Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

amz112_113

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

Data sheet

ON/OFF zone valves


AMZ 112, AMZ 113
Description The ON/OFF zone valves can be applied
together with most Danfoss Room Thermostats,
particulary type RET 230 (single poled switch)
and programmable Room Thermostats type
RET 1000/2000. Other compatible room
thermostats are available, please see
www.danfoss.com/heating for details.
Features:
• Indication of actual valve position;
• LED indication of turning direction;
• Manual valve turning mode enabled by a
permanent clutch;
• No damage in case of valve blocking;
• Silent and reliable operation;
• Maintenance free;
• Integrated AUXILIARY switch;
• LED indication of activated AUXILIARY switch.
Main Data:
• Nominal voltage:
- 230 V AC, 50/60 Hz
- 24 V AC, 50/60 Hz
The ON/OFF zone valves type AMZ 112 and • Rotation angle 90°
AMZ 113 are typical used in connection with: • Actuator running speed
• Domestic and commercial central heating - AMZ 112
applications - DN 15-20: 30 sec / 90°
• Domestic hot water applications - DN 25-50: 60 sec / 90°
• Solar energy plants - AMZ 113
• Priority control of hot water supply and - DN 15: 30 sec / 90°
heating (diverting function) - DN 20-32: 60 sec / 90°
• Priority control of boiler and solid fuel • Control signal: 2-point
installations (diverting function).

Ordering AMZ 112 2-port valve/actuator AMZ 113 3-port valve/actuator


kVS Code No. kVS Code No.
DN Connection DN Connection
(m3/h) 230 V 24 V (m3/h) 230 V 24 V
20 28 Cu-Cu 22 - 082G5427 15 4,3 Rp ½ 082G5418 082G5412
15 17 Rp ½ 082G5406 082G5400 20 8,3 Rp ¾ 082G5419 082G5413
20 28 Rp ¾ 082G5407 082G5401 25 13 Rp 1 082G5420 082G5414
25 39 Rp 1 082G5408 082G5402 32 21 Rp 1¼ 082G5421 082G5415
32 84 Rp 1¼ 082G5409 082G5403
40 156 Rp 1½ 082G5410 082G5404
50 243 Rp 2 082G5411 082G5405

© Danfoss | 2016.02 VD.IR.J5.02 | 1


Data sheet ON/OFF Zone valves AMZ 112 & AMZ 113

Technical data Actuator


Power supply V 24 AC or 230 AC
AMZ 112: 2,5
Power consumption VA
AMZ 113: 3,5
Frequency Hz 50/60
Running speed 1) sec/90° 30, 60
Control input 2-point
Operating torque Nm 5, 10, 15
Rotation angle 90 °
Auxiliary switch adjustable 0-90°
Auxiliary switch max. load A 6 (24V AC, 230V AC)
Max. medium temperature 110
Ambient temperature °C 0 … 50
Storage and transport temperature −10 … 80
Protection Class II according to EN 60730-1
Grade of enclosure IP42 according to EN 60529
AMZ 112 728
Weight g
AMZ 113 906
Color / material dark grey/PC
Low Voltage Directive 2006/95/EC
EMC-Directive 2004/108/EC
- marking in accordance with standards RoHS II: 2011/65/EU
Applied standards: EN 60730-1, EN 60730-2-14
1) 5 Nm is 30 sec/90°; 10, 15 Nm is 60 sec/90°

Valve AMZ 112


DN 15 20 25 32 40 50
Nominal pressure PN 40 25
Flow (kVS) m3/h 17 28 39 84 156 243
Medium temperature °C 2 … 130 (Actuator max. 110)
Medium Drinking water, water, glycol ≤50%, air, nonaggressive fluids
Max. operating Δp bar 6
Valve neck ISO 5211
Connection Internal thread Rp ISO 7/1
Certifications and standards CE-PED – CSA - GOST
Materials
Body CW 617 N UNI EN 12165
Ball, Stem CW 614 N UNI EN 12164
Antifriction ring PTFE

Valve AMZ 113


DN 15 20 25 32
Nominal pressure PN 40
Flow (kVS) m3/h 4,3 8,3 13 21
Medium temperature °C 2 … 130 (Actuator max. 110)
Medium Drinking water, water, glycol ≤50%, air, nonaggressive fluids
Max. operating Δp bar 6
Valve neck ISO 5211
Connection Internal thread Rp ISO 7/1
Certifications and standards CE-PED – CSA - GOST
Materials
Body CW 617 N UNI EN 12165
Ball, Stem CW 614 N UNI EN 12164
Antifriction ring PTFE

2 | © Danfoss | 2016.02 VD.IR.J5.02


Data sheet ON/OFF Zone valves AMZ 112 & AMZ 113

Application principles

82G318.10
DEN-SMT
DEN-SMT
ON/OFF control of Radiator -, ON/OFF control of one or more heating/
under floor heating and zone systems (night set back). surfaces.

DEN-SMT

Priority control of hot water supply and heating - Priority control of boiler and solid fuel installations -
diverting function. diverting function.

Installation positions

Hydraulic installation Recommended installation of the eletric actuated ball


valve

1. Ball valve
2. Strainer
3. AMZ

VD.IR.J5.02 © Danfoss | 2016.02 | 3


Data sheet ON/OFF Zone valves AMZ 112 & AMZ 113

Manual override


Close Open

AMZ 112 AMZ 113

LED signalling
LED orange (Rotate Left)
LED red
LED orange (Rotate Right)

AMZ 112/113
LED color 2-point
orange Rotation Left / Right
red AUX switch activation

Wiring
N L 230 V (24 V) ~
Under cover
0 1

Direct/Inverse function
1 0
Jumper Wiring Open Port
1 2 3 4 5 L=2 AB-B
0 1 DIR
1 2 3 4 5 6 L=2&3 AB-A

NL 1 0 INV L=2 AB-A


L=2&3 AB-B
2-point+switch

4 | © Danfoss | 2016.02 VD.IR.J5.02


Data sheet ON/OFF Zone valves AMZ 112 & AMZ 113

Dimensions
AMZ 112 - Copper
connection

AMZ 112
Connection L B N
DN
G mm
20 Cu-Cu 22 111,5 33 37

AMZ 112

Connection L B N
DN
G mm
15 ½” 61 29,4 37
20 ¾” 69,5 33 37
25 1” 84,5 37,2 42
32 1¼” 98,5 47,5 42
40 1½” 110 53 42
50 2” 130 64 48

VD.IR.J5.02 © Danfoss | 2016.02 | 5


Data sheet ON/OFF Zone valves AMZ 112 & AMZ 113

Dimensions (continuous)
AMZ 113

Connection L B N
DN
G mm
15 ½” 64,5 38 49,5
20 ¾” 78 42 59,5
25 1” 97 46,5 74,5
32 1¼” 118 61,25 95,5

6 | © Danfoss | 2016.02 VD.IR.J5.02


Data sheet ON/OFF Zone valves AMZ 112 & AMZ 113

VD.IR.J5.02 © Danfoss | 2016.02 | 7


Data sheet ON/OFF Zone valves AMZ 112 & AMZ 113

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alterations can be made without subsequential changes being necessary eady agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

8 | © Danfoss | DHS-SRMT/SI | 2016.02 VD.IR.J5.02