Data sheet

ON/OFF zone valves (PN 16)


AMZ 112, AMZ 113

Description

AMZ 112/2-port valve AMZ 112/2-port valve AMZ 113/3-port valve


DN15-DN32 DN40-DN50

The ON/OFF zone valves type AMZ 112 and The ON/OFF zone valves can be applied
AMZ 113 are typical used in connection with: together with most Danfoss Room Thermostats,
particulary type RET 230 (single poled switch)
• Domestic and commercial central heating and programmable Room Thermostats type
applications TP 5000/7000. Other compatible room
• Domestic hot water applications thermostats are available, please see www.
• Solar energy plants danfoss.com/heating for details.
• Priority control of hot water supply and
heating (diverting function) The actuator can be controlled by a SPST or SPDT
• Priority control of boiler and solid fuel switch.
installations (diverting function).
The limit stop switch can be used for start/stop
of a fan or a circulation pump in an entirely open
valve.

Ordering AMZ 112 2-port valve/actuator


kVS Max. ∆p Code No.
DN Connection
(m3/h) Valve 230 V 24 V
15 17 Rp ½ 082G5501 082G5520
20 41 Rp ¾ 082G5502 082G5521
25 68 Rp 1 082G5503 082G5522
6 bar
32 123 Rp 1¼ 082G5514 082G5523
40 198 Rp 1½ 082G5515 082G5524
50 290 Rp 2 082G5516 082G5525

AMZ 113 3-port valve/actuator


kVS Max. ∆p Code No.
DN Connection
(m3/h) Valve 230 V 24 V
15 3,8 Rp ½ 082G5511 082G5526
20 7,7 Rp ¾ 6 bar 082G5512 082G5527
25 11,6 Rp 1 082G5513 082G5528

DEN-SMT/SI VD.HC.N5.02 © Danfoss 05/2013 1


Data sheet ON/OFF Zone valves AMZ 112 & AMZ 113

Application principles

ON/OFF control of Radiator -, under floor heating and zone systems (night set back).

AB-QM AB-QM

ON/OFF control of one or more heating/surfaces.

310

Priority control of hot water supply and heating - diverting function.

Priority control of boiler and solid fuel installations - diverting function.

2 VD.HC.N5.02 © Danfoss 05/2013 DEN-SMT/SI


Data sheet ON/OFF Zone valves AMZ 112 & AMZ 113

Technical data Actuator


AMZ 112 AMZ 112 AMZ 113
Type
(230 VAC, DN 15-32) (230 VAC, DN 40/50) (230 VAC)
Supply voltage 230 V, 50/60 Hz
Micro switch 1 (1) A, 250 VAC
9,3 VA @ By operation 9 VA @ By operation 9,3 VA @ By operation
Power consumption 5 VA @ Open position 5 VA @ Open position 5 VA @ Open position
0 VA @ Closed position 0 VA @ Closed position 0 VA @ Closed position
Electrical protection class Class II acc. EN-60335-1
Enclosure IP 44 acc. IEC 60529
Rotation time 30 sec/90° 32 sec/90° 60 sec/90°
Ambient temperature 0 ... 50 °C
Humidity RH 0 % ... 80 % Non condensed
Wire 4 × 0.5 mm2, L= 1.5 m 4 × 0,5 mm2, L= 2 m 4 × 0,5 mm2, L=1,5 m

AMZ 112 AMZ 113


Type
(24 VAC, DN 15-32) (24 VAC)
Supply voltage 24 V, 50 Hz
Micro switch 1 (1) A, 250 VAC
6 VA @ By operation
Power consumption 1 VA @ Open position
0 VA @ Closed position
Electrical protection class Class II acc. EN-60335-1
Enclosure IP 44 acc. IEC 60529
Rotation time 30 sec/90° 60 sec/90°
Ambient temperature 0 ... 50 °C
Humidity RH 0 % ... 80 % Non condensed
Wire 4 × 0,5 mm2; L= 1,5 m 4 × 0,5 mm2; L= 1,5 m

Valve
Type AMZ 112, AMZ 113
Medium temperature 2 … 130 °C
Nominal pressure PN 16
Medium Circulation water/glycolic water up to 30 %
Max. operating torque 8 Nm
Max. ∆p valve 6 bar
Materials
Body - stem Hot stamped brass CuZn40Pb2 Ni plated
Ball Hot stamped brass CuZn40Pb2 Cr plated
Gaskets PTFE - FPM - EPDM
Connection Internal thread Rp ISO 7/1

Sizing

290
k
50
DN
198
k
40
DN

AMZ 112 AMZ 113

DEN-SMT/SI VD.HC.N5.02 © Danfoss 05/2013 3


Data sheet ON/OFF Zone valves AMZ 112 & AMZ 113

Wiring
L N L N
Black (L) OPEN / PORT A Black (L) OPEN / PORT A
1 1
Blue (N) Blue (N)
2 2
Brown (L) CLOSE / PORT B Brown (L) CLOSE / PORT B
3 3
F1A/250V F1A/250V
Red (L) Red (L)
4 4
Out signal OPEN (AMZ 112) Out signal OPEN (AMZ 112)
A+B (AMZ 113) A+B (AMZ113)

AMZ 112/113 SPST switch AMZ 112/113 SPDT switch

L N
Black (L) OPEN / PORT A
1
! Dp Fr
2 Blue (N)

Brown (L) CLOSE / PORT B


3
WARNING! F1A/250V RELAY 230VAC
Red (L)
By controlling electronic pump 4
Out signal OPEN (AMZ112)
(energy saving, pressure controlled) A+B (AMZ113)
use relay because of generating
hight current peaks! ! Dp Fr

AMZ 112/113 SPST switch

Installation positions ! FORBIDDEN !


AMZ 112 - DN15-DN32

AMZ 113 ! FORBIDDEN !

AMZ 112 - DN40-DN50


! FORBIDDEN !

Hydraulic installation Recommended installation of the eletric actuated ball


valve

1. Ball valve
2. Strainer
3. AMZ

4 VD.HC.N5.02 © Danfoss 05/2013 DEN-SMT/SI


Data sheet ON/OFF Zone valves AMZ 112 & AMZ 113

Manual control
Manual control - AMZ 1 12, DN15-DN32 Position indication

Manual control - AMZ 1 13 Position indication

Manual control - AMZ 1 12, DN40, DN50 Position indication


1 2 3
OPEN CLOSE

MA
N

90°

90°

Note:
When button for manual
operating is in <MAN>
position, actuator stays in
temporary position
irrespective of control signal.

DEN-SMT/SI VD.HC.N5.02 © Danfoss 05/2013 5


Data sheet ON/OFF Zone valves AMZ 112 & AMZ 113

Dimensions
AMZ 112, DN 15-32
125 78

60,2
B
A

D
C
Connection A B C D kVS Weight
DN
G mm (m3/h) (kg)
15 ½” 139 121,5 17,5 63 17 0,84
20 ¾” 144 124,5 19,5 57 41 0,81
25 1” 153 129,5 23,5 68 68 0,97
32 1¼” 163 134,5 28,5 81 123 1,24

AMZ 112, DN 40/50


125 78

93
B
A

D
C

Connection A B C D kVS Weight


DN
G mm (m3/h) (kg)
40 1½” 212 176 36 119 198 2,32
50 2” 228 184 44 135 290 3,23

AMZ 113

125 78
60,2

99,8
B
A
C

Connection A B C D kVS Weight


DN
G mm (m3/h) (kg)
15 ½” 152 118 34 64 3,8 0,88
20 ¾” 164 125 39 74 7,7 1,10
25 1” 175 130 45 87 11,6 1,40

6 VD.HC.N5.02 © Danfoss 05/2013 DEN-SMT/SI


Data sheet ON/OFF Zone valves AMZ 112 & AMZ 113

DEN-SMT/SI VD.HC.N5.02 © Danfoss 05/2013 7


Data sheet ON/OFF Zone valves AMZ 112 & AMZ 113

8 VD.HC.N5.02 Produced by Danfoss A/S © 05/2013

You might also like