °C
Alarm sludge temp. high, above normal 15 °C
Min. CCT for run sludge 680 °C
CCT low hysteresis – stop sludge 40 °C
Purging start sludge 5 Sec.
Purging stop sludge – CCT below 300 °C
Time start sludge before adjust 60 Sec.
Time check CCT after adjust 30 Sec.
CCT inc between adjust – inc sludge 0 °C
CCT inc. sludge – dec. diesel oil 690 °C
Hys dec sludge – inc diesel oil 30 °C
CCT stop burner diesel oil 870 °C
Hys restart burner diesel oil 30 °C
Maximum CCT 1150 °C
Hys max CCT – stop dec sludge 10 °C
Set CCP running step 4 & 5 -15 mmWC
Set min CCP for temperature regulation -15 mmWC
Max. FGT – start adjust CCP 330 °C
Hys max FGT – stop adjust CCP 0 °C
Time check FGT adjust CCP 30 Sec.
FGT max inc CCP -3 mmWC
56 OG200/400C
OPERATOR PANEL
13
Visible if heat tracing installed
14
Visible if heat tracing installed
OG200/400C 57
OPERATOR PANEL
15
Only visible if frequency controlled FGF
16
Changes after 3 hours continious sludge burning
58 OG200/400C
OPERATOR PANEL
17
Only available if water injection is installed
OG200/400C 59
OPERATOR PANEL
60 OG200/400C
OPERATOR PANEL
-U1
Menu 1.3 Settings
Flue gas fan
Acceleration 5.0 Sec
Deceleration 10.0 Sec
Low speed 0 Hz
High Speed 60 Hz
Mot. therm. current 17.2 A
Current limitation 17.2 A
-U1
Menu 1.4 Motor control
Flue gas fan
Standard mot. freq. 50 Hz
Rated motor power 7.5 kW
Rated motor voltage 380 V
Rated mot. current 17.2 A
Rated motor speed 1455 rpm
Max. frequency 60 Hz
Auto tuning Yes
-U1
1.5 Inputs/outputs CFG
Flue gas fan
2 wire type Level
AI2 configuration AI2 min. value 4.0 mA
AO1 assignement I motor
AO1 conf. AO1 min. value 4.0 mA
-U1
1.6 Command
Flue gas fan
Ref. 1 channel AI2 (enter two times)
Stop key priority No (press 2 sec.)
OG200/400C 61
OPERATOR PANEL
-U1
1.7 Application funct.
Flue gas fan
Auto DC injection Continous
-U1
1.8 Fault management
Flue gas fan
Fault reset LI5
Motor thermal prot. Overload fault mgt Fallback spd.
Drive overheat Overtemp fault mgt Fallback spd
4-20mA loss AI2 4-20 mA loss Fallback spd.
Fallback speed 15 Hz
-U1
1.12 Factory settings
Flue gas fan
Config source Config1
Save config Yes (hold for 5 sec)
62 OG200/400C
PROGRAM DESCRIPTION
Program description
Overall program function description
The TeamTec Incinerator type OG200/400C is controlled by a Programmable logic controller (PLC) witch
handles both the operating functions and the alarm system. The Human Machine Interface (HMI) is a touch
screen operator terminal. The operator terminal allows the user to view and monitor the process and to give
input to the process by choosing appropriate program to the desired task.
The Incinerator has 5 programs to select from; “Sludge”, ”Sludge and Water18”, “Solid waste & Sludge”,
“Solid Waste” and “Slag”. Some functions are general and controlled in the same way regardless of choice of
program.
General
The diesel oil burner heats up the incinerator. The burner runs in different steps, each program calculates the
required burner step and the burner responds accordingly by controlling the diesel oil valves, the burner air
damper the burner motor and the ignition electrodes.
The airflow through the burner is adjusted by the burner damper to different air flow at different steps on the
burner. The damper opening is corrected for the actual pressure in the combustion chamber (CCP) and the
actual speed of the sludge dosing pump (SDP)
2 – Nozzle 2
3 – Nozzle 1 and 2
4 – Nozzle 1 and sludge.
5 – Nozzle 2 and sludge.
6 – Nozzle 1 and 2 and sludge.
7 – Sludge only
18
Only available if water injection is installed
OG200/400C 63
PROGRAM DESCRIPTION
Burner step 0 X X X X
Burner step 1 X X X X
Burner step 2 X X X X
Burner step 3 X X X X
After sludge program is started there is two criteria that needs to be fulfilled before incinerating starts; Sludge
temperature above 80°C and Diesel oil temperature above 60°C.
When the combustion chamber temperature (CCT) has reached set point “min CCT for run Sludge”(680°C),
the steam line will flush for 10 seconds to drain out condensate water before starting up the sludge burner. The
sludge dosage pump (SDP) starts. If the temperature increases after 60 seconds, the diesel oil burner reduces
“CCT inc sludge – dec diesel oil”(690°C). If temperature decreases below 640°C, sludge burning stops and
retries with a higher burnerstep at “min CCT for run Sludge”(680°C) if sludge quality counter is above the
initial value for increasing sludge burner step. At set point “CCT stop burner diesel oil” (870°C), the sludge
program requires burner step 7 from the burner program and runs sludge only if selected in the sludge settings.
64 OG200/400C
PROGRAM DESCRIPTION
The temperature and pressure in the combustion chamber is controlled by calculations in the control system.
By adjusting:
All checks of temperature are made in time intervals. After each change in state or function, further
adjustments are not made until time interval has elapsed.
At the end of each time interval (30sec), the change in combustion chamber temperature (CCT) is calculated.
Depending of temperature raise (or drop), adjustments are made, according to calculations, to components that
will influence the combustion chamber temperature (CCT), and the present combustion chamber temperature
(CCT) is stored.
OG200/400C 65
PROGRAM DESCRIPTION
At the end of next time interval new calculations are made with reference to stored and actual combustion
chamber temperature (CCT) and components adjusted again.
The control system will adjust the sludge dosage pump (SDP) to keep the combustion chamber temperature
(CCT) at “CCT max. for water injection”(1150°C). The maximum water dosage pump (WDP) RPM starts at
200/600 rpm and increases by “Increase RPM WDP” (5 rpm) every 60 second, until “Max. RPM WDP”
(600/1200) RPM is reached. Water dosage pump (WDP) RPM is controlled as a function of the combustion
chamber temperature (CCT), see illustration.
If combustion chamber temperature (CCT) drops below “CCT min. for water injection”(840°C), the water
dosage pump (WDP) stops.
WDP[RPM]
1200
1000
800
WDP[RPM]
600 WDP[RPM]
400
200
0
840 860 880 900 920 940 960 980 1000 1020 1040 1060 1080 1100 1120 1140 1150
CCT[°C]
66 OG200/400C
PROGRAM DESCRIPTION
Note: All references to settings and values are for explanation only. The values on your incinerator or
application may be different.
The program assumes a batch load of waste in the incinerator and will have initial speed and pressure set points
to facilitate enough combustion air to handle this (CCP=28 mmWC, burnerstep 1).
All checks of temperature are made in time interval. After each change in state or function, further adjustments
are not made until time interval has elapsed.
At the end of each time interval (40 sec), the change in combustion chamber temperature (CCT) is calculated.
Depending of temperature raise (or drop), adjustments are made, according to calculations, to components that
will influence the combustion chamber temperature (CCT), and the present combustion chamber temperature
(CCT) is stored.
At the end of next time interval new calculations are made with reference to stored and actual combustion
chamber temperature (CCT) and components adjusted again according to tabular below.
Delta CCT Delta step 1 Delta Delta Delta step Delta step
step 2 step 3 4 5
CCT < -1C°
STEP CCT -1 to + 3 to +10 to > +17C°
+3C° +10C° +17C°
> 1000C° P +1 0 -2 -4 -5
4 B 0 -1 -1 -1 -2
900 - 1000C° P +2 +1 0 -2 -2
3 B +1 0 -1 -1 -1
700 – 900C° P +4 +3 +2 0 -2
2 B +1 +1 +1 0 0
< 700C° P +8 +6 +4 +2 -1
1 B +1 +1 +1 +1 0
P = Combustion chamber pressure (-mmWC)
B = Burnerstep
Delta CCT = Temperature rise after 40 seconds.
The diesel oil burner heats up the incinerator. The burner starts and runs in 3 steps (burner step 1-3). Change in
burner steps are made in time intervals as described above.
When combustion chamber temperature (CCT) reaches set point 1000 °C, the diesel oil burner reduces one
step, and further increase in combustion chamber temperature (CCT), reduces burner to step 1.
At the end of time interval (see description above), corrections are made to combustion chamber pressure
(CCP), according to calculations involving a combination of actual temperature in combustion chamber (CCT)
and the temperature raise (or drop) since last correction.
Combustion chamber pressure is also controlled by the flue gas temperature (FGT). At flue gas temperature
(FGT) above set point (330 °C), the control system overrides calculations made in time interval (as described
above).
OG200/400C 67
PROGRAM DESCRIPTION
68 OG200/400C
MAINTENANCE INSTRUCTION
Maintenance instruction
Preventive maintenance
Preventive maintenance periods are defined in the
control system apart from the daily checks. The
control system counts the running hours of the diesel
oil burner. Each group is connected to a list of service
points required to perform. The preventive
maintenance is divided into four groups: Weekly,
monthly, 6 monthly and yearly. Based on experience
the intervals correspond to respectively 100h, 400h,
2500h and 5000h programmed with a service interval
“Hours service”. 6 monthly and yearly service is also
triggered by standby time on the incinerator. When
the actual running hours since last performed
maintenance exceeds the service interval the control
system calls for service by a pop up screen.
6 months and yearly service banner will appear, regardless of running hours, when 180/365 days has elapsed.
It is then required to follow the appropriate procedure. When the maintenance has been carried out press
“Done” and “Hours since last service” is reset. If not logged in as user “usr”, values on different setup screens
are “view only”. Also the “Done” buttons are only visible if user “usr” has logged in.
Service hours:
When “Hours since last service” is above
setting “Hours service”, a red banner is
activated in line for the item. By pressing
“Done”, the hour counter “Hours since
last service” is reset to 0 and the red
banner is turned off.
Daily
1. Inspect the combustion chamber. Remove all ash and slag before loading and starting the incinerator.
2. NOTE: The combustion chamber air inlets in the bottom must always be cleaned.
3. Check diesel oil pressure. Normal reading 16 bar.
3. Visually inspect the flue gas outlet for deposits, clean if necessary.
OG200/400C 69
MAINTENANCE INSTRUCTION
3. Clean diesel oil burner, blast tube flame scrod and ignition electrodes.
4. Dismantle, clean and adjust sludge oil burner.
5. Dismantle, clean and adjust water injection nozzle19.
6. Check spark arrester (if installed) and clean if necessary.
2. Replace the rubber stator on sludge oil dosage pump and check the rotor for wear. It should have a
smooth polished surface.
3. Grease the flue gas fan bearings.
4. Check the ventilation on the Flue Gas Fan frequency inverter20.
5. Visually check the thermocouple for combustion chamber.
6. Lubricate the sluice bearings (if incinerator has sluice). See Sluice Assembly drawing.
7. Lubricate door hinges and check the door gaskets for proper sealing. Use chalk on the edges of the
door opening. Close the door. Open and check that the door gasket had contact with the edge all the
way around the opening. If not adjust the door.
8. Open the inspection hatches on the lower side of the incinerator cooling panel. Clean as required with
steam or hot water.
19
If water injection is installed
20
If frequency controlled flue gas fan is installed
21
If water injection is installed
70 OG200/400C
MAINTENANCE INSTRUCTION
Inspection
ITEM ACTION
Monthly check: Check the fan belts for sufficient tightness. Correct
Flue gas fan:
deflection is 10 mm using a force of approx. 3 kg. weight load.
Weekly check: Check visually for leakage. Turn the shaft by hand to check
Sludge dosage pump:
it is moving freely.
Weekly check: Check visually for leakage. Turn the shaft by hand to check
Water dosage pump22:
it is moving freely.
22
If water injection is installed
OG200/400C 71
MAINTENANCE INSTRUCTION
ITEM ACTION
The slag must be removed daily before starting up the incinerator. Make
Ashes: sure that trash has been incinerated completely and that the fire is dead
and ashes cold. Use a hoe for this purpose.
Caution: The main switch must be in OFF position whenever working with
the burner.
For dismantling and re-assembly, see Appendix C. The blast tube, flame
Diesel oil burner: scrod and diesel nozzle should be cleaned every month. This can be
cleaned with Kerosene, White Spirit or Marine Diesel Oil and a brush. The
electrodes should be wiped off with a cloth dipped in one of the above
mentioned agents.
The filter must be cleaned every 6 month. For dismantling and re-
Diesel oil pump:
assembly, see Appendix D.
The grease in the bearings must be changed every six months. Make sure
the bearings are clean before they are re-greased. Pay special attention to
reinstalling of the top half of the housing to its respective base after re-
Flue gas fan:
greasing. The top halves must not be mixed, each top half is made unique
to the base.
Also check the tension of the V-belts.
Door hinges to be greased every six months. Use ordinary ball bearing
Door hinges:
grease.
The sluice bearings must be lubricated every month. Use a graphite grease
type Esso Beacon Q2 or equal.
Sluice: Unscrew the blinding plug and lubricate the nipple. Replace the plug. Also
lubricate the bearing on the opposite side by lubricating the nipple through
the expanded metal.
Lubricate the bearings for the pusher with a grease gun every 6-month.
Pusher:
Use heat resistant type (Esso Beacon EP2 or equal).
23
If water injection is installed
72 OG200/400C
MAINTENANCE INSTRUCTION
OG200/400C 73
MAINTENANCE INSTRUCTION
For re-lubrication of the bearings, the caps must be demounted. The housing base and cap are
matched during manufacture and are not interchangeable. To prevent mixing, the same
consecutive number is marked on the cap and base of each individual housing.
The bearings are mounted with an adaptor sleeve. The bearings have a small internal clearance
and an accurate mounting is very important. When the bearing is properly mounted, the outer
ring can be easily turned, but there should be a slight resistance when the ring is swivelled out.
When mounting a new bearing to the fan’s shaft, the following procedure should be followed:
Before mounting the threads of the nut and the side face of the nut witch is about the bearing
should be greased and the outside diameter of the sleeve should be lightly oiled. The bearing is
then pushed on to the sleeve and the nut screwed on by hand. Check that the bearing is correctly
located on the shaft. Use a hook spanner and turn the nut an angle of 90°. By turning the nut
through this given angle of 90° the bearing will be pressed up on the tapered seating of the
sleeve. Re-position the hook spanner and apply a light hammer blow to the spanner. The bearing
will straighten up on its seating and is correctly fastened to the shaft. Lock the nut but bending
down one of the tabs on the locking washer. The residual clearance of the bearing should be
checked.
74 OG200/400C
SPARE PARTS
Spare parts
Recommended minimum spare parts
24
1 pcs if no water injection.
OG200/400C 75
SPARE PARTS
Name / Article One year wear and tear parts, OG200/400C/CI, TG5 / Art.No.18232/18377
25
1 pcs if no water injection
26
1 pcs if no water injection
27
2 pcs if no water injection
28
1 pcs if no water injection
29
1 pcs if no water injection
76 OG200/400C
SPARE PARTS
30
1 pcs if no water injection
31
1 pcs if no water injection
32
1 pcs if no water injection
OG200/400C 77
STORAGE AND INSTALLATION
Once a month, check visually that the Control Panels are not damaged. Special attention must be paid to the
silica gel inside the panels. If there has been humidity in the panel, the Silica Gel must be replaced.
Check that the coating of the steel work is OK. If the coating is damage and the steel is exposed to the
atmosphere, it must be touched up with new paint according to paint spec.
Monthly the fan, pumps and electrical motors must be rotated.
The equipment is delivered with plastic sheet, the plastic sheeting does not offer protection against hot work.
If the incinerator is exposed to high humidity for a period of time, silica gel must be placed inside the control
panel.
78 OG200/400C
STORAGE AND INSTALLATION
Pre-commissioning
Mechanical completion check list.
Prior to function testing at first start up, the following mechanical completion must be checked.
1. Check that the foundation support and the deck strength are adequate for the incinerator unit. (5. ton)
2. Check that flue gas fan foundation is of a sturdy design for fan to run without vibration.
3. Check that the air inlet to the incinerator room has sufficient capacity.
4. Check that the necessary drainpipe are installed and connected.
5. Check that the incinerator door can be fully opened and locked in the installed locking mechanism.
6. Check that the insulation, flue gas duct and flue gas fan is installed and fixed.
7. Check that the flue gas duct is not welded direct into painted wall penetration. (fire hazard)
8. Check that the refractory brickwork has been dried out with a portable heater for 48 hours at
approximately 100°C.
9. Check the diesel oil line for correct hook up, and make sure that no valve is closed on the return line.
(A blocked return line will result in a leak in the diesel oil pump shaft seal)
10. Check the electrical power supply for correct rated protection at the ship distribution board.
11. Check that all pipes (sludge, steam and water) ducts and cables hooked up have been correctly
completed according to arrangement drawings.
12. Check that the “Burn In” program has been run for 10 hours. The “Burn In” program starts with a
combustion chamber temperature at 300°C and runs for 10 hours. The Burn In Program is available
from the set up menu in the operator panel when logged in as user.
Pre-check of live equipment.
Prior to function test, the following live equipment should be tested.
1. Start the flue gas fan and check for correct rotation direction.
2. Start the diesel oil burner and check for correct rotation direction, and that normal diesel oil pressure
is reached.
3. Check that the operator control panel is live, and indicating normal.
4. Make sure that sludge is filled in the sludge tank to a level above the low level switch before starting
the pump. Start the sludge pump and check for correct rotation direction, and normal pressure
indication.
5. Make sure that water is filled in the water tank to a level above the low level switch.
After having checked out the above items, a function test according to this manual can take place
OG200/400C 79
STORAGE AND INSTALLATION
Flame failure
2) FLUE GAS TEMP. HIGH At flue gas temperature above alarm set point,
Adjust alarm set point the alarm will activate and the burner stops.
[Alarm max. FGT]
below operating temp.
5) MOTOR OVERLOAD The motor stops, the alarm will activate and the
Activate test button at front of the burner stops.
motor circuit breaker.
80 OG200/400C
STORAGE AND INSTALLATION
8) DIESEL OIL TEMP HIGH At release of safety thermostat-S3 the alarm will
Start a burner program. Adjust activate and the burner stops
down the safety thermostat -S3 to The safety thermostat require manual reset.
below set point for working
thermostat -S4.
9) DIESEL OIL TEMP LOW At start of heating the alarm activates and the
Adjust alarm set point burner stops.
[Alarm max. time dieselheater start]
to "0".
Start a burner program.
10) DIESEL OIL PRESSURE LOW At pressure switch +2-S1 set point, the alarm
Start a burner program. Reduce the activates and the burner stops.
fuel oil pressure by adjusting the
pump.
OG200/400C 81
STORAGE AND INSTALLATION
12) STEAM/AIR PRESSURE SLUDGE After 10 sec. alarm activates and the burner
LOW stops.
Adjust the steam/air pressure sludge
alarm switch to 1.5 bar.
13) STEAM/AIR PRESSURE SLUDGE After 10 sec. alarm activates and the burner
HIGH stops.
Adjust the steam/air pressure high
sludge alarm switch to 4.5 bar.
Start a sludge program.
Close test valve steam/air supply.
When running sludge, close off
steam-air supply. Steam/air press. - sludge high
14) SLUDGE PRESSURE LOW After 10 sec. alarm activates and the burner
Adjust the sludge pressure low stops.
alarm switch to 0.1 bar.
15) SLUDGE TEMP LOW Alarm activates and the burner stops.
Start a sludge program. Adjust set
point
[Min. sludge temp run sludge]
above actual temperature and
adjust [Alarm sludge temp low] to 0.
82 OG200/400C
STORAGE AND INSTALLATION
16) SLUDGE TEMP HIGH Alarm activates and the burner stops.
Start a sludge program.
Adjust set point
[Min. sludge temp run sludge]
below actual temperature and
adjust [Alarm sludge temp high] to 0.
17) STEAM/AIR PRESSURE WATER After 15 sec. alarm activates and the burner
LOW/HIGH33 stops.
Adjust the steam/air water pressure
low alarm switch to 1,5 bar.
18) FREQUENCY INVERTER FAILURE After 10 second delay, alarm activates and the
SDP burner stops.
19) FREQUENCY INVERTER FAILURE After 10 second delay, alarm activates and the
WDP34 burner stops.
20) FREQUENCY INVERTER FAILURE After 10 second delay, alarm activates and the
FGF35 burner stops.
33
If water injection is installed
34
If water injection is installed
35
If frequency controlled FGF is installed
OG200/400C 83
STORAGE AND INSTALLATION
21) SLUDGE SERVICE TANK TEMP Alarm activates and the burner stops.
HIGH36
Start a sludge program Adjust down
safety thermostat +3.1-S1 below
operating temperature. The safety thermostat requires manual reset.
22) LOW LEVEL SLUDGE SERVICE After 5 sec. delay the Alarm/Warning activates
TANK and burner stops
23) CIRCUIT FAILURE FGT Alarm activates and the burner stops.
Disconnect wire terminal
+1–X1-114
24) CIRCUIT FAILURE CCT Alarm activates and the burner stops.
Disconnect wire from U2 terminal 4
25) CIRCUIT FAILURE SDP TEMP Alarm activates and the burner stops.
Disconnect wire from U3 terminal 4
36
Only available if El.heater installed
84 OG200/400C
STORAGE AND INSTALLATION
26) COMMUNICATION FAILURE PLC- Alarm activates after 40 sec. and the burner
DISPLAY stops.
Disconnect cable between A1 and
A2
OG200/400C 85
STORAGE AND INSTALLATION
37
Display is text at main menu
86 OG200/400C
STORAGE AND INSTALLATION
OG200/400C 87
STORAGE AND INSTALLATION
88 OG200/400C
STORAGE AND INSTALLATION
14. ALARM IN SYSTEM Start a program when there is Not possible to start
incinerator is in Alarm state. program – Alarm is active –
please check Alarms
15. CLEANING OF WATER 1. After testing is completed
INJECTION SYSTEM with water injection,
system must be
preservated with diesel oil.
2. If system has water
booster pump, attach
diesel hose to both inlet
and return on the booster
pump.
OG200/400C 89
STORAGE AND INSTALLATION
90 OG200/400C
STORAGE AND INSTALLATION
OG200/400C 91
OPERATION INSTRUCTIONS
Operation instructions
Prior to start
1. Main switch on the control panel is switched to position "ON" .The operator panel is
energised and the Process picture will show in the display.
Slagging
1. Check that there are no flames in the incinerator.
2. Push the "SLAG" key, the flue gas fan will run at a fixed speed when the temperature is
below 170°C (+50 hysteresis).
3. Open the ash door and remove ashes and slag, partly burned cans, can remain. These will
burn out eventually.
NOTE! Combustion air inlet openings at "floor" level must be cleaned.
This is important for a free airflow to the combustion chamber.
Solid Waste
1. Fill the combustion chamber half full with waste (max 400l)
NOTE: The Solid waste program start up sequence assumes a batch load. If the incinerator
is to be heated up without a batch load, choose the sludge program.
2. Close the door.
3. Push the key "START" and choose "SOLID WASTE" from the menu. The flue gas fan will
start and automatically control the pressure in the chamber. If there are conditions not met
required for starting the incinerator, the operator panel will display a message explaining the
condition.
4. When the key "STOP" is pushed, the burner will stop, and the cooling down sequence starts.
5. When the temperature in the combustion chamber has decreased to 170°C, the flue gas fan
will stop and door locks energized.
Sludge
1. Fill up the sludge tank and activate the heater. This is done by the pressing the heater
symbol on the operator panel. Choose start heater and the heater symbol will change colour
to indicate that the heater is on and the temperature is controlled locally by the thermostat
2. Drain off water from the settling tank. (The sludge should be settled overnight before water
is drained off) . Remember, longer settling time, better settling!
3. Start the filling pump by pressing the pump symbol and choose start pump. The symbol will
change colour to green to indicate that the pump is running. The pump will stop
automatically if the service tank level is high or the settling tank level is low.
4. Start the service tank circulation pump by pressing the pump symbol and choose start pump.
The symbol will change colour to green to indicate that the pump is running. Check the
sludge pressure on the pressure indicator to be in the range of 0.2 bar, adjust if required,
using the by pass valve. Run the circulation pump for at least 1 hour prior to burning sludge!
5. Check the atomising -air /-steam supply pressure to be 6 - 8 bar. If steam is used, the
condensate must be drained off by use of the valve located at sludge equipment drip tray.
6. Push the key "START" and choose "SLUDGE" from the menu. The flue gas fan will start
and automatically control the pressure in the chamber. If there are conditions not met
92 OG200/400C
OPERATION INSTRUCTIONS
required for starting the incinerator, the operator panel will display a message explaining the
condition.
7. The manual regulating valve for air / steam atomising located at sludge equipment drip tray
should be from ¾ to 1 turn open. The pressure should be shown in the upper half of the
green area (3.3 bar or 48 PSI) when the sludge burner/nozzle is clean. If pressure rises, do
NOT adjust the valve, but clean the sludge burner.
8. When the low level in sludge tank, or the key "STOP" is pushed, the burner will stop, and
the cooling down sequence starts.
9. When the temperature in the combustion chamber has decreased to 170°C the flue gas fan
will stop and door locks will be energized.
OG200/400C 93
OPERATION INSTRUCTIONS
Emergency stop
In the incinerator room.
Turn the main switch at the control panel "OFF".
94 OG200/400C
TROUBLE SHOOTING
OG200/400C 95
TROUBLE SHOOTING
Trouble shooting
1. OPERATOR PANEL 1. Faulty main power supply. Check main switch -Q1
DEAD. Check power supply from main
switchboard.
2. Emergency stop switch Check switch -S1.
open.
3. Faulty fuse for pilot Check fuses –F11 and –F12
transformer.
4. Faulty fuse -F13. Check fuse.
5. Temperature raising 1. Loaded too much waste Stop loading, and tray to block
"uncontrolled" with high calorific value. lower four corner ventilation
slots.
2. Damaged sludge dosing Change stator.
pump stator.
3. Sludge speed control not Check sludge speed.
working.
4. Leaking diesel oil solenoid Change the valve.
valve.
96 OG200/400C
TROUBLE SHOOTING
10. DRAUGHT FAILURE 1. Leaking sensor tube. Check sensor tube for damage
(low under pressure) and fixing.
2. Defect pressure sensor Check and replace, DO NOT
ADJUST.
3. Door gasket damaged. Check door gasket
4. Broken flue gas fan belts. Tighten or replace.
5. Flue gas fan motor Check direction
running in wrong
direction.
OG200/400C 97
TROUBLE SHOOTING
98 OG200/400C
TROUBLE SHOOTING
OG200/400C 99
APPENDIX A
Appendix A: PLC
General
The Standard PLC contain of 4 units. See Figure 11 and 12.
1 2 3 4
Figure 11
100 OG200/400C
APPENDIX A
Base Unit
Figure 12
OG200/400C 101
APPENDIX A
2. Align the connector on the memory module with the connector pins on the controller.
102 OG200/400C
APPENDIX A
OG200/400C 103
APPENDIX A
Dimension:
A – 90mm (3.5 in.)
B – 27.5mm (1.08 in.)
C – 27.5mm (1.08 in.)
104 OG200/400C
APPENDIX A
Diagnostics
OG200/400C 105
APPENDIX A
106 OG200/400C
APPENDIX A
Error Conditions
OG200/400C 107
APPENDIX B
Touch screen
Figure 14.
See also chapter Operator Panel, page 21, for user functions.
108 OG200/400C
APPENDIX B
Technical data
COMM and
FAULT LEDs
The operator panel is a RS-232 only display with 1 USB port, and consist of a colour
(320X240) graphics display. Colour terminals support a fixed palette of 32 standard EGA
colours. All colours in an application is defined when the application is created, and not
selectable at the terminal.
The compact flash slot is used to program the display. Normally this will be done by TeamTec
personnel.
The operator panel is connected to the PLC with RS-232 serial communication.
The terminal requires 24VDC.
Reset Button resets the terminal.
Display temperature should be less than 55°C. The CPU temperature should be less than 95°C.
The terminal has two LED indicators isolate operating problems:
COMM indicator (green) for communications
FAULT indicatior (red) for hardware faults
Product certification compliance with European Union Directives. EMC tests satisfies EN
50081-1-2:1993 and EN 61000-6-2:1999
OG200/400C 109
APPENDIX C
Nozzle 2
Nozzle 1
Re-assembly Sludge burner
Reassemble the burner in reverse order. Figure 1
110 OG200/400C
APPENDIX C
Air adjustment
The Burner damper motor is analogue, and will open the damper proportionally to the control voltage applied
by the control system. The only two checks necessary is Closed position and that it operates freely.
To check that the damper is closed make sure that the damper blade is vertical to the opening when the control
system shows 0% opening (after power up, flue gas fan not running).
To check that the damper operates freely, wind up the actuator by using a 4mm hex key on the top of the
damper motor, then release and observe that the damper closed by the spring action.
DO nozzles
Standard nozzle
For special cases other nozzles can be used.
Maintenance
Burner nozzle cannot be repaired.
OG200/400C 111
APPENDIX C
Capacities
G.P.H. l/h 10 11 12 13 14 15 16
38
Sp gr 0,85 @ 25C and viscosity 1,3E @ 20°C
39
Pressure = 100 P.S.I.
112 OG200/400C
APPENDIX C
OG200/400C 113
APPENDIX D
Applications
Light and medium oil
Nozzle flow up to 110 l/h (2850 rpm, 5 cSt, 10 bar)
Normally associated with in-line solenoid valve.
One or two-pipe system
Bleed Figure 2
Figure 3
114 OG200/400C
APPENDIX D
Technical data
General
Mounting Flange according to DIN 24220
Connection:
Inlet 1/4" NPTF
Return 1/4 " NPTF
Nozzle outlet 1/8" NPTF
Pressure gauge port 1/8" NPSF
Vacuum gauge port ¼" NPTF
Valve function Pressure regulating cut-off.
Strainer 45 cm² open area 120 opening size.
Shaft 11 mm according to DIN 24220
By-pass plug Inserted for 2 pipe system. To be removed with
3/16" allen key for 1 pipe system.
Weight 4 kg
Rotation Anti-clockwise rotation. Left hand nozzle.
(seen from shaft end).
Hydraulic data
Nozzle pressure range. 10 to 21 bar.
Delivery pressure setting. 16 bar
Viscosity range. 2.8 to 200 cSt
Inlet and return pressure. 1.5 bar max.
Suction height. 0.45 bar max. vacuum to prevent air separation
from oil.
Rated speed. 3600 rpm max.
Oil temperature. Max. 90°C in the pump.
Starting torque. 0.4 N.m
Figure 4 Figure 5
OG200/400C 115
APPENDIX D
Pump dimensions
Pipe dimensions
The tables below give the maximum length (in meters) of suction line as function of 3 variables:
Q (l/h) 150
d (mm)
H (m) 10 12 14 16
0 11 24 46 80
0.5 12 27 51 90
1 14 30 57 99
2 17 36 68 118
3 20 42 79 136
4 22 48 90 155
Q (l/h) 150
d (mm)
H (m) 10 12 14 16
0 11 24 46 80
0.5 9 21 41 71
1 8 18 35 61
2 5 12 24 42
3 2 6 13 24
4 0 0 2 5
Installation
The pump is ready for use with 2 pipe systems (i.e. with by-
pass plug fitted, in the return port.)
Figure 6 The inlet and return pressures must not exceed 1.5 bar.
The vacuum must not be more than 0.45 bar to prevent air
116 OG200/400C
APPENDIX D
Start up
Check that the sense of rotation for pump and motor are the same (an arrow is stamped on the pump body).
In order to purge pumps used on 1 pipe systems, loosen one of the high pressure connections. On 2 pipe
systems, purging is automatic.
Pressure regulation
Remove end cap nut from pump for access to pressure stetting screw. Turning the regulator screw clockwise
increases the pressure.
Systematic maintenance
1. Check the stop valve and in line filters.
2. Check the pump filter.
This filter should be cleaned with a soft brush and fuel oil.
Each time, the cover gasket should be changed.
3. Check the tightness of all couplings and unused plugs.
4. Check the shaft coupling.
5. Check the pump pressure.
Fit a pressure gauge in the fitting provided and run the pump in normal manner.
If the pressure required cannot be obtained, check that the pump is completely purged. If air
bubbles are found in the fuel, check all connections for tightness.
6. Check the pump vacuum.
Fit a vacuum gauge in fitting provided and run the pump in the normal manner, making sure
to fully purge the pump.
The vacuum should not exceed 0.45 bar. If this is the case, check condition of all
components (non return valve, stop valves, filters....).
If the pump does not suck correctly, check for any leaks in the line by retightening all
fittings.
OG200/400C 117
APPENDIX D
Figure 7
Parts list
Pos. no. Description Article no.
118 OG200/400C
APPENDIX D
OG200/400C 119
APPENDIX E
40
Line current: Typical value without additional inductance.
41
Transient current: for 60seconds
120 OG200/400C
APPENDIX E
Technical characteristics
Degree of protection IP 20 without protective vent cover. IP31 other areas.
Vibration and shock 1 gn from 13 to 150 Hz, 15 g for 11 ms
resistance
(EN60068)
Degree of pollution Degree 2 according to UL840. Protect the drive against dust,
corrosive gases, and falling liquid.
Relative maximum 96% without condensation or dripping water (if there is a risk
humidity of condensation provide a heating system).
Ambient air temp. in Operating: -10°C to +60°C (with vent cover removed)
acc. with EN50178 Storage: -25°C to +70°C
Maximum operating 1000 m. without derating. Above this, derate the current by
altitude 1% for each additional 100 m.
Output voltage Maximum voltage equal to mains voltage.
Frequency range 0 Hz to 500 Hz.
Maximum transient 150% of nominal drive controller current for 60 seconds
current
Breaking torque 100% of the nominal motor torque without break resistor
(typical value). Up to 150 % with braking resistor as an
option.
Frequency - Display: 0.1 Hz
resolution - Analog inputs: 0.1 Hz for 100 Hz maximum
Switching frequency Can be adjusted from 2.0 to 16 kHz
Speed controller - Galvanic isolation between power and control circuits
protection and (inputs,
safety outputs, supplies)
- Protection against short-circuits:
within internal power supplies
between output phases
between the output phases and earth
- Protection against input phase loss
- Thermal protection from excessive overheating and
overcurrents
- Under and overvoltage supply
- Overvoltage safe on braking
Motor protection Thermal protection integrated into the drive controller by
calculating I²t. Protection against motor phase loss.
OG200/400C 121
APPENDIX E
Control
terminals
Power
terminals
Figure 31
Power Terminals
The power terminals must be connected before connecting the control terminals!
Figure 32
122 OG200/400C
APPENDIX E
Control Terminals
Figure 33
OG200/400C 123
APPENDIX E
Programming
124 OG200/400C
APPENDIX E
OG200/400C 125
APPENDIX E
126 OG200/400C
APPENDIX E
OG200/400C 127
APPENDIX E
128 OG200/400C
APPENDIX E
OG200/400C 129
APPENDIX E
130 OG200/400C
APPENDIX E
The Assignment of the “Fast stop” or “Freewheel stop” functions will prevent the drive from starting
if the corresponding logic inputs are nor powered up. The ATV12 then displays “nSt” in freewheeel
stop mode and “FSt” in stop mode. This is normal since these functions are active at zero so that the
drive will be stopped safely if there is a wire break.
Check that the run command input(s) have been actuated in accordance with the chosen control mode
(tCC parameter in the I-O menu).
If an input is assigned to the limit switch function and this input is zero, the drive can only be started
up by sending a command for the opposite direction, see ATV 12 programming manual.
If the LED on the DC bus is lit and nothing appears on the display, check that there is no short-circuit
on the 24 V power supply.
If the drive displays “rdY” and refuses to start, check that there is not short circuit on the 24 V power
supply and check the wiring of input AI1 and LI1.
OG200/400C 131
APPENDIX E
132 OG200/400C
APPENDIX E
OG200/400C 133
APPENDIX E
134 OG200/400C
APPENDIX E
OG200/400C 135
APPENDIX F
Weight 22 kg
Figure 34
42
Only for incinerators with frequency controlled flue gas fan
43
Line current: Typical value without additional inductance.
44
Transient current: for 60seconds
136 OG200/400C
APPENDIX F
Technical characteristics
Maximum operating 1000 m. without derating. Above this, derate the current by 1% for each
altitude additional 100 m.
Maximum transient
120% of nominal drive controller current for 60 seconds
current
30% of the nominal motor torque without braking resistor (typical value)
Breaking torque
Up to 130 % with braking resistor installed as an option,
- Display: 0.1 Hz
Frequency resolution
- Analog inputs: 0.024/50 Hz (11 bits)
Standards /
Certification / UL, CSA, DNV, C-Tick, NOM 117 and GOST
Recommendation
OG200/400C 137
APPENDIX F
Power cable
A standard power cable, 3 x 1,5 + E, from control panel to frequency inverter flue gas fan, ATV61, yard
supply. TeamTec recommend a cable type LM-HF 0,6/1 kV or similar type.
To access the power terminal on frequency inverter for flue gas fan, unlock the power part access flap and
remove it as shown below:
Arrangement of the power terminals:
Motor cable
From U/T1, V/T2 and W/T3 on frequency inverter flue gas fan to motor for flue gas fan, you must use a
shielded motor cable, yard supply. TeamTec recommend a cable type LSM-HF 0,6/1kV or similar type.
Shielded cable for motor connection with shielding connected to ground at both end. The shielding must be
continuous and intermediate terminals must be in EMC shielded metal boxes. Connect the shield to ground at
each end by using EMC Cable Gland. The frequency inverter cabinet is delivered with two EMC cable glands
with nut. M40 is to be used for motor cable. The shield is to be grounded on the EMC cable gland.
Ensure that an EMC-compliant cable gland is
provided at the motor. TeamTec recommend an
EMC Cable gland with nut, M40, IP68.
If using conduit, do not lay the motor, power supply and control cables in the same conduit. Keep the metal
conduits containing the power supply cables at least 8 cm (3 in.) away from the metal conduit containing the
control cables. Keep the non-metal conduits or cable ducts containing the power supply cables at least 30 cm
(12 in.) away from the metal conduits containing the control cables. If necessary for control and power cables
to cross each other, be sure they cross at right angles.
NOTE: EMC-filter, on frequency inverter flue gas fan, is not dimensioned for motor cable length over 15
meters. Depending on the cable lengths it may be necessary to use an output filter.
The motor cables must be at least 0,5 m (20 in.) in length.
138 OG200/400C
APPENDIX F
Figure 31
Power Terminals
Maximum connection 2
AWG 14 – 2,5 mm
capacity:
Tightening torque: 3.0 Nm
Figure 32
OG200/400C 139
APPENDIX F
Control Terminals
Figure 33
140 OG200/400C
APPENDIX F
OG200/400C 141
APPENDIX F
Programming:
142 OG200/400C
APPENDIX F
OG200/400C 143
APPENDIX F
144 OG200/400C
APPENDIX F
-U1
Menu 1.3 Settings
Flue gas fan
Acceleration 5.0 Sec
Deceleration 10.0 Sec
Low speed 10.0 Hz
High Speed 60 Hz
Mot. therm. current 15.2 A
Current limitation 15.2 A
-U1
Menu 1.4 Motor control
Flue gas fan
Standard mot. freq. 50 Hz
Rated mot. current 15.2 A
Max. frequency 60 Hz
Rated motor power * 7.5 kW
Rated motor voltage * 380V
Rated motor speed * 1455 rpm
Auto tuning Yes
* See motor plate
-U1
1.5 Inputs/outputs CFG
Flue gas fan
2 wire type Level
AI2 configuration AI2 min. value 4.0 mA
AO1 assignement I motor
AO1 conf. Ao1 min. value 4.0 mA
-U1
1.6 Command
Flue gas fan
Ref. 1 channel AI2 (enter two times)
Stop key priority No (press 2 sec.)
OG200/400C 145
APPENDIX F
146 OG200/400C
APPENDIX F
OG200/400C 147
APPENDIX F
148 OG200/400C
APPENDIX F
Faults that can be reset with the automatic restart function, after cause has
disappeared
These faults can also be reset by turning on and off or by means of a logic input or control bit ({Fault reset]
(rSF) parameter). APF, SnF, COF, EPF1, EPF2, FCF2, LFF2, LFF3, LFF4, nFF, ObF, OHF, OLC, OLF,
OPF1, OPF2, OSF, OtF1|, OtF2, OtFL, PHF, PtF1, PtF2, PtFL, SLF1, SLF2, SLF3, SPIF, SSF, tJF and ULF
faults can be inhibited and cleared remotely by means of a logic input or control bit ({Fault inhibit assign.]
(InH) parameter.
OG200/400C 149
APPENDIX F
Faults that can be reset with the automatic restart function, after the cause has
disappeared (continued)
150 OG200/400C
APPENDIX F
OG200/400C 151
APPENDIX G
Loosen setscrews (A), and nut (B) and pull out the external pipe (C).
Clean the external (C) and internal (D) pipes.
After cleaning, re-assemble the sludge burner in reverse order.
Check that internal pipe (D) is centred (concentric) in the external pipe (C), adjust with set-
screw (A) according to the adjustment procedure below.
152 OG200/400C
APPENDIX G
OG200/400C 153
APPENDIX H
Dimension
Weight:19,5 kg
Figure 34
154 OG200/400C
APPENDIX H
Figure 35
Figure 35
OG200/400C 155
APPENDIX H
156 OG200/400C
APPENDIX H
Installation
Installation and Safety Recommendations
In common with other items of process plant a pump must be installed correctly to ensure satisfactory and safe
operation. The pump must also be maintained to a suitable standard. Following these recommendations will
ensure that the safety of personnel and satisfactory operation of the pump is achieved.
General
When handling harmful or objectionable materials, adequate ventilation must be provided in order to disperse
dangerous concentrations of vapours. It is recommended that wherever possible pumps should be installed with
provision for adequate lighting, thus ensuring that effective maintenance can be carried out in satisfactory
conditions. With certain product materials, a hosing down facility with adequate draining will simplify
maintenance and prolong the life of pump components.
Storage
Short-term storage
Where a pump has to be stored for 6 months or less then the following steps are advised:
1. Store pump inside wherever possible or if this is not feasible then provide protective covering. Do
not allow moisture to collect around the pump.
2. Remove the drain plug, if fitted. Any inspection plates fitted should also be removed to ensure that the
suction housing could drain and dry completely.
3. Loosen the packing gland and inject sufficient grease into the stuffing box. Tighten the gland nut
hand tight. If a water flush system is to be used do not grease, a small amount of light oil is
recommended for these.
4. See Manufacturers instructions for motor/gearbox/drive instructions for storage procedures.
Long-term storage
If the pump is to be kept in storage for more than six months then in addition to the above the following
procedures should be carried out regularly (every 2 - 3 weeks if possible):
1. If practicable rotate the pump at least three quarters of one revolution to avoid the rotor setting in the
stator.
2. Note, however, that the pump is not to be rotated for more than two revolutions each time because
damage could be caused to the rotor/stator elements.
OG200/400C 157
APPENDIX H
Electrical
Electrical connection should only be made using equipment suitable for both rating and environment. Where
any doubts exist regarding the suitability of equipment, supplier should be consulted before proceeding.
Normally the pump should be installed with starting equipment arranged to give direct on line starting.
Earthing points will be provided on electric drives (if supplied) and it is essential that these are correctly
connected. When the motor is being wired and checked for rotation, the start/stop sequence must be
instantaneous to prevent dry running or pressurising upstream equipment. (Check direction arrow on pump
nameplate). The electrical installation should include appropriate isolating equipment to ensure that the pump
unit is safe to work on.
Important
The pump must never run against a closed inlet or outlet valve, as this could result in mechanical failure.
General safety
Great care must be taken to protect all electrical equipment from splashing when hosing down.
All nuts and bolts, securing flanges and base mounting fixtures must be checked for tightness before operation.
To eliminate vibration, the pump must be correctly aligned with the drive unit, and all guards must be securely
flexed in position. When commissioning the plant, all joints in the system must be checked thoroughly for
leakage.
If, when starting, the pump does not appear to operate correctly, the plant must be shut down immediately and
the cause of the malfunction established before operations are recommenced. It is recommended that
depending upon plant system operation, either a combined vacuum and pressure gauge, or a vacuum gauge
only be fitted to the pump inlet port, and a pressure gauge fitted to the outlet port, these will then continuously
monitor the pump operating conditions.
Start-up procedure
Pumps must be filled with liquid before starting. The initial filling is not for priming purposes, but to provide
the necessary lubrication of the stator until the pump primes itself. When the pump is stopped, sufficient liquid
will normally be trapped in the rotor/stator assembly to provide lubrication upon re-starting.
If, however, the pump has been left standing for an appreciable time, moved to a new location, or has been
dismantled and re-assembled, it must be refilled with liquid and given a few turns before starting. The pump is
normally somewhat stiff to turn by hand owing to the dose rotor/stator fit. However, this stiffness disappears
when the pump is running normally against pressure.
Dryrunning
Never run the pump in a dry condition even for a few revolutions, the stator will be
damaged immediately. Continual dry running could produce some harmful or
damaging effects.
158 OG200/400C
APPENDIX H
Guards
In the interests of safety, all guards must be replaced after necessary adjustments have been made to the pump.
Warning/control device
Prior to operating the pump, if any warning or control devices are fitted these must be set in accordance with
their specific instructions.
OG200/400C 159
APPENDIX H
Diagnostic chart
160 OG200/400C
APPENDIX H
OG200/400C 161
APPENDIX I
Figure 37
162 OG200/400C
APPENDIX I
Valve
Valve housing Brass
Cove Red brass
Repair kit for sludge valve article no. 12806 consist of:
Figure 38
OG200/400C 163
APPENDIX J
Technical data
Noise level
The maximum noise level is generally determined by the drive motors via air, magnet and bearing
noises. The system does not exceed the permissible limit curves for electric motors as specified by
VDE 0530 part 9/12.84. Lowest noise generation during operation is close to Q OPT
164 OG200/400C
APPENDIX J
Drawing
Figure 39
Parts list
OG200/400C 165
APPENDIX J
Commissioning
Before commissioning, the pump should be inspected and a functional check carried out. In
particular, the following points should be checked:
Is the motor circuit-breaker correctly set?
Are the valves required for operation open?
Checking the direction of rotation. (Looking at the motor fan, it should rotate in a
clockwise direction.)
CAUTION When commissioning, the pump and intake line should be vented and primed with
pumping liquid before starting up! The shut-off valve in the intake and discharge lines must be fully
open.
Maintenance
Maintenance instructions following a prolonged shutdown
Preserve the mechanical shaft seal with glycerine. To do so, squirt onto the motor shaft several
times through the leakage opening on the back panel.
NOTE Before switching on the pump after a prolonged shutdown, rotate the motor shaft several
times by hand on the fan.
7. Maintenance
166 OG200/400C
APPENDIX J
Clean the shaft from sediments and contamination by using very fine structured emery cloth. Check
all dismantled components for damage and renew defective parts.
Assembly
Before re-assembling
check all parts on damages and wear,
if necessary, replace by original spare parts,
clean the parts.
NOTE If the seal- or stationary ring of the seal is damaged, change the complete mechanical seal.
OG200/400C 167
APPENDIX J
NOTE To facilitate fitting, the outer faces of the O-ring can be moistened with a parting or anti-
friction agent such as for example water, glycerine or soap. CAUTION - do not use oil!
1. Stationary ring (c) with O-ring (d) press into the rear wall (3) by hand (first of all O-ring
then stationary ring).
CAUTION When pressing in the stationary ring (c), ensure that the pin safety (e)
device against twisting is fixed in the slot of the stationary ring.
2. Carefully push rear wall (3) along the motor shaft on to the centering of the motor.
CAUTION Do not damage the stationary ring on the thread or shoulder of the shaft or
push it crooked in its seating!
3. Bolt rear wall (3) and motor.
4. Push seal ring (a) with O-ring (b) carefully over the shoulder of the motor shaft along to the
fitted stationary ring.
CAUTION Ensure that the O-ring is not damaged!
5. Insert the shaft key (f) into the slot of shaft and seal ring (a).
6. Push impeller (2) onto the shaft and fasten it by the impeller nut (13).
7. Insert the rear wall (3) to the casing and fix it with the screws.
CAUTION Check free running of impeller (2) by turning fan!
8. Reconnect motor electrically! Ensure clockwise rotation (see item 5.7 Checking the
direction of rotation)
NOTE Start up pump unit (see Commissioning page 165)
168 OG200/400C
APPENDIX J
Performance curves
2880 rpm 50 Hz 3480 rpm 60 Hz
3,00
2,50
2,00
60Hz
Pressure [bar]
50Hz
1,50
1,00
60Hz
0,50 50Hz
0,00
0,00 5,00 10,00 15,00 20,00 25,00 Flow [m3/h] 30,00
OG200/400C 169
APPENDIX K
Dimension
Weight:19,5 kg
Figure 41
170 OG200/400C
APPENDIX K
Figure 42
Figure 35
OG200/400C 171
APPENDIX K
172 OG200/400C
APPENDIX K
Installation
Installation and Safety Recommendations
In common with other items of process plant a pump must be installed correctly to ensure satisfactory and safe
operation. The pump must also be maintained to a suitable standard. Following these recommendations will
ensure that the safety of personnel and satisfactory operation of the pump is achieved.
General
When handling harmful or objectionable materials, adequate ventilation must be provided in order to disperse
dangerous concentrations of vapours. It is recommended that wherever possible pumps should be installed with
provision for adequate lighting, thus ensuring that effective maintenance can be carried out in satisfactory
conditions. With certain product materials, a hosing down facility with adequate draining will simplify
maintenance and prolong the life of pump components.
Storage
Short-term storage
Where a pump has to be stored for 6 months or less then the following steps are advised:
1. Store pump inside wherever possible or if this is not feasible then provide protective covering. Do
not allow moisture to collect around the pump.
2. Remove the drain plug, if fitted. Any inspection plates fitted should also be removed to ensure that the
suction housing could drain and dry completely.
3. Loosen the packing gland and inject sufficient grease into the stuffing box. Tighten the gland nut
hand tight. If a water flush system is to be used do not grease, a small amount of light oil is
recommended for these.
4. See Manufacturers instructions for motor/gearbox/drive instructions for storage procedures.
Long-term storage
If the pump is to be kept in storage for more than six months then in addition to the above the following
procedures should be carried out regularly (every 2 - 3 weeks if possible):
1. If practicable rotate the pump at least three quarters of one revolution to avoid the rotor setting in the
stator.
2. Note, however, that the pump is not to be rotated for more than two revolutions each time because
damage could be caused to the rotor/stator elements.
OG200/400C 173
APPENDIX K
Electrical
Electrical connection should only be made using equipment suitable for both rating and environment. Where
any doubts exist regarding the suitability of equipment, supplier should be consulted before proceeding.
Normally the pump should be installed with starting equipment arranged to give direct on line starting.
Earthing points will be provided on electric drives (if supplied) and it is essential that these are correctly
connected. When the motor is being wired and checked for rotation, the start/stop sequence must be
instantaneous to prevent dry running or pressurising upstream equipment. (Check direction arrow on pump
nameplate). The electrical installation should include appropriate isolating equipment to ensure that the pump
unit is safe to work on.
Important
The pump must never run against a closed inlet or outlet valve, as this could result in mechanical failure.
General safety
Great care must be taken to protect all electrical equipment from splashing when hosing down.
All nuts and bolts, securing flanges and base mounting fixtures must be checked for tightness before operation.
To eliminate vibration, the pump must be correctly aligned with the drive unit, and all guards must be securely
flexed in position. When commissioning the plant, all joints in the system must be checked thoroughly for
leakage.
If, when starting, the pump does not appear to operate correctly, the plant must be shut down immediately and
the cause of the malfunction established before operations are recommenced. It is recommended that
depending upon plant system operation, either a combined vacuum and pressure gauge, or a vacuum gauge
only be fitted to the pump inlet port, and a pressure gauge fitted to the outlet port, these will then continuously
monitor the pump operating conditions.
Start-up procedure
Pumps must be filled with liquid before starting. The initial filling is not for priming purposes, but to provide
the necessary lubrication of the stator until the pump primes itself. When the pump is stopped, sufficient liquid
will normally be trapped in the rotor/stator assembly to provide lubrication upon re-starting.
If, however, the pump has been left standing for an appreciable time, moved to a new location, or has been
dismantled and re-assembled, it must be refilled with liquid and given a few turns before starting. The pump is
normally somewhat stiff to turn by hand owing to the dose rotor/stator fit. However, this stiffness disappears
when the pump is running normally against pressure.
Dry running
Never run the pump in a dry condition even for a few revolutions, the stator will be
damaged immediately. Continual dry running could produce some harmful or damaging
effects.
174 OG200/400C
APPENDIX K
Guards
In the interests of safety, all guards must be replaced after necessary adjustments have been made to the pump.
Warning/control device
Prior to operating the pump, if any warning or control devices are fitted these must be set in accordance with
their specific instructions.
OG200/400C 175
APPENDIX K
Diagnostic chart
176 OG200/400C
APPENDIX K
OG200/400C 177
DRAWINGS
DRAWINGS
178 DRAWINGS
List of drawings
Project: K1704
Incinerator
Dwg.no. Rev. Name of drawing.
2009245 B P&ID OG400CI/CIS, Steam H. DO tank, therm loose
1009048 B Main Dimensions OG200/400CIS
1010109 Combustion Chamber Assy. 200/400CIS with water flow meter
1008973 B Combustion Chamber Mounting Drawing OG200/400C
1008073 A Oil Burner F-50-45-T, OG200/400C
1007868 B Oil Burner F-50-45-T, Sub Assy. w/ Three-Way Test.
1008970 B Refractory and Insulation OG200/400C
1009273 Sludge Oil Dosage Valve Assembly, OG200/400C.
1009038 D Door Assy. CO 1310x510 with Sluice
2008096 D Steam Inlet Assembly w/Dual Valve w/Three-Way Test Cock
2008097 B Sludge Inlet Assembly
3010169 Sounding Cock
Flue gas
Dwg. no. Rev. Name of drawing.
4006931 C Main Dimensions Flue Gas Fan DN 350 H2
1007664 A Flue Gas Fan Assy. DN 350, w/ Pl and Insul. H2, 60 Hz
1006993 B Flue Gas Fan Assy. DN 350, H2, 60Hz
3007250 E Flue Gas Damper DN 400/350
1007001 B Flue Gas Damper DN 400/350
1007000 Flue Gas Damper, Sub. Assy. DN 400/350
14653 Expansion Compensator DN 350, L=400
Sludge Tank
Dwg. no. Rev. Name of drawing.
1010147 Main Dimensions Waste Oil Service Tank 1100L Net.
1010149 A Sludge Tank Assy. 1100L Steam Heating w/Level Gauge/Sounding
Electrical diagrams
Dwg. no. Rev. Name of drawing.
4008939 Cable Arrangement OG200/400CAI, 380/440V - 220V, Flowmeter
1010120 Control Panel OG200/400CAI, 380/440V - 220V, Flowmeter
1010121 Mounting Plate OG200/400CAI, 380/440V - 220V, Flowmeter
3010574 Electrical Diagram, OG200/400CAI, 380/440V - 220V, Flowmeter
4007918 A Terminal Diagram Diesel Oil Burner F-50-45-T with Analog Motor
2006948 C Control Panel 380/440V-220V, Sl.Tank w/Steam Heater
2006949 B Mounting Plate w/El.Components Sludge Tank w/Steam Heating
3007895 E Electric Diagram Sludge Tank w/Steam Heating
3006996 G Thermocouple with Transmitter for Flue Gas
2008535 Control Panel, Water injection St.heat 380/440V-220V
4008419 A Cable Arr. Water Tank w/Steam Heating, 380/440V - 220V
2008536 A Mounting Plate, Water injection St.heat 380/440V-220V
3009866 C El. Diagram Water Tank w/Steam Heating, 380/440V - 220V
3009835 Junction Box for High- & Low Level Switch Diesel Oil Tank
4006721 C Terminal Diagram Diesel Oil Tank w/High and Low Level Switch
4006619 A Emergency Stop Switch