Chapter 6: Stray Loss Terminology For The Power Transformer and It'S Perspective Analysis For Design Optimization
Chapter 6: Stray Loss Terminology For The Power Transformer and It'S Perspective Analysis For Design Optimization
Chapter 6: Stray Loss Terminology For The Power Transformer and It'S Perspective Analysis For Design Optimization
The load loss in the transformer consists of losses due to the ohmic
resistance of windings and certain additional losses. These additional losses
are generally known as stray losses. The stray losses take place in the
winding and metal parts surrounding the windings. These also take place in
the metal parts around the leads. The stray losses are largely associated with
the leakage flux and magnetic field surrounding the leads.
Leakage flux dominantly influences the stray loss, leakage impedance and
electromagnetic force under short circuit conditions. The leakage flux can
some time lead to local overheating. Hence in large power transformer, the
leakage is crucial factor in design of the transformer. For a transformer with a
definite impedance, some quantity of leakage flux can be forbidden and stray
losses resulting out of the leakage flux can be considerably abridged and local
over heating can be controlled .Lessen in stray loss will advance the efficiency
and will effect large saving in cooler, oil and steel costs.
Chiragkumar N Parekh 61
6.Stray Loss Perspective Analysis for TDO
Figure: 6.1 (B). 2-D Flux Distribution in the Core of 3 Phase Transformer
Chiragkumar N Parekh 62
6.Stray Loss Perspective Analysis for TDO
Chiragkumar N Parekh 63
6.Stray Loss Perspective Analysis for TDO
The above presented real case study indicates the vulnerability of wrong
transposition in the winding.
The leakage field pass through the various metallic parts namely tank wall,
core clamping plates, and flitch plates on limb etc. whereas magnetic field
interacts with the metallic surface. Eddy current are position in the plate and
give rise to additional losses and the losses in the region of high concentration
of field can lead local overheating.
Chiragkumar N Parekh 64
6.Stray Loss Perspective Analysis for TDO
Chiragkumar N Parekh 65
6.Stray Loss Perspective Analysis for TDO
Chiragkumar N Parekh 66
6.Stray Loss Perspective Analysis for TDO
Figure 6.5 Tank Wall Shunts Arrangement for Stray Loss Reduction
Magnetic shield made up of laminated core plates are used under the yoke
providing a low reluctance return path. A large proportion of axial leakage flux
is fed back in to the transformer yokes. The yoke clamp assembly is shielded
and reduction of radial flux to tank side is also achieved depending on the
pacing between shield & winding.
Chiragkumar N Parekh 67
6.Stray Loss Perspective Analysis for TDO
controlled. Severe heating of Fitch plates can take place in large transformer
due to high intensity of radial flux. The reduction of losses in Fitch plates can
be achieved by using Fitch plates of high resistivity material like SS or other
material. Substantial reduction of losses & temperature rise can be achieved
by provision of slots on the Fitch plates.”
Chiragkumar N Parekh 68
6.Stray Loss Perspective Analysis for TDO
Table 6.1 Total Losses with and Without Throat for a 4000 kVA
Transformer
Tank Wall CS throat SSP
Total Loss
Simulation Losses Losses Losses
(watt)
( watt) (watt) (watt)
Without LV Throat 580 --- 50 630
6.11 Stray Losses Due to the Core Clamps of A Transformer and Method
For Reduction
Figure 6.8 3-D Finite-Element Model of The Transformer (a) Solid Model.
(b) Meshed Model
The losses have been calculated for the case of reduced voltage short circuit
test with rated current flowing in 31.5 MVA 110/33 kV transformer. There are
698 turns at high-voltage (HV) side which corresponds to the tap position for
rated voltage and 146 turns at low voltage (LV) side. The current at HV side is
165 A and at LV side is 551 A. In yoke clamp different mechanical design
applied accordingly the stray losses are resulted. The bottom yoke clamp is
more prone to the stray loss component compare to the top yoke clamps. The
yoke clamps with less brackets (mild steel) are more advisable for stray loss
reduction. The mechanical reinforcement can be provided by laminated wood
brackets.”
Chiragkumar N Parekh 69
6.Stray Loss Perspective Analysis for TDO
The losses in the clamps can be reduced by using different materials and by
changing the clamp dimensions. Fig.6.9 shows an example of using a
narrower clamp whose width has been reduced so that its edge coincides with
the narrowest core lamination step.
Chiragkumar N Parekh 70
6.Stray Loss Perspective Analysis for TDO
Material Details
1. Winding-Copper,
2. Core-CRGO,
3. Tank –Electrical Steel,
Chiragkumar N Parekh 71
6.Stray Loss Perspective Analysis for TDO
Chiragkumar N Parekh 72
6.Stray Loss Perspective Analysis for TDO
Chiragkumar N Parekh 73
6.Stray Loss Perspective Analysis for TDO
Chiragkumar N Parekh 74
6.Stray Loss Perspective Analysis for TDO
Here the 3D-model of 15MVA, 66/11 kV, D/Y, is shown. The model is
simplified & stray losses are analyzed. They occur at Tank, Yoke Beams,
Flitch plates &Other Structural parts of the Transformer.
The average flux density in the core is 1.67 T.
The flux density at tank wall is 0.27 T.
The average ohmic losses at tank wall is 2.39 x 104 watts/m3
The average flux density at yoke and Fitch plate is 0.97 T
Before Analysis:
Chiragkumar N Parekh 75
6.Stray Loss Perspective Analysis for TDO
So 2969 watts stray loss reduced after detailed study and respective analysis
of stray field. There is further scope of reduction of this losses by precise
geometrical data analysis by FEM.
3310 watts stray loss reduced after implementation of FEM analysis on real
manufacturing process of 15 MVA 66/11 kV transformer. Directly it is almost
4.5% reduction in Load loss more precisely it is 21% reduction in stray loss.
Chiragkumar N Parekh 76
6.Stray Loss Perspective Analysis for TDO
6.18 Conclusion:
‘The proposed technique of FEM analysis is very complex task due to lack of relevant
academic and research references. However the 15 MVA power transformer model
was developed analyzed with the help of many experts and on line literatures. After
analysis it is concluded that the obtained value of stray losses are 18.31 % of full
load loss @75 ⁰C instead of 22% of previous one before FEM analysis and
respective implementation. The most important thing is, there is just 1.22% cost rise
identified for this process and the gain is 4.5 % load loss reduction, which is very
helpful for Transformer design optimization concern for cost reduction.
However there is further scope for this loss reduction. We can get 12-14% stray
losses by more precise modeling and analysis.
Chiragkumar N Parekh 77