Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
0% found this document useful (0 votes)
344 views16 pages

ASCO SERIES 185 Automatic Transfer Switches 100-400 Ampere Sizes Operator's Manual

Download as pdf or txt
Download as pdf or txt
Download as pdf or txt
You are on page 1/ 16

ASCO SERIES 185 Automatic Transfer Switches

100-400 ampere sizes


Operator’s Manual
381333-319F
9/2018
An experienced licensed electrician must install the
ATS
DANGER is used in this manual to warn of a
hazard situation which, if not avoided, will result
in death or serious injury

WARNING is used in this manual to warn of a


hazardous situation which, if not avoided, could
result death or serious injury.

CAUTION is used in this manual to warn of a


hazardous situation which, if not avoided, could
result in minor or moderate injury.

Refer to the outline and wiring drawings provided with


your ASCO Series 185 ATS for all installation details.
ASCO Series 185 Automatic Transfer Switches (ATSs)
are Listed under Underwriter’s Laboratories Standard for
Transfer Switch Equipment, UL–1008. They are intended
for use only in optional standby systems in accordance
with the National Electrical Code, NEC/NFPA 70, Article
702. This ATS is for use with 2–wire automatic–start
generators only.
Refer to Application Information 381339–292 to confirm
that you have selected the appropriate product for the 100-230 ampere sizes
intended installation.
Rating Label
This automatic transfer switch is intended for standby
Each automatic transfer switch contains a rating label to
power applications in residential / light commercial use
define the loads and fault circuit withstand / closing
only.
ratings. Refer to the label on the transfer switch for
This product is not intended for emergency specific values.
or life–support systems.
If you have more stringent application requirements
contact ASCO Power Technologies for other products
Do not exceed the values on the rating label.
suitable for critical applications. Exceeding the rating can cause person injury or
serious equipment damage
Operators Manual Controller

Table of Contents
Rating Label.............................................................................................................................................................. 1
Nameplate ................................................................................................................................................................ 3
Catalog Number Identification .................................................................................................................................. 3
Installation .................................................................................................................................................................. 4
1-Mounting ................................................................................................................................................................ 4
2-Electrical Power Connections................................................................................................................................ 4
Controller .................................................................................................................................................................... 5
1-Push Buttons ......................................................................................................................................................... 5
2-Indicator Lights ...................................................................................................................................................... 5
3-Generator Starting Contacts.................................................................................................................................. 5
4-Settings.................................................................................................................................................................. 6
5-Automatic Generator Exerciser ............................................................................................................................. 6
6-Remote Control & Load Disconnect ...................................................................................................................... 9
7-Factory Settings - Summary ................................................................................................................................ 10
Functional Test ....................................................................................................................................................... 11
1-Manual Operation ................................................................................................................................................ 11
2-Electrical Operation ............................................................................................................................................. 11
Sequence of Operation ......................................................................................................................................... 12
Troubleshooting ....................................................................................................................................................... 13
California Proposition 65 Warning .................................................................................................................. 15
Index .......................................................................................................................................................................... 16

2 381333-319F
Operator’s Manual Series 185

Nameplate Catalog Number Identification


The Transfer Switch nameplate includes data for A typical Catalog Number is shown below with its
each specific ASCO Series 185 ATS. Use the ATS elements explained. The example is for a D–design,
only within the limits shown on this nameplate. 2 pole, 200 A, 220–240 V, in Type 1 indoor enclosure:

D 185 A 2 100 F 4 C
Neutral Phase Poles Amperes Voltage Controller Enclosure
A-standard 2-single Ø 100 F-220-240 4-standard C- Type 1
200 4X-If M- Type 3R
230 accessories
260 ordered
400

cable spacers load power emergency


clock battery
(see INSTALLATION) connections power
connections

neutral
connections

terminals for
optional
switch
position
contacts
(shown
installed)

Transfer
Switch

ground
connections

membrane generator utility power


controls control Controller harness plug connections
connections
200 ampere size in typical enclosure with location of customer connections

381333-319F 3
Operators Manual Controller

Installation
Installation of the ASCO Series 185 automatic transfer 2 - Electrical Power Connections
switch (ATS) must be performed by a licensed electrician.
It must be installed according to the National Electrical Refer to the wiring diagram. The ATS must be protected
Code (NEC) and all local electrical code requirements. by suitably sized circuit breakers feeding the utility and
Remove the enclosure cover and inspect the ATS for generator source terminals. The rating of the circuit
shipping damage. If damage is evident do not install the breakers must be based on the requirements of the
ATS. National Electrical Code for its nameplate ampere and
short circuit withstand ratings.
1 - Mounting
Refer to the enclosure outline drawing. Mount the ATS
according to details and instructions shown on this
diagram. Mount the ATS vertically to a rigid supporting ELECTROCUTION HAZARD Turn off utility power
structure. Level all mounting points by using flat washers and turn off the generator to prevent electrocution
behind the holes to avoid distortion of the enclosure. when wiring the transfer switch.
Cable Spacers for 150, 200, and 230 A
Three cable spacers are included with 150, 200, and 230
MALFUNCTION or SHORTENED LIFE ampere transfer switches. Run the copper power cables
Protect the automatic transfer switch from through the cable spacers as shown in Figure 2. Position
construction grit and metal chips to prevent the cable spacers approximately 1½ inches from the
malfunction or shortened life of the ATS. terminal lugs.
Transfer switches rated 260 and 400 amperes are
mounted on an insulator backing piece (installed behind
the transfer switch). If the transfer switch is removed
CABLE LOOSENING DUE TO SHORT CIRCUIT
from the enclosure and then reinstalled, this insulator
must be placed behind the transfer switch. See Figure Install three cable spacers 1 1/2 inches from the
1. power terminals to prevent the cables from
loosening during a short–circuit condition on 150,
200, and 230 ampere transfer switches.

FLASH HAZARD – DAMAGE


Be sure that the insulator piece is installed behind
the 260 and 400 ampere transfer switches.

Figure 2. Cable spacers for 150, 200, and 230 A.

Figure 1. Insulator for 260 and 400 A.

4 381333-319F
Controller Operators Manual

Controller
The Group 4 digital Controller is used in ASCO Series Set Engine Exerciser
185 automatic transfer switches. It provides the sensing, Use this button to set the automatic generator exerciser
timing, and control functions for the ATS. This micro– (page 5).
processor–based controller includes built–in control
buttons and status lights for control of the ATS and 2-Indicator Lights
generator.
On the front control display are five lights that indicate
the status of the sources and the ATS.
Utility Acceptable
This light indicates that the utility voltage is acceptable
for connection to the load.
Generator Acceptable
This light indicates that the generator voltage is
acceptable for connection to the load.
Load on Utility
This light indicates that the load is connected to the
utility.
Load on Generator
This light indicates that the load is connected to the
generator.
Automatic Generator Exerciser
This light indicates the status of the generator exerciser:
- blinks during the exercise period (including cooldown).
- stays on when the exerciser has been set.
- is off when the exerciser has not been set.

3-Generator Starting Contacts


The generator starting contacts connections are on the
controller. Refer to the generator manual. Disconnect
the generator battery and verify that the ignition switch is
in the OFF position. Connect the generator starting
wires to the appropriate terminals on terminal block TB7
as shown on the wiring diagram. For wiring
convenience terminal block TB7 has a removable plug.
See Figure 4 and Table A.
Figure 3. Front view of controller

1-Push Buttons
On the front control display are three push buttons that
control the operation of the generator and the ATS.

Before using the transfer test button, be sure that TB7


conditions are safe for running the generator and removable
for load transfer. terminal
Transfer Test block
Use this button to test the system. This operation starts
the generator and transfers the load. Be sure that
conditions are safe to do this operation. TB7-4, TB7-5, TB7-6
Bypass Time Delay Figure 4. TB7 generator starting contact terminals
Use this button to cancel the active time delay or exercise
period (stops the generator after cooldown).

381333-319F 5
Operators Manual Controller

Controller continued
Exercise with or without Load
Table A. Generator Start Connections
The generator should be exercised under load or
When the Utility fails Terminals on Controller follow the recommendations of the generator
contact closes TB7–4 and TB7–5 manufacturer. Be sure the exerciser is turned on.
Then select either exercise with or without load. The
contact opens TB7–5 and TB7–6 ATS will transfer the load to the generator when the
exercise with load is selected. See Figure 6 and
4-Settings Table B.

The time delay and sensor setting in the Group 4 To Set Exerciser
controller are accessible on the inside. Refer to Press and hold (5 seconds) the Set Engine
Tables B and C and to Figures 6 and 7. Use a ball– Exerciser button. The exercise period occurs
point pen or other pointed tool to slide the DIP switch immediately and at approximately the same time
actuators up or down to match setting shown. weekly thereafter. The status light below the button
blinks during the exercise period (including the
All power must be off before making any changes. cooldown). The light stays on to indicate that the
The factory default settings are shown in Table G on exerciser has been set. If the light is off, the exerciser
page 9. has not been set.
5-Automatic Generator Exerciser To Cancel an Active Exercise Period
Press the Bypass Time Delay button to stop an
The built–in automatic generator exerciser can be set
exercising generator. If exercise with load is set, the
to exercise the generator for 20 minutes once every
ATS retransfers the load to the utility, then stops the
week.
generator after cooldown.
Clock Battery
Be sure a fresh battery is installed and turned on. It
will maintain the exerciser clock for about 24 hours in
case of a power outage.

cover must be removed


to replace 9V battery
(use alkaline type)

screw

Figure 5. Battery replacement


Recommended 9-volt alkaline batteries are (see
Figure 5): Duracell MN 1404, Eveready 522,
Panasonic 6AM6. Turn on battery by putting S2 DIP
switch actuator 10 in the on position (up). See Table
B and Figure 6.

Table B. Generator Exercise Settings


Function Factory Setting DIP Switch DIP Actuator Actuator Position
clock on (up)
off S2 10
battery off (down)
on (up)
exerciser off S1 7
off (down)
with load or without without with (up)
S1 8
load load without (down)

6 381333-319F
Controller Operators Manual

Controller continued

S3 DIP switch
S1 DIP switch S2 DIP switch

Figure 6. DIP switches S1 and S2 at the top right


The time delay settings are shown in Figures 6 and 7
and in Table C. The sensor settings are shown in
Figure 6 and in Table D. The standard (factory) settings
are shown in Tables C, D, and H.

Figure 7. DIP switch S3 at the bottom center


Table C. Time Delay Settings
Time Delay Description Factory Settings DIP Switch DIP Actuator Actuator Position
Setting

override momentary 3 1 second S2 1 on (up)


utility outages seconds 3 seconds S2 1 off (down)
10
transfer to generator seconds – – – –
(approx.)

override momentary 4 4 second S3 9 on (up)


generator outages seconds 0 S3 9 off (down)
5 minutes
transfer to utility – – – –
(approx.)

unloaded running 2 minutes S1 10 on (up)


2 minutes
(generator cooldown) 5 minutes S1 10 off (down)
0 seconds S3 7, 8 both on (up)
load disconnect delay 3 seconds S3 7, 8 7 on (up), 8 off (down)
0
before transfer (and delay
seconds 10 seconds S3 7, 8 7 off (down), 8 on (up)
after transfer, if enabled)
20 seconds S3 7, 8 both off (down)

381333-319F 7
Operators Manual Controller

Controller continued
Table D. Voltage and Frequency Settings
Setting Factory Actuator
Setting Settings DIP Switch DIP Actuator
Description Setting Position
non–
voltage – 220 – 240 V S2 2 on (up)
adjustable
50 Hz S1 4 on (up)
frequency nominal 60 Hz
60 Hz S1 4 off (down)
non–
phase – single S1 6 on (up)
adjustable
198 V S1 3 on (up)
pickup 198 V
209 V * S1 3 off (down)
S1 1 off (down)
198 V *
S1 2 off (down)
S1 1 on (up)
utility voltage 187 V
S1 2 off (down)
dropout 187 V
S1 1 off (down)
176 V
S1 2 on (up)
S1 1 on (up)
154 V
S1 2 on (up)

generator pickup 198 V non–


– – –
voltage dropout 165 V adjustable

57 Hz (nom 60
generator Hz)
pickup
frequency 48 Hz (nom 50
Hz) non–
– – –
51 Hz (nom 60 adjustable
Hz)
dropout
43 Hz (nom 50
Hz)
* If the dropout voltage is set to 198 V, the pickup voltage must be set to 209 V

8 381333-319F
Controller Operators Manual

Controller continued
6-Remote Control & Remote test (with automatic retransfer)
Load Disconnect Normally–closed input. When opened, it simulates a
utility failure. The generator is signaled to start
These remote control features require a customer– immediately and the load transfers to the generator (if
supplied normally–closed contact suitable for a 5 V dc acceptable). If the generator fails, the load transfers
low energy circuit. Refer to the wiring diagram back to the utility (if acceptable).
provided with the ATS. Activate the appropriate DIP
switch S3 actuators as shown in Tables E, F, or G. Bypass load transfer to utility time delay
See Figure 7. Normally–closed input. When opened, it bypasses or
Remote test cancels the generator to utility load transfer time
Normally–closed input. When opened, it simulates a delay. The load transfers back to the utility.
utility failure. The generator is signaled to start Load disconnect feature
immediately and the load transfers to the generator (if
acceptable). If the generator fails, the load stays on Connect external circuits to the terminals indicated on
the generator until the remote test circuit is closed. the wiring diagram. The double throw (Form C)
contact operates prior to a selectable 0, 3, 10, or 20
Remote test (with automatic retransfer) second delay before transfer of the ATS. The contact
Normally–closed input. When opened, it simulates a resets either immediately following transfer or after
utility failure. The generator is signaled to start the same delay as set for pre-signal before transfer.
immediately and the load transfers to the generator (if Time delay between the load disconnect control
acceptable). If the generator fails, the load transfers signal and initiation of transfer is set on the controller
back to the utility (if acceptable). DIP switch S3 (actuators 6, 7, 8).

Table E. Remote test


Function Factory Setting DIP Switch DIP Actuator Actuator Position
disabled disabled on (up)
S3 3
enabled (on) off (down)

Table F. Remote transfer to generator


Function Factory Setting DIP Switch DIP Actuator Actuator Position
disabled disabled on (up)
S3 2
enabled (on) off (down)
Table G. Bypass load transfer to utility delay
Function Factory Setting DIP Switch DIP Actuator Actuator Position
disabled disabled on (up)
S3 1
enabled (on) off (down)
Table I. Load disconnect delay before transfer
Function Factory Setting DIP Switch DIP Actuator Actuator Position
7 on (up)
0 seconds disabled S3
8 on (up)
7 on (up)
3 seconds S3
8 off (down)
7 off (down)
10 seconds S3
8 on (up)
7 off (down)
20 seconds S3
8 off (down)

381333-319F 9
Operators Manual Controller

Controller continued
Table J. Load disconnect delay after transfer*
Function Factory Setting DIP Switch DIP Actuator Actuator Position
disabled disabled S3 6 off (down)
enabled S3 6 on (up)
* Enabling the delay after transfer will cause the control signal to reset after the same delay as set for the delay
before transfer

7 - Factory Settings – Summary


Table H. Factory Settings – Summary
DIP Switch DIP Actuator Actuator Position
1 on (up)
2 off (down)
3 on (up)
4 off (down)
5 off (down)
S1
6 on (up)
7 off (down)
8 off (down)
9 off (down)
10 on (up)
1 off (down)
2 on (up)
3 off (down)
4 on (up)
5 on (up)
S2
6 on (up)
7 on (up)
8 on (up)
9 off (down)
10 off (down)
1 on (up)
2 on (up)
3 on (up)
4 on (up)
5 on (up)
S3
6 off (down)
7 on (up)
8 on (up)
9 on (up)
10 on (up)

10 381333-319F
Functional Test Operators Manual

Functional Test
After installing the Series 185 automatic transfer switch maintenance handle
(ATS) perform the following three–part functional test.
With ALL POWER OFF
1 - Manual Operation grasp maintenance
A handle is provided on the transfer switch for handle and turn it
maintenance purposes only. Manual operation of the quickly with your
transfer switch should be checked before it is thumb and fingers.
energized (operated electrically).

weight marked P (utility) and A (generator)


Figure 8. Maintenance handle for 100-230 A
Do not manually operate the transfer switch until
both power sources are disconnected: open both
circuit breakers.
1. Turn OFF both the utility and generator circuit
breakers feeding the ATS. Verify that ALL POWER IS
OFF!
2. 100–230 A
Grasp the maintenance handle and turn it quickly with
your thumb and fingers to manually operate the
transfer switch. Figure 9. Maintenance handle for 100-230 A
260–400 A
Insert the maintenance handle into the hole in the 3 - Electrical Operation
shaft, left side of the operator. Move the handle as
This procedure checks the electrical operation of the
shown to manually operate the transfer switch.
ATS.
3.The switch should operate smoothly without
1. Install the enclosure cover and tighten the screws.
binding. If it does not, check for shipping damage or
construction debris. 2. Verify that the generator battery is connected and
that the generator’s starting controls are set for
4.After checking the manual operation, use the handle
automatic.
again to return the transfer switch to the utility source
position. 3. Turn on both the utility and generator circuit
100–230 A see Figure 8. breakers.
The letter P (utility) on the round weight is facing you.
260–400 A see Figure 9. 4. Verify that the Utility Acceptable and Load on
The letter N (utility) on the round weight is facing you. Utility lights are on.
Remove the maintenance handle and store it on the 5. This step will start the generator. Press and hold the
transfer switch in the place provided. Transfer Test button until the Generator Acceptable
light comes on and stays on. Then release the button.
6. After the Generator Acceptable light comes on, the
260–400 A Remove the maintenance handle ATS transfers the load from the utility to the generator
before proceeding! (after approx. 10 second delay). The Load on
Generator light comes on.
2 - Voltage Checks 7. The ATS stays connected to the generator for
5 minutes (approx.). The utility must be acceptable for
The ATS is rated for 220–240 V ac 60 or 50 Hz. Verify
5 minutes continuously. Then the load is transferred
that both the utility and generator sources are 220–240
back to the utility. To bypass time delay, press the
V ac 60 or 50 Hz.
Bypass Time Delay button.
8. After load retransfer to utility, the generator runs
2 minutes (without load), then shuts down. The
Generator Acceptable light goes off indicating that the
generator is off.
This completes the Functional Test.

381333-319F 11
Operators Manual Sequence of Operation

Sequence of Operation - Utility Failure

light is on
light is off
¡
generator Utility power good.
stops Electrical loads on utility Utility fails
(longer than
generator runs utility acceptable 3 sec.)
unloaded
for 2 min.
load on utility

¥
electrical loads ©
switched back
utility acceptable utility off start
to utility
generator
generator off
load on utility load off

generator generator off


observe observe
acceptable
wait 5 min. these these
for utility power switch generator
to stabilize utility lights lights utility off
starting
acceptable

load on utility

load on generator

generator acceptable utility off generator ¢


acceptable generator
¤ acceptable
utility
returns wait 10 sec.
for generator
waiting for utility load on generator to warm up
to return

generator acceptable

£
electrical loads
switched to generator

12 381333-319F
Troubleshooting Operators Manual

Troubleshooting
This troubleshooting guide describes some of the
simple causes of problems with the installation of
the automatic transfer switch. Troubleshooting
beyond the scope of this guide should not be
attempted by the installer. A licensed electrician ELECTROCUTION FLASH HAZARD Do not work on
must perform all internal troubleshooting. ASCO the transfer switch until both the utility and generator
Power Technologies can be contacted at: 1–800– are off. Turn OFF both circuit breakers.
800–2726 or customercare@ascopower.com

Problem Cause and Solution


The Utility Acceptable light 1. Verify that the utility feed is connected and that its circuit breaker is ON.
does not come on when utility
power is connected to the 2. With ALL POWER OFF, verify that the utility feed is 220–240 V ac and 60 Hz.
ATS. Check DIP switch S2 actuator 2, and DIP S1 actuator 4. See Table D for
voltage and frequency settings.
3. With ALL POWER OFF, verify that the utility feed is wired to the terminal lugs
on the bottom of the transfer switch marked L1 and L5. See the wiring
diagram.
4. With ALL POWER OFF, verify that the transfer switch harness is connected
properly to the controller (plug and receptacle tight).
The generator does not crank 1. Hold the Transfer Test button for at least 15 seconds.
when the utility source fails or
when the Transfer Test button 2. Verify that the generator starting controls are set for automatic operation (not
is pressed. in manual mode).
3. Verify that the generator battery is connected and that the battery voltage
meets the generator manufacturer’s recommendation.
4. Verify that the correct contact (normally open or normally closed) is being
utilized (see the generator manual).
5. With ALL POWER OFF, verify engine start low voltage wiring between the
controller terminal block and the generator. See the wiring diagram. Check
that the plug is properly seated in the receptacle on the controller.
The generator cranks but does 1. Verify proper generator operation (fuel in tank, oil level, spark plugs - see
not start and run when the generator manual).
utility source fails or when the
Transfer Test button is 2. With ALL POWER OFF, verify engine start low voltage wiring between the
pressed. controller terminal block and the generator. See the wiring diagram. Check
that the plug is properly seated in the receptacle.
The generator starts and runs 1. Verify that the generator feed is connected and that its circuit breaker is ON.
but the Generator Acceptable
light does not come on. 2. With ALL POWER OFF, verify that the generator feed is 220–240 V ac and
60 Hz. Check DIP switch S2 actuator 2, and DIP S1 actuator 4. See Table D
for voltage and frequency settings.
3. With ALL POWER OFF, verify that the generator feed is wired to the terminal
lugs on the top of the transfer switch marked L2 and L6. See the wiring
diagram.
4. With ALL POWER OFF, verify that the transfer switch harness is connected
properly to the controller (plug and receptacle tight).
5. Verify generator ac output (voltage and frequency - see generator manual).
The generator starts and runs 1. Verify that the Generator Acceptable light is on. If it is off, see previous
but the ATS does not transfer troubleshooting problem. The ATS will not transfer the load to an
the load to the generator.
unacceptable source.
2. With ALL POWER OFF, verify that the transfer switch harness is connected
properly to the controller (plug and receptacle tight).

381333-319F 13
Operators Manual Troubleshooting

Troubleshooting continued
Problem Cause and Solution
The ATS does not immediately 1. Verify that the Generator Acceptable light is on. If it is off, see previous
transfer the load to the troubleshooting problem. The ATS will not transfer the load to an
generator. unacceptable source.
2. Wait approximately 10 seconds for the transfer to generator time delay. This
fixed delay allows the generator output to stabilize before a load is applied to
it.
3. Press the Bypass Time Delay button for immediate load transfer to the
generator.
The ATS transfers the load to 1. The generator may be overloaded. Check to see if the generator circuit
the generator, but the breaker tripped. Check the sum of the loads to be sure it does not exceed the
generator bogs down capacity of the generator. Some motor loads require three times more power
(struggles or slows down). for starting.
The ATS retransfers back to
the utility. 2. Check for short circuit in a connected load.
3. Observe the Load on Utility and Load on Generator lights.
The generator stops after a 1. Verify proper generator operation; it may have run out of fuel or shut down
running for a while. The ATS because of low oil level (see generator manual).
retransfers back to the utility (if
2. The generator may be overloaded. Check to see if the generator circuit
acceptable).
breaker tripped. Check the sum of the loads to be sure it does not exceed the
capacity of the generator. Some motor loads require three times more power
for starting.
3. Check for short circuit in a connected load.
4. Observe the Load on Utility and Load on Generator lights.
The ATS does not retransfer 1. Verify that the Utility Acceptable light is on. The ATS will not transfer the load
the load back to the utility. to an unacceptable source.
2. Wait approximately 5 minutes for the retransfer to utility time delay. The utility
must be acceptable for 5 minutes continuously.
3. Press the Bypass Time Delay button for immediate load retransfer to the
utility.
The ATS retransfers the load 1. Wait approximately 2 minutes for the unloaded running (engine cooldown)
back to the utility but the time delay.
generator keeps running.
2. The engine cooldown fixed time delay is important to prevent generator
damage.
The generator exerciser does 1. Verify that the Automatic Generator Exerciser status light is blinking.
not seem to work. - Light blinks during the exercise period.
(when the generator is running and during cooldown).
- Light stays on when then exerciser has been set.
- When light is off, no exercise period is set.
2. With ALL POWER OFF, verify that the exerciser is turned on. Check DIP
switch S1 actuator 7, and S2 actuator 10. See Table B for generator
exerciser settings.
3. With ALL POWER OFF, check the 9-volt battery. Replace, if necessary, with
a quality alkaline battery: Duracell MN1404, Everready 522, Panasonic 6AM6,
or equivalent. See Figure 5.
The generator exerciser does 1. With ALL POWER OFF, verify that exercise with load is turned on. Check DIP
not transfer the load to the switch S1 actuator 8. See Table B for generator exerciser settings.
generator.

14 381333-319F
Cal Prop 65 Warning Operators Manual

California Proposition 65 Warning—Lead and Lead


Compounds
Advertencia de la Proposición 65 de California—Plomo y
compuestos de plomo
Avertissement concernant la Proposition 65 de Californie—
Plomb et composés de plomb

WARNING: This product can ADVERTENCIA:Este producto AVERTISSEMENT: Ce produit


expose you to chemicals puede exponerle a químicos peut vous exposer à des agents
including lead and lead incluyendo plomo y compuestos chimiques, y compris plomb et
compounds, which are known to de plomo, que es (son) composés de plomb, identifiés
the State of California to cause conocido(s) por el Estado de par l'État de Californie comme
cancer and birth defects or other California como causante(s) de pouvant causer le cancer et des
reproductive harm. For more cáncer y defectos de nacimiento u malformations congénitales ou
information go to: otros daños reproductivos. Para autres troubles de l’appareil
www.P65Warnings.ca.gov mayor información, visite : reproducteur. Pour de plus
www.P65Warnings.ca.gov. amples informations, prière de
consulter:
www.P65Warnings.ca.gov

381333-319F 15
Operators Manual Index

INDEX
A H S
Automatic Generator Exerciser, 5, 6, handle, maintenance, 11 service,
14 warning, 15 800–800–2726 (ASCO)
harness,3
B HELP
customercare@ascopower.com
buttons, push, 5 800–800–2726 (ASCO) Set Engine Exerciser, button, 5, 6
Bypass Time Delay, button, 5 11 customercare@ascopower.com settings
bypass time delay, 14 changing, 5-7
I factory, 5-7
C indicator lights, 5 frequency, 8
cable spacers, 3,4 installation, 4 phase, 8
California Proposition 65 Warning., insulator, backing piece, 4
time delay, 7
15 illustration of, 4
warning, 4 voltage, 8
catalog number, 3 source acceptable lights, 4
clock battery, 3, 5, 6 L spacer, cable, 3
connections lights, 5, 11, 12, 14
electrical power, 4 load disconnect feature, 9, 10 T
contacts Load on Generator, light, 5, 11, 12,14 TB7 generator start connections, 5
engine start, 13 terminal block, 5
Load on Utility, light, 5, 11, 12,14
control features, remote, 9 time delay
controller, 5-11 M adjustment, 6, 7
gen–set cooldown, 7
manual operation, 11
D illustration of, 11
how to change, 7
settings, 7-8
DIP switches, 6-10 warning, 11 transfer to generator, 7
dropout, 8 mounting, 4 transfer to utility, 7
timer (gen exerciser), how to set, 6-7
E O transfer switch position lights, 4
electrical operation, 11 operation Transfer Test, button, 5, 11
electrical power connections, 4 electrical, 11 troubleshooting, 13-14
engine exerciser, 5, 6 manual, 11
sequence of, 12 U
F override momentary outages, 7 unloaded running, gen. cooldown, 7
features, see control features Utility
frequency, pickup and dropout, 8
P failure, 9
pickup, 8
functional test, 11 frequency, 8
problem, 13-14
settings, 8
G R voltage, 8
generator
rating label, 1 Utility Acceptable, light, 5, 11, 12, 13,
exerciser, 5, 6, 14 14
remote control features, 9
frequency, 8, 13
settings, 14
remote test, 9 V
remote transfer to utility, 9 voltage, phase, 8
starting contacts, 3
voltage, 5, 8, 13 voltage, pickup & dropout settings, 8
voltage checks, 11
Generator Acceptable, light,
5, 11,13 ,14
ground connection, 3

ASCO Power Technologies


160 Park Avenue
Florham Park, NJ 07932-1591 USA
Phone: 1 800 800-2726 (ASCO) for sales or service
www.ascopower.com

©2011 ASCO Power Technologies. All Rights Reserved Printed in U.S.A

16 381333-319F

You might also like