Circuit Breaker Maintenance, Sentinels On Guard
Circuit Breaker Maintenance, Sentinels On Guard
BREAKER MAINTENANCE
www.rittal.ca
See page 4444and 45
For Product Release
Switch to perfection
Reference this Ad No. MRKT A001
Continued from page 33 more. This can be disastrous ager. After a brief, colourful
the breaker to operate. This may be the because the fault will eventu- description of how the
case because the calibration process is ally erupt into something product can’t flow without
being undertaken while the system is much larger later on. power, the poor electrician
still in operation. If this has been done, Reliable settings are the returns to the substation to
make sure that the breaker is entirely first step for proper circuit fix the breaker once and for
operated through the protective system breaker performance. With an Figure 3: Typical Siemens all. This time his repair
as soon as possible after the relay cali- accurate and up-to-date co- 1600 Amp Contacts involves a 2x4 piece of
bration is completed. In all too many ordination study on file for lumber. The breaker is now
cases, I have found breakers your power system, you have the permanently closed, fixed for good!
where trip coils, mechanisms or ability to make an educated deci- Thirty minutes later, our friend is in
control wiring have become sion about changing settings with- the cafeteria having coffee, on break,
inoperative, and the breaker out putting your entire operation at telling his pals how he saved the shift
would never trip regardless of risk. and was thanked by the night shift man-
the signal it receives. ager. Coffee is suddenly interrupted by a
The other extreme exists as TRUE STORY! loud bang (explosion), the lights go out,
well. We go from the breaker A plant maintenance electrician on the plant goes very quiet and in the dis-
that refuses to trip to the one night shift gets a call that a main tance he can hear fire trucks.
that is constantly tripping — 600-volt, 3000 amp breaker has Three days of down time and
better known as the nuisance tripped. This has happened before $400,000 in repair bills later, the plant
Figure 4: 44kV
trip. Personally, I think this is and he has reset it without was back in service.
GE OCB Arc
more than just a nuisance when trouble. He goes to the substa- The electrician was
Chamber
you consider the down time and tion and does what he usually reminded that 2x4s are
frustration that these cause. A breaker does, closes the breaker. He has a not part of his tool kit.
nuisance trips for one of five reasons: quick look around and sees no The start of the prob-
defective relay; the protection settings problem, so he returns to his tool lem was a burning
are wrong; the settings were changed by crib. ground fault in an out-
someone; the proper settings were never About 20 minutes later another Figure 5: 13.8kV FPE door bus duct. The
applied; or the connected load has call comes in. The same breaker has Bus Fingers poor breaker was
changed. Sometimes these operations tripped. Now he’s mad. He goes to the doing what it was supposed to do. No
are misinterpreted as false trips instead substation and this time turns up the one took the time to look at what was
of real trips. A real trip is overcurrent relay settings fig- causing the symptoms (see Figure 7).
a symptom of a problem, uring there is an overload
not a problem. Often somewhere. Again he closes INSULATION SYSTEM DECAY
though, the action taken the breaker and returns back Insulation system failures are attrib-
to eliminate the breaker to the crib. uted to the operating environment and
trip symptom is to turn About 30 minutes pass and a the frequency and severity of operation.
up the settings so that the Figure 6: Destroyed third call comes to him. Now You must be aware of the environment.
breaker doesn’t trip any Contactor Insulation it’s the production shift man- Substations that are unattended for long
periods of problem. The application of an excessive look at the application of the breaker.
time can de- amount of force is only making the prob- This could be a very dangerous situation
velop prob- lem worse. waiting to get a lot worse.
lems without
notice. This POWER AND CONTROL LOSS OF INSULATING MEDIUM
is particular- PROBLEMS Gas, vacuum and oil breakers
Figure 7: What Was Left
ly the case in Power and control connection prob- require an additional extinguishing
outdoor, medium-voltage stations. Here, lems result from a misalignment in the medium to break the arc when the con-
moisture from a leaky roof or excess switchgear cell (again, usually caused by tacts part. Most manufacturers will tell
humidity can cause the formation of using too much force to remove and you that their breakers will survive an
corona (a faint glow adjacent to the sur- insert draw-out type breakers). operation under fault if the medium dis-
face of an electrical conductor at high If a bus finger fails under load, the appears. I would not want to be around
voltage) very quickly. This can eventual- result would be disastrous. The bus fin- to witness this! Oil is simple because
ly lead to serious tracking and insulation gers are not designed to break any type there is always a sight glass. And a large
failure. of current what so ever. If they were to puddle under the breaker is sure sign of
Obviously, any water leaking into fail under full load, the ensuing arc wou- problems. Vacuum breakers are another
switchgear is very serious and may cause ld destroy the breaker and cause serious story. Most are fitted with pressure
an arc well before corona even begins. A damage to the switchgear. The failure of switches to monitor the vacuum level. It
dirty environment contaminated with control fingers is just as important since amazes me to see so many of these
conductive or corrosive material will this may disconnect the trip and close switches not wired up to some type of
also lead to premature insulation decay controls from the protection system. warning or annunciation system. SF6
and eventual failure. breakers have the same type of level
Breakers that frequently operate CONTACT WEAR detection system as vacuum breakers.
under heavy loads and faults, will suffer Rarely do you see contact wear, But, again, the system is rarely wire to a
insulation damage caused by the extreme unless the breaker is really over-worked warning system. This gas can be detect-
heat of the arcs drawn. It is common to because of the operation frequency, ed by using a simple Freon gas detector.
see inter-phase barriers, arc chutes and switching heavy loads, multiple opera- If there are arc by-products in the gas
pole supporting insulation burned. This tions under fault, under-rating or insuffi- you will also notice the smell of rotten
will also lead to tracking and eventual cient interrupting rating. When you find eggs in the substation.
failure. excessive contact wear take a very close
Continued on page 37
MECHANICAL SYSTEM STIFFNESS
General mechanical failure of the The ONLY 3 - Color, 3-D Engraved Signs Made to
trip, close and the racking mechanism is
caused by wear and tear, contamination Last a Lifetime!
from a dirty environment and finally,
excessive force (the human kind!). TM
Lubrication is essential to keep the link-
ages, rollers and bearings in the mecha-
nism working freely. Dirt buildup inside PATENT PENDING
the mechanism can dry out or gum up
the mechanism, causing the bearings and Made of Tri-Extruded UV Stabilized High
rollers to seize. You are eventually left Density Polyethylene, and 3-D engraved,
with a breaker that is, for all intents and these Danger Signs are impervious to
purposes, stuck shut or stuck open. On virtually all acids, alkalis and caustic
the other side, the breaker could be very chemicals. Resistant to extreme changes
sluggish in operation. Both of these in temperature or environment, they will
cases would allow fault currents to flow not chip, fade, crack or peel.
for a much greater time than your equip- In fact, Almetek believes so strongly in
ment can withstand, leading to a destruc- the durability, longevity and dependability
tive failure. of this innovative and revolutionary prod-
Many circuit breakers are physically uct line, that every danger sign is backed
abused. This comes from a complete by an unprecedented 30-Year Warranty.
lack of knowledge on how to safely For further information on our entire line
operate a breaker. Any breaker that of standard or custom TRIDENT ™
requires some type of lever, several peo- Danger and Safety Signs, call, fax or
ple or a pry bar to make it work, has a visit us on the web at www.almetek.com.
INDUSTRIES, INC.
® 800-248-2080
TM
If You Identify With Quality You Identify With Us.
908 850-9700 • Fax: 908-850-9618