Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

EM1000/EM1200 Energy Meter: Va Va1 Va2 Va3 W W1 W2 W3

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

EM1000/EM1200 Energy Meter

The energy meter ships in two different configurations.


Table 1: Energy meter models and parameters

EM1000 EM1200

VA VA1 VA2 VA3

W W1 W2 W3

VAR VAR1 VAR2 VAR3

PF PF1 PF2 PF3

kVAh

kWh

kVARh

Run.h

On.h

INTR
S1 1 2 S2 S1 3 4 S2 S1 5 6 S2
A1 A2 A3 7

D0
D1

50mA to 6A

DANGER SHOCK HAZARD

DANGER SHOCK HAZARD


AccX.X
S/N:XXXXXX/XXXXXX-XXXX Acc Cl: Cl: X.X RS 485 terminals for EM1200 energy meters

RS 485
VER:XX.XX.XX ITEM CODE: XXXXXXXX
Or
80 to 480
480 Vac
Vac LL
LL 44 to 277 Vac 50/60Hz
50/60Hz << 3VA
3VA POP terminals for EM1000 energy meters
Class 0.5 Accuracy V1 V2 V3 VN L N D0

D1
8 9 10 11 12 13 14

Class 1.0 Accuracy

NOTE: = Standard = Option specified while ordering

One (1) EM1000/EM1200 digital meter.


One (1) quick start guide (QSG).
One (1) test and calibration certificate for the energy meter.

90.0
System type Meter configuration Figure number
3.54

Star/Wye StAr 6
Delta, open delta dLtA 7, 8 S1 1 A1 2 S2 S1 3 A2 4 S2 S1 5
A3 6 S2
D1
7

50mA to 6A

2-phase 2 ph 9 Acc Cl: X.X

RS 485
Single-phase 1 ph 10 80 to 480 Vac LL 44 to 277 Vac 50/60Hz < 3VA
L N D0
8 V1 9 V2 10 V3 11 VN 12 13 14

80.0
3.15

8.00
0.31

< 5 mm. The Diameter ³ 5 mm will get stuck in the cover.

90° 90°

Figure 6: 3-phase 4-wire star/wye connection

S1 1 2 S2 S1 3 4 S2 S1 5 6 S2
A1 A2 A3 D1
7

50mA to 6A
Acc Cl: X.X

RS 485
1 2 3 S1 1 A1
50mA to 6A
2 S2 S1 3 A2 4 S2 S1 5
A3 6 S2
D1
7
80 to 480 Vac LL

V1 V2 V3 VN
44 to 277 Vac 50/60Hz < 3VA
L N D0
8 9 10 11 12 13 14
Acc Cl: X.X

RS 485
80 to 480 Vac LL 44 to 277 Vac 50/60Hz < 3VA
L N D0
8 V1 9 V2 10 V3 11 VN 12 13 14
Figure 9: 2-phase 3-wire connection Keys and Operation PROG Menu - Setup Enter Setup Menu in Edit Mode
Keys Description The PROG menu setup gives the complete list of user-programmable parameters.
L1 L2 N
CT ? You must set up the energy meter to match the application settings before use. Otherwise,
LINE LOAD The EM1000/ EM1200 energy meter has four keys. The keys and their descriptions are
S1 S2 explained in the following table : readings will be wrong.
S1 S2 ? All the setup parameters can be re-programmed, using SET. However, the following
Table 6: Keys and Description settings critically determine the scaling of the measured readings: SYS (star or delta),
* other meters in series
* * OK key:
Vpri, Vsec, Apri, Asec.
S1 1 A1 2 S2 S1 3 A2 4 S2 S1 5
A3 6 S2
D1
7 OK It is used to go forward to the sub-parameter pages. ? The scaling may be used to minimize the errors in reading due to Instrument
50mA to 6A
Transformer errors. However, wrong settings will introduce errors in readings on other
Acc Cl: X.X RS 485 or POP connection

RS 485
running systems.
ESC key:
80 to 480 Vac LL 44 to 277 Vac 50/60Hz < 3VA ESC It is used to go back to the main parameter pages. Press OK four times
L N D0
8 V1 9 V2 10 V3 11 VN 12 13 14 You can enter PROG menu setup in
Fuse
0.25 A 0.25 A ? View mode: To view the set parameters.
0.25 A
Up Key: ? Edit mode: To view or edit the set parameters.
It is used to scroll up through the display pages of same level, within the same function.
In Set mode, used to increase the value by one .
Aux supply (control power)
Down Key:
NOTE:
Use PT(VT), if VAC LL > 480 V It is used to scroll down through the display pages of same level, within the same function. HAZARD OF UNINTENDED OPERATION - Means blinking.
In Set mode, used to decrease the value by one.
Figure 10: Single-phase connection Only qualified personnel are authorized to set up the energy meter. 2 - Means 2 is blinking.

L1 N
CT Failure to follow this instruction can result in injury or equipment damage.
LINE LOAD NOTE: The following symbols are used to represent the different keys operations.
S1 S2 / - OK operation. 1. Press from RMS. The display shows SET.
2. Press . The display shows SET VIEW.
OK

* other meters in series / - ESC operation. Enter Setup Menu in View Mode 3. Press . The display shows SET EDIT. You are required to enter CODE to enter into
* setup in Edit mode.
S1 1 A1 2 S2 S1 3 A2 4 S2 S1 5
A3 6 S2
D1
7
/ - operation. 4. Press .The display shows CODE 2000 with blinking 2.The factory set CODE is 1000.
OK

50mA to 6A
Acc Cl: X.X
5. Press . The display shows CODE 1000 with blinking 1.
RS 485 or POP connection
RS 485

/ - operation. 6. Press four times. The display flashes PASS and then Ed A.PRI 100.0.
OK

80 to 480 Vac LL 44 to 277 Vac 50/60Hz < 3VA

V1 V2 V3 VN L N D0 Keys Operation
8 9 10 11 12 13 14 This indicates that you have successfully entered the setup menu in edit mode.
Fuse The following example explains how to navigate from the RMS page to the W VA PF
0.25 A
display page and back to the RMS page.
0.25 A

NOTE: If you enter a wrong CODE, the display flashes FAIL and then shows SET EDIT.
1. Press OK
from RMS. The display shows W VA PF. Repeat the steps and make sure that you enter the correct CODE.
2. Press . The display shows VAR VA PF. 1. Press from RMS. The display shows SET.
Aux supply (control power) 3. Press
RMS ESC to return to RMS page.
W VA PF 2. Press . The display shows SET VIEW.
OK

Use PT(VT), if VAC LL > 480 V 3. Press . The display shows VI A.PRI 100.0. Use
OK and to view the setup parameters
NOTE: and their default values.
VAR VA PF Use OK to go forward to the sub parameter pages.
Use ESC to go back to the main parameter pages.
Use and to scroll up and down through the display
pages.

Setup Parameters in View and Edit Modes (EM1000) Setup Parameters in View and Edit Modes (EM1200) Edit Set Parameters Save New Value to the Setup

This section explains how to edit the setup parameter A.PRI from 100.0 to 5000 in the
A.PRI = Current primary winding (CT)*; Input range 1 A to A.PRI = Current primary winding (CT)*; Input range 1 A to EM1000/EM1200 energy meter.
99 kA. Default value is 100.0 99 kA. Default value is 100.0
For better understanding, the editing is explained in two parts: Edit and Accept Setup, Save
A.SEC = Current secondary winding (CT)*; Default value is A.SEC = Current secondary winding (CT)*; Default value is New Value to the Setup. NOTE:
5.000. 5.000. - Means blinking.
V.PRI = Voltage primary winding (PT), line to line*; V.PRI = Voltage primary winding (PT), line to line*; Edit and Accept Setup
Input range 100 V to 999 kV; Default value is 415.0. Input range 100 V to 999 kV; Default value is 415.0.
y - Means y is blinking.
1. After you edit and accept the parameter as previously described, press ESC. The display
V.SEC = Voltage secondary winding (PT), line to line*; V.SEC = Voltage secondary winding (PT), line to line*;
Input range 50 V to 600 V; Default value is 415.0. Input range 50 V to 600 V; Default value is 415.0.
shows SAVE y with blinking y.
2. Press . The display flashes PASS and shows SET EDIT.
OK

SYS = System configuration; Select from StAR, dLtA, 2 ph, SYS = System configuration; Select from StAR, dLtA, 2 ph, 3. Press . The display shows SET.
ESC

1 ph; Default value is StAR. 1 ph; Default value is StAR. Press OK four times
NOTE:
St.A = Starting current; 1 to 200 mA St.A = Starting current; 1 to 200 mA 1.If you do not want to save the new value, press to change SAVE y to SAVE n in
Default value is 005. Default value is 005. Press four times step 1. Press . The display flashes FAIL and shows SET EDIT. Proceed to step 3.
OK

PF.STD = PF standard; Select from IEC, IEEE, TRIG PF.STD = PF standard; Select from IEC, IEEE, TRIG
2.If you want to go back to the ED A.PRI 5.000 page from SAVE y in step 1,
Default value is TRIG. Default value is TRIG. then press . ESC

VA.FN = VA function selection; Select between 3D and Arth; VA.FN = VA function selection; Select between 3D and Arth;
Default value is 3D. Default value is 3D. Edit ID
NOTE:
OFLO= Overflow parameter selection; Select from Wh, OFLO= Overflow parameter selection; Select from Wh,
VAh; Default value is Wh. VAh; Default value is Wh.
- Means blinking.

E.POP = Energy POP


Baud = Baud rate; Select from 4800, 9600, 19200; 2 - Means 2 is blinking.
Default value is 1.00M Press OK
four times
Default value is 19200.
POP.ON = POP on time
Default value is 50 millie secs PRTY = Parity and stop bit settings; Select from EVN.1, 1. After you have successfully entered the setup in Edit mode (See “Enter Setup Menu in Edit NOTE:
ODD.1, no.2; Default value is EVN.1. Mode” for more information), press OK . The display shows ED A.PRI 100.0 with blinking 1. - Means blinking.
P.POP = POP parameter selection; Select from Wh or VAh; 2. Press four times. The display shows ED A.PRI 500.0 with blinking 5.
Default value is Wh. ID = RS 485 device ID number; 001 to 247; Default value is
001.
3. Press OK four times. The display shows ED A.PRI 500.0 with blinking “.”. 2 - Means 2 is blinking.
4. Press once. The display shows ED A.PRi 5.000 with blinking “.” and k indicator.
The value 5000 is represented as 5.00 with k indicator. 1. Press from RMS. The display shows SET.
See “Indicators” on page 3 for more information. 2. Press . The display shows SET VIEW.
OK

5. Press OK . The new value is accepted. 3. Press . The display shows SET EDIT.
4. Press . OK

NOTE: * Changing these values is not recommended, while the device is in use. NOTE: * Changing these values is not recommended, while the device is in use. You are required to enter CODE to enter into setup in Edit mode.
5. Press .The display shows CODE 2000 with blinking 2.The factory set CODE is 1000.
OK

6. Press . The display shows CODE 1000 with blinking 1.


7. Press OK
four times. The display flashes PASS and then Ed A.PRI 100.0.
8. Press . The display shows ED ID 001.
To edit the values, press OK
and set the values as required.
9. Press , the display shows SAVE y with blinking y.
ESC

2 10.Press . The display flashes PASS and shows SET EDIT.


OK
CLR INTG Energy Integrator INTG, OLD, Overflow Table 7: Integrator Overflow kVA Measurement
The EM1000/EM1200 energy meters are equipped with an energy integrator INTG where the
energy parameters are accumulated. Energy Integrator INTG Minimum time to overflow in
V.PRI x A.PRI Max Reading (Wh/VAh) EM1000/EM1200 energy meter has two different kVA measurements 3D and arithmetic.
Your EM1000/EM1200 energy meter is equipped with an energy integrator function which x 1.732 months at full scale These are available in the setup parameter VA.FN and can be edited upon entering the
provides several parameters for Energy Management: VAh, Wh, VARh, Run.h SET.
ON.h, INTR . All the values stored in INTG are direct readings and have high resolution.
Press four times
? 3D measurement (factory-set): Advanced method which provides most accurate and
OK

< 1000 k 9999999.0 k 13.88


A few of these need explanation: predictable measurement under unbalanced as well as distorted waveform conditions .
RUN.h: Indicates the period the load is ON and has run. This counter gets accumulated as < 1000 M 9999999.0 M 13.88
? Arithmetic measurement: Used when the energy meter needs to match the readings of
the older or simpler meters.
long as the load is ON.
NOTE: ON.h: The period for which the input voltage is ON. Table 8: kVA measurement selection
< 1000 G 9999999.000 G 13.88
- Means blinking. INTR: The number of input voltage interruptions or input voltage outages.

y - Means y is blinking. Integrator Overflow OLD Data Register kVA function Formula Other names Which one?

The energy values stored in INTG are based on V.Pri x A.Pri; they are independent of When the integrator is cleared (manually or due to overflow), the energy values stored in
secondary values of V and A. the integrator will be transferred to the OLD register. 3D kVA3 D = å W + åVAR + å D
2 2 2
U, Apparent vector Best all around
1. Press from RMS page. The display shows SET. where D = Distortion power per kVA
2. Press . The display shows CLR. The energy value readings will overflow based on V.Pri x A.Pri of the primary settings in Thus the old energy values are not lost even after the integrator is cleared and can be IEEE 100
You are required to enter CODE to clear the INTG values. setup. viewed with the OLD parameter.
2. Press OK . The display shows 2000 with blinking 2. The factory set CODE is 1000. The energy parameter for overflow is user selectable (Wh or VAh) through setup. By
3. Press . The display shows 1000 with blinking 1. default it is Wh. Arth kVA Arth = kVA1 + kVA2 + kVA3 Arithmetic scalar kVA Good under low
NOTE: For energy studies clear the Integrator at the end of each observation. This transfers unbalance, to match
4. Press OK four times to accept the new CODE value. The display flashes PASS and then
shows CLR INTG. all the stored energy values to the OLD register, where they are held while the integrator simple meters
begins accumulating data for the next observation. without 3D capability.
5. Press OK . The display shows CLR INTG y with blinking y.
6. Press OK to clear the INTG values. The display flashes PASS and then shows CLR INTG. When the integrator is cleared next time, the OLD values will be overwritten.
7. Press ESC . The display shows CLR.
8. Press twice. The display shows RMS.

NOTE: If you do not want to clear the INTG, press to change the value from CLR INTG
y to CLR INTG n in step 5. Press OK . The display flashes FAIL and then shows CLR INTG.
Proceed to step 7.

Features EM1000 Series Energy Meter Menu Hierarchy


Table 11:Energy Readings 1
Auto-scroll 1
? Auto-scroll allows you to view a group of display pages sequentially every five seconds Energy Reading, Range As shown in the Display
without manual key operation. 3-Phase RMS = RMS value display pages are in sub level DIAG = Represents diagnostic pages. The values contained
? During auto-scroll, the energy meter displays parameter name for one second and value 00001.0000 to 9999999.00 K to RMS W VA PF
DIAG MDL in these pages are for factory testing only
W = Active power total
for four seconds. Active(wh) / VAR VA PF VA = Apparent power total MDL = Product model number
? Auto-scroll is possible only within the page groups. i.e., the parameters within the page Apparent(VAh) / 10000.0000 to 9999999.00 M to VER
PF = Power factor average
Reactive(VARh) VER = Product version number
groups like RMS or INTG or DIAG will be auto-scrolled sequentially. 10000.0000 to 9999999.00 G to
VA1 VA2 VA3 C.SUM
VAR = Reactive power total
? The following table explains the auto-scroll operation in RMS parameter pages in EM1000 VA = Apparent power total
C.SUM = Check sum
W1 W2 W3 M.ON
\EM1200 energy meter. PF = Power factor average M.ON = Energy meter power ON hours
VAR1 VAR2 VAR3 VA1 = Apparent power, phase 1 M.INT M.INT = Energy meter power interruptions
Table 9: Auto-scroll Default Display Page VA2 = Apparent power, phase 2
PF1 PF2 PF3 VA3 = Apparent power, phase 3 001 EVN1 19.2k* Communication settings*
Step Perform Output
The default display page feature enables you to select any display page as user-set display W1 = Active power, phase 1 CT rev = CT reverse indication
kVAh CT rev
1 Press OK from RMS. The display shows W VA PF. page. You can scroll to other pages, when the default display page is active. The default INTG W2 = Active power, phase 2 No.Ain = No current input
display page will be displayed two minutes after you stop the manual key operation. W3 = Active power, phase 3
kWh No. Ain
2 Press and hold or for The display flashes AUTO and scrolls through the No.Vin = No voltage input
VAR1 = Reactive power, phase 1
three seconds. RMS parameter pages. To LOCK default display page: kVARh VAR2 = Reactive power, phase 2 No. Vin E.RST = Energy reset status
Go to the desired page you want to set as default display page. VAR3 = Reactive power, phase 3
Run.h E.RST All the segments glow
Press and together until the display shows LOCK and the display page is locked. PF1 = Power factor, phase 1
NOTE:
PF2 = Power factor, phase 2 CLR = Clears INTG values.
Press any key to revert to manual scrolling. On.h
PF3 = Power factor, phase 3 Display Check
To unlock default display page:
Auto scrolling is not possible in setup parameters.
Once the default display page is active, press and together until the display shows INTR SET = PROG menu setup. Has two modes to View and Edit
INTG = Integrator CLR
UN LOCK and the default display page is unlocked. setup parameters.
kVAh kVAh = Kilo apparent energy
Indicators NOTE: OLD SET VIEW = To view the setup parameters.
INTG kWh = Kilo active energy
Table 10: Indicators Entry to PROG menu setup is possible only when the default display page is unlocked. kWh
SET SET VIEW SET EDIT = To edit the setup parameters.
kVARh = Kilo reactive energy
kVARh SET EDIT
Kilo: When lit, indicates that the reading is in Kilo (10^3). The value 1000 is displayed as Run.h = Run hours
1.00 K and 10,000 is displayed as 10.0 K.
Run.h On.h = Duration for which input voltage is ON.
INTR = Number of input voltage interruptions.
Mega: When lit, indicates that the reading is in Mega (10^6). The value 1000 k is displayed On.h
as 1.00 M and 10,000 K is displayed as 10.0 M. OLD INTG = OLD integrator
INTR
Giga: When both K and M are lit, indicates that the reading is in Giga (10^9). kVAh = OLD Kilo apparent energy
The value 1000 M is displayed as 1.00 G and 10,000 M is displayed as 10.0 G.
kWh = OLD Kilo active energy 2
Negative: When lit, indicates that the reading is in negative as per IEEE 100 and kVARh = OLD Kilo reactive energy
industry standard.
When power factor(PF) is lead (capacitive load): Both PF and VAR will be negative Run.h = OLD Run hours
When current is reversed, W will be negative. NOTE: * Communication setting is available only for EM1200 energy
On.h = OLD Duration for which input voltage is ON.
1 meter.
INTR = OLD Number of input voltage interruptions.

3
Technical Specifications
Table 11: Technical specifications
Description Specification
Sensing/measurement True RMS, two quadrant power and energy, one second
update time.

Active power (kW) & Active energy* (kWh) Class 1.0 Class 0.5S

Apparent power (kVA) & Apparent energy* (kVAh) Class 1.0 Class 0.5S
Measurement
Accuracy (3 Phase) Reactive power (kVAR) & Class 2.0 Class 1.0
Reactive energy** ( kVARh)

Power Factor*(PF) Class 1.0 Class 0.5S

Auxiliary supply (control power) 44 to 277 VAC/DC


Three voltage inputs (V1, V2, V3, VN)
Input voltage 110 or 415 VLL nominal (80 to 480 VLL)
Input current
(energy measurement) 50 mA to 6 A (5 mA is the starting)*
Frequency 45 to 65 Hz
Burden Voltage and current input < 0.2 VA per phase
Auxiliary supply (control power) < 3 VA
Overload 10 A max continuous
Display and resolution Backlight LCD display;
Resolution: RMS Three digits (phase wise, average values);
INTG Nine digits.
Standards - Measurement category III,
Pollution degree 2
- Double insulation at user-accessible area
RS 485 serial channel connection industry standard Modbus
Communication (EM1200) RTU protocol
Environmental Operating temperature: -10 °C to 60 °C (14 °F to 140 °F)
Storage temperature: -25 °C to 70 °C (-13 °F to 158 °F)
Humidity 5 % to 95 % non-condensing
Weight 400 gms approx, unpacked
500 gms approx, shipping
Protection against dust and water Front panel: IP 51
Rear panel: IP 40

NOTE:
* Class 1.0 as per IEC 62053-21(Wh) and Class 0.5S as IEC 62053-22(Wh);
For 5A nominal CT.
** Class 2.0 as per IEC 62053-21(Wh)and Class 1.0 as per IEC 62053-21(Wh);
For 5A nominal CT.

Schneider Electric India Pvt Ltd Electrical equipment should be installed,


44 P, Electronics City East Phase, operated, serviced, and maintained only by
Hosur Road, qualified personnel. No responsibility is assumed
Bangalore - 560 100 , India by Schneider Electric for any consequences
E:in-care@in.schneider-electric.com arising out of the use of this material.
Toll Free Help desk Numbers:
1800 180 1707, 1800 103 0011 SEI/EM1000-EM1200/0311/V01.d01
www.schneider-electric.co.in © 2011 Schneider Electric All Rights Reserved
4

You might also like