Applsci 10 00822 v4 Good Paper
Applsci 10 00822 v4 Good Paper
Applsci 10 00822 v4 Good Paper
sciences
Article
Experimental Study on the Flexural Behavior of over
Reinforced Concrete Beams Bolted with Compression
Steel Plate: Part I
Shatha Alasadi 1,2, * , Payam Shafigh 3,4, * and Zainah Ibrahim 1, *
1 Department of Civil Engineering, Faculty of Engineering, University of Malaya, Kuala Lumpur 50603,
Malaysia
2 Department of Civil Engineering, Faculty of Engineering, Al-Mustansiriyah University, P.O. Box 46049
Baghdad, Iraq
3 Department of Building Surveying, Faculty of Built Environment, University of Malaya, Kuala Lumpur
50603, Malaysia
4 Center for Building, Construction & Tropical Architecture (BuCTA), Faculty of Built Environment, University
of Malaya, Kuala Lumpur 50603, Malaysia
* Correspondence: shsk_alasadi@yahoo.com or shatha@uomustansiriyah.edu.iq (S.A.); pshafigh@gmail.com
or pshafigh@um.edu.my (P.S.); Zainah@um.edu.my (Z.I.)
Received: 16 December 2019; Accepted: 15 January 2020; Published: 23 January 2020
Featured Application: A bolt-compression steel plate (BCSP)-system is usually used for effective
method to improve flexural behavior of over-reinforced concrete beams. Using steel plate in
compression zone increase flexural capacity of RC beam. The BCSP beam can behave as ductile
structural member.
Abstract: The purpose of this paper is to investigate the flexural behavior of over-reinforced concrete
beam enhancement by bolted-compression steel plate (BCSP) with normal reinforced concrete beams
under laboratory experimental condition. Three beams developed with steel plates were tested
until they failed in compression compared with one beam without a steel plate. The thicknesses
of the steel plates used were 6 mm, 10 mm, and 15 mm. The beams were simply supported and
loaded monotonically with two-point loads. Load-deflection behaviors of the beams were observed,
analyzed, and evaluated in terms of spall-off concrete loading, peak loading, displacement at mid-span,
flexural stiffness (service and post-peak), and energy dissipation. The outcome of the experiment
shows that the use of a steel plate can improve the failure modes of the beams and also increases the
peak load and flexural stiffness. The steel development beams dissipated much higher energies with
an increase in plate thicknesses than the conventional beam.
Keywords: over-reinforced; bolting; BCSP; energy dissipation; steel plate; flexural stiffness
1. Introduction
In the development of civil engineering, the increase in critical sections is essential for the
improvement and strengthening of the critical section. One of the most significant aspects is the
over-reinforced section in the structure. However, due to various reasons, improvement is essential in
over-reinforced members to prevent brittle failure and undue aging. With this improvement, the beams
possess higher ductility and stiffness, including high energy absorption to carry extra loads [1,2].
Notably, the most conventional techniques for the design of flexural beam in the brittle failure
of concrete are not permitted by several international codes of practice [3,4] due to the low ductility
of the members. According to ACI 318–02 and AS3600 [3,4], the reinforcement ratio of the flexural
reinforced concrete beams is classified into three categories, which may be balanced, under-reinforced,
and over-reinforced. Therefore, the development of the over-RC beams can be obtained by replacing
the steel bars in compression with quality materials, which exhibit better performance. The section
of the replacement material will depend on the method of the section development. Moreover,
several methods were used in the past with various degrees of success. The methods included helical
reinforcement [5–8], short stirrups with/without steel fiber [9], hybrid system, hybrid reinforced
concrete beams. These beams consisted of two or three layers of diverse concrete strength levels. This
range of strength could be seen from the top section made of high strength concrete (HSC), with a
bottom layer, which was made of normal strength concrete (NSC) [10], and an external bonding with
a steel plate in the side of the RC beam [11,12]. The steel plate bonding in compression was the
current method.
Overall, these methods were used to avoid brittle behavior and crushing failure. The use of helical
reinforcements in the critical zone at the mid-span of the beam was one of the most important methods
to develop the over-reinforced beam [13,14]. However, the studies conducted on the confinement
of columns have recently been the basis of the development of the confined compression zone in
beams [15,16]. Accordingly, further investigation on the behavior of confined normal strength concrete
(NSC), high strength concrete (HSC), and pre-stressed beams are required [6,7,16–18]. Elbasha and
Hadi [5] observed a linear increase in the spalling-off loads and decrease in ultimate load as the helical
pitch increased. However, the decrease in helical pitch was due to the increase in displacement. They
also reported that the failure yields and deflections were reduced with the increase in compressive
strength of the concrete. This was followed by a significant decrease in the ductility index as the
concrete compressive strength increased. Overall, it was indicated that the increase in the ratio of
longitudinal reinforcements would increase the displacement ductility index, allowing the occurrence
of a higher ultimate in the beam [8]. Several other findings were also developed on the installation of
short stirrups as confinements [19]. Specifically, Jeffery and Hadi reported that helical reinforcements
had higher effectiveness compared to short stirrups to improve the flexural capacity and displacement
ductility index of the confined concrete [6]. Further studies on the hybrid system involved the use
of different steel bars types, including normal reinforcement and Fiber Reinforced Polymer FRP
bars, as recorded by Qin et al. (2017) [20]. It was found in their study that high strength concrete
and ultra-high-strength concrete were reinforced with glass fiber reinforced polymer (GFRP). It was
also found that the highly reinforced beams exhibited a higher level of ductility compared to the
under-reinforced beams. Following that, ultra-high-strength concrete beams recorded higher energy
absorption potentials compared to the high-strength beams with the same amount of reinforcement [20].
Importantly, the main objective of the implementation of various techniques is to improve flexural
capacity and stiffness for the prevention of brittle failure of the over-reinforced beams.
Additionally, the use of external strengthening by bolted/glued steel plates system, which is a
low-cost system with high stiffness, has been proven to be an effective technique for the improvement
of the reinforced concrete structures. The system is glued to the beams and attached to the
compression/tension zones of the beam to increase its flexural capacity, ductility, and stiffness [21–23].
According to Oehlers and Moran (1990), RC beams that are strengthened with tension-face plates
may undergo brittle failure as a result of the disconnection between steel plates and concrete surfaces.
Therefore, overcoming premature failure is key in the design of beams with externally glued steel [24].
Oehlers et al., (1998), also highlighted that the use of web bonded steel plates could prevent premature
failure of reinforced concrete members with flexural strengthening [25]. Based on Siu and Su’s (2011),
study on the flexural performance of bolted steel plates BSP beams, it was found that omitting the
partial interaction between the beams and the steel plates would lead to up to 30% of overestimation
of the enhancement [11,26]. However, various techniques and materials to strengthen structural has
received significant attention among researchers in the recent decades.
To date, a few studies have investigated the behavior of concrete beams that are over-reinforced
using the bolts compression steel plates (BCSP) system. Therefore, this study aims to investigate the
Appl. Sci. 2020, 10, 822 3 of 20
effects of bolts compression steel plates (BCSP) on the behavior of over-RC beams. It attempts to
change the behavior failure from brittle to ductile. Furthermore, achieving an inelastic mechanism with
appropriate deformation capacity will reduce the crushing by the BCSP-system. This was followed
by the improvement in strength, strain, and energy absorption (EA) for the over-reinforced section.
In this research, simply supported beams and steel plates of different thicknesses were used in the
development sections.
2. Experimental Work
Specimen Reinforcement Steel Plate (mm) No. of Shear Span Stirrup Spacing
ρ% ρb%
Designation Bolts Ratio (a/d) (mm) 6Ø (c/c)
Ten. Com. t L
CB 5Ø20 2Ø6 - - - 3.27 2.856 2.7 50
BCSP-6 5Ø20 2Ø6 6 1100 24 3.27 2.856 2.7 50
BCSP-10 5Ø20 2Ø6 10 1100 24 3.27 2.856 2.7 50
BCSP-15 5Ø20 2Ø6 15 1100 24 3.27 2.856 2.7 50
Cement (kg) Fine Aggregate Coarse Aggregate Water (kg) W/C (%)
375 888 933 150 0.4
A beam specimen without a steel plate was prepared and used as a control beam (CB) to
demonstrate the structural performance of an over-reinforced beam without a development. Meanwhile,
the BCSP beams used in this study were divided into three series, namely the BCSP-6, BCSP-10,
and BCSP-15 beams developed by the steel plate of 6 mm, 10 mm, and 15 mm thicknesses. To develop
a bond between the steel plate and the concrete, 24 bolts with 200 mm length and 12 mm diameter
were used [32]. The steel plates were 1100 mm long and 180 mm wide. Additionally, holes of 12.5 mm
clearance were added to the plates to enable tolerances during the bolting. Corresponding details
Appl. Sci. 2020, 10, 822 4 of 20
are presented in Table 1. Each of the beams was cast using a steel formwork. However, as shown
in Figures 4 and 5b, the BCSP beams of bolting-compression plates were provided by placing two
pieces of wood under the plates during concrete casting. As shown in Figure 5a. The beams were then
cured for 28 days before the external plates were fixed to cast-in sockets with the bolts. Afterward, the
bolts were cast to the beam in order to prevent any slip within the clearance hole of plates and avoid
buckling of the steel plates.
Figure 1. Detailing of all the over-reinforced beam specimens (a) control beam (CB) and (b) bolts
compression steel plates the (BCSP-6), BCSP-10, and BCSP-15 beam (all dimensions in mm).
Figure 2. Details of the reinforcement for the over-reinforced specimens (all dimensions in mm).
Appl. Sci. 2020, 10, 822 5 of 20
Figure 4. Casting the over-reinforced beam and after one day of the cast and location of bolts.
Figure 5. View of (a) curing for all specimens and (b) all the over-reinforced beam specimens.
jack with 50 mm stork length was used to apply the static load. The load was then transferred from the
actuator to the spreader beam through a stub column of 2000 mm. Figure 6a,b present a schematic view
of the experimental specimen for the test-setup and equipment used in the study. Moreover, a linear
variable displacement transducer LVDT was used to measure the mid-span displacement of the beams
at a rate of 2 mm/min until peak flexural failure took place. The initial cracks were observed during
the experiment, followed by the visual monitoring of the propagation of the cracks. The crack pattern
was carefully marked and the loads were recorded accordingly. Two electrical resistance strain gauges
were attached at the top of the beams, directly underneath the position of the load cell, to measure
the concrete strain; the same position was also used to measure the strain of the steel plate. Two
strain gauges were attached at the middle of the beam span in the longitudinal direction of the tensile
bars on the bottom to measure tensile strain. All the experimental data including strains, load and
displacement at mid-span for over-RC beams were recorded by a data logger, as shown in Figure 6a,b.
Figure 6. (a) Schematic of the test-setup for over-reinforced beam specimens and (b) experimental for
the BCSP beams test-setup.
Figure 7. Modes of failure and crack patterns of all the over-reinforced specimens.
Table 3. Measured values of the type loads of all the over-reinforced specimens.
Specimens Pcr Pcr of Web PSpall PYieldl ∆spall ∆Yield PPeak ∆peak
∆ (mm)
Designation (kN) Shear (kN) (kN) (kN) (mm) (mm) (kN) (mm)
CB 71.5 1.87 220 356 - 8.33 - 375.5 10.8
BCSP-6 247 3.48 322 521 - 8.2 - 652.3 11.7
BCSP-10 362 3.73 722 635 - 6.9 - 837.6 12.5
BCSP-15 460 3.99 833 - 935.3 - 10.2 935.3 15.5
Appl. Sci. 2020, 10, 822 8 of 20
Figure 8. Modes of failure and crack patterns of all the CB, BCSP-6, BCSP-10, and BCSP-15 beam
specimens at 80% peak load.
Table 4. Experimental and predicted nominal loads and the type of failures of the tested.
Specimens
PSpall (kN) PYield (kN) Panaly (kN) Panaly /PSpall (%) Panaly /PYield (%) Failure Mode
Designation
CB 356 - 354 0.98 - crushing, brittle failure
spalling under
two loading
BCSP-6 521 - 514 0.98 -
point(compression-shear)
and yield of steel plate
spalling under two
BCSP-10 635 - 637 1.00 - loading point and yield of
steel plate
flexural and yield of steel
BCSP-15 - 935.3 850 - 0.90 plate (No spalling of the
concrete)
In the case of the specimen, the BCSP-6 beam was developed with the thickness of the steel plate
as 6 mm and 24 bolts-compression arrangement. Slow propagation of flexure and flexure-shear cracks
was also observed. Additional cracks were found on the concrete cover beyond the peak 1 loading.
As for this beam, the observed peak 1 loading amounted to 521 kN. After the crushing of the concrete
cover at the peak 1 loading, the beam was able to sustain additional loading, which was identified
as the reserve capacity or a pseudo ductility of the beam. Although a slower rate of crack formation
was present, higher crushing strength of the concrete cover was observed. The loading was stained by
the beam until horizontal cracks were formed in the compression zone at another loading, which was
denoted as peak 2. Although the reserve capacity of the beam was retained, a slight decrease in load
occurred at this point until total failure occurred at peak 3, as shown in Tables 3 and 4, Figures 7b
and 8b. As the peak 2 loading amounted to 560.1 kN, whereas peak 3 loading amounted to 652.3 kN.
Meanwhile, the load at peak 2 ranged from 560.1 to 644.2 kN, while the load at peak 3 ranged from
633.14 to 601.3 kN.
The BCSP-10 beam was developed with a 10 mm thickness of the steel plate. Peak 1 was observed
in this beam when the spalling of the concrete cover occurred. This was followed by observation on
the horizontal cracks at the compression zone underneath the loading points. The peak 1 loading for
this beam was 635 kN. Additionally, the beam was able to carry additional loads and exhibit reserve
capacity (pseudo ductility). Notably, there was a remarkable increase in the load-bearing capacity of
the beam at this stage until the observation of peak 2 at 837.6 kN load. The peak loading ranged from
Appl. Sci. 2020, 10, 822 9 of 20
801.25 to 794.7 kN. The concrete on the top of the surface was not damaged even at the point of failure
of the beam. Subsequently, its failure took place in a flexural mode with a slight horizontal cracking,
as shown in Tables 3 and 4, Figures 7c and 8c.
The last specimen, the BCSP-15 beam, was developed using 15 mm thickness of steel plate. As a
result, the beam remained stiff despite the widening of the cracks. The peak 1 loading for this beam
was observed as 935.3 kN. The beam sustained the additional load, exhibiting the reserved capacity or
pseudo ductility properties. Other than that, a stabilized and continuous load-bearing capacity was
evident at the B stage of loading into phase C due to the 935.3 kN increase in displacement. Phase D
led to the decline in the loading capacity into the phase F. Despite the failure of the beam, there was
no damage at the top of the concrete. Subsequently, the beam failure took place in the flexural mode
without horizontal cracking, as shown in Tables 3 and 4, Figures 7d and 8d.
The procedures for the failures of the BCSP-6 and BCSP-10 beams were similar in terms of the
concrete crushing at the loading points. Furthermore, the failure mode of these beams had been
developed through a bolting steel plate. Moreover, the failures of the BCSP-6, BCSP-10, and BCSP-15
beams occurred with a yield of steel plate. However, no buckling was involved. As the cross-section
was unaltered, a high load capacity could be maintained in the beams after the peak load for the
BCSP-10 and BCSP-15 beams.
Therefore, three types of failure modes were present in the over-reinforced beams, namely (1)
the crushing of concrete cover at compression mid-span, (2) initial spalling of concrete cover and
crushing underneath the loading point, and (3) the flexural failure. Additionally, an extension of the
shear cracks was present, including an increase in the crack width within the span. The flexural cracks
were formed at an approximate average spacing, which ranged from 80 to 120 mm. The stress-strain
diagrams were used to compute the analytical load capacities (Panaly ) based on the RC specifications of
the ACI-code [33]. This computation was also performed on the analytical load capacities based on the
results of the material test, as shown in Table 4.
Dear editor…
Please, of
3.3. Responses this
thefigure
Beams10
to has four Loads
Flexural figures such as , (a)CB , (b) BCSP-6, (c) BCSP-10 & (d) BCSP- 15,
can use the figure
Various responses were present in the over-reinforced beams towards the applied loads. To describe
the individual responses of the beams, regardless of the presence or absence of steel plates,
the characteristics of the beam bending were considered. Furthermore, the loading phases were
divided into five phases, as illustrated in Figure 10.
1000
90 0
900
75 0 800
700
60 0
600
500
45 0
400
30 0 300
200
15 0
100
0
0
0 4 8 12 16 20 24 28 32 36
0 5 10 15 20 25 30 35
Figure 10. Location varies of load–displacement curves for all the over-reinforced beam specimens.
Figure 10. Location varies of load–displacement curves for all the over-reinforced beam
specimens.
Appl. Sci. 2020, 10, 822 11 of 20
The peak load present in the horizontal cracking in the compression zone was indicated as a
spalling load by Pspall . Meanwhile, the center point deflection of the spalling load was identified as
∆spall . The second maximum loading, which was obtained after the spalling load was the peak load,
(Ppeak ), with the center point deflection being denoted as ∆peak . This peak was identified as a result of
the deformation-controlled testing system.
Five phases of response were identified as the beams were tested, which were represented in the
response curve by the areas ranging from 0 to F. The phase 0-A took place before the initial crack was
formed on the concrete. As the initial crack was observed, the cracked section responded to the loading
in a linear manner, as shown in the second phase A–B. Phase B–C was the non-linear phase before the
compressive capacities of the beams was achieved. In this phase, the spalling of the concrete started at
point B. Following this phase, the CB beam exhibited highly brittle characteristics, leading to failure of
compression shown in phase C–F in the response curve. During the fourth phase, another peak was
observed in the beams with the development of steel plates in section C–D due to the redistribution of
the internal stresses. Following this peak, the beams with the development of steel plates exhibited a
significantly ductile characteristic due to the increased stiffness and strength mobilized by the steel
plates. This phase was denoted as D–F.
Figure 10 presents the load-displacement curves for the center points of the four over-reinforced
beams. The maximum capacity of the CB beam was the spalling load. Therefore, the beam in which
capacity exceeded this load exhibited highly brittle characteristics. The responses of the beams indicated
the influence of the confinement configurations by system development on the behavior of the beams
during and after the spalling of the concrete cover. However, the introduction of confinement into the
compression zone resulted in an increase in elastic bending stiffness. The BCSP-6 beam experienced
a significant capacity increase from Pspall to Ppeak , indicating a combination of higher compressive
strength and increased ductility. Beyond the peak load, the significantly high load was sustained in
the beam. Furthermore, the BCSP-10 and BCSP-15 beams exhibited an increase in section stiffness.
A remarkable decrease in load was then observed after the first peak as a result of the spalling o the
concrete cover under the two-point loading. However, the only failure in flexure was observed in the
BCSP-15 beam, with no horizontal cracks in the compression zone or at the point loads. However,
through the increased thickness of the steel plate, it was ensured that the beams’ cross-section was
maintained with reduced flexural cracks through the redistribution of the internal stresses. Figure 11
illustrates the loads and displacement curves for each over-RC beams with the spalling loads and the
obtained displacements. The sections of the curve after the peak load indicated the ductile characteristic
of the beams.
Figure 11. Maximum width of flexural crack for all the over-reinforced beam specimens.
Appl. Sci. 2020, 10, 822 12 of 20
Figure 12. Typical load-displacement curves for evaluating the energy absorbed (EA) for all the
over-reinforced beam specimens.
Appl. Sci. 2020, 10, 822 13 of 20
Table 5. Energy absorption and ultimate strength increase for results of the tested all the
over-reinforced specimens.
Specimens Increase in
EA (kN.m) Ppeak (kN) Increase in EA (%)
Designation Strength (%)
CB 4.03 375 - -
BCSP-6 13.9 652.3 247.5 73.9
BCSP-10 16.7 837.6 317.5 123.6
BCSP-15 22.5 935.3 462.5 149.3
Figure 13. Energy absorption (EA) capacity for all the over-reinforced beam specimens.
3.6. Ductility
The ductility of the material is indicated through the energy absorbed by a material until a complete
failure takes place. In fact, material ductility is a crucial factor in the design of structures [11,37,38].
To quantify the ductility of a reinforced concrete structure, the ratio of curvature of the concrete from
the crushing to the yielding of the reinforcement is usually reported as the ductility index [10,18,39–42].
As over-reinforced beams were used in this study, the use of the yielding of reinforcements to
find the ductility index was more challenging. Alternatively, ductility indices were evaluated at 90%
of the spalling load based on the behaviors of the over-RC beams at the spalling load, peak load,
and post-peak response. This phenomenon is different from the seismic design methodology explained
in Euro-code 8 [43], where a post-peak value of 85% of the maximum bending value was used to define
the local sectional ductility index.
The definition of ductility presented in this study was based on the load-deflection curve under
compressive loading. Therefore, the displacement ductility ratios were defined as µ1 = ∆peak /∆spall
and µ2 = ∆0.9, spall /∆spall , while the center point deflection at 90% of the spalling load was defined as µ
0.9, spall . Tables 6 and 7 illustrate the BCSP-15 beam, where the calculation of the ductility was based on
the yield load.
Table 6. Test results of over-reinforced beams for index displacement ductility (µ1 ).
Table 7. Test results of over-reinforced beams for index displacement ductility (µ2 ).
Essentially, increasing the thickness of steel plates led to higher ultimate deflection and ductility.
A ductility of 10%, 19.1%, and 17% was achieved in the BCSP-6, BCS-10, and BCSP-15 beams respectively,
which was higher than the ductility of the CB-beam according to the spalling load (µ1 ). However, the
ductility of the BCSP-15 beam was based on the yield load. Meanwhile, the ductility index (µ2 ) for the
BCSP-6 and BCSP-10 beams amounted to 2.7 and 2.9 respectively due to the increase in the thickness
of the steel plate in the compression zone. As a result, the beam stiffness increased which restricted the
crack propagation and improved the ductility. An improvement in the BCSP-15 ductility index (µ2 ) by
2.2 was observed. For this reason, the toughness of the compression zones of the BCSP-15 beam posed
a minor influence on structural ductility. However, the capacity strength significantly increased due to
the inverse relationship between flexural capacity and ductility, as shown in Tables 6 and 7.
Table 8. Stiffness flexural for results of the tested all the over-reinforced specimens.
Figure 14. Flexural stiffness (K0.3Ppeak , Kspall , Kyield , and KPpeak ) of all the over-reinforced
beam specimens.
Table 9. Increased stiffness flexural for results of the test all the over-reinforced specimens.
stiffness, ductility, flexural cracking, and mode failure of the beams were compared, followed by the
development of several inferences.
The single or double helical reinforcement was found to be a satisfactory method to develop the
over-reinforced beam section [7]. This finding was proven through the fact that the experimental flexural
strengths of all the beams, which are developed with helical reinforcement, are higher than the strength
of the calculated ultimate flexural loads. Furthermore, the beams with helical confinements exhibited
lesser deformation compared to the control beams without development. Similarly, the BCSP beams
investigated in this study exhibited the same characteristic in terms of flexural strength and deflection.
Moreover, as the BCSP-system possessed a different curve of load-deflection, the system exhibited
more ductile characteristics compared to the conventional system. Besides being dependent on the
helical pitch, the helical system’s diameters were the main parameters influencing the effectiveness
of helical confinement of concrete. The BCSP-system was influenced by the thickness and length of
steel plates.
The helical reinforcements were found to be more efficient in improving the strength and ductility
of confined concrete compared to short stirrups [6]. Comparatively, the bolts-compression steel plate
was found to be more effective than helical. It also possessed short ties to enhance the strength, stiffness,
and EA of the beams.
Therefore, it could be concluded that crushing failure (spalling cover) is present in all methods
of the development of over-flexural sections at compression with flexural cracking. Accordingly, the
BCSP-system improved the mode failure and transitioned the behavior failure from brittle to ductile.
It also avoided sudden failure in the compression zone. Overall, the development of mode failure was
observed in this study using failure modes and crack patterns. The details of the flexural behavior
are presented in Section 3.1. This failure was due to the strain gradient effect, which occurred in
the effective thickness in the BCSP beams subjected to flexural stress. For this reason, the horizontal
cracking was reduced to a lower level compared to the cracking in tension. However, the systems with
the helical steel and side-steel plate experienced section improvement, which maintained the crushing
failure, as seen in Figures 15–17. These findings could be compared with the mode of failure of the
BCSP beams presented in Figure 7.
Figure 15. Modes of failure and crack patterns of over-reinforced beams with helical reinforcements
(beam 5) [7].
Figure 16. Modes of failure and crack patterns of over-reinforced beams with stirrups (3B) and fiber +
stirrups (4B) [9].
Appl. Sci. 2020, 10, 822 17 of 20
Figure 17. Modes of failure and crack patterns of over-reinforced beams with a side-steel plate (a) SBSP
and (b) SBWP [12].
4. Conclusions
A laboratory investigation was conducted on over-reinforced beams with a bolted compression
steel plate arrangement using various thickness levels. Based on the results of the investigation,
the following conclusions can be drawn.
1. Bolting the steel plates at the compression zone resulted in a significant increase in the load-bearing
capacity of the BCSP beams as the increase in steel plate thickness took place with the control
beam. The peak load-capacity of the BCSP beams ranged from 73.7% to 149% of the CB beam.
Notably, the BCSP beams sustained higher loads before the appearance of initial cracks. Therefore,
the use of steel plates was found to be an effective crack control strategy, which is highly important
in ensuring the serviceability of RC structures.
2. It could be concluded that the EA of the BCSP beams increased due to the increase in steel plate
thickness compared to the control beam. It was also observed that the increase in EA amounted
to by 247.5%, 317.5%, and 462.5% for the beams with 6 mm, 10 mm, and 15 mm steel plate
thicknesses respectively.
3. There was also an increase in the beams with the steel plates compared to the CB beam. Meanwhile,
the increase in the flexural service stiffness ranged from 73.7% to 122.7%. The steel plates exerted
additional resistance against the compressive forces after the concrete cracked.
4. The use of steel plates for the development of over-reinforced beams could contribute to an
increase in stiffness of the BCSP beams. This increase was due to the control of the steel plates on
the spalling of the concrete cover and the improvement in the failure modes of the BCSP beams.
5. The improvement in the over-RC beams with steel plates led to the transition of the nature of
failure from brittle to ductile. The beams sustained higher loads until the ultimate capacities were
achieved with the reduction of crushing on the top of the concrete, which was one of CB beam
weaknesses due to the sudden brittle failure.
6. Bolting the steel plates to the concrete led to a confining effect on the concrete, leading to less
severe horizontal cracks at the compression zone. Notably, due to a more significant confinement
effect on the beams, higher steel plate thicknesses were developed, which failed at higher loads.
Author Contributions: Conceptualization, S.A.; methodology, S.A., P.S. and Z.I.; software, S.A.; validation, S.A.,
P.I. and Z.I.; formal analysis, S.A.; investigation, S.A.; resources, S.A.; data curation, S.A.; writing—original draft
preparation, S.A.; writing—review and editing, S.A., P.S. and Z.I.; visualization, S.A., P.S. and Z.I.; supervision, Z.I.
and P.S.; project administration, S.A.; funding acquisition, S.A. All authors have read and agreed to the published
version of the manuscript.
Funding: This research received the funding no (Project No: GPF015A-2018) by the Faculty Research Grant of the
University of Malaya (UM).
Acknowledgments: The authors are grateful to the University of Malaya (UM) for the financial support provided
by the Faculty Research. The first author appreciates the Department of Civil Engineering, College of Engineering,
Al-Mustansiriyah University, and the Ministry of Higher Education of Iraq for providing support for her studies.
Conflicts of Interest: The authors declare no conflict of interest.
Appl. Sci. 2020, 10, 822 18 of 20
Nomenclature
As Area of tensile longitudinal reinforcement, mm
Ap Area of steel plate, mm
tp Thickness of steel plate
Ec Modulus of elasticity for concrete, GPa
Ep Modulus of elasticity of steel plate, GPa
Modulus of elasticity of tensile longitudinal
Es
reinforcement, GPa
fc’ Concrete compressive strength, MPa
ƒy Steel yielding strength, MPa
Pspall Spall loading, kN
Ppeak Peak loading, kN
∆Ppeak Displacement at peak loading, mm
∆spall Displacement at spall loading, mm
∆cr Displacement at first loading, mm
KPspall Stiffness at spall loading, kN.mm
KPpeak Stiffness of peak loading, kN.mm
K0.3Ppeak Stiffness of 0.3% peak loading, kN.mm
EA Energy absorption, kN.mm
µ1 Index ductility = ∆Peak /∆spall
µ2 Index ductility = ∆0.9 spall /∆spall
SBSP Strong-Bolt Strong-Plate
WBSP Weak-Bolt Strong-Plate
RC Reinforced concrete
References
1. Ahmed, M.; Farghal, O.; Nagah, A.; Haridy, A. Effect of confining method on the ductility of over-reinforced
concrete beams. J. Eng. Sci. 2007, 35, 617–633.
2. Alasadi, S.; Ibrahim, Z.; Shafigh, P.; Javanmardi, A.; Nouri, K. An experimental and numerical study on the
flexural performance of over-reinforced concrete beam strengthening with bolted-compression steel plates:
Part II. Appl. Sci. 2020, 10, 94. [CrossRef]
3. Portland Cement Association. Notes on ACI 318-02: Building Code Requirements for Structural Concrete with
Design Applications; Portland Cement Association: Skokie, IL, USA, 2002.
4. AS3600. Australian Standard for Concrete Structures; Standards Association of Australia: Sydney, Australia, 2001.
5. Hadi, M.N.; Schmidt, L.C. Use of helixes in reinforced concrete beams. Struct. J. 2002, 99, 191–198.
6. Jeffry, R.; Hadi, M.N. The effect of confinement shapes on over-reinforced HSC beams. Proc. World Acad. Sci.
Eng. Technol. 2008, 30, 286–293.
7. Hadi, M.N.; Elbasha, N. Effects of tensile reinforcement ratio and compressive strength on the behaviour of
over-reinforced helically confined HSC beams. Constr. Build. Mater. 2007, 21, 269–276. [CrossRef]
8. Elbasha, N.M.; Hadi, M.N. Effect of helical pitch and tensile reinforcement ratio on the concrete cover spalling
off load and ductility of HSC beams. In Proceedings of the Australian Structural Engineering Conference
2005, Sydney, Australia, 11–14 September 2005; p. 538.
9. Øverli, J.A.; Jensen, T.M. Increasing ductility in heavily reinforced LWAC structures. Eng. Struct. 2014, 62,
11–22.
10. Alasadi, S.S.; AlKafaji, J.M.; Kheder, G.F. Flexural Behavior of Hybrid Reinforced Concrete Beams;
Al-Mustansiriyiah University Republic of Iraq; Ministry of Higher Education & Scientific Research: Baghdad,
Iraq, 2006.
11. Su, R.; Siu, W.; Smith, S.T. Effects of bolt–plate arrangements on steel plate strengthened reinforced concrete
beams. Eng. Struct. 2010, 32, 1769–1778.
12. Siu, W.; Su, R. Effects of plastic hinges on partial interaction behaviour of bolted side-plated beams. J. Constr.
Steel Res. 2010, 66, 622–633.
13. Base, G. Helical reinforcement in the compression zone of concrete beams. Constr. Eng. 1962, 456–460.
Appl. Sci. 2020, 10, 822 19 of 20
14. Base, G. Effectiveness of helical binding in the compression zone of concrete beams. J. Proc. 1965, 62, 763–782.
15. Li, J.; Hadi, M. Behaviour of externally confined high-strength concrete columns under eccentric loading.
Compos. Struct. 2003, 62, 145–153. [CrossRef]
16. Hadi, M.N. Behaviour of high strength axially loaded concrete columns confined with helices. Constr. Build.
Mater. 2005, 19, 135–140. [CrossRef]
17. Hadi, M.N. Helically reinforced HSC beams reinforced with high strength steel. Int. J. Mater. Prod. Technol.
2005, 23, 138–148. [CrossRef]
18. Jeffry, R.; Hadi, M.N.S. Improving the Ductility of Over-Reinforced HSC Beams Using Different Helix
Diameters. In Proceedings of the 20th Australasian Conference on the Mechanics of Structures and Materials,
Toowoomba, Australia, 2–5 December 2008; Aravinthan, T., Karunasena, W., Wang, H., Eds.; CRC Press:
London, UK; pp. 457–462.
19. Delalibera, R.G.; Giongo, J.S. Theoretical and numerical analysis of reinforced concrete beams with
confinement reinforcement. Rev. Ibracon De Estrut. E Mater. 2008, 1, 17–30. [CrossRef]
20. Qin, R.; Zhou, A.; Lau, D. Effect of reinforcement ratio on the flexural performance of hybrid FRP reinforced
concrete beams. Compos. Part B Eng. 2017, 108, 200–209. [CrossRef]
21. Swamy, R.; Jones, R.; Charif, A. The effect of external plate reinforcement on the strengthening of structurally
damaged RC beams. Struct. Eng. 1989, 67, 45–56.
22. Swamy, R.; Gaul, R. Repair and Strengthening of Concrete Members with Adhesive Bonded Plates; American
Concrete Institute: Farmington Hills, MI, USA, 1996.
23. Jones, R.; Swamy, R.; Charif, A. Plate separation and anchorage of reinforced concrete beams strengthened
by epoxy-bonded steel plates. Struct. Eng. 1988, 66, 85–94.
24. Oehlers, D.J.; Moran, J.P. Premature failure of externally plated reinforced concrete beams. J. Struct. Eng.
1990, 116, 978–995. [CrossRef]
25. Oehlers, D.; Ali, M.M.; Luo, W. Upgrading continuous reinforced concrete beams by gluing steel plates to
their tension faces. J. Struct. Eng. 1998, 124, 224–232. [CrossRef]
26. Siu, W.; Su, R. Analysis of side-plated reinforced concrete beams with partial interaction. Comput. Concr.
2011, 8, 71–96. [CrossRef]
27. Tee, H.H.; Al-Sanjery, K.; Chiang, J.C.L. Behaviour of over-reinforced concrete beams with double helix and
double square confinements related to ultimate bending and shear strength. J. Phys. Sci. 2018, 29, 77–98.
28. Nie, J.-G.; Hu, H.-S.; Fan, J.-S.; Tao, M.-X.; Li, S.-Y.; Liu, F.-J. Experimental study on seismic behavior of
high-strength concrete filled double-steel-plate composite walls. J. Constr. Steel Res. 2013, 88, 206–219.
[CrossRef]
29. Rassouli, B.; Shafaei, S.; Ayazi, A.; Farahbod, F. Experimental and numerical study on steel-concrete composite
shear wall using light-weight concrete. J. Constr. Steel Res. 2016, 126, 117–128. [CrossRef]
30. Bsi, B. 8110-1: 1997, Structural Use of Concrete, Code of Practice for Design and Construction, Part 1; British
Standard Institution: London, UK, 1997.
31. Concrete Centre. Structural Use of Concrete; BS8110; British Standard Institution: London, UK, 1986.
32. Bickford, J. Handbook of Bolts and Bolted Joints; CRC Press: New York, NY, USA, 1998.
33. American Concrete Institute. Building Code Requirements for Reinforced Concrete (ACI 318M-89) and
Commentary-ACI 318RM-89; American Concrete Institute: Farmington Hills, MI, USA, 1990.
34. CSA. Design and Construction of Building Structures with Fibre-Reinforced Polymers; CSA: Mississauga, ON,
Canada, 2012.
35. Al Zand, A.W.; Badaruzzaman, W.H.W.; Mutalib, A.A.; Hilo, S.J. The enhanced performance of CFST
beams using different strengthening schemes involving unidirectional CFRP sheets: An experimental study.
Eng. Struct. 2016, 128, 184–198. [CrossRef]
36. Arivalagan, K.; Kandasamy, K. Energy absorption capacity of composite beams. J. Eng. Sci. Technol. Rev.
2009, 2, 145–150. [CrossRef]
37. Pugnaire, F.; Valladares, F. Functional Plant Ecology; CRC Press: Boca Raton, FL, USA, 2007.
38. Wang, H.; Belarbi, A. Ductility characteristics of fiber-reinforced-concrete beams reinforced with FRP rebars.
Constr. Build. Mater. 2011, 25, 2391–2401. [CrossRef]
39. Ho, J.; Lam, J.; Kwan, A. Flexural ductility and deformability of concrete beams incorporating
high-performance materials. Struct. Des. Tall Spec. Build. 2012, 21, 114–132. [CrossRef]
Appl. Sci. 2020, 10, 822 20 of 20
40. Duthinh, D.; Starnes, M. Strength and ductility of concrete beams reinforced with carbon fiber-reinforced
polymer plates and steel. J. Compos. Constr. 2004, 8, 59–69. [CrossRef]
41. Park, R. Ductility evaluation from laboratory and analytical testing. In Proceedings of the 9th world
Conference on Earthquake Engineering, Tokyo-Kyoto, Japan, 2–9 August 1988; pp. 605–616.
42. Aziz, A.H.; Kareem, S.S.; Ban Sahib, A. Experimental study for punching shear behavior in RC flat plate with
hybrid high strength concrete. J. Eng. Dev. 2013, 17, 105–119.
43. European Committee for Standardization. Final Draft of Euro Code 8: Design of Structures for Earthquake
Resistance Part 1: General Rules, Seismic Actions and Rules for Buildings; European Committee for Standardization:
Brussels, Belgium, 1988.
44. Baran, E.; Arsava, T. Flexural strength design criteria for concrete beams reinforced with high-strength steel
strands. Adv. Struct. Eng. 2012, 15, 1781–1792. [CrossRef]
© 2020 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).