Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Fact Sheet: Criteria For Large-Capacity On-Site Sewage Disposal Systems

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

Nevada Division of Environmental Protection

Bureau of Water Pollution Control


Groundwater Protection Branch
Underground Injection Control Program

FACT SHEET
WTS – 23
Criteria for Large-Capacity On-site Sewage Disposal Systems
Including Commercial and Multiple-Dwelling Structures
(Ref: NAC 278, NAC 444, NAC 445A) Rev. June 2004

Note: For plan submittals, please complete the checklist attached to this document

1. General
In Nevada, a large-capacity individual sewage disposal systems (ISDS) is defined as: 1) a system
having a capacity equal to or greater than 5,000 gallons per day (gpd), and 2) as one large tank or a
group of smaller tanks under one ownership for a single or multiple-dwelling structure(s) on a
common property. These systems are referred to as individual sewage disposal system in the
regulations as follows:
NAC 444.764 "Individual sewage disposal system" defined. (NRS 439.200, 444.650)"Individual sewage disposal system" means a
single system of sewage treatment tanks and effluent disposal facilities serving:
1. A single-family dwelling; or
2. In the case of a commercial system, one or more buildings that are not used as single-family dwellings.

Generally, for purposes of this and other documents, we will refer to these systems as large-capacity
septic systems (LCSS).

The requirements below are to be met for design and installation of LCSS, and may be more
stringent than requirements found in NAC 444. At a minimum, NAC 444 requirements must be met
unless requirements in WTS-23 are more stringent, then those requirements supersede those of NAC
444. The minimum design criteria for large-capacity septic systems are to be complied with unless
approval for revision is obtained from the Nevada Division of Environmental Protection (NDEP),
Bureau of Water Pollution Control (BWPC). These criteria are not meant to supersede or circumvent
any existing state or local policy, statute or regulation. The BWPC reserves the right pursuant to
regulations to require further site characterization and additional design criteria.

All plans and specifications submitted to the Division require an Engineer’s stamp, signature and
date in accordance with NAC 625.565. A letter with the engineer’s stamp, signature and date
shall be submitted to the Division to certify installation pursuant to plans and specs within ten
(10) days after installation.

All ISDSs are required to be located on the same lot as the building or structure that the system
serves. The BWPC may approve the use of a part of an abutting lot to provide additional space for
an ISDS or any part thereof, however the owner must demonstrate compliance with subsection a. and
b. of NAC 445A.792(1). And adequate reserve drain field space must be shown on plans.

The owner/operator of a facility with a large-capacity septic system is required to obtain a


permit to operate with the BWPC as required by Nevada law NRS 445A.465. Depending on
the size and type of system would be covered under a general permit, GU9201, or issued an
individual permit. See the permit fact sheet for criteria under general permit GU9201.

For abandonment requirement of large-capacity septic systems - see Section 6 of this document.

333 West Nye Lane, Room 129


Carson City, Nevada 89706-0851
Ph: 775-687-9418
Underground Injection Control Program
WTS-23 Large-Capacity Septic Systems Fact Sheet

2. Site Evaluation Information Required:


a) A minimum of two percolation test holes. Percolation tests must be completed in
accordance with NAC Chapter 444 including NAC 444.796. Infiltration/permeability tests
may be used to supplement percolation test findings, but they may not be used as a
substitute. These pits must be excavated to a minimum of five feet below the bottom of the
proposed disposal system elevation, and within the area of the proposed soil absorption
system. The following factors must be evaluated:

1) Depth to bedrock, which is any rock that can not be excavated by power equipment, or is so
slowly permeable that it will not transmit effluent, or has open fractures or solution
channels.
2) Depth to estimated high groundwater level, which is the highest elevation to which soil is
saturated, as observed as a free water surface, or has been saturated as may be indicated by
mottling.
3) Depth to limiting soil layer, which is soil based on observed characteristics could have a low
percolation rate, i.e. caliche.
4) Thickness and texture of each soil layer encountered.
5) General color and color variation (i.e. mottling).
6) Other prominent features such as structure, roots, fines etc.

b. The land slope and amount of suitable area for subsurface disposal.

c. If not determined under Section b above, determine from existing well, or other means, the depth
to the seasonal high groundwater level at the proposed leach field site(s).

d. The location and distance to wells and sewage systems on the lot of interest, and surrounding
lots. If the lots are vacant, the plot plan must so indicate

3. Site and ISDS Map, and Documentation Requirements


a. Name, address and telephone number of Nevada registered professional engineer.
b. Engineer wet stamp, signature and date on map.
c. Elevation Contour lines at a minimum interval of 5 feet. The direction of north clearly indicated.
Contours must cover the entire project area.
d. Indicate the location of all components of the septic system. If more than one septic system on
property, identify the location and components of each system.
e. Location of the percolation and boring test holes
f. Location of all domestic and/or municipal water supply wells on the property and within 200
feet of the property.
g. The 50-year flood zone must be delineated, or a statement must be made that the property is not
within a flood zone.
h. The distance within 500 feet to any watercourse (pond, lagoon, stream, etc.). If none, so
indicate.
i. Indicate that the local government will be able to dispose of septage from septic tank(s) and
septage pumping will be done by a permitted contractor (as per NAC 444.820).
j. Indicate all setbacks on the map.
k. The distance to city sewers from the nearest edge of the property line. If there are none, the plot
plan must so indicate.
l. The maximum slope across the absorption system area.

Page 2 of 12
Underground Injection Control Program
WTS-23 Large-Capacity Septic Systems Fact Sheet

m. The location of the reserve absorption area, which must be of a size not less than the size of the
primary absorption area.
n. The location of the source of water to be used by the dwelling units, including, without
limitation, a well or other source approved by the administrative authority.
o. The location of the fence or other structures that will be used to protect the tanks, lines, and
adsorption field.
p. Estimated groundwater flow direction.

If not displayed on the map, please provide Onsite Wastewater Disposal System Notes referencing
construction and installation standards that shall be followed, such as but not limited to, the UPC and
Nevada Administrative Code Chapters 278 and 444. These standards should address the following
minimum requirements:

a. Water and sewer line separations; ref. NAC 445A.677


b. All joints shall be watertight
c. Septic tank
1) Level installation
2) Leak testing
d. Disposal field
1) Breaking up of impermeable layers within 5-feet of bottom of proposed adsorption bed.
2) Located in unshaded, unobstructed area
3) No pavement, evaporation inhibiting material, or vehicular traffic shall be atop the disposal
field
4) Type of distribution pipe material used
5) Slope of perforated distribution pipe and pipe bends
6) Type of fill materials to be used
7) Bottom of disposal field shall be level
e. Distribution Box
1) Design shall ensure equal flow to each leach line within the field
2) Installation shall be on a level, concrete slab
f. The discharge of surface, rain, and other clear water into an ISDS is prohibited; ref. NAC
444.818

4. Septic Tank Requirements


a. All liquid waste and wastewater shall discharge into the septic tank. Roof, footing, garage and
surface water drainage and cooling and process water is prohibited and shall be excluded.

b. The septic tank shall be located so that it is readily accessible. The following are minimum
horizontal separation distances that must be provided between the tank and the features listed
below:

1. Building or structures 8'


2. Property lines 10'
3. Lakes, streams or watercourse 100'
4. Water supply wells 100'
5. Public water supply wells 150’
6. Water supply wells, not sealed for the first 50 feet 150'
7. Water supply lines (mains & laterals) 10'

Page 3 of 12
Underground Injection Control Program
WTS-23 Large-Capacity Septic Systems Fact Sheet

c. The septic tank shall be constructed of sound and durable material not subject to excessive
corrosion or decay and structurally capable of supporting the loads to which it will be subjected.
The tank shall be watertight.

d. NAC Chapter 444 should be reviewed for the specific requirements for septic system
construction specifications not found in this document.

e. The size of a large-capacity septic tank shall be determined by the requirements found in
NAC 444.8308, NAC 444.832, and NAC 444.8312; whichever is appropriate for the
type of facility. The size of the tank(s) shall be determined by the largest calculated flow based
on either occupancy flow (section f below) or fixture unit count.

f. The following sewage flow rates should be used when existing or closely related data is not
available.

TYPE OF OCCUPANCY UNIT GALLONS PER DAY


1. Airports 15 per employee
5 per passenger
2. Auto washers Check with equipment manufacturer
3. Bowling alleys (snack bar only) 75 per lane
4. Camps:
Campground with central
comfort station 35 per person
with flush toilets, no showers 25 per person
Day camps (no meals served) 15 per person
Summer and seasonal 50 per person
5. Churches (Sanctuary) 5 per seat
with Kitchen waste 7 per seat
6. Dance halls 5 per person
7. Factories
No showers 25 per employee
With showers 35 per employee
Cafeteria, add 5 per employee
8. Hospitals 250 per bed
Kitchen waste add 25 per bed
Laundry waste add 40 per bed
9. Hotels (no kitchen waste) 60 per bed -(2 person bed)
10. Institutions (Resident) 75 per person
Nursing home 125 per person
Rest home 125 per person
11. Laundries, self-service
(minimum 10 hours per day) 50 per wash cycle
Commercial Per manufacturer's specifications
12. Motel 50 per bed space
with kitchen 60 per bed space
13. Offices 20 per employee
14. Parks, mobile homes 250 per space
picnic parks (toilets only) 20 per parking space
recreational vehicles -
without water hook-up 75 per space
with water and sewer hook-up 100 per space

15. Restaurants - cafeterias 20 per employee


toilet 7 per customer

Page 4 of 12
Underground Injection Control Program
WTS-23 Large-Capacity Septic Systems Fact Sheet

kitchen waste 6 per meal


add for garbage disposal 1 per meal
add for cocktail lounge 2 per meal
kitchen waste -
disposable service 2 per meal
16. Schools - Staff and office 20 per person
Elementary students 15 per person
Intermediate and high 20 per student
with gym and showers, and 5 per student
with cafeteria, add 3 per student
Boarding, total waste 100 per person
17. Service station, toilets 1000 for 1st bay
500 for each additional bay
18. Stores 20 per employee
public restrooms, add 1 per 10 sq.ft. floor space
19. Swimming pools, public 10 per person
20. Theaters, auditoriums 5 per seat
drive-in 10 per space

5. Disposal Design
A. Absorption Trench

1) The absorption trench gives additional treatment to the sewage from the septic tank. Disposal
trenches shall treat only domestic sewage.

2) NAC Chapter 444 should be reviewed for the specific requirements for septic system
construction specifications not found in this document.

3) The following are minimum horizontal separation distances that must be provided between the
trench and the features listed below:

1. Building or structures 8'


2. Property lines 10'
3. Lakes, streams or watercourse 100'
4. Water supply wells (sealed to 50 feet) 100'
5. Public water supply well 150’
6. Water supply wells, not sealed for the first 50 feet 150'
7. Water supply lines (mains & laterals) 25'

4) The disposal trench system shall be designed in accordance with:

5
Q=
t

where Q = rate of sewage application (gallons per sq. ft. per day) and t = percolation
rate (minutes per inch).

a) Septic tank capacity divided by Q (application rate) equals the area in square feet
of absorption area required.

Page 5 of 12
Underground Injection Control Program
WTS-23 Large-Capacity Septic Systems Fact Sheet

b) The maximum useable sidewall is three (3) feet. Thus the maximum absorption
area allowed per linear foot of trench is six square feet.

5) For domestic sewage from commercial or industrial sewage disposal systems, or systems
servicing more than one residential dwelling, the minimum or “fastest” acceptable percolation
rate is 10 minutes per inch. The Division may approve faster rates depending on site conditions
and characteristics. The Maximum percolation rate is 60 min/inch. Soils with fast perc rates
may require special trench design if a shallow water table is present.

6) Each absorption trench system shall have a minimum of two (2) trenches.

7) The maximum length of any one trench shall be 110 feet.

8) The bottom of the absorption trenches shall be at least eighteen (18) inches and no more than
sixty (60) inches below the finished grade.

9) Plans must show a reserve absorption area equal in size to the primary absorption area.

10) Leach field inspection pipes are required for all newly constructed large-capacity septic systems
(with tank sizes 4,000 gallons and above). For those existing systems that do not have
inspection pipes, inspection pipes may be required if signs of failure develop.

B. Absorption Bed

1) The information described under items 5a.1, 5a.2 and 5a.3 apply.
5
2) The disposal bed shall be designed in accordance with: Q=
t

Where Q = rate of sewage application (gallons per sq. ft. per day) and t = percolation rate
(minutes per inch).
a. Septic tank capacity divided by Q (application rate) equals the area in square feet of
absorption area required.
b. The absorption area required must equal the area of the bottom of the disposal bed.

3) For commercial or industrial domestic sewage disposal systems, or systems servicing more than
one dwelling, the minimum or “fastest” acceptable percolation rate is 10 minutes per inch.
Maximum is 60 minutes per inch.

4) Each absorption bed shall have a minimum of two distribution lines.

5) The maximum length of any distribution line shall be 110 feet.

6) Distribution lines within an absorption bed shall be uniformly spaced no more than six (6) feet
nor less than four (4) feet apart.

7) Distribution lines within an absorption bed shall be placed no more than three (3) feet, nor less
than one and one-half (1 ½) feet, from the sidewall of the bed.

8) The bottom of the absorption bed shall be at least eighteen inches and no more than sixty inches
below the finished grade.

Page 6 of 12
Underground Injection Control Program
WTS-23 Large-Capacity Septic Systems Fact Sheet

C. Dosing Tanks.

1) Construction and materials shall conform to the provisions of NAC 444.800 to 444.812,
inclusive.

2) Dosing tanks shall be provided where there are over 500 lineal feet of distribution lines in the
absorption system (trench or bed).

3) Dosing tanks shall have sufficient capacity to distribute sewage equally to all parts of the
absorption system at 3 to 4 hour intervals. Sufficient capacity is equivalent to 60 to 75 percent
of the interior volume of the tile in the system.

4) Siphons shall be automatic and must be of an alternating type when the length of the distribution
lines is over 1,000 feet. Alternating siphons must discharge to separate disposal areas.

5) Dosing tanks shall be constructed in a manner that will permit venting the absorption system.

6) Each dosing tank or compartment shall be provided with an access opening located to facilitate
repair or adjustment of the siphon. The openings shall be over the siphon or siphons and
conform to the provisions of subsection 6 of NAC 444.800.

6. Large-Capacity Septic System Abandonment


NAC 444.818(9) states, "with the approval of the administrative authority, an abandoned septic tank
may be pumped, removed, and disposed of. An abandoned tank must be filled with dirt or sand after
all sewage and sludge have been removed and disposed of in an approved manner. An excavation
site created by the removal of a septic tank must be backfilled with suitable material that is
compatible to the intended future use of the site". In addition the Nevada Division of Environmental
Protection requires the following:

Any pumps/manhole covers/frames shall be removed and sewer lines disconnected and plugged
or capped;
If a diversion box and/or dosing tank exist, they shall be filled with dirt or sand and the sewer
lines disconnected and plugged or capped;
Sewer lines and distribution lines from a distribution box shall be disconnected and plugged or
capped, and the boxes filled with sand;
Outlets, including monitoring ports to the leach field shall be plugged or capped;
All monitoring wells shall be abandoned in conformance with the requirements of the Nevada
Division of Water Resources;
If applicable, any addition tanks, i.e. grease, etc., shall be filled or removed and lines plugged or
capped; and
The holder of the permit shall submit to the Bureau of Water Pollution Control photo
documentation and a certification that the facilities were abandoned according to the above
noted requirements.

Recommended reference material for:

Alternative absorption system: The term includes, without limitation, 1) capping fill trench,
2) stepped network of trenches utilizing relief lines, 3) leaching bed, 4) sand filter and 5)
elevated mound system
Onsite Wastewater Treatment Systems Manual - EPA/625/R-00/008

Page 7 of 12
Underground Injection Control Program
WTS-23 Large-Capacity Septic Systems Fact Sheet

APPENDIX

I. Responsibilities of septic system users

The key responsibilities of the Permittee/user in ensuring the best operation of an existing or new septic
tank/SWIS system include the following:

• Using household cleansers in moderation. Excessive use of household cleansers, disinfectants, and other common
products can kill bacteria residing in the septic tank and the soil adsorption field. Used in moderate amounts and
according to label directions, however, cleaners and disinfectants can be flushed into the wastewater system with no
significant impacts. The wastewater stream dilutes the product, and organic material adsorbs it. Slug loading
(excessive, instantaneous loadings) of household cleaners can be lethal to septic system bacteria, but normal follow-up
usage usually reestablishes the tank's bacterial population within a few hours.
• Avoiding disposal of toxic and hazardous materials in the wastewater stream. Many common household products have
toxic properties and should never be poured down the drain. The list includes drugs and antibiotics, solvents, paints,
varnishes, photography chemicals, weed killers, and insecticides. All of these products have the potential to wipe out
septic system bacteria and percolate into ground water supplies.
• Curbing the use of drain cleaners and openers. Products aimed at unclogging indoor wastewater pipes contain strong
acids or alkalis as the active ingredient. Used according to the label directions, they can be effective in removing clogs
of organic matter in indoor drainpipes. Most product labels warn, however, that the product is caustic or corrosive to
pipes and can be hazardous to the user if applied improperly. A controlled study concluded that as little as 1.3 ounces
of a name brand drain cleaner could destroy the bacteria population in a 1,000-gallon septic tank. This amount is within
the general range of normal usage for some people. Bacteria populations in the tank will recover in a few days if the
system inputs return to normal levels.
• Disposing of solids appropriately. Items such as cigarette butts, condoms, sanitary napkins, paper towels, and kitty litter
should never be flushed or washed down the toilet or sink. Septic tanks are not designed as a disposal receptacle for
these wastes. They can clog drainpipes and cause excessive and rapid sludge buildup in the tank.
• Keeping fats, oils, and grease out of kitchen drains. Fats, oils, and grease are natural by-products of cooking meats and
other foods. Grease washed down the drain can stick, accumulate, and in some cases block wastewater drain pipes and
the inlet and outlet structures in septic tanks. Food wastes should be scraped from plates and utensils and discarded as
solid waste.
• Avoiding the use of a garbage disposal unless the treatment system is designed for one. Homes with garbage disposals
generally have 20 to 28 percent higher biochemical oxygen demand (BOD) and 25 to 40 percent higher suspended solid
loadings to septic tanks than homes without disposals. These significant contributions of organic matter require special
consideration when sizing and installing a septic tank or soil absorption system.
• Conserving water. To function at peak efficiency, the septic tank needs to provide a quiescent environment and
adequate detention time (i.e., more than 24 hours) for the solids and floatable matter to separate from the wastewater.
Limiting water flows and timely repair of leaking fixtures help maintain these conditions and prevent overloading of
the soil adsorption field.

Page 8 of 12
Underground Injection Control Program
WTS-23 Large-Capacity Septic Systems Fact Sheet

SUBMITTAL CHECKLIST – Attachment – Large Capacity Septic System


Engineer’s Stamp WTS-23: LARGE CAPACITY SEPTIC TANK AND DISPOSAL SYSTEMS
Project:

Contact:

Phone:

General Additional Notes:

Lot Size:

Type of Facilities served by the septic system(s) on property:

Number and size of Septic Tank(s) to be Installed:

Number and size of existing Septic Tank(s) on property:

Total capacity of all Septic Tanks on property, in gallons:

Fixture Count – Current: Proposed:

Number of people served by system(s): Current or typical: and Maximum:

Please circle one answer for each question below. All questions must be answered. If N/A, please explain.
N/A Yes No Are all the system parts on one property/lot? If no, explain and provide legal documents.

N/A Yes No Is a water well on site? Depth of well(s): Sealed to:

Water well is used for? Domestic Irrigation Both Other

N/A Yes No Is a community/public sewer system greater than 400’ to the nearest property line?

N/A Yes No Is the project served by a community water supply system?

N/A Yes No Is the site located outside the 50-year or 100-year Flood Zone?
Will all of the wastewater treatment system be located in or under areas NOT subjected to vehicular
N/A Yes No
traffic?
N/A Yes No Do local ordinances or zoning require special design of septic systems? (i.e. nitrate removal)

Page 9 of 12
Underground Injection Control Program
WTS-23 Large-Capacity Septic Systems Fact Sheet

Percolation Information

N/A Yes No Are the soils classified from surface to 10 feet in depth?

N/A Yes No Submitted the depth to an impermeable soil layer, if any?

N/A Yes No Submitted depth to seasonal high groundwater, if any?

N/A Yes No Submitted percolation test results in tabular format?

N/A Yes No Did the percolation test procedure follow NAC 444.796?

N/A Fast Slow Was a Fast or Slow (presoaking) Percolation Test used as required by NAC 444.7962?
If percolation rate < 10 min/inch, was 10 min/inch used as percolation rate to determine rate
N/A Yes No
of application?
N/A Yes No Are locations identified on enclosed map?

N/A Yes No Is there a minimum of two test holes for each proposed disposal area?

N/A Yes No Are the holes dug to the proposed bottom of the disposal field?
Are the test results indicative of the driest/wettest time of year?
N/A Yes No
i.e. perhaps Summer/Fall or Winter/Spring? Identify
Building Plans (only for commercial and non-dwelling units)

N/A Yes No Submitted plans showing plumbing fixtures connecting to septic system(s)?

Utility Plan or equal

N/A Yes No Is the Project Name displayed?

N/A Yes No Are contours at a minimum interval of 5 feet?

N/A Yes No Does the plan show sewer lines, cleanouts, septic tank, disposal field etc.?

N/A Yes No Is the cross-section of the disposal field displayed?

N/A Yes No Are notes for the septic system displayed?

N/A Yes No Is there a note stating the potable water supply source (well or agency)?

N/A Yes No If the potable water source is a well, submit the well log(s)

N/A Yes No Within ¼ mile radius of septic system, have all water wells been located?

N/A Yes No Has the groundwater flow direction been determined?

Septic Tank – if no proceed to next section

N/A Yes No Are calculations for sizing the tank(s) submitted?

N/A Yes No For dwelling occupancies, is the volume sized per UPC Table K-2?
For non-dwelling occupancies, is the volume sized per UPC Table K-3 or UPC Table K-2
N/A Yes No
whichever is greater?
N/A Yes No Is the clearance to water supply lines greater than 10 feet?

N/A Yes No Is the distance to the nearest public well greater than 200 feet?

Page 10 of 12
Underground Injection Control Program
WTS-23 Large-Capacity Septic Systems Fact Sheet

N/A Yes No Is the distance to the nearest surface water greater than 100 feet?

N/A Yes No Is the distance to the nearest building greater than 8 feet?

N/A Yes No Is the distance to the nearest property line greater than 10 feet?
Is it noted that the septic tank shall be designed and constructed in conformance with NAC
N/A Yes No
Chapter 444 and UPC?
N/A Yes No Do plans state risers will be installed around each tank access hole?

—CONSTRUCTION—supply verification of the following

N/A Yes No Does the tank have 2 compartments minimum?

N/A Yes No Is the septic tank approved by NDEP?

N/A Yes No —Dosing Tank—(if ‘no’ proceed to next section)

Why is a dosing tank required for this system? ____________________________________


a) It is necessary to raise the elevation of the wastewater for further treatment or disposal of
sewage
b) Intermittent dosing of the disposal field is desired

c) A pressure distribution system is used

d) Is there greater than 500 lineal feet of distribution lines in the SOA?

N/A Yes No Submitted volume calculation if dosing tank required?


Is the dosing rate determined? If greater than 6-8 times/24 hrs., have calculations for
N/A Yes No
increasing the size of absorption field been submitted?
— Distribution Box —

N/A Yes No Do plans state that D-Box will be level, and will be tested after installation?

N/A Yes No Is the D-Box a type that can short circuit (straight flow through) Does it require a baffle?

N/A Yes No Statement in letter fill around D-Box must be hand-packed – no heavy equipment use!!

N/A Yes No —Disposal Field—


Is there suitable area for a back-up disposal field in the event that the original disposal field
N/A Yes No
fails?
N/A Yes No Is the most porous or absorptive portion of soil formation utilized?
Is it noted that any impermeable layer within 5 ft. of the bottom of disposal field shall be
N/A Yes No
broken up?
N/A Yes No Is disposal only from domestic sewage wastes?

N/A Yes No Is the distance to the nearest surface water greater than 100 feet?

N/A Yes No Is the distance to the nearest public well greater than 200 feet?
Is the distance to nearest water supply well that has no sanitary seal the first 50’ greater than
N/A Yes No
150’?
N/A Yes No Is the distance to any building is greater than 8 feet?

Page 11 of 12
Underground Injection Control Program
WTS-23 Large-Capacity Septic Systems Fact Sheet

N/A Yes No Is the distance to any property line greater than 10 feet?

N/A Yes No Is the distance to any water supply line greater than 25 feet?
Is the depth from the bottom of the disposal field to the maximum seasonal high groundwater
N/A Yes No
greater than 4 feet? If no, indicate alternative method on plans.
N/A Yes No Is it located in an unshaded, unobstructed area?

N/A Yes No Is it noted that no pavement or evaporation inhibiting material shall be atop the field?

N/A Yes No Is it located outside a noncompacted filled area?

N/A Yes No Is it located outside an area subject to vehicular traffic?

N/A Yes No Is Q=5/SQR(t) used to determine the rate of disposal?


Was a 10 min/inch minimum percolation rate used for sizing the disposal field for
N/A Yes No
commercial, industrial, or multi-residential dwellings?
N/A Yes No Is the gravel size in the field/trench stated on plans?

N/A Yes No Trench? (If ‘no’ proceed to next section)

N/A Yes No Is only the sidewall height used for calculating the available absorption area?

N/A Yes No Is the maximum sidewall height used in determining the absorption area 3 feet?

N/A Yes No Are there a minimum of 2 trenches?

N/A Yes No Is the maximum distribution line length 110 feet?

N/A Yes No Is the distribution line spacing greater than 4 feet and less than or equal to 6 feet?

N/A Yes No Leaching Chambers? (if ‘no’ proceed to next section)

N/A Yes No Submitted a calculation to determine the number of chamber sections required?

Construction Installation Procedure

N/A Yes No Is it noted the septic tank shall be installed level?

N/A Yes No Is it noted the septic tank shall be leak tested?

N/A Yes No Is it noted the bottom of the disposal field shall be level?

N/A Yes No Is it noted all bends in pipe fitting will be 45 deg? (No 90 deg bends.)

Page 12 of 12

You might also like