Instrumentation and Control (I&C) Design
Instrumentation and Control (I&C) Design
Inputs Required
Below listed references are the required inputs for the preparation of
the document “Instrumentation & Control Design Basis”.
2
Typical Structure of Design Basis of Instrumentation
& Control
Instrumentation & Control Design Basis should cover below listed
technical requirements as a minimum.
2. Units of Measurements
9. Spare Philosophy
In this article, we shall talk about the first THREE points in detail.
Examples: ASME Boiler and Pressure Vessel Code, BS, DIN, etc.
3
The rule issued by a regulatory body appointed by a state and/or
central government.”
Units of Measurement
System for measuring unit either “Metric” or “Imperial” should be
clearly identified in the I&C design basis with respect to the system
follows in a country where plant to be build or as per requirement
specified in the client’s specification/philosophy.
“Metric” system is generally preferred all over the world for units of
measurement except the USA where the “Imperial” system is being
followed.
4
5
Control System Philosophy
I&C design basis should cover the below-listed details/requirements
as applicable for the control systems.
6
Generally preferred for MCC/VFD signal interface, where the
distance between electrical sub-station building or Instrument
equipment room is more.
Package control by
Plant main DCS and SIS
PLC / other control system (Supplied by package vendor)
Type of package configuration
Package skid with dedicated local control panel
Package skid with junction boxes and without dedicated local
control panel
Package skid without junction box and local control panel
Type of communication between DCS and package control
panel
Hardwired Interface
Serial communication (e.g. Modbus RS 485, 232, Modbus
TCP/IP)
Power Supply & Instrument Air Supply Philosophy
Power Supply Requirements:
Below is a sample illustration to specify the power
supply requirement for type of Instruments and control system.
Specific requirement if specified in client’s specification/philosophy
then same to be covered in I&C design basis.
7
Instrument Air Requirements:
Requirements are generally specified in input document “Process
design basis”. Which shall be basis/reference for Instrument
manufacturers (e.g. Control & On-off valve), Mechanical package
supplier and other pneumatically operated field Instruments.
8
Preferred method of Instrument to be specified either “Intrinsic safe
(Ex ia)” or “Flameproof (Ex d)” as per the requirements.
9
o Analog Signals (4 to 20 mA, HART)
o Digital Signals
Digital input signals (either pot free or inductive
proximity signal)
Digital output signals (either pot free or Voltage
power signal)
Pot free contact shall always wired through relay
o Frequency Signals (Speed monitoring)
o Serial communication signals
Power supply
o Remote mount
o Direct mount
o Close coupled assembly
o Instrument manifold requirement (2 way, 3 way or 5 way)
o Pneumatic tubing size & Material (Generally stainless
steel tube and size of ¼” OD used. ¾” or ½” may use for
Pneumatically powered Instruments like, control valve / on-off
valve.)
o Cable routing philosophy
o Under ground (duct / tranches)
o Above ground (Perforated trays / Ladder Trays / Cable
conduits)
o Process connection for all In-line field instrument
generally flanged type as per ANSI B16.5 and B16.47 in
accordance with the piping specifications.
Instrument Cable Entry Type
11
Instrument cable tray spacing requirement
13