Protect Transformer Assets: Serveron TM8
Protect Transformer Assets: Serveron TM8
Protect Transformer Assets: Serveron TM8
Product Summary
Description: Our industry leading on-line DGA
• Serveron TM View™ software and services offer simple yet powerful analytical tools for transformer monitor
management, data visualization and analysis including our exclusive TOAN diagnostic tool.
• Seamlessly move from single user software to enterprise capability for large deployments of monitors in your
fleet with our SmartSUB solution.
• SmartSUB includes the DGA analysis features of TM View and adds the ability of combining data from
additional transformer condition based monitoring devices (tank pressure, cooling bank current, winding
current & temperature, bushing monitor, partial discharge and others).
• On-line correlation of 8 fault gases for the most • Neural network based DGA diagnostic technology
comprehensive DGA condition assessment that provides the most accurate DGA diagnostic
available. results over all other diagnostic tools.
• Multiple Duval Triangles provide diagnostic • Offer three dimensional views of diagnostic
outcomes for various combinations of the fault outcomes for various combinations of the fault
gases (IEC 60599‑2007‑05). gases (IEEE C57.104‑2008 & IEC 60599-2007-05).
SERVERON® TM8™ on-line DGA monitor
Accuracy and Reliability • The Model TM8 measures all fault gases using a single Gas
Chromatography (GC) measurement system. Gas Chromatography
is the accepted measurement science for DGA and is the only DGA
measurement technology specified in IEEE, ASTM, CIGRE and IEC
standards.
Low Total Cost of • Field-proven reliability combined with low lifetime maintenance
Ownership (TCO) requirements offers superior value.
Avoid transformer failures • Continuous trending of key fault gases gives early and immediate
notification of incipient faults that can lead to transformer failure.
Enable condition based • Only comprehensive on-line monitoring can provide the information that
maintenance enables continuous transformer condition assessment.
• Data from the Model TM8 supports all IEEE and IEC diagnostic tools for
rapid warning and diagnosis of developing faults.
Extend transformer life and • Comprehensive analysis of key fault gases, moisture and other key
defer capital expenditures parameters enables intelligent management of transformers, extending
their useful life and deferring capital expenditures.
Technical Specifications
Total Dissolved True Total rue Total Dissolved Combustible Gas (TDCG) output is available reporting
T
Gases Combustible Gas 100% of detected level in PPM for H2, C2H2, C2H4, CO, CH4, C2H6
Total Hydrocarbons Total Hydrocarbons (THC) output is available reporting 100% of detected
level in PPM for CH4, C2H2, C2H4, C2H6
Gas Analysis Oil Sampling Rate Oil sampling is continuous and gas analysis intervals are user-selectable
Parameters from 2 hours to 12 hours (Default: 4 hours). Automatic schedule
acceleration when rate of change alarm limit is exceeded (Default: 1 hr)
Data Management All data is date and time stamped and up to two years of data is stored
in memory
Automated Calibration System performs periodic automated calibration verification to National
Verification Institute of Standards and Technology (NIST) traceable gas standard
Alarms Two individually 50 VDC or 240 VAC @ 3 A max. (125 VDC @ 1 A max.); relay contacts
programmable relays operate as normally open or normally closed
Supported Alarms Gas Caution & Alarm for Level (ppm), Rate-of-Change (ppm/day), Power
and/or Service Event
External Sensor Analog Inputs Three (3) analog 4 to 20 mA inputs, ambient temperature sensor
Inputs included. Optional sensors include transformer load guide and moisture-
in-oil with temperature probe (uses 2 inputs)
www.serveron.com
SERVERON® TM8™ on-line DGA monitor
Technical Specifications
Physical Product Dimensions HxWxD: 22.0 in x 20 in x 11.2 in (55.9 cm x 50.8 cm x 28.4 cm)
Specifications
Packaging Dimensions 26.4 in x 26.4 in x 15.9 in (67 cm x 67 cm x 40.3 cm)
Product Weight 65 lb (29.5 kg)
Shipping Weight 70 lb (31.8 kg) (monitor package only)
Enclosure Rating NEMA 4X, IP66
Safety Specification
IEC 61010-1 IEC 61010-2-81
UL 61010-1 (2nd Edition) CSA-C22.2 No. 61010-1-04
www.serveron.com
SERVERON® TM8™ on-line DGA monitor
Model DGA
150/250/400
Model TM8™
Model TM3™
Model TM2™
Model TM1™
About Serveron®
Serveron transformer condition assessment and management tools are critical to utilities in improving grid reliability while
optimizing the management and economics of their asset base. We are a leader in on-line DGA monitoring of power
transformers with solutions across the entire power transformer fleet. Serveron is a QUALITROL Company.
© 2014 Serveron® Corporation. All rights reserved. Information subject to change without notice.
QUALITROL is a registered trademark of Qualitrol Company LLC. SERVERON, LOADGUIDE, and TRUEGAS are registered trademarks
and TM1, TM2, TM3 and TM8 are trademarks of Serveron® Corporation.
All trademarks are properties of their respective companies, as noted herein. AP-G35-02L-03E
Email: info@serveron.com