Yonis Hussain Report

Download as pdf or txt
Download as pdf or txt
You are on page 1of 9

Theraepocaipntw

lshevraberispleedyverlial
orcks!

Three applications where variable speed drive really rocks! (photo credit: achrnews.com)

Esnpeab&segavliryedir
Many industrial sectors have discovered the benefits of using variable speed drive (VSD) control in a wide variety of
applications. Businesses in the commercial and public sectors can also utilise the benefits of VSDs, largely in applications
involving pumps and fans, such as ventilation and air conditioning systems, combustion air for boiler systems, chillers and
water–pumping systems.

Now… let’s talk about the three applications where variable speed drives really rock in energy saving:

1. Fans
2. Pumps and
3. Air compressors

1. Fans
Although dampers are often used to regulate the output of fans, reducing the speed of the fan is a much more energy
efficient way of achieving the same effect. This is illustrated by the graph below (Figure 1).

Note: Because of the losses inherent in VSDs, there is a point where they will be less efficient than dampers. This is around
92%-95% and is not shown on this simple graph.

converted by Web2PDFConvert.com
Figure 1 – Comparison of speed reduction in fans using dampers and VSDs

With damper control, the input power reduces as the flow rate decreases. However, under variable speed drive control, the
variable torque characteristic of the fan means that the relationship between flow and the speed of the fan is such that the
input power reduces in a cube law relationship with the speed reduction.

This can be seen by the graph, where the energy expended using a VSD is significantly less than that of
damper controlled motors. It also shows one of the limitations of a VSD, in that it will not normally be able to
reduce the flow all the way to zero, but will only slow down as far as 20-30% (depending on the specification of the
VSD and motor).

This type of fan application could be used in industrial cooling, commercial


ventilation systems and combustion–air control systems for boilers.

converted by Web2PDFConvert.com
As well as being a more efficient use of power, using VSDs in fan
applications can also result in reduced noise in heating and ventilation
air–duct systems due to the elimination of dampers.

Making flow rate changes in a damper system can lead to unwanted vortexes appearing in the air flow, which create noise
and vibration in addition to the mechanical noise generated from the damper changing position. In a VSD system,
making flow rate changes generally only results in slight changes to the noise levels, which are normally undetectable to
the ear. Figures 2 and 3, overleaf, demonstrates this.

FACT! Reducing fan speed not only reduces energy consumption but may also reduce noise and vibration!!

Flow rate changes using dampers compared with using VSDs


Typical fan and motor with flow controlled by a damper
In the figure 2, flow is controlled by a damper, which is informed by a sensor (in some applications this could be a flow
meter). The motor continues to operate at a constant speed regardless of flow required. In addition, some kinds of dampers,
such as butterfly valves, can cause adverse vortexes in the flow.

Figure 2 – A typical fan and motor with ow controlled by a damper

Typical fan and motor with ow controlled by a variable speed drive


In the figure 3, the pressure sensor is connected directly to the variable speed drive which slows the motor when required. As
well as leading to better automatic control of the motor’s speed, the adverse flow conditions are also improved.

converted by Web2PDFConvert.com
Figure 3 – A typical fan and motor with ow controlled by a variable speed drive

Go back to VSD applications ↑

2. Pumps
In a similar way to using damper control in fan applications, using throttle control for pumping applications results in a
poor efficiency as the pump is not being run at its design point. This is particularly true for applications with a steep
flow/head characteristic, where there is a high static head such as in underfloor heating circuits, geothermal pumps and for
small pumps.

Further details on this will be available from equipment suppliers.

Using a variable speed drive to control the pump rather than using simple throttle control can result in significant
power – and therefore cost – savings!!

This is illustrated in the graph, right, where the broken line indicates the power input to a fixed speed device and the solid line
indicates the power input to a VSD. The shaded area represents the power saved by using a VSD for a given flow.

converted by Web2PDFConvert.com
Figure 4 – Power saved using a VSD in a pump

Note: To be strictly accurate, there is a crossover point where a VSD can use more energy than a fixed speed power input.
This is because of the losses inherent in VSDs which are not balanced by savings when incorrectly used.

It is important to note that on systems with a high static head (for


example, boiler feedwater pumps), where the pump must overcome the
inherent resistance of the system before any flow starts, the benefits of
using VSDs will be slightly reduced.

This is because the additional resistance affects the relationship between the speed of the pump and the flow. Factor this into
any calculations and consult an equipment supplier for further information if needed. Typical examples of pump applications for
VSDs include moving hot water in HVAC systems, boiler feedwater pumps and product flow pumps, such as chemicals or
inks.

converted by Web2PDFConvert.com
Go back to VSD applications ↑

3. Air compressors
The potential for energy savings from using VSDs for air compressors will depend on the control system being replaced. The
following diagram (Figure 5) illustrates the energy savings generated from fitting a VSD as compared to other methods of
flow control.

Figure 5 – Energy savings due to VSDs on a typical air compressor

Most air compressors are a constant torque load and, therefore, have less scope for energy savings than fan and pump
applications, which are variable torque loads. Therefore, it is less likely to be economic to retrofit a VSD to a compressor
unless it is very lightly loaded for long periods of time.

Air compressors tend to be used for industrial rather than commercial


applications!

converted by Web2PDFConvert.com
IMPORTANT! You can check if a compressor is lightly loaded by listening to the amount of time the compressor is on–load
compared to the amount of time it is off–load at various times throughout the day.

You will be able to hear the pitch change when the compressor is idling
in off–load!

If your compressor is off–load more than it is on–load, it may be appropriate to consult the compressor manufacturer or a
VSD supplier to assess its suitability for either retrofitting a VSD, or buying a new, suitably sized VSD compressor.

Go back to VSD applications ↑

Reference // Variable speed drives Introducing energy saving opportunities for business by Carbon Trust

Related electrical guides & articles //

Article Tags // Filed Under Category //


air compressors, compressor, energy savings, fan, motor, Energy Efficency Variable Speed Drives
pumps, variable speed drive, vsd,

About Author //
Edvard Csanyi

converted by Web2PDFConvert.com
Edvard - Electrical engineer, programmer and founder of EEP . Highly specialized for design of LV high power busbar
trunking (<6300A) in power substations, buildings and industry fascilities. Designing of LV/MV
switchgears.Professional in AutoCAD programming and web-design.Present on Google+

One Comment RSS Feed for Comments

Hi Edvard,
thank you for this article on VFD’s/VSD’s/AFD’s and your other great articles you write or share very
Kevin helpful information.
Harper
A U G 0 3 ,
here2 are
0 1 6
some other benefits to using VFD’s on equipment even if they run full speed most of the time:

• Help prevent excessive mechanical wear and tear on equipment with smooth starts and stops or running
slower instead of stopping.
• Help prevent excessive Stress electrically on motors and feeders with smooth starts and stops.
• Prevent large current draw when starting larger motors, that new smart meters can sense and penalize
customers for.
• Improve power factor of you facility.
• Improve Building automation and control
A great link about unspoken benefits of using VFD’s to :

http://ecmweb.com/contractor/behind-scenes-vfds\

Below is the main link to the ABB free energy savings software for VFD’s

http://www.abb.com/product/ap/seitp322/24b03100d005c31ac1256e040043f4c1.aspx?country=us

thanks again and have a great rest of your week,


regards,
Kevin Harper

(reply)

Leave a Comment RSS Feed for Comments

Tell us what you're thinking... we care about your opinion!

N A M E *

E M A I L *

W E B S I T E

converted by Web2PDFConvert.com
× = 

SUBMIT COMMENT

© 2016 EEP - Electrical Engineering Portal. All Rights Reserved | Privacy Policy | Terms of Service | 48 queries in 0.392 seconds.

converted by Web2PDFConvert.com

You might also like