Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Chapter 6: Stray Loss Terminology For The Power Transformer and It'S Perspective Analysis For Design Optimization

Download as pdf or txt
Download as pdf or txt
You are on page 1of 17

6.

Stray Loss Perspective Analysis for TDO

CHAPTER 6: STRAY LOSS TERMINOLOGY FOR THE POWER


TRANSFORMER AND IT’S PERSPECTIVE ANALYSIS FOR
DESIGN OPTIMIZATION

6.1 Stray Loss in Transformer


Stray loss is the byproduct of copper loss, which varies from 10% to 40% of
total losses. Increase in % of stray loss compared to designed value, leads
towards the hot-spot temperature increase in electrical as well as magnetic
circuit in the transformer and that is considered as catalysts for transformer
lifecycle.

Generally stray losses appear in all metal parts penetrated by magnetic


leakage field produced by the windings or current loops(3). This means that
there are many potential locations where stray losses may appear and the
most important ones are those in winding conductors due to eddy-current
(skin-effect) in winding parallel strands, due to circulating currents in tank, due
to magnetic leakage flux from the windings in tank cover around the high
current bushings, in clamping plates of core due to winding leakage flux, in
core sheets at the outer packages of the core limbs due to the winding
leakage flux(128).

The load loss in the transformer consists of losses due to the ohmic
resistance of windings and certain additional losses. These additional losses
are generally known as stray losses. The stray losses take place in the
winding and metal parts surrounding the windings. These also take place in
the metal parts around the leads. The stray losses are largely associated with
the leakage flux and magnetic field surrounding the leads.

Leakage flux dominantly influences the stray loss, leakage impedance and
electromagnetic force under short circuit conditions. The leakage flux can
some time lead to local overheating. Hence in large power transformer, the
leakage is crucial factor in design of the transformer. For a transformer with a
definite impedance, some quantity of leakage flux can be forbidden and stray
losses resulting out of the leakage flux can be considerably abridged and local
over heating can be controlled .Lessen in stray loss will advance the efficiency
and will effect large saving in cooler, oil and steel costs.

Chiragkumar N Parekh 61
6.Stray Loss Perspective Analysis for TDO

Figure: 6.1 (A). 3-D Flux Distribution During Operation

Figure: 6.1 (B). 2-D Flux Distribution in the Core of 3 Phase Transformer

Chiragkumar N Parekh 62
6.Stray Loss Perspective Analysis for TDO

Figure: 6.2 % Component Stray Losses

6.2 Losses in Winding


The major portion of stray losses take place in the winding and is called eddy
current losses. In large transformers, the turns in the winding consists of large
numbers of conductors and if they are not correctly transposed can give rise
to circulating currents within the parallel conductors. In such arrangement
unequal voltage are induced in different conductor due to varying leakage
field. Unequal voltages in parallel strands gives rise to circulating current. The
losses due to circulating current within few strands of conductor may not
reflect much in overall losses but still can cause overheating of strands.

6.2.1 Case Study


Transformer “of 15 MVA ,66/11 was designed for 65 kW load loss. The I2R &
stray losses were calculated 55 kW and 10 kW respectively. After
manufacturing, the transformer was tested. The measured losses were 110
kW instead of 65 kW, which comprises 54.7 kW I 2R loss and 55.3 stray loss.
The load loss test value unexpected in which the stray losses value was most
volatile. After investigation it was concluded that the transposition in LV
winding was improper and that was initiating the circulating current for
boosting the winding eddy current losses. The same was rectified and all
winding were remanufactured and completed the entire transformer
manufacturing process. Now the tested Load loss value was almost near to
the design value i.e. 63.75 kW.”

Chiragkumar N Parekh 63
6.Stray Loss Perspective Analysis for TDO

The above presented real case study indicates the vulnerability of wrong
transposition in the winding.

6.3 Losses in Metallic Parts Due to Leakage Field

The leakage field pass through the various metallic parts namely tank wall,
core clamping plates, and flitch plates on limb etc. whereas magnetic field
interacts with the metallic surface. Eddy current are position in the plate and
give rise to additional losses and the losses in the region of high concentration
of field can lead local overheating.

Figure6.3 Leakage Field on Tank Walls

Figure 6.4 Leakage Field on Yoke Clamps

Chiragkumar N Parekh 64
6.Stray Loss Perspective Analysis for TDO

6.3.1 Case Study


Transformer of 25 MVA 66/11 was designed for 120 kW load loss. The I 2R &
stray losses were calculated 100 kW and 20 kW respectively. After
manufacturing, the transformer was tested for 75% load current in open
condition without tank. The measured load losses were 117 kW (99 kW I 2R +
18 kW Stray). The same CCA was placed in its tank and again measures the
load losses and that was 132 kW (99 kW I 2R+ 33 kW Stray).That means the
excess 15 kW stray losses due to tank wall and leakage flux interaction. In
similar transformer the top and bottom yoke clamp were replaced from mild
steel material to laminated insulated perm wood. That again resulted in
reduction of stray loss up to 4 kW. Further in similar transformer the flitch
plate of core was change from mild steel to stainless steel material. That also
respond to further reduction of stray loss of 1 kW.
The above presented real case study with consecutive experiment indicates
the phenomenon of stray loss in metallic parts due to leakage field in the
transformer.”
6.4 Losses Due to Current Carrying Leads
Winding termination as well as connection Leads carrying current, induce
magnetic field around the leads. If this field is strong enough and in close
vicinity of metallic parts produces eddy current losses. Inside the transformer
the connection used for making star delta connection in 3 phase transformer
carries heavy current which produces high flux intensities in the nearby tank
surface and clamping structure. It is depend up on the magnitude of current,
distance of lead from metallic parts and property of material.

6.5 Methods of Stray Loss Reduction and Results


Stray losses in the transformer are reduced by taking several appropriate
measures depending on the type and geometry of the transformer. Few
among them are as following: use of small dimensioned conductors for
windings, use of CTC conductors in case of higher current windings, optimum
transposition of the parallel strands, magnetic shielding of the inner tank walls,
use of non-magnetic shield in the area of strong magnetic fields, optimum
selection of winding type which can reduce the stray up to 50 to 60 %
compared to conventional design.

Chiragkumar N Parekh 65
6.Stray Loss Perspective Analysis for TDO

A minimum losses design can be achieved by analyzing symmetrically the


source of leakage flux, path of leakage flux and it’s relation to the stray losses.
Main leakage in the transformer will always exist and losses arising out of this
can be reduced by various means. Stray loss due to leads can either be
eliminated or reduced to great extent by properly running the leads or
shielding the leads.”

6.6 Eddy-Stray Losses Reduction In Winding


Subdivision of conductors radially reduces the eddy current due to axial
leakage field and subdivision of conductor axially reduces the eddy current
loss due to the radial component of leakage field. Optimum transposition of
the conductors controls induced voltage in each strip and eliminates the
circulating current. For high current windings, use of CTC conductors would
be ideal to minimize total eddy current losses. The reduction by CTC is about
50 to 60 % on large transformer.
For High voltage winding with moderate current requirement, bunched
conductor arrangement is now a days most popular which is used to improve
winding space factor and to improve radial subdivision of conductors.

6.7 Stray Loss Reduction by Magnetic Shielding on Tank Wall


Transformer “with large rated power and high stray fluxes have the side wall
of the tank and in some cases the covers provided with a screen to reduce
eddy current losses in the tank wall and covers which prevents local
overheating. For this purpose magnetic shunt are used. In the large power
transformers the stray-field loss and the local loss density caused in the
conducting parts are considerably increased with the capacity of the
transformer which probably result in the hazardous local overheating and/or
because the insulation material damaged and as a result endangering the
transformer running. In larger power transformer, the stray-field loss must be
controlled in an acceptable level for saving energy as well as avoiding the un-
allowed overheating. So the possible engineering strategies to cope with it
have been adopted such as the optimum material configuration and structures
any possible shielding, etc. An example of the magnetic shields installed
inside the oil-tank of a large power transformer is shown in Fig.6.5. The

Chiragkumar N Parekh 66
6.Stray Loss Perspective Analysis for TDO

electromagnetic shielding is used to prevent the leakage magnetic flux into


the conducting parts by the reaction of the eddy current field induced in the
shields of high conductivity, which is also called electromagnetic screen.
However the magnetic shielding makes the leakage magnetic flux changing
the path into the shields of high permeability named magnetic shunt.””

Figure 6.5 Tank Wall Shunts Arrangement for Stray Loss Reduction

6.8 Stray Loss Reduction by Magnetic Yoke Shield Application

Magnetic shield made up of laminated core plates are used under the yoke
providing a low reluctance return path. A large proportion of axial leakage flux
is fed back in to the transformer yokes. The yoke clamp assembly is shielded
and reduction of radial flux to tank side is also achieved depending on the
pacing between shield & winding.

Figure 6.6 Yoke Shunts Arrangement for Stray Loss Reduction

6.9 Stray Loss Reduction by Fitch Plate Modification Concept


The core limb plates use to strengthen the core mechanically are very near to
the leakage field and are subjected to increase radial field of winding. The
losses in the Fitch plates are significant but the temp rise should be

Chiragkumar N Parekh 67
6.Stray Loss Perspective Analysis for TDO

controlled. Severe heating of Fitch plates can take place in large transformer
due to high intensity of radial flux. The reduction of losses in Fitch plates can
be achieved by using Fitch plates of high resistivity material like SS or other
material. Substantial reduction of losses & temperature rise can be achieved
by provision of slots on the Fitch plates.”

6.10 Stray Loss Reduction at Bushing Mounting Plate on Top Cover or


Side Wall
The termination lead of windings are connected to the bushings mounted on
the tank plates or tank cover. This area is prone to high eddy current and
excessive heating as a skin effect phenomenon. To reduce the losses and
heating nonmagnetic steel inserts are welded in to the mounting plates at
bushing locations. Sometimes mounting plates of Non-magnetic material like
aluminum are used for high current bushings.

Figure 6.7 Magnetic flux density distribution in LV Throat.

In Table-6.1 it can be observed that there is a significant difference in total


losses of a 4000 kVA transformer with and without throat, as total losses
increase from 630 Watts to 1650 Watts, the comparison is made when both
transformers have the SS plate in the tank wall where the LV bushings
are mounted. It is recommend the use of plastic throats to avoid the
1020 watts of losses in the low voltage throats of 4000 kVA transformers.

Chiragkumar N Parekh 68
6.Stray Loss Perspective Analysis for TDO

Table 6.1 Total Losses with and Without Throat for a 4000 kVA
Transformer
Tank Wall CS throat SSP
Total Loss
Simulation Losses Losses Losses
(watt)
( watt) (watt) (watt)
Without LV Throat 580 --- 50 630

With LV Throat 415 1175 70 1650

6.11 Stray Losses Due to the Core Clamps of A Transformer and Method
For Reduction

Figure 6.8 3-D Finite-Element Model of The Transformer (a) Solid Model.
(b) Meshed Model

The losses have been calculated for the case of reduced voltage short circuit
test with rated current flowing in 31.5 MVA 110/33 kV transformer. There are
698 turns at high-voltage (HV) side which corresponds to the tap position for
rated voltage and 146 turns at low voltage (LV) side. The current at HV side is
165 A and at LV side is 551 A. In yoke clamp different mechanical design
applied accordingly the stray losses are resulted. The bottom yoke clamp is
more prone to the stray loss component compare to the top yoke clamps. The
yoke clamps with less brackets (mild steel) are more advisable for stray loss
reduction. The mechanical reinforcement can be provided by laminated wood
brackets.”

Chiragkumar N Parekh 69
6.Stray Loss Perspective Analysis for TDO

Figure 6.9 Distribution of Losses on the Surface of the Core Clamps


(a) Front Side (b) Back Side

The losses in the clamps can be reduced by using different materials and by
changing the clamp dimensions. Fig.6.9 shows an example of using a
narrower clamp whose width has been reduced so that its edge coincides with
the narrowest core lamination step.

Figure 6.10 Cross-Section of the Transformer Core and Core Clamp

6.12 3D-FEM Modeling of Power Transformer for Detailed Analysis

The complete transformer comprising Core, Windings, Frames, Flitch plates,


Tank, Wall shunts and the epures (pre-defined line on which magnetic field
values are computed in all 3-directions) is modeled for stray losses
estimation.The field quantities obtained at these epures are used for
estimation of stray losses.

Chiragkumar N Parekh 70
6.Stray Loss Perspective Analysis for TDO

6.13 Transformer Rating (Case Study)

15 MVA, 66/11kV, Delta/star, 3-Phase, Impedance =9.5% 50Hz, core


type power transformer.

Material Details
1. Winding-Copper,
2. Core-CRGO,
3. Tank –Electrical Steel,

Table 6.2 Dimensions of Transformer for FEM Modeling and Analysis

1.Core Diameter =472mm 11.Top Clearance=100mm

2.Leg Centre =865mm 12.Tank =3080*1190*2320 mm

3.Window Height=1275mm 13.Tank Thickness=10mm

4.Radial Diameter, LV Winding 14.Flitch plate=2100*80*10mm


(472/2+68.5)=304.5mm
5.Radial Diameter HV winding 15.Yoke Beam=2720*300*90
(304.5+31+70.5)= 406mm
6.Thickness of LV winding=68.5mm 16.LV turns =118

7.Thickness of HV winding=70.5mm 17.HV turns =1066

8.Height of LV winding=1095mm 18.LV current=750A

9.Height of HV winding=1095mm 19.HV current=131.22A

10.Bottom Clearance=80mm 20.HV to HV clearance=31mm

Chiragkumar N Parekh 71
6.Stray Loss Perspective Analysis for TDO

6.14 FEM Model & Simulation Results


The simplified FEM model of 15MVA, 66/11 kV, D-Y transformer is shown in
Figure 6.11 and 6.12. It contains LV windings, HV windings, Core, Yoke
beams, Tank & Flitch plate. The simulation is carried out with reference
to Winding, Core and tank geometry of 15 MVA power transformer. The
losses and leakage field concentration in different component like core,
Fitch Plate, Yoke beam, Tank, etc. are informed in Figure 6.13 to 6.17.

Figure 6.11.FEM Model of 15 MVATransformer

Figure 6.12. 3-D FEM Meshed Model of 15 MVA Transformer

Chiragkumar N Parekh 72
6.Stray Loss Perspective Analysis for TDO

Figure 6.13. Flux Density in Core of 15 MVA Transformer by FEM

Figure 6.14 Flux Density on Tank Wall of 15 MVA Transformer by FEM

Chiragkumar N Parekh 73
6.Stray Loss Perspective Analysis for TDO

Figure 6.15 Ohmic Loss in Tank Wall of 15 MVA Transformer by FEM

Figure 6.16 Flux Density in Flitch Plate &Yoke Beam of 15 MVA


Transformer by FEM

Chiragkumar N Parekh 74
6.Stray Loss Perspective Analysis for TDO

Figure 6.17 Ohmic Loss in Flitch Plate &Yoke Beam of 15 MVA


Transformer by FEM

Here the 3D-model of 15MVA, 66/11 kV, D/Y, is shown. The model is
simplified & stray losses are analyzed. They occur at Tank, Yoke Beams,
Flitch plates &Other Structural parts of the Transformer.
The average flux density in the core is 1.67 T.
The flux density at tank wall is 0.27 T.
The average ohmic losses at tank wall is 2.39 x 104 watts/m3
The average flux density at yoke and Fitch plate is 0.97 T

6.15 Analysis of This Transformer Respective to the Stray Loss

Before Analysis:

Calculated Load Loss from test result @ 75 ⁰C = 72280 watts

I2R loss @ 75 ⁰C = 56370 watts

Stray loss @ 75 ⁰C = 15910 watts

6.16 FEM Analysis and Respective trial-error Method for Reduction of


Stray Losses by Simulation:

Calculated Load Loss from test result @ 75 ⁰C = 69216 watts

I2R loss @ 75 ⁰C = 56275 watts

Stray loss @ 75 ⁰C = 12941 watts

Chiragkumar N Parekh 75
6.Stray Loss Perspective Analysis for TDO

So 2969 watts stray loss reduced after detailed study and respective analysis
of stray field. There is further scope of reduction of this losses by precise
geometrical data analysis by FEM.

6.17 Implementation of FEM Concept in Similar Capacity


Transformer for Stray Loss Analysis During Manufacturing Process.

Test result after implementation of FEM concept to Manufacturing process for


15 MVA transformer.

Tested Load Loss after FEM implementation@75⁰C= 68970 watts


I2R loss @ 75 ⁰C = 56288 watts
Stray loss @ 75 ⁰C = 12682 watts

3310 watts stray loss reduced after implementation of FEM analysis on real
manufacturing process of 15 MVA 66/11 kV transformer. Directly it is almost
4.5% reduction in Load loss more precisely it is 21% reduction in stray loss.

These reduced losses components are shown in Table 6.3.

Table 6.3 Result of Stray Loss Component After FEM Analysis

Sr. Stray reduction Load Loss after % of reduction Cost hike


No. Application Application

1 Winding 70769 2.09% 0.095%


Construction
&Transposition

2 Tank Wall shunting 69884 1.25% 0.62%

Chiragkumar N Parekh 76
6.Stray Loss Perspective Analysis for TDO

3 Bottom Yoke Shunts 69302 0.83% 0.31%

4 Flitch Plates, Yoke 69191 0.16 % 0.05%


clamps and & core
clamps

5. SS structure Near 68970 0.32% 0.23%


LV & HV termination
on Tank

6.18 Conclusion:

‘The proposed technique of FEM analysis is very complex task due to lack of relevant
academic and research references. However the 15 MVA power transformer model
was developed analyzed with the help of many experts and on line literatures. After
analysis it is concluded that the obtained value of stray losses are 18.31 % of full
load loss @75 ⁰C instead of 22% of previous one before FEM analysis and
respective implementation. The most important thing is, there is just 1.22% cost rise
identified for this process and the gain is 4.5 % load loss reduction, which is very
helpful for Transformer design optimization concern for cost reduction.

However there is further scope for this loss reduction. We can get 12-14% stray
losses by more precise modeling and analysis.

Chiragkumar N Parekh 77

You might also like