Reaffirmed 2001
Reaffirmed 2001
Reaffirmed 2001
IS I 2511 i 1963
Indian Standard
SPECIFICATION FOR POLYCRYSTALLTNE
SEMI-CONDUCTOR RECTIFIER STACKS
Power Converters Sectional Committee, ETDC 31
Choirmon Re~rrsenting
SHBI J. D. MALHOTRA Railway Board ( Ministry of Railways )
ISr2511-1963
Indian Standard
SPECIFICATION FOR POLYCRYSTALLTNE
SEMI-CONDUCTOR RECTIFIER STACKS
8. FOREWORD
2
IS:251L- 1963
1. SCOPE
2. TERMINOLOGY
2.0 For the purpose of this standard, the following definitions shall
apply.
2.1 Rectifier -A device for converting an alternating or oscillating
current into a unidirectional current, either by inversion or suppression of
alternate half-waves.
2.2 Semi-conductor Rectifier -A rectifier using the properties of a
semi-conductor as the basis of operation.
2.3 Rectifier cell - A basic rectifier, consisting of a combination of
semi-conductors or a semi-conductor and a metal or metals in contact with
one another, which presents an asymmetrical conductance according to
the polarity of the voltage applied to it ( see Fig. 1 ).
2.4 Rectifier Stack ( Unit ) - A single structure of one or more rectifier
cells with its ( their) associated mounting(s), cooling attachment(s), if
any, ( for example a blower or fan ) and connections whether electrical or
mechanical ( see Fig. 2 ).
2.5 Rectifier Stack Assembly -An electrically and mechanically com-
bined structure of one or more rectifier stacks, complete with all its
connections together with the means for cooling, if any, ( for example a
blower or fan ) in its own mechanical structure ( see Fig. 3 ).
2.6 Rectifier Equipment - An operative assembly comprising one or
more rectifier stacks, together with trnnsformcrs and otller auxiliaries, if
any, for conversion of ac into dc ( J’PBFig. 4).
3
SUPPLIED BY BOOK SUPPLY BUREAU TO L&T LIMIED ECC DIVISION
UDYOG VIHAR GURGAON FOR INTERNAL USE AT THIS LOCATION ONLY
4
+
ISr2511-1963
SUPPLIED BY BOOK SUPPLY BUREAU TO L&T LIMIED ECC DIVISION
UDYOG VIHAR GURGAON FOR INTERNAL USE AT THIS LOCATION ONLY
IS : 2511- 1963
N
+
FIG. 4 RECTIFIEREQUIPMENT
5
-_(I
h- --_-. .-... _ .-.
FIG. 6 RECTIFIERCONNECTION
2.9 Arm of a RecMer Connection- One rectifying element of a rectifier
connection ( see Fig. 7 ) .
? 9
6
IS t 2511*1%3
7
‘1s I 2511-1963
3. RATINGS
3.1 Semi-conductor rectifiers shall be rated in terms of ac rms input
voltage of approximately sinusoidal form and of mean dc output voltage
and current.
3.1.1 Basic Chd- The basic rating shall be for operation on a
single-phase bridge circuit with a purely resistive load with unaided and
unimpeded convection cooling in clean air,
The ratings of a rectifier stack may be calculated from the rating
of the reference rectifier stack in the basic circuit. A manufacturer may,
therefore, give the ratings of a series of stacks comprising one type
8
IS t 2511- 1963
9
IS : 2511.1963
3.5.2 Utili<ation Factor - This factor shall be stated as the ratio between
the load time and the total time for non-continuous load where each load
period is long enough to give practically stationary temperature conditions.
3.6 Types 6f Load - For the purposes of rating, the type of rectifier load
should be specified, that is resistive load, inductive load, capacitive load,
battery load,’ machine load or combination of loads. If not otherwise
specified, the load shall be taken to be resistive.
3.7 The rating of rectifiers may be increased by asslsted cooling; on the
1 Half-wave connection 1
2
+
m_ Back-wave connection 1
+
3
P- Centre-tap connection 2
10
I
~--_---.___-._ _
rSr2511-1%3
+ NUMBEB
6
d3! Two-step voltage-doubler connec-
tion 1
!b-
9 Three-phase star ( shown with
zig-zag tranrformer a8 an
example ) 3
+
10 Six.phase star 6
Three-phase bridge 6
11
P
IS I 2511- 1963
5. MARKING
5.1 Each rectifier stack shall be clearly and indelibly marked with the
following information:
a) The manufacturer’s name and/or trade-mark,
b) Date of manufacture ( may be given by quarter ),
c) Country of manufacture,
d) The following symbols or colours for the terminal markings:
AC 4 Yellow
DC positive + Red
DC negative - Blue
5.4 Rectifier stacks may also be marked with the IS1 Certification Mark.
NOTE- The use of the IS1 Certification Mark is governed by :be provisions of
the Indian Standards Institution (Certification Marks) Act and the Rules and
Regulations made thereunder. The IS1 Mark on products covered by an Indian Standard
conveys the assurance that they have been produced to comply with the requirements
‘of that standard under a well-defined system of inspection, testing and quality control
which is devised and supervised by ISI and operated by the producer. IS1 marked
products are also continuously checked by IS1 for conformity to that standard as a
further safeguard. Details of conditions under which a licence for the use of the IS1
Certification Mark may be granted to manufacturers or processors, may be obtained
from the Indian Standards Institution.
12
IS t 2511- 1963
FORWARO
CURRENT
REVERSE
CURRENT
REVERSE
REVERSE VOLTAGE
CURRENT
ALTERNATIVE 1 ALTERNATIVE II
13
IS : 2511- 1963
7. PERFORMANCE REQUIREMENTS
7.1 Service Time
7.1.1 During the service time, which applies for rated service (corn;
prising a given duty factor ) and includes the off time, the ac voltage has
to be increased for maintaining the rated dc voltage on account of the
steady increase in the forward voltage drop. But at the end of the rated
time, the ac voltage necessary shall be the rated ac voltage and shall not
be increased further. As the forward voltage drop is steadily increasing;
RATED DC VOLTAGE
- -%_VcL_ra_cE
RATED SERVICE TIME --__
(INCLUDING OFF TIME) ’ --__
AT GIVEN DUTY FACTOR
TIME WHEN RATED OUTPUT
I, CAN NO LONGER DE OBTAINED
END OF RATED
s%x SERVICE TIME
14
IS: 2511-1963
2x$.+1ooov
ull
7.3.3 -- 2
Where 1/ is not higher than 90 V, insulation may be tested at
a lower voltage than given in which shall be clearly stated by the
7.3.2,
manufacturer.
8. TESTS
8.1Type tests for approval and routine tests during manufacture shall be
applied as detailed below:
Tyke Test Routine Tat
Inspection ( 8.2 ) Inspection ( 8.2 )
Forward Voltage Drop ( 8.3 ) Forward Voltage Drop ( 8.3)
Reverse Leakage ( 8.4) Reverse Leakage ( 8.4 )
High Voltage (8.5 ) High Voltage ( 8.5 )
Output Voltage ( 8.6)
Conversion Efficiency ( 8.7)
Load ( 8.8)
Shelf Life ( 8.9 )
8.1.1 The type tests shall be made by a recognized testing authority
which may be the manufacturer itself.
8.2 Inspection
8.2.1The rectifiers shall be subjected to a general inspection for the
quality of workmanship and finish.
15
IS I 2511- 1963
8.3.1 The average voltage drop measured at the temperature of 27 & 5°C
and between adjacent pairs of terminals shall not exceed I.5 volts per
series connected cell when the normal rated dc output current of the
section under test is caused to flow in the conducting direction of the
rectifier ( see also Appendix C ).
8.5.1 All the terminals in the same circuit shall be connected together
and the test voltage in accordance with 7.3 shall be applied between the
terminals and the spindle and between the different circuits, if there are
more than one on the same spindle, for a period of one minute. There shall
be no breakdown or other evident deterioration.
8.6.1 For this test, the rectifier unit in association, if necessary, with
others of the same type shall be connected into a single-phase bridge
circuit and operated on resistance load at its rated current and input
voltage. The input shall be obtained from a low impedance source of
sinusoidal voltage.
8.6.2 The dc output voltage shall be measured and shall not be less
than the manufacturer’s rated figure.
8.6.3 Where it is also important that a maximum value shall not be
exceeded, the purchaser shall draw the attention of the supplier to this
fact at the time of enquiry and order.
8.7.1 Under the test conditions of 8.6, the measurement of input volta e,
input watts, mean output currents and mean output voltage shall % c
recorded and the conversion efficiency calculated f see 2.28 ).
16
IS : 2511 - 1%3
8.9.1 The rectifier stack shall be stored for a period of six months under
clean and dry condition and at all times in equilibrium with the atmos-
pheric conditions of the room. At the end of this period, the rectifier
stack shall be capable of meeting the requirements of 8.2 to 8.6 after
re-forming, if necessary.
APPENDIX A
( czausf?3.9 )
RATINGS OF RECTIFIER STACKS
A-l.1 The rectifier stacks are largely rated on thermal basis, that is ratings
are chosen so that the corresponding internal heat losses will not result in
excessive stack temperatures.
A-1.1.1 Internal heat losses in stacks consist of: (a) the forward loss due
to the passage of load current. through the forward resistance of the cells,
and (b) the reverse loss due to the flow of reverse or leakage current
through the reverse resistance of the cells.
17
Is : 2511-1%3
A-1.1.3 The total internal heat loss in watts is the sum of the forward
and reverse losses and may vary directly or inversely with the cell
temperature or may remain substantially constant over a wide range of
temperature depending upon the choice of voltage and current per cell.
A-l.2 When a rectifier stack has more than one cell in series per elemen),
it is only necessary to multiply the voltage rating for the specified circmt
by the number of cells in series to get the total voltage rating of the stack.
Likewise, when there is more than one cell in parallel per element, the
current rating should be multiplied by the number of cells in parallel to
get the total current rating of the stack.
APPENDIX B
( czause5.2 )
B-1.1.1 Strucfu~e Code-A code giving the structure of the stack with
regard to connection and number of cells in series and parallel per arm.
18
ISr2511-1963
and the first five positions are the manufacturer’s own code for other
indications not given in the structure code, such as ratings, brackets,
finish, etc.
xxxxx xxxxx
Manufacturer’s Code Structure Code
xxxxx 12 A 02
Connection
Example 2;
xxxxx 123 A 1
B-2.3 Code letters according to the following table shall be used for
designating the stack connection.
NOTE -As these designations refer only to the structure of stacks, these
connections may be used for several purposes. The connections F and S may be used
with or without interphase transformer. More stacks may be combined to form
another connection, for example two D stacks may be used to make a single-phase
bridge.
19
iS : 2511- 1963
0 4
7 0
1 Half-wave A
3 Centre-tap, negative N
4 Voltage doubler
Single-phase bridge,
positive outer P
20
_^__._
IS t 2511- 1963
9 Three-phase star,
common negative Y
h N N
12 Three-pulse bridge G
__-__-__--_-~----
t - + - +
APPENDIX C
( Clauses 6.2, 8.3 and 8.4)
TEST METHODS
C-O. GENERAL
C-O.1 Power losses, forward voltage drop and reverse current are prefer-
C-l. PROCEDURE
C-1.2 The short-circuit test gives the forward power losses and forward
voltage drop. The open-circuit test gives the reverse pov.er losses and
reverse current.
22
SUPPLIED BY BOOK SUPPLY BUREAU TO L&T LIMIED ECC DIVISION
UDYOG VIHAR GURGAON FOR INTERNAL USE AT THIS LOCATION ONLY
SHORT’ CIRCUIT OPEN CIRCUIT SHORT CIRCUIT
Al = ac ammeter.
A2 = Moving coil ammeter ( low voltage drop ).
A, = Moving coil ammeter with rectifier for measuring the average reverse current.
VI = ac voltmeter.
k2; = Electra-dynamic wattmeter.
NOTE- Amme&zrs,voltmeters and wattmeters used in this connection diagram shall be of an accuracy class
not inferior to 1.5 [ se$S : 1248-1968 Specification for direct acting electrical indicating instruments (Jirst reuisiun )].
FIG. 10 CONNECTIONDIAGRAM
IS':2!511-1963
24