Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
0% found this document useful (0 votes)
66 views

Acmv Calc

This document provides information about two rooms - a UPS room and battery room. It includes details about the size, orientation, construction materials and occupancy of each room. It also calculates the internal and external heat gains for each room based on factors like lighting, equipment load and wall conduction. The total BTU requirements are calculated to be 21206.49 BTU/hr for the UPS room and 14893.02 BTU/hr for the battery room, which can be met by specific Daikin air conditioning units.

Uploaded by

Yvonne Toh
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
66 views

Acmv Calc

This document provides information about two rooms - a UPS room and battery room. It includes details about the size, orientation, construction materials and occupancy of each room. It also calculates the internal and external heat gains for each room based on factors like lighting, equipment load and wall conduction. The total BTU requirements are calculated to be 21206.49 BTU/hr for the UPS room and 14893.02 BTU/hr for the battery room, which can be met by specific Daikin air conditioning units.

Uploaded by

Yvonne Toh
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 8

1 Location of space: Jurong Island / coastal area

Ambient temperature for outdoor air: 33 °C

2 Room/ space datas & orientation (façade orientation)

Size of room
UPS area = 4650 x 3200
= 14.88 m2

UPS room: (W x Dx H) mm x mm x mm
= 4650 x 3200 x 3225
3
= 47.988 m

Battery room area = 2410 x 3200


3
= 7.712 m

Battery room: (W x Dx H) mm x mm x mm
= 2410 x 3200 x 3225
= 24.8712 m3

Room is located at North west of the station.

3 Room construction materials


wall, partition & floor

4 No. of occupancy & room usage


4 persons, occasional maintenance

I Internal heat gain


i- heat gain from lighting
Based on SS530, Office lighting power = 15 W/m2
UPS room lighting load = 15 x 14.88
= 223.2 W

Battery room lighting load = 15 x 7.712


= 115.68 W

ii- heat gain from human (4x)


Based on ASHRAE, office human sensible = 75 W/person
latent = 55 W/person

human load (S) = 75 x 4= 300


human load (L) = 55 x 4= 220

iii- Electrical equipment (General office 25 W/m2)

II External heat gain


i- heat gain from wall (conduction heat gain)
Q = A x U x ΔT

UPS room perimeter = 15.7


UPS room wall area = 16 x 3.225
= 50.63
Wall U-value =

Battery room perimeter = 11.22


Battery room wall area = 11 x 3.225
= 36.18
Wall U-value =
W
W
Battery Ah = 325 Ah
no. of cells = 316
T, battery recharge time = 12 hrs
I charging = 29.79167 A (vendor doc, charging cur

Hydrogen Evolution
per AH per Cell = 0.00042 m3
Total Volume of hydrogen evolved = 3.95395 m3 per hour
(vendor doc, charging current 32.5A)

(as per vendor doc EL-DAS-2020) - value same


(as per vendor doc EL-DAS-2020, pg 29, H2 emission is 4.31 m 3/hr) - value quite close, due to charging current difference.
arging current difference.
1 Room/ space datas & orientation (façade orientation)

Size of room
UPS area = 4650 x 3200
2
= 14.88 m

UPS room: (W x Dx H) mm x mm x mm
= 4650 x 3200 x 3225
= 47.988 m3

Battery room area = 2410 x 3200


= 7.712 m3

Battery room: (W x Dx H) mm x mm x mm
= 2410 x 3200 x 3225
3
= 24.8712 m

Room is located at North west of the station.

2 Room BTU

1 ton = 12000 Btu/hr


Office space heating / cooling = 26 m2/ ton
UPS heat dissipation = 4.2 kW (Reduce UPS heat dissipation, 7kW h
= 14338.8 Btu/hr

X, UPS room BTU based on area = 14.88 x 12000 / 26


= 6867.692 Btu/hr

UPS room BTU total = X + UPS heat dissipation


= 6868 + 14338.8
= 21206.49 Btu/hr (Daikin FTKS71FVM is OK)

Battery heat dissipation = 1 kW


= 3414 Btu/hr

Y, Battery room BTU based on area = 24.87 x 12000 / 26


= 11479.02 Btu/hr

Battery room BTU total = Y + Battery heat dissipation


= 11479 + 3414
= 14893.02 Btu/hr (Daikin FTKS50GVMG is OK)
UPS heat dissipation, 7kW heat dissipation is for full load operation; MOV not working for most of the time)

KS50GVMG is OK)

You might also like