Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
Download as pdf or txt
Download as pdf or txt
You are on page 1of 64

Atlas Copco

Refrigerant compressed air dryers

FD 120, FD 150, FD 185, FD 220, FD 245, FD 285

Instruction book
Atlas Copco
Refrigerant compressed air dryers

FD 120, FD 150, FD 185, FD 220, FD 245, FD 285


From following serial No. onwards: CAQ 533 220

Instruction book
Original instructions

Copyright notice
Any unauthorized use or copying of the contents or any part thereof is prohibited.
This applies in particular to trademarks, model denominations, part numbers and drawings.
This instruction book is valid for CE as well as non-CE labelled machines. It meets the
requirements for instructions specified by the applicable European directives as identified
in the Declaration of Conformity.

2012 - 01
No. 2920 7103 80

www.atlascopco.com
Instruction book

Table of contents

1 General description........................................................................................................5

1.1 INTRODUCTION...................................................................................................................................5

1.2 AIR SYSTEM......................................................................................................................................8

1.3 REFRIGERANT FLOW...........................................................................................................................9

1.4 CONDENSATE DRAIN SYSTEM..............................................................................................................10

2 Controller.......................................................................................................................12

2.1 ELEKTRONIKON® REGULATOR.............................................................................................................12

2.2 CONTROL PANEL..............................................................................................................................13

2.3 ICONS AND SYMBOLS USED ON THE DISPLAY..........................................................................................13

2.4 MAIN SCREEN..................................................................................................................................15

2.5 SCROLLING THROUGH ALL SCREENS.....................................................................................................15

2.6 CALLING UP AMBIENT TEMPERATURE....................................................................................................19

2.7 DIGITAL INPUTS................................................................................................................................19

2.8 CALLING UP RUNNING HOURS..............................................................................................................20

2.9 CALLING UP MOTOR STARTS...............................................................................................................20

2.10 CALLING UP MODULE HOURS...............................................................................................................20

2.11 CALLING UP/RESETTING THE SERVICE TIMER .........................................................................................21

2.12 SHUT-DOWN WARNING.......................................................................................................................22

2.13 SHUT-DOWN....................................................................................................................................23

2.14 SELECTION BETWEEN LOCAL, REMOTE OR LAN CONTROL........................................................................24

2.15 CALLING UP/MODIFYING CAN ADDRESS CONTROL..................................................................................25

2.16 CALLING UP/MODIFYING IP, GATEWAY AND SUBNETMASK........................................................................26

2.17 CALLING UP/MODIFYING SERVICE TIMER SETTINGS...................................................................................28

2.18 CALLING UP/MODIFYING THE UNIT OF TEMPERATURE................................................................................28

2.19 CALLING UP/MODIFYING UNIT OF PRESSURE...........................................................................................28

2.20 CALLING UP/MODIFYING DRYER REGULATION MODE.................................................................................28

2.21 CALLING UP/MODIFYING FLOW SWITCH FUNCTION....................................................................................29

2 2920 7103 80
Instruction book

2.22 TEST SCREENS................................................................................................................................30

2.23 ACTIVATING AUTOMATIC RESTART AFTER VOLTAGE FAILURE......................................................................30

2.24 ACTIVATING PASSWORD PROTECTION...................................................................................................31

2.25 SELECTION BETWEEN FLEXIBLE ALARM AND FIXED ALARM.........................................................................31

2.26 CALLING UP/MODIFYING FIXED DEW POINT ALARM SETTING........................................................................32

2.27 CALLING UP/MODIFYING FLEXIBLE DEW POINT ALARM SETTING...................................................................32

2.28 CALLING UP/MODIFYING THE LOW DEW POINT SETTING.............................................................................33

2.29 CALLING UP/MODIFYING HIGH AMBIENT TEMPERATURE SETTING..................................................................33

3 Installation.....................................................................................................................34

3.1 DIMENSION DRAWINGS.......................................................................................................................34

3.2 INSTALLATION PROPOSAL...................................................................................................................39

3.3 ELECTRICAL CONNECTIONS.................................................................................................................41

3.4 PICTOGRAPHS.................................................................................................................................44

4 Operating instructions.................................................................................................46

4.1 WARNINGS......................................................................................................................................46

4.2 INITIAL START..................................................................................................................................46

4.3 STARTING.......................................................................................................................................47

4.4 DURING OPERATION..........................................................................................................................47

4.5 STOPPING.......................................................................................................................................48

5 Maintenance instructions............................................................................................49

6 Problem solving............................................................................................................51

7 Technical data...............................................................................................................55

7.1 SETTINGS OF FUSES.........................................................................................................................55

7.2 REFERENCE CONDITIONS AND LIMITATIONS............................................................................................55

7.3 AIR DRYER DATA..............................................................................................................................56

8 Pressure equipment directives...................................................................................58

2920 7103 80 3
Instruction book

9 Declaration of conformity............................................................................................59

4 2920 7103 80
Instruction book

1 General description

1.1 Introduction

General
FD air dryers remove moisture from the compressed air by cooling the air to near freezing point. This causes
the water to condense. The condensate is automatically drained. The dried air is warmed up before leaving
the dryer.
The dryer can be provided with an optional OSD (a device to separate the oil from the condensate) and
compressed air filters.
An Elektronikon® regulator (ER1) controls and protects the dryer.

General view

Reference Designation
AO Dry air outlet
AI Wet air inlet
ER1 Elektronikon® regulator

2920 7103 80 5
Instruction book

Side view

The front panel and the side panel can be removed for service operations.

Reference Designation
1 Supply cable passage
Dm Manual drain valve
Da Automatic drain connection

6 2920 7103 80
Instruction book

Internal components FD, basic version

Internal components FD, version with options

2920 7103 80 7
Instruction book

Reference Designation
AI Air inlet
AO Air outlet
OSD Oil/condensate separator (option)
GpOSD Pressure gauge of OSD (option)
EWD Electronic water drain
DD DD filter (option)
PD PD filter (option)
1 Service indicator (DD and PD filter)
2 Compressor
3 Condenser
4 Heat exchanger
5 Oil can (OSD and/or filters)
6 Condenser fan
7 Hot gas bypass valve
8 Capillary tube
9 Refrigerant dryer/filter

1.2 Air system

Air flow diagram

Air flow diagram

Description
Compressed air enters heat exchanger (1) and is cooled by the outgoing cold, dried air. Water in the incoming
air starts to condense. The air then flows through heat exchanger/evaporator (2) where the refrigerant
evaporates, causing the air to be further cooled to close to the evaporating temperature of the refrigerant. More
water in the air condenses. The cold air then flows through separator (3) where the condensate is separated
from the air.

8 2920 7103 80
Instruction book

The separator is integrated in the heat exchanger/evaporator.


The condensate collects in the Electronic Water Drain (EWD) and is automatically drained. The cold, dried
air flows through heat exchanger (1), where it is warmed up by the incoming air to approx. 5 ˚C (9 ˚F) below
the temperature of the incoming air.
Condensation in the air net cannot occur unless the air is cooled to below the dew point indicated on the
control panel.

1.3 Refrigerant flow

Flow diagram

Flow diagram

Operation
The liquid separator (10) ensures that only refrigerant enters the compressor.
Compressor (4) delivers hot, high-pressure refrigerant gas which flows through condenser (6) where the
refrigerant condenses.
The liquid refrigerant flows through dryer/filter (7) to the capillary tube (8). The refrigerant leaves the capillary
tube at evaporating pressure.
The refrigerant enters evaporator (2), where it withdraws heat from the compressed air by further evaporation
at constant pressure. The refrigerant leaves the evaporator and is sucked in again by the compressor.

Automatic regulation
The condenser pressure must be kept as constant as possible to obtain stable operation. The fan control switch
therefore stops and starts the condenser cooling fan (11).
If, under partial or no load, the evaporator pressure drops to 7.3 bar(e) (105.8 psig), the bypass regulator (5)
opens and hot, high-pressure gas is fed to the evaporator circuit to prevent the evaporator pressure from
dropping any further.

2920 7103 80 9
Instruction book

1.4 Condensate drain system

Description

The dryers are equipped with an electronic water drain (EWD). The condensate from the condensate trap
accumulates in a collector. When the condensate reaches a certain level, it is discharged through the drain
outlet.
The condensate can also be drained by pressing the test button (1).

Control panel

Control panel

Text on control panel

Reference Description
(1) Power
(2) Alarm
(3) Test

Table with references

10 2920 7103 80
Instruction book

Name Description
L1 LED "drain voltage on"
L2 LED alarm
F Funtions button

The control panel on top of the drain includes a multifunction button and two state display LED's. When LED
L1 is continuously on, this indicates that the solenoid valve is energized; when LED L1 is blinking, this
indicates that the valve is draining. If no water is supplied to the drain, the valve will make a short forced
opening every three hours. LED L2 indicates an alarm situation.
The test button can be used in three different ways:
• When it is pressed during normal operation, it starts a manual drain test.
• When it is pressed during an alarm, it resets the control logic.
• By pressing it for at least five seconds, the self-diagnosis routing will be started. This function is very
useful when the installation is finished, to check if the installation has been successful and to simulate the
alarm situation without having to wait for condensate to build inside the dryer. To return to normal
operation, just switch the drain off and on again.

2920 7103 80 11
Instruction book

2 Controller

2.1 Elektronikon® regulator

Control panel

General description
The Elektronikon regulator automatically controls the dryer, i.e.:
• Monitors the pressure dew point and the digital switches to ensure safe operation.
• Stops the dryer whenever necessary.
• Restarts the dryer when required.
• Allows selection of the control mode. See section Calling up/modifying dryer regulation mode.
In order to control the dryer and to read and modify programmable parameters, the regulator has a
control panel provided with:
• LED's, indicating the status of the dryer
• A display, indicating the operating conditions or a fault
• Keys to control the dryer and to access the data collected by the regulator
• Buttons to manually start and stop the dryer

12 2920 7103 80
Instruction book

2.2 Control panel

Detailed description

Control panel of the Elektronikon with standard display

Reference Designation Function


1 Display Shows icons and operating conditions.
2 Automatic operation symbol
3 LED, Automatic operation Indicates that the regulator is automatically controlling the
dryer. The dryer is stopped and restarted depending on the
air consumption and the data programmed in the regulator.
4 Warning symbol
5 LED, Warning Is lit if a warning condition exists.
6 Voltage symbol
7 LED, Voltage on Indicates that the voltage is switched on.
8 Service symbol
9 LED, Service Is lit when service is needed.
10 Start button This button starts the dryer. Automatic operation LED (3)
lights up. The Elektronikon is operative.
11 Stop button This button is used to stop the dryer. Automatic operation
LED (3) goes out.
12 Scroll buttons Use these buttons to scroll through the menu .
13 Enter button Use this button to confirm the last action
14 Escape button Use this button to go to previous screen or to end the
current action.

2.3 Icons and symbols used on the display


Function Icon Description
Dryer status When the dryer is stopped, the icon is standing still.
When the dryer is operating, the icon is rotating.

2920 7103 80 13
Instruction book

Function Icon Description


Machine control mode Remote start / stop

LAN control

Automatic restart Automatic restart after voltage failure is active

Timer Indicates a timer is active

Service Service required

Units Temperature unit

Temperature unit

Hours

The value shown must be multiplied by 1000 to get the actual


value

Other icons Motor

Filter

Drain

Flow switch on, energy saving mode off

Energy saving mode on (flow switch off)

Energy saving mode on and flow switch on

Ambient temperature

14 2920 7103 80
Instruction book

Function Icon Description


Dew point temperature

2.4 Main screen

Main screen
When the voltage is switched on, the first screen is a test screen. The next screen is the main screen, shown
automatically:

Main screen, basic indications

In above image, the screen shows:


• The dryer status (the icon is rotating when the dryer compressor is running, standing still when stopped).
• The dew point temperature (3 °C/37.4 °F) with the dew point icon.
If certain other options are active, e.g. Energy efficient mode activated (see section Calling up/modifying
dryer regulation mode), the main screen may also display the corresponding icons (see section Icons used).

Just after starting, the timer icon is displayed during a programmed time. After this period,
the timer icon disappears again.

2.5 Scrolling through all screens

Scroll buttons
Scroll buttons (12) can be used to scroll through all screens. The screens are divided into register screens,
measured data screens, digital input screens (numbered as <d. in>, <d. 1>, ...), parameter screens (numbered
as <P. 1>, <P. 2>, ...), protections screens (numbered as <Pr. 1>,...) and test screens (numbered as <t. 1>,...).
During scrolling, the numbers of the screens appear in a consecutive order. For most screens, the unit of
measurement and the related pictograph are shown together with the screen number.

2920 7103 80 15
Instruction book

Example (operating hours)

The screen shows the screen number <d. 1>, the unit used <hrs> and the related icon (operation). Press Enter
key (13) to call up the number of operating hours.

Overview of the screens

Digital input Designation Related topic


screens
<d. in> Status of the digital inputs See section Digital inputs
<d. 1> Running hours See section Calling up running hours
<d. 2> Motor starts See section Calling up motor starts
<d. 3> Module hours See section Calling up module hours
<d. 4> Service timer reading See section Calling up/Resetting the service
timer
<d. 5 Actual program version

Parameter Designation Related topic


screens
<P. 1> Selection between local, remote or LAN See section Selection between Local
control Remote and LAN control
<P. 2> Setting a node ID for LAN control and the See section Calling up/modifying CAN
channels for Mk 4 and Mk 5 address control
<P. 3> Settings for IP, gateway and Subnet mask See section Calling up/modifying IP,
Gateway and Subnetmask
<P. 4> Service timer See section Calling up/modifying service
timer settings
<P. 5> Setting of the temperature unit See section Calling up/Modifying unit of
temperature
<P. 6> Setting of the pressure unit See section Calling up/Modifying unit of
pressure
<P. 7> Function: Automatic restart after voltage See section Activating automatic restart
failure
<P. 8> Setting of dryer regulation mode See section Calling up/modifying dryer
regulation mode
<P. 9> Flow switch See section Calling up/modifying flow switch
function
<P. 10> Setting a password See section Activating password protection
<P. 11> Flexible or fixed alarm See section Selection between flexible
alarm and fixed alarm

16 2920 7103 80
Instruction book

Parameter Designation Related topic


screens
<P. 12> Setting of fixed alarm See section Calling up/modification fixed
dew point alarm setting
<P. 13> Setting of flexible alarm See section Calling up/modification flexible
dew point alarm setting

Protections Designation Related topic


screens
<Pr. 2> Low dew point alarm See section Shutdown warning
<Pr. 3> High ambient temperature alarm This value is fixed and cannot be modified.
See section Shutdown warning

Test screens Designation Related topic


<t. 1> Display test See section Test screens

2920 7103 80 17
Instruction book

Menu flow

Simplified menu flow

Ref. Description Ref. Description


(1) Dew point (main screen) (13) Temperature unit
(2) Ambient temperature (14) Pressure unit
(3) Digital input status (15) Auto restart function
(4) Running hours (16) Dryer regulation mode
(5) Motor starts (17) Flow switch setting
(6) Module hours (18) Password setting
(7) Service timer reading (19) Alarm options
(8) Actual program version (20) Fixed alarm setting
(9) LAN selection (21) Flexible alarm setting
(10) Settings node ID (22) Low dew point alarm and shutdown setting
(11) IP settings (23) High ambient alarm and shutdown setting

18 2920 7103 80
Instruction book

Ref. Description Ref. Description


(12) Service timer setting (24) Display test

2.6 Calling up ambient temperature

Calling up ambient temperature


Starting from the Main screen, press Scroll button (12). The ambient temperature will be shown:

In the above example, the screen shows that the ambient temperature is 25 ˚C (77 °F).
This temperature is used by the regulation algorithm to calculate a safe dew point in the energy efficient mode
(see section Calling up/modifying dryer regulation mode).

2.7 Digital inputs

Status of digital inputs


Starting from the Main screen, press Scroll button (12) until <d. In> is shown and then press the Enter button
(13). A screen similar to the following appears:

The screen shows (from left to right) the status of the remote start/stop switch, the electronic condensate drain
contact, the flow switch and the contact of the (optional) filters (1 = closed, 0 = open contact).

Contact Description Value Status


1 Remote Start/Stop switch 0 Stop
1 Start
2 Condensate drain contact 0 Drain alarm
1 No problem
3 Flow switch 0 No flow
1 Air flow
4 Filters contact (optional) 0 No problem

2920 7103 80 19
Instruction book

Contact Description Value Status


1 Filter alarm

2.8 Calling up running hours

Calling up running hours


Starting from the Main screen, press Scroll button (12) until <d. 1> is shown and then press Enter button (13).
A screen similar to the following appears:

The number of hours is shown in <hrs> (hours) or in <x1000 hrs> (hours x 1000). In above example, the
screen shows the dryer has been running during 100 hours.

2.9 Calling up motor starts

Calling up motor starts

This screen shows the number of motor starts (x 1 or - if <x1000> lights up - x 1000). In the above example,
the number of motor starts is 10100.

2.10 Calling up module hours

Calling up module hours


Starting from the Main screen, press Scroll button (12) until <d. 3> is shown and then press Enter button (13).
A screen similar to the following appears:

20 2920 7103 80
Instruction book

In the example shown, the screen shows the unit used (hrs) and the value (5000): the regulator module has
been in service during 5000 hours.

2.11 Calling up/resetting the service timer

Calling up the service timer


The controller has a built-in timer to give a warning when certain maintenance activities are to be carried out.
Starting from the Main screen, press Scroll button (12) until <d. 4> is shown and then press Enter button (13).
A screen similar to the following appears:

This screen shows the unit used <hrs> (or <x1000 hrs>) and the value <1191>. In the example shown, the
compressor has run 1191 hours since the previous service (i.e. the last time the timer was reset).

Service warning
A service warning will appear when the service timer has reached the programmed time interval. See section
Calling up/modifying service timer settings.
If the service timer exceeds the programmed time interval, alarm LED (5) will light up.
Stop the compressor, switch off the voltage and carry out the required service actions. See section Maintenance
instructions.
After servicing, reset the service timer.

Resetting the service timer


• Scroll to register screen <d. 4> and press Enter button (13).
• The reading (e.g. 4000) will appear.
• Press Enter button (13) and - if a password is set - enter the password. The value shown will start blinking,
indicating that resetting is possible.
• Press Enter button (13) to reset the timer or - in case you desire to leave the screen without changes - press
the Escape button (14) to cancel the operation.

2920 7103 80 21
Instruction book

2.12 Shut-down warning

Description
A shutdown warning will appear in the event of:
• A too low or too high dew point temperature
• A too high ambient temperature
• A drain fault
• Too high pressure drop over the (optional) DD and PD filter
The dryer remains running. Alarm LED (5) is lit. The alarm disappears automatically when the abnormal
condition ends.

Dew point temperature warning


If the dew point temperature is lower than the programmed value (default value -0.1 °C (31.8 °F), see section
Calling up/modifying low dew point setting) or if it exceeds the warning level (see section Selection between
flexible alarm and fixed alarm), alarm LED (5) will light up and the related pictograph (dew point) starts
flashing.

Main screen with dew point temperature warning

In the example shown, the dew point is 20 °C (68 °F) and the dew point icon is flashing.
If the dew point becomes normal again, the alarm will disappear.

High ambient temperature alarm


If the ambient temperature is higher than the programmed value (default value 50 °C (122 °F), see section
Calling up/modifying high ambient temperature setting) during at least 25 seconds, but still below 60 °C (140
°F), alarm LED (5) will light up and the related pictograph (ambient temperature) starts flashing.

Main screen with ambient temperature warning

In the example shown, the dew point is 30 °C (86 °F) and the ambient temperature icon is flashing. See section
Calling up ambient temperature to check the temperature.

22 2920 7103 80
Instruction book

If the ambient temperature drops again below the programmed value, the alarm will disappear.

Drain alarm
The drain alarm appears when:
• The drain is not able to drain all the condensate.
• The compressed air pressure is too low.
• During initial start-up it may indicate that the automatic drain is connected wrongly. See section Problem
solving.

Main screen with drain alarm

In case of a drain alarm, alarm LED (5) will light up and the related pictograph (drain) starts flashing.

Filter alarm
If the pressure drop over the DD and PD filter is too high, alarm LED (5) will light up and the related pictograph
(filter) starts flashing.

Main screen with filter alarm

Remedy
• It remains possible to scroll through other screens (using Scroll buttons 12) to check the actual status of
the related parameters.
• If necessary, press the Stop button (11) to stop the dryer.
• If necessary, switch off the voltage, inspect the dryer and remedy.
• The warning message will disappear as soon as the warning condition disappears.

2.13 Shut-down

Description
The dryer will shut down:

2920 7103 80 23
Instruction book

• In case the dew point temperature gets below - 0.5 °C (31.1 °F) (delay = 30 s)
• In case the ambient temperature is higher than 60 °C (140 °F) (delay = 60 s)
• In case of a problem with one of the temperature sensors
Alarm LED (5) will light up and the related icon (dew point or ambient temperature) starts flashing. The dryer
is stopped and will have to be restarted manually after remedying the problem.

After the dryer is stopped, it can take up to 5 minutes before the dryer can be restarted
(protection against too frequent starting).

Temperature sensor alarm


If the dew point sensor or the ambient temperature sensor is disconnected or out of order, alarm LED (5) will
light up and the related pictograph (dew point or ambient temperature) starts flashing.

Main screen with ambient temperature alarm

The display still shows the dew point (30 °C - 86 °F), but the ambient icon is flashing.

Main screen with dew point sensor alarm

The display shows <Err> and the dew point icon is flashing.
Press the Escape button (14) to reset and restart the dryer manually.

2.14 Selection between local, remote or LAN control

Selection between local, remote or LAN control


Starting from the Main screen, press Scroll button (12) until <P. 1> is shown and then press Enter button (13).
The actually selected control mode is shown: <LOC> for local control, <rE> for remote control or <LAn>
for LAN control.

24 2920 7103 80
Instruction book

To change: press Enter button (13) and - if necessary - enter the password (see section Activating password
protection). The actually selected control mode is blinking. Use Scroll button (12) to change the control mode.
Press Enter button (13) to program the new control mode or press Escape button (14) to cancel.

2.15 Calling up/modifying CAN address control

Calling up
Starting from the main screen, press the Scroll button (12) until <P. 2> is shown and then press Enter button
(13).
If necessary enter the password. The next screen shows that the function is ON or OFF. Press the Enter button
(13) to change this mode. Use the Scroll buttons (12) to select <On> or <OFF> and press Enter to program.
When this function is ON, use the Scroll buttons up or down (12) to see the node ID.
If desired the user can change this ID. Press the Enter button (13): the node ID value starts blinking. Use the
Scroll buttons (12) to change the node ID. Press the Enter button (13) to program the new node ID or press
the Escape button (14) to leave this screen or to cancel this operation.

Modifying the Node ID


The Node ID can be changed; use a value between 1 and 31. When the function is ON, the parameters cannot
be modified. Change the function to OFF to change the node ID.

2920 7103 80 25
Instruction book

It is also possible to change the channels. The controller has 4 channels. When changing the channels, the
controller can act as a Mk IV controller (a previous version of the controller). To set the channels, go to the
screen where the node ID is visible. Press the Scroll button down (12). The following screen appears:

Press the Enter button (13) to modify the setting. The utmost left value will blink. Change this value by using
the Scroll buttons (12). Press the Enter button (13) to confirm. Change the other values in the same way, as
required.
After modifying the settings, the screen may look as follows:

2.16 Calling up/modifying IP, Gateway and Subnetmask

Calling up
Starting from the Main screen, press the Scroll button (12) until <P. 3> is shown and then press Enter button
(13).
The next screen shows either <OFF> or <On>. If <On>, press the Enter button (13) to modify it to <OFF>.
Use the Scroll buttons Up or Down (12) to scroll between the items in this list (<IP> for IP address, <Sub>
for Subnetmask or <GAtE> for Gateway):

26 2920 7103 80
Instruction book

Modification
Press the Enter button (13) and if necessary enter the password. The first digits are blinking. Use the Scroll
buttons Up or Down (12) to modify the settings and press Enter (13) to confirm. Modify the next digits the
same way. The standard IP address is set as 192.168.100.100.

2920 7103 80 27
Instruction book

2.17 Calling up/modifying service timer settings

Calling up/modifying service timer settings


Starting from the Main screen:
• Press Scroll button (12) until <P. 4> is shown and then press Enter button (13): the setting of the service
timer is shown in <hrs> (hours) or <x1000 hrs> (hours x 1000). Example: <4000 hrs> means the timer is
set at 4000 running hours.
• Press Enter button (13) to modify this value (a password may be required): the value starts blinking. Use
the Scroll buttons (12) to modify the setting.
• Press Enter button (13) to program the new value.
• Press Escape button (14) to return to the parameter screen.

2.18 Calling up/modifying the unit of temperature

Calling up/modifying unit of temperature


Starting from the Main screen, press Scroll button (12) until <P. 5> is shown and then press Enter button (13).
The actually used unit is shown. Possible settings are <˚C> and <˚F>.
Press Enter button (13) (unit starts blinking) and use the Scroll buttons (12) to select another unit of
temperature.
Press Enter button (13) to program the new unit.
Press Escape button (14) to return to the parameter screen.

2.19 Calling up/modifying unit of pressure

Calling up/modifying unit of pressure


In a similar way as explained in section Calling up/Modifying unit of temperature, also the unit of pressure
can be modified. This is done in screen <P. 6>.
For dryers however, there is no indication of the pressure on the controller, so this setting is of no importance.

2.20 Calling up/modifying dryer regulation mode

Description
The dryer has two regulation modes:
• Regular mode
The dryer achieves the lowest possible dew point.
• Energy efficient mode
The dryer will regulate the dew point between the best achievable dew point and a safe dew point.

Calling up/modifying dryer regulation mode


Starting from the Main screen, press arrow key (12) until <P. 8> is shown and then press enter key (13): the
actual dryer regulation mode is shown as <rEG> (regular mode) or <En.EF.> (Energy efficient mode)

28 2920 7103 80
Instruction book

Press enter key (13) to modify this value (a password may be required), the value starts blinking. Use arrow
keys (12) to modify this setting.
Press enter key (13) to program the new value and to return to the parameter screen.
Press Escape button (14) to return to the parameter screen.

2.21 Calling up/modifying flow switch function

Description
The flow switch monitors the compressed air flow through the dryer. If the function is active and when no
flow is detected, the controller stops the dryer. The controller will restart the dryer when air flows through
the dryer.
If the flow switch is not active, the dryer keeps running independently from the air flow.

Calling up/modifying flow switch function


Starting from the Main screen, press arrow key (12) until <P. 9> is shown and then press Enter key (13): the
actual flow switch setting is shown: <StOP> (flow switch function is active) or <OFF> (flow switch function
is not active).
Press Enter key (13) to modify this value (a password may be required), the value starts blinking. Use arrow
keys (12) to modify the setting.
Press Enter key (13) to program the new value and use Escape key (14) to return to the parameter screen.

The option <StbY> is not used and has therefore the same result as selecting <OFF>.

2920 7103 80 29
Instruction book

The flow switch is active

The flow switch is not active

2.22 Test screens

Display test
Starting from the Main screen, press Scroll buttons (12) until <t. 1> is shown and then press Enter button (13).
The display now shows all icons that can be displayed:

2.23 Activating automatic restart after voltage failure

Description
This function allows the compressor to restart automatically after a power failure.
This parameter, accessible in screen <P. 7>, can only be modified after entering a code. Consult Atlas Copco
if this function is to be activated.

30 2920 7103 80
Instruction book

2.24 Activating password protection


Important settings such as the setting of the service timer and control mode settings can be protected by a
password.
Starting from the Main screen:
• Press Scroll buttons (12) until <P. 10> is shown and press Enter button (13):

• Password (<PASS>) appears on the screen. Press the Enter button (13).
• The screen shows the password status (ON (<On>) or OFF (<OFF>). Press Enter button (13) to modify.
• Change the value with Scroll buttons (12).
• Select <On> and press Enter button (13).
• Enter the new password and press Enter button (13) to confirm.
• Enter the password again and press Enter button (13) to confirm.
• <On> appears on the display. Press Escape button (14) to return to the previous screen.

Lost passwords can not be recovered. Save the password carefully.

2.25 Selection between flexible alarm and fixed alarm

Selecting between flexible alarm and fixed alarm


The dew point alarm can be set in fixed or flexible mode. If set to fixed mode, an alarm will be triggered when
the dew point exceeds the alarm setting (e.g. 20°C/68 °F). If set to flexible mode, an alarm will be triggered
if the dew point exceeds an offset of the desired dew point (e.g. ambient temperature minus 20 °C/68 °F).
Starting from the Main screen, press Scroll button (12) until <P. 11> is shown and then press Enter button
(13). The actually selected control mode is shown on the display: <FI.AL> for fixed alarm, <FL.AL> for
flexible alarm.

2920 7103 80 31
Instruction book

Fixed alarm is selected

To change: press Enter button (13) . The actually selected alarm mode is blinking. Use Scroll button (12) to
change the alarm mode. Press Enter button (13) to program the new alarm mode. Press Escape button (14) to
return to the parameter screens.

2.26 Calling up/modifying fixed dew point alarm setting

Calling up/modifying fixed dew point alarm setting


Starting from the Main screen, press Scroll button (12) until <P. 12> is shown and then press Enter button
(13): the actual setting of the fixed dew point alarm is shown.
Press Enter button (13) to modify this value the temperature unit starts blinking. Use the Scroll buttons (12)
to modify the setting.
Press Enter button (13) to program the new value. Press Escape button (14) to return to the previous screen.

2.27 Calling up/modifying flexible dew point alarm setting

Calling up/modifying flexible dew point alarm setting


Starting from the Main screen, press Scroll button (12) until <P. 13> is shown and then press Enter button
(13). <FL.AL> is shown.
Press Enter button (13) again. Next screen is shown:

<SEt> is the offset value that will trigger the alarm. Press Enter button (13): the programmed value starts
blinking. To change, use the Scroll buttons (12). Press Enter button (13) to modify and Escape button (14) to
return to the previous screen.
It is also possible to adjust the value when the alarm must disappear again. This is done by adjusting the
<rSEt> value. From the <SEt> screen, press the Scroll buttons (12). Following screen is shown:

32 2920 7103 80
Instruction book

Press Enter button (13): the programmed value starts blinking. To change, use the Scroll buttons (12). Press
Enter button (13) to modify.
Press Escape button (14) to exit.

2.28 Calling up/modifying the low dew point setting

Calling up/modifying the low dew point setting


In protection parameter set Pr. 2, the Low dew point alarm level (<AL-L>) and the Low dew point shutdown
level (<Sd-L>) can be set. Both values are adjustable between -0.5 °C (31.1 °F) and -0.1 °C (31.82 °F).
Starting from the Main screen, press Scroll button (12) until <Pr. 2> is shown and then press Enter button
(13): <AL-L> is shown.
Press Enter button (13): the programmed value starts blinking. Use the Scroll buttons (12) to modify.
Press Enter button (13) to confirm the new value and press Escape button (12) to return to previous screen.
From the screen where <AL-L> is shown, use the Scroll buttons (12) to go to <Sd-L>.
The value of <Sd-L> can be modified in a similar way.
Press Escape button (14) to return to the parameter screen.

2.29 Calling up/modifying high ambient temperature setting

Calling up/modifying high ambient temperature setting


In protection parameter set Pr. 3, the High ambient temperature alarm level (<AL-H>) and the High ambient
temperature shutdown level (<Sd-H>) can be set. Both values are adjustable between 35 °C (95 °F) and 60
°C (140 °F).
Starting from the Main screen, press Scroll button (12) until <Pr. 3> is shown and then press Enter button
(13): <AL-H> is shown.
Press Enter button (13): the programmed value starts blinking. Use the Scroll buttons (12) to modify.
Press Enter button (13) to confirm the new value and press Escape button (12) to return to previous screen.
From the screen where <AL-H> is shown, use the Scroll buttons (12) to go to <Sd-H>.
The value of <Sd-H> can be modified in a similar way.

2920 7103 80 33
Instruction book

3 Installation

3.1 Dimension drawings

FD 120 and FD 150 (standard version)

34 2920 7103 80
Instruction book

FD 120 and FD 150 (with options)

2920 7103 80 35
Instruction book

FD 185 up to FD 285 (standard version)

36 2920 7103 80
Instruction book

FD 185 up to FD 285 (with options)

Reference Description
1 Cooling air flow
2 Air inlet
3 Air outlet
4 Manual drain valve
5 Electrical cable entry
6 Automatic drain connection

2920 7103 80 37
Instruction book

Reference Description
7 Dryer type
8 Air connection for 50 Hz dryer
9 With integrated filter/ OSD option (male thread)
10 Air connection for 60 Hz dryer
11 Weight
12 Note: for 60 Hz dryers, use air connection (p.n. see drawing) and bushing (see drawing).
By using this bushing, the dryer height increases: see drawing

38 2920 7103 80
Instruction book

3.2 Installation proposal

Installation proposal

Text on drawings:

2920 7103 80 39
Instruction book

Reference Description
(1) Installation proposal for the standard dryer (without options)
(2) Installation proposal for the dryer with options
(3) Installation proposal with reference to minimum required free area
(4) Service side
(5) Service front
(6) Ventilation proposal
(7) Air flow
(8) Floor
(9) Side view
(10) Top view

Instructions

Reference Description
1 The inlet grids and ventilation fan should be installed in such way that any recirculation of
the cooling air is avoided. The maximum air velocity through the grids is 5 m/s (16.5 ft/s).
The maximum allowable pressure drop over the cooling air ducts is 30 Pa (0.12 in wc).
When 30 Pa is exceeded a ventilation fan should be installed at the outlet of the cooling
air ducts.
2 Make sure all free water is removed from the compressed air before it enters the dryer.
The water separator and drain system of the dryer are not designed to handle the water
formed in the aftercooler of the compressor.
3 Make sure that no dirt particles (e.g. coming from corrosion in the compressed air network)
can enter the dryer. These particles may be harmful to the dryer's heat exchanger and the
condensate drain.
4 It is recommended to install bypass pipes over the dryer with bypass valves in order to
isolate the dryer during service operations, without disturbing the compressed air delivery.
5 Power supply cable to be sized and installed by a qualified electrician.
6 Filter, type DD for general purpose (optional). The filter traps solids particles down to 1
micron with a maximum oil carry-over of 0.5 mg/m3. A high-efficiency filter, type PD
(optional), may be installed downstream of a DD filter. This filter traps solid particles down
to 0.01 micron with a maximum oil carry-over of 0.01 mg/m3. Should oil vapours and odours
are undesirable, a QD type filter should be installed downstream of the PD filter.
The standard dryer is supplied without filters. Integrated DD and PD filters can be provided
as an option.
For dryers without integrated filters it is recommended to install the filters downstream the
dryer with bypass valves.
7 The condensate drain pipes must not dip into the water of the drain collector.
Do not allow untreated condensate to enter the draining system.
Optionally an integrated OSD can be provided to separate the oil from the water.
For units without integrated OSD, an OSC separator can be installed to separate the oil
from the water.
8 The refrigerant air dryer should be installed on a level floor suitable for taking the weight
of the dryer.

40 2920 7103 80
Instruction book

• All pipes to be installed stress-free to the dryer. Do not use the dryer as support for
external pipes.
• Avoid installation of the dryer in corrosive atmosphere.
• The dryer is not designed for outdoor use.
• Install a safety valve on the connection pipe between the compressor and the dryer!

3.3 Electrical connections

Electrical connections
1. Provide an isolating switch nearby the dryer.
2. Check that the electric cables and wires inside the electric cabinet are clamped tight to their terminals.
3. Check the fuses and the setting of the overload relay. See section Settings of fuses.
4. On single-phase units: connect the power supply cables to terminals L1, L2 of terminal strip (1X0).
5. On three-phase units: connect the power supply cables to terminals L1, L2, L3 of terminal strip (1X0).
6. Connect the earth conductor to earth bolt (1X3).

2920 7103 80 41
Instruction book

Electrical diagram for single-phase units

42 2920 7103 80
Instruction book

Electrical diagram for three-phase units

Typical designations used in the electrical diagrams

Reference Designation
(1) Customer’s installation
(2) Flow switch
(3) Alarm EWD
(4) Remote start/stop

2920 7103 80 43
Instruction book

Reference Designation
(5) Option filters
B1 Electronic drain
1X0/6 Terminals
F1-6 Fuses
F23 Internal protection
K02 Relay ON/OFF compressor and fan
K03 Auxiliary relay, general warning
K04 Auxiliary relay, general shut-down
K05/6 Auxiliary relay, forced drain
K11 Contactor compressor
K12 Contactor fan motor
K25 Phase sequence relay
K5 Auxiliary relay (alarm functions)
M1 Compressor
M2 Fan motor
PDS10 Δp switch, DD filter
PDS11 Δp switch, PD filter
PSHH13 High pressure switch
PSR12 Fan switch
S1’ Remote start/stop
S2 Flow switch
X209 Connector

3.4 Pictographs

Pictographs

44 2920 7103 80
Instruction book

Reference Description
1 Dryer outlet
2 Dryer inlet
3 Automatic condensate drain
4 Warning: switch off the voltage, depressurise the compressor and read the instruction book
before carrying out maintenance work.
5 Warning, voltage
6 Information label refrigerant: Contains fluorinated greenhouse gases covered by the Kyoto
Protocol.

Pictographs shown on OSD

Reference Description
1 Oil
2 Oil outlet
3 Condensate outlet
4 Pressure
5 Inlet
6 Service point drain
7 Separator inlet pressure
8 Oil gasket, screw on filter and tighten by hand (approx. half a turn)
9 Consult instruction leaflet before carrying out maintenance or repair

2920 7103 80 45
Instruction book

4 Operating instructions

4.1 Warnings

Safety precautions
The operator must apply all relevant safety precautions, including those mentioned in this manual.

Altitude operation
Consult your supplier if operating above 3000 m (9843 ft).

4.2 Initial start

Procedure

Step Action
1 A few minutes before starting, the main supply to the dryer must be switched on to initialize
the Elektronikon and the flow switch.
2 Press start button (10).
After a few seconds the dryer is started.
Three-phase units are provided with a phase sequence relay. When the dryer does not
start, switch off the voltage and reverse two incoming electric lines.

46 2920 7103 80
Instruction book

4.3 Starting

Control panel

Procedure
To prevent that wet air gets into the compressed air circuit, it is advised to follow next procedure:

Step Action
1 Switch on the main supply to the dryer a few minutes before starting, to allow the
Elektronikon and the flow switch to initialize.
2 If installed, close the dryer bypass valve and the dryer outlet valve (customers installation).
3 Open the dryer air inlet valve (customers installation) and pressurize the dryer.
4 Press start button (10).
After a few seconds the dryer is started.
5 Approximately 5 minutes later, open the dryer air outlet valve (customers installation).
6 Approximately 10 minutes later, the dew point will be stabilized.

4.4 During operation

Description

2920 7103 80 47
Instruction book

Regularly check:
• The pressure dew point on the display of the control panel. The pressure dew point will deviate from
nominal if the air inlet conditions or volume flow differ from nominal.
• That condensate is discharged. The amount depends on the operating conditions.

4.5 Stopping

Control panel

Procedure

Step Action
1 Close dryer inlet and outlet valves (customer's installation).
2 Press stop button (11).
The dryer stops. Voltage on LED (4) remains lit. Leave the voltage on if the dryer has to
remain on stand-by.

48 2920 7103 80
Instruction book

5 Maintenance instructions

Attention
Cooling dryers of FD type contain refrigerant HFC.

Safety precautions
When handling refrigerant, all applicable safety precautions must be observed. Please be aware of the
following points:
• Contact of refrigerant with the skin will cause freezing. Special gloves must be worn. In case of contact
with the skin, the skin should be rinsed with water. On no account may clothing be removed.
• Fluid refrigerant will also cause freezing of the eyes; safety glasses must hence be worn.
• Refrigerant is harmful. Do not inhale refrigerant vapours. Check that the working area is adequately
ventilated.
When removing the service panels of the dryer, be aware that internal elements such as the pipes can reach a
temperature of 110˚C (230˚F). Therefore, wait until the dryer has cooled down before removing the panels.
Before starting any maintenance or repair work, switch off the voltage and close the air inlet and outlet valves.
Mind the sharp edges of the fan blades in case the condenser fan needs to be replaced. The use of hand
protection is a requisite.

Local legislation
Local legislation may stipulate that:
• Work on the refrigerant circuit of the cooling dryer or on any equipment which influences its function
must be undertaken by an authorised control body.
• The installation should be checked once a year by an authorised control body.

General
The following remarks should be kept in mind:
• Keep the dryer clean.
• The dryer is equipped with a new condenser technology, which provides the best efficiency on condition
that the condenser maintenance instructions are followed closely.

2920 7103 80 49
Instruction book

Preventive maintenance schedule

Period Operation
Daily Check that condensate is discharged during operation
Weekly Drain cleaning: open the manual drain valve during a few seconds. Hold a towel against
the drain outlet when opening.
Monthly Drain inspection: press the test button on top of the electronic water drain (EWD)
Condenser cleaning: proceed as follows:
• Stop the dryer and turn off the supply voltage.
• Remove the front service panel.
• Remove dust from the condenser surface using a vacuum cleaner.
• Clean the condenser by blowing compressed air from outside to inside. Keep the
compressed air nozzle more than 30 cm away from the condenser to avoid damaging
of the condenser fins.
• Remove dust from inside the dryer, e.g. with vacuum cleaner.
• Close the front service panel
• Start up the dryer.
Do not use water or solvents to clean the condenser.
Yearly/every Replace the wearing parts of the electronic water drain (service kit)
8000 hours

Dryers equipped with optional filter(s) (DD and/or PD)


• Regularly check differential pressure indicators.
• Regularly check the oil level of the oil can. If the oil can is filled with oil, take the can out of the bracket
and deliver the oil to the local oil collection service.
• For DD and PD filters, change the filter element yearly or when the pressure drop reaches approx. 0.35
bar (5 psi), as indicated by the differential pressure indicators.

Dryers equipped with optional oil/condensate separator (OSD)


• Regularly check the pressure gauge on the control panel.
• Regularly check the oil level of the oil can. If the oil can is filled with oil, take the can out of the bracket
and deliver the oil to the local oil collection service.
• Change the oil separator every 6000 operating hours or when the pressure gauge on the control panel
reaches a pressure differential of 2 bar (29 psi).

50 2920 7103 80
Instruction book

6 Problem solving

Warnings

• Before starting any maintenance or repairs, close the air outlet valve and press the
test button on top of the electronic water drain to depressurise the air system.
• Apply all relevant instructions in section Safety precautions during maintenance or
repair.

Faults and remedies

Condition Fault Remedy


Pressure dew point too high Air inlet temperature too high Check and correct. If necessary,
install a pre-cooler
Ambient temperature too high Check and correct. If necessary,
draw cooling air via a duct from a
cooler place or relocate the
dryer.
Air inlet pressure too low Increase inlet pressure
Dryer capacity exceeded Reduce air flow
Shortage of refrigerant Have circuit checked for leaks
and have the refrigerant circuit
recharged

Condition Fault Remedy


Condenser pressure too high or too Fan control switch out of order Replace
low Fan or fan motor out of order Check fan/fan motor
Ambient temperature too high Check and correct. If necessary,
draw cooling air via a duct from a
cooler place or relocate the
dryer.
Condenser externally clogged Clean condenser

Condition Fault Remedy


Compressor stops or does not start Electric power supply to compressor Check and correct as necessary
is interrupted
Thermic protection of refrigerant Motor will restart when motor
compressor motor has tripped windings have cooled down
On three-phase units, phase Reverse two incoming electric
sequence relay fault indication lines.

2920 7103 80 51
Instruction book

Condition Fault Remedy


Condensate trap remains Automatic drain system clogged Flush the assembly by opening
inoperative the manual drain valve. Have
system inspected
Clean the inlet filter of the
automatic drain

Condition Fault Remedy


Condensate trap continuously Automatic drain system out of order Have system checked, if
discharges air and water necessary replace automatic
drain

Condition Fault Remedy


Evaporator pressure is too high or Hot gas bypass valve incorrectly set Have hot gas bypass valve
too low at unload or out of order adjusted
Shortage of refrigerant Have circuit checked for leaks
and recharged

Drain alarm visible (red light and blinking drain icon)

Condition Fault Remedy


Drain alarm No pressure in the air net Error disappears when the
pressure in the air net is restored
Drain was not able to drain all the Push drain button manually.
water When this occurs frequently the
drain should be replaced
No voltage supply to the drain Check and correct supply to the
drain

Condition Fault Remedy


Phase sequence relay shut down (3- Voltage supply connected wrong Reverse two incoming electric
phase units) lines.
Also correct the rotation direction
of the fan motor; if necessary
change wiring K12:1, K12:3

Condition Fault Remedy


High pressure switch has shut down Condenser pressure too high Push the small button of the high
the dryer pressure switch
Clean condenser
Improve ventilation of the cooling
air

52 2920 7103 80
Instruction book

Dew point alarm visible (red light and blinking dew point icon)

Condition Fault Remedy


Dryer does not start Circuit has not cooled down Wait 1 minute before restarting
the dryer

Condition Fault Remedy


Too high flow or inlet temperature too Dryer undersized Try running in regular mode
high

Condition Fault Remedy


Phase sequence relay shut down Voltage supply connected wrong Reverse two incoming electric
lines.
Also correct the rotation direction
of the fan motor if necessary
change wiring K12:1, K12:3

Condition Fault Remedy


High pressure switch has shut down Condensing pressure too high Push the small button of the high
the dryer pressure switch
Clean condenser
Improve ventilation of the cooling
air

Condition Fault Remedy


Dew point alarm Dew point sensor in wrong position Place the sensor in the correct
or defective position or replace it.

Electronic condensate drain

Condition Fault Remedy


No LED lights up and the drain alarm The power supply is faulty Check if the power supply
appears on the display voltage to the drain is 115V
50/60Hz
The control Printed Circuit Board Replace the complete drain
(PCB) of the drain is defective.

2920 7103 80 53
Instruction book

Condition Fault Remedy


LED L2 lights up and no drain alarm Note: In alarm situations, the drain valves make an automatic series of
on the display forced openings (2 seconds ON; 2 seconds OFF)
Slow draining or no draining The feed line has insufficient slope Lay the feed line with an
adequate slope
The outlet line is partially blocked Check the outlet line
Excessive amount of condensate Check if the venting line is
properly installed
Check if the maximum drain
capacity of 15 litres/hour is not
exceeded. Make sure all free
water is removed from the
compressed air before it enters
• Condensate is only being
the dryer.
discharged when the test button
is pressed The air pressure has dropped below Ensure there is the minimum
• No condensate is being the minimum pressure pressure
discharged when the test button The drain filter is blocked by dirt Open the manual drain valve to
is pressed clean the drain filter
The feed and/or outlet line is shut off Check the feed line and the outlet
or blocked line
Wear Order the wear kit and substitute
all the parts included
The control Printed Circuit Board Replace the complete drain
(PCB) of the drain is defective
Both LED L2 on drain and the drain Note: Drain alarm on display lights up after a series of 30 forced
alarm on the display light up openings (2 seconds ON; 2 seconds OFF). The drain will now start a
Slow draining or no draining second series of forced openings with a different regime (3 seconds ON;
60 seconds OFF).
Irreversible drain fault Reset the drain by holding the
test button pressed for at least 5
seconds. Should the problem
persist, replace the drain.

• All above remedies were


checked and did not lead to
solution of the problem

54 2920 7103 80
Instruction book

7 Technical data

7.1 Settings of fuses

Overload relay and fuses

FD 120 FD 150 FD 185


Frequency (Hz) Voltage (V) Main fuses, supply Main fuses, supply Main fuses, supply
line (A) line (A) line (A)
IEC
50 230 20 20 25
60 220 -- -- --
cUL
50 230 -- -- --
60 220 20 20 25

FD 220 FD 245 FD 285


Frequency (Hz) Voltage (V) Main fuses, supply Main fuses, supply Main fuses, supply
line (A) line (A) line (A)
IEC
50 230 25 25 25
50 400 16 16 16
60 230 25 25 25
60 460 16 16 16
cUL
60 230 25 25 25
60 460 16 16 16

7.2 Reference conditions and limitations

Reference conditions

Unit 50 Hz 60 Hz
Compressed air inlet pressure bar(e) 7 7
Compressed air inlet pressure psig 101.53 101.53
Compressed air inlet temperature °C 35 38
Compressed air inlet temperature °F 95 100.4
Ambient temperature °C 25 38
Ambient temperature °F 77 100.4
Relative humidity at inlet % 100 100
Pressure dew point °C 3 4

2920 7103 80 55
Instruction book

Unit 50 Hz 60 Hz
Pressure dew point °F 37.4 39.2
Cooling air inlet temperature °C 25 38
Cooling air inlet temperature °F 77 100.4

Limits

Unit 50 Hz 60 Hz
Maximum compressed air inlet pressure bar(e) 14 14
Maximum compressed air inlet pressure psig 203 203
Minimum ambient air temperature °C 1 1
Minimum ambient air temperature °F 34 34
Maximum ambient air temperature °C 50 50
Maximum ambient air temperature °F 122 122
Minimum compressed air inlet temperature °C 1 1
Minimum compressed air inlet temperature °F 34 34
Maximum compressed air inlet temperature °C 60 60
Maximum compressed air inlet temperature °F 140 140

7.3 Air dryer data


All data specified below apply under reference conditions, see section Reference
conditions and limitations.

Specific data

Air dryer type Units FD 120 FD 150 FD 185


Volume flow at dryer inlet 50 Hz l/s 120 150 185
Volume flow at dryer inlet 50 Hz cfm 254 318 392
Volume flow at dryer inlet 60 Hz l/s 120 150 185
Volume flow at dryer inlet 60 Hz cfm 254 318 392
Pressure drop over dryer without filters, 50 Hz bar 0.11 0.15 0.22
approx.
Pressure drop over dryer without filters, 50 Hz psi 1.60 2.18 3.19
approx.
Pressure drop over dryer without filters, 60 Hz bar 0.11 0.14 0.22
approx.
Pressure drop over dryer without filters, 60 Hz psi 1.60 2.03 3.19
approx.
Total power consumption, including cooling fan 50 Hz kW 1.0 1.0 1.4
Total power consumption, including cooling fan 50 Hz hp 1.34 1.34 1.88
Total power consumption, including cooling fan 60 Hz kW 1.5 1.5 2.3

56 2920 7103 80
Instruction book

Air dryer type Units FD 120 FD 150 FD 185


Total power consumption, including cooling fan 60 Hz hp 2.28 3.22 3.08
Refrigerant type R410a R410a R410a
Refrigerant charge (approx.) kg 0.86 0.86 0.92
Refrigerant charge (approx.) lb 1.90 1.90 2.03
Dryer mass (approx.) - standard version kg 170 170 185
Dryer mass (approx.) - standard version lb 375 375 408

Air dryer type Units FD 220 FD 245 FD 285


Volume flow at dryer inlet 50 Hz l/s 220 245 285
Volume flow at dryer inlet 50 Hz cfm 466 519 604
Volume flow at dryer inlet 60 Hz l/s 220 245 285
Volume flow at dryer inlet 60 Hz cfm 466 519 604
Pressure drop over dryer without filters, 50 Hz bar 0.12 0.18 0.22
approx.
Pressure drop over dryer without filters, 50 Hz psi 1.74 2.61 3.19
approx.
Pressure drop over dryer without filters, 60 Hz bar 0.12 0.18 0.22
approx.
Pressure drop over dryer without filters, 60 Hz psi 1.74 2.61 3.19
approx.
Total power consumption, including cooling fan 50 Hz kW 1.9 1.9 2.2
Total power consumption, including cooling fan 50 Hz hp 2.28 2.55 2.82
Total power consumption, including cooling fan 60 Hz kW 2.5 2.9 3.1
Total power consumption, including cooling fan 60 Hz hp 3.49 3.89 4.16
Refrigerant type R410a R410a R410a
Refrigerant charge (approx.) kg 1.55 1.20 1.28
Refrigerant charge (approx.) lb 3.42 2.65 2.82
Dryer mass (approx.) - standard version kg 197 197 197
Dryer mass (approx.) - standard version lb 434 434 434

2920 7103 80 57
Instruction book

8 Pressure equipment directives

Components subject to 97/23/EC Pressure Equipment Directive


Components subject to 97/23/EC Pressure Equipment Directive greater than or equal to category II

Dryer type Part number Description PED Class


FD 120 up to FD 285 1089 9139 14 High pressure switch IV
FD 120 and FD 150 1624 2274 00 Heat exchanger II
FD 185 1624 2275 00 Heat exchanger II
FD 220 up to FD 285 1624 2276 00 Heat exchanger II

Overall rating
The dryer is conform to PED category II.

58 2920 7103 80
Instruction book

9 Declaration of conformity

Typical example of a Declaration of Conformity document

(1): Contact address:


Atlas Copco Airpower n.v.
P.O. Box 100
B-2610 Wilrijk (Antwerp)
Belgium

2920 7103 80 59
In order to be First in Mind—First in Choice® for all your quality
compressed air needs, Atlas Copco delivers the products and
services that help to increase your business’ efficiency and
profitability.
Atlas Copco's pursuit of innovation never ceases, driven by our
need for reliability and efficiency. Always working with you, we are
committed to providing you the customized quality air solution that
is the driving force behind your business.

No. 2920 7103 80 / 2012 - 01 - Printed in Belgium

www.atlascopco.com

You might also like