Nistir4758 PDF
Nistir4758 PDF
Nistir4758 PDF
NISTIR #758
James Y. Kao
NIST
United States Department of Commerce
Technology Administration
-QC -V-_Lm al Institute of Standards and Technology
100
. U56
4758
1992
C.2
V
NISTIR 1758
James Y. Kao
Building Environment Division
Building & Fire Research Laboratory
March 1992
Prepared for:
U.S. Department of Commerce General Services Administration
Barbara Hackman Franklin, Secretary Richard G. Austin, Administrator
Technology Administration Public Building Service
Robert M. White, Under Secretary for Technology William C. Coleman, Commissioner
National Institute of Standards and Technology Office of Real Property Development
John W. Lyons, Director Washington, DC 20405
Abstract
ABSTRACT
This guide is developed for the Public Building Service (PBS) of the General
Services Administration (GSA) for final inspection and testing of heating,
ventilating, and air-conditioning (HVAC) systems in Federal buildings prior to
Government acceptance. The guide describes in detail the functional
inspection and testing procedures and calculations. It includes eight
chapters: General, Basic Measurement, Refrigeration Plant, Heating Plant, Air
Handling Equipment and systems, Building Automation Systems, Fire Safety Air
Moving Systems, and Unitary Air Conditioning Equipment. The appendix contains
detailed inspection checklist and test work sheets designed to be used in the
field.
iii
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
Acknowledgment
iv
Table of Contents
Table of Contents
CHAPTER 1 GENERAL 1
1. Scope 1
2. Purpose. . 1
3. Organization of This Guide 1
4. The Commissioning Team ..... 2
5. Designated Inspection and Testing Agent 2
6. Codes, Regulations, and Standards . . 3
7. General Principles 3
8 . Procedures and Sequences 4
9. Preparation and Coordination 5
10. Witness of Tests 5
11. Maintenance and Operation Manuals 5
12. Spare Parts . 5
13. Documentation 5
14. System Capacity 6
15. System Energy Consumption 6
16. Safety 6
17. Notation/ Abbreviation 7
v
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
vi
Table of Contents
vii
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
viii
Table of Contents
ix
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
x
CHAPTER 1 GENERAL
CHAPTER 1 GENERAL
1. Scope. This document addresses general criteria and procedures for the
functional inspection and testing of heating, ventilating, and air
conditioning (HVAC) equipment and systems prior to their acceptance.
Functional inspection and testing as used herein refers to those actions
necessary to verify system performance and operating conditions.
Commissioning process is defined by ASHRAE in ANSI/ASHRAE 1-1988 "Guideline
for Commissioning of HVAC Systems" as the overall process which includes
procedures and methods for documenting and verifying the performance of HVAC
systems so that the systems operate in conformity with the design intent. The
process starts at the pre-design phase and goes through the design phase, the
construction phase, the functional performance tests of installed equipment,
sub-systems and complete systems before acceptance, and ends with the post
acceptance phase. The functional inspection and testing as described in this
guide correspond to the functional performance tests phase of the ASHRAE
commissioning process. For brevity, this functional inspection and testing
will be referred to as commissioning in this document.
Page 1
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
3.2 Often used equations for calculations are called Standard Equations
in this guide and are designated as SE- (number)
4.4 The project contract should require the contractor to assist the
commissioning team in inspections when needed (e.g. access to inside boilers).
5.1 Designated testing agents are the persons actually operating the
equipment/systems and performing tests during commissioning. Contractually,
Page 2
. . . . . . .
CHAPTER 1 GENERAL
7.2 Since product data, shop drawings, and wiring diagrams of major
equipment are typically required by construction contract documents to be
submitted for approval before installation, the following should be done.
7.2.2 For the equipment and systems whose submittals are approved
Page 3
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
7.4 Any equipment which has been used extensively before commissioning
inspection and testing must be cleaned or reconditioned to meet the project
specification requirements.
Page 4
. .
CHAPTER 1 GENERAL
9.3 The commissioning team shall plan, prepare and review the test
procedures for the equipment and systems to be tested and coordinate the
tests
10. Witness of Tests. The commissioning team must witness all tests.
12. Spare Parts. During the inspection, verify the quality and quantity
of spare parts as may be required by project specifications.
13. Documentation.
13.1 The testing inspection agent and the commissioning team shall
Page 5
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
record and maintain detailed inspection and testing data. The data recorded
shall be comprehensive, concise, and precise.
13.2 All data must be recorded as soon as possible during the course of
the inspection and testing.
13.3 All documentation shall have the date, time, and names of persons
participating in the inspection and testing.
13.5 The recommended data recording work sheets and inspection check
lists are shown in the appendices cross referenced to the various chapters of
this guide where inspection and testing procedures/criteria are detailed.
13.6 The commissioning team should be aware that inspection and testing
records may be used as evidence in legal disputes.
14.1 The capacities of HVAC systems and components at full load shall
be not less than those indicated in contract documents, project specifications
and drawings
14.2 At full load conditions, the space temperature shall not differ
from design set temperature +/- set point control tolerances.
15. System Energy Consumption. The installed HVAC system must operate
efficiently. The energy consumption rates shall not be greater than the full
and part load energy rates as indicated in the contract documents, project
specifications and drawings.
16. Safety.
16.1 All equipment and systems must be able to operate safely for the
system operating personnel, building occupants, and the public.
Page 6
CHAPTER 1 GENERAL
Page 7
Page 8
: . . .
4.2 The expected accuracies of the most commonly used field test
instruments and some precautions for their use are listed in EXHIBIT 2-A.
4.3 The 1989 ASHRAE Handbook of Fundamentals, Chapter 13 also lists the
commonly used test instruments and their associated ranges and accuracies.
Page 9
.
Standard Equations.
7.2 Standard test procedures are listed in EXHIBIT 2-C as well as other
chapters of this guide where equipment and system test procedures are
described
Page 10
. . . 4
2
3
1. Selection of instruments.
1.1 A general principal of selecting instruments is to match the
minimum instrument accuracies to the allowed measurement tolerances. The
required measurement tolerances are specified in contract documents or given
in testing procedures of this guide.
Temperature.
Page 11
6
5 , ,
Page 12
.
Humidity.
2.2.1
2. 2. 1.2
1.3 Thermometers need calibration.
2.2.1
2. 2. 1.4 Sling psychrometer is simple in construction and
easy to use. It should be considered as an essential instrument in all
commissioning work.
2.3 Pressure.
3.1
U-tube manometer. Accuracy +/- 7 Pa (0.03 in. of water).
2.3.3 Bourdon- tube and bellow type pressure and compound gage.
Accuracy +/- 0.1% full scale.
Page 13
2
3
Page 14
2
velocity, or air flow rate. Units equipped with air straighteners upstream of
pressure sensing tips are available.
2.4.5 Flow hoods are used to measure volume flow of air from
devices such as air diffusers and registers. Accuracy depends on the velocity
reading instrument used. The hood and reading instrument must be calibrated
as a unit.
Page 15
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
2.10 Orsat flue gas analyzer. For measuring and analyzing flue gas.
Measures oxygen, carbon dioxide, and carbon monoxide components in the
combustion product.
Page 16
: .
air properties in terms of standard air. When air flow rate measurement is
performed at conditions considerably different from these conditions, it may
be necessary to adjust to standard conditions in order to compare the measured
results with specified quantities.
If the temperature of air is higher than 29 °C (85 °F) or lower than 13 °C (55
°F) the measured volume flow rate should be adjusted to that of the standard
,
air by using SE-7 and SE-14 (see example 2). Without adjusting between these
temperatures, the maximum error is 3%.
The effect of static pressure inside an air duct or air handling apparatus can
usually be ignored in air calculations (e.g. the error of air density for
ignoring a 995 Pa (4 in. of water) static pressure under 101.039 kPa (29.92
in. of mercury) barometric pressure is less than 1%). Barometric pressure
changes have far more influence on air properties and should be used in all
pertinent calculations. The commissioning team should note under what
conditions the air quantities are specified in the construction documents (at
standard conditions or at high elevation conditions) The air equations given
.
For sample air property calculations at high altitude, see Example 1 below.
Page 17
.
2.1
728A/(Td + 392))
P sw = e (15 A636
"
(For Customary)
2.2 Vapor pressure. Knowing the relative humidity of air (by direct
measurement) and saturated vapor pressure (SE-1), the vapor pressure of air
may be calculated.
Pw *= RH x P sw SE-2
287.055 (273.15 + T d )
v - (1 + 1.6078 x W) (For SI) SE-5
Pb
0.7543 (459.67 + T d )
v = - (1 + 1.6078 x W) (For Customary)
Pb
D *= (1 + W) / v SE-6
Page 18
CHAPTER 2 BASIC MEASUREMENT
2.7
Adjusting density of air. Air density may be adjusted from one set
of temperature and pressure to another set.
Di Pi + Pb i T d2 + 273.15
---- - ( ) ( ) (For SI) SE-7
D2 P 2 + Pb2 Tdi + 273.15
Di Pi + 13.6 P bl T d2 + 459..67
= ( ) ( ---) (For Customary)
d2 P 2 + 13.6 P b2 T dl + 459..67
Pv - P t - SE-8
At 101.325 kPa (29.921 in. Hg) atmospheric pressure and 21.1 °C (70
°F) air temperature, the air density is 1.20 kg/m 3 (0.075 lb/ft 3 ). The
equation reduces to:
1/2
sum [(P v ) ]
Q = A x V SE-12
Qi / Q 2 = V x / V 2 = D 2 / Di SE-13
Page 19
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
M = QxD = Q/ v SE-14
2.12 Duct system air friction. The following equation may be used in
most applications to plot duct system curves or to calculate new air friction
from known air flow rates and air friction.
2
(Qi / Q2 ) “ (Fi / F 2 ) SE-15
P a = Pb + P 6 SE-16
Page 20
t : :
0.6296
W - 0.622 ( )
= 0.01614 kg (lb) of moisture/kg (lb)
24.90 - 0.6296 of dry air
1 + 0.01614
D 0.9678 kg/m 3
1.050
1 + 0.01614
D - - 0.06056 lb/ft 3
16.78
Air flow rate is measured in a duct with pitot tube and a pressure
measuring device to be 4.248 m 3 /s (9000 ft 3 /min) The temperature . of air at
the place of flow measurement is 48.9 °C (120 °F) The barometric . pressure is
at standard atmospheric pressure 101.325 kPa (29.92 in. Hg) The . volume flow
Page 21
)
273.15 + 21.1
Q - 4.248 x 3.881 m 3 /s
273.15 + 48.9
460 + 70
Q *= 9000 x 8224 ft 3 /min
3.1
460 + 120
3. 3.1.1
Fan calculations.
Definition of fan pressure.
Pt = Ps + Pv
where Pt, Ps ,
and Pv can all be measured.
Special cases:
Ps(out) “ 0
Psf = *
Pt(in) 21
Page 22
3
2 )
Ps in)(
= Pv(in) “ Pt(in) - ®
Qi = q 2 X (N, / N 2 ) SE--26
Ptl or ]
?sl = (P t2 or P s2 ) x (N x / n 2 ) 2 SE--27
Wi = W 2 X (N x / N 2 ) 3 SE-•28
Wi " SE-30
3
W2 X (Qi / Q 2 )
Pti or P sl
(3/2)
Wi = W 2 X ( ) SE-31
Pt 2 or P s2
Page 23
:
3.2.2 For the same fan and speed, at varying air density:
Pti or P.i Di
SE-32
P t2 or P s2 D2
Wi / W2 - D x / D 2 SE-33
Symbols
D = air density, kg/m 3 (lb/ft 3 )
(e) s - fan static efficiency, %
(e) t = fan total efficiency, %
N = fan speed, RPM
P s - static pressure, Pa (in. of water)
P t = total pressure, Pa (in. of water)
Q = volume flow rate, m /s (ft /min)
3 3
D hw
(1/2)
M = 0.01252 (C Y d 2 Fa) [-- ]
(For SI)SE-36
A
(1 - B )
D hw
(1/2)
M = 358.93 (C Y d 2 Fa) [
]
(For Customary)
(1 " B*)
hw
2 (1/2)
Q = 0.01252 (C Y d Fa) [
]
(For SI)SE-37
D (1 - B*)
Page 24
. : )
hw
2 (1/2)
Q = 358.93 (C Y d Fa) [
]
(For Customary)
D (1 - BA )
(1/2)
M = 0.01252 (K Y d 2 Fa) ( D hw ) (For SI) SE-38
(1/2)
M = 358.93 (K Y d 2 Fa) ( D hw ) (For Customary)
hw
2 (1/2)
Q = 0.01252 (K Y d Fa) ( ) (For SI) SE-39
D
hw
(1/2)
Q = 358.93 (K Y d 2 Fa) ( ) (For Customary)
D
Symbols
Q = 60 (f / K) (For Customary)
Page 25
::
Symbols
Vf x Gf (G f - G)
1/2
M = K a D w (---- ) SE-42
Af
(1/2)
Mref = Mwater ( G ) SE-43
Symbols
a = annular area of flow, m 2 (ft 2 )
Dw = density of water, kg/m 3 (lb/ 3 )
G = specific gravity of fluid
Gf = specific gravity of float
GF = gravitational force of float, grams
K = flow constant
M = mass flow rate, kg/s (lb/h)
M ref = flow rate of refrigerant, kg/m 3 (lb/ft 3 )
Mwater = meter reading calibrated for water, kg/m
3
(lb/ft 3 )
V f = volume of float
5. Electric power. (Horsepower equations are for customary unit use only)
Watt input
HP - SE-44
746
Page 26
CHAPTER 2 BASIC MEASUREMENT
I x E x Eff x Pf
HP - SE-45
746
1.73 x I x Ex Eff x Pf
HP SE-46
746
where
E is the line potential, volts
Eff is the motor efficiency, %
Pf is the motor power factor, %
HP is motor horsepower, hp
I is the measured current, A
Page 27
,
2. Reference standards.
a. ASHRAE Standard 41.1 (Standard Measurements Guide: Section on
Temperature Measurements) describes instruments, measurement techniques, and
recommended practices for temperature measurement generally encountered in
HVAC equipment testing. The temperature range is limited between 4.4 to 204.4
°C (40 to 400 °F) The instruments covered are mercury- in- glass thermometers,
.
Page 28
.
h.ASME PTC 19.5 (Flow Measurement Instruments and Apparatus) deals with
flow measurement and is similar in purpose to the standard in f. above.
4. Simulation of sensors.
4.1 Reasons for simulating sensors. At the time of commissioning, a
sensor responds to only one condition of the controlled variable where the
sensor is situated. Therefore only one response of the control loop may be
observed. It is desirable to vary the controlled variable so that more than
one or a continuous set of responses may be tested. In most cases, it is not
practical to subject the sensor to the full range of possible changes.
However, a simulated change may be easily and accurately accomplished.
Page 29
. 2 . ,
Humidity, STP-2.
Page 30
; 4
1
2
3
* water manometer;
* count generator.
5.2 For round ducts divide the duct cross sectional area into at least
5 annular rings of equal area. Take 4 velocity pressure readings with pitot
tube in each ring along two diameters of the duct at right angles. Measured
from the center of the duct, pitot measurement positions are 0.316r, 0.548r,
0.707r, 0.837r, and 0.949r, where r is the radius of the duct.
Page 31
. . . . .
5.3For rectangular ducts divide the duct cross sectional area into at
least 16 sub -rectangles of equal area. Take one velocity pressure reading
with pitot tube at the center of each sub - rectangle
5.8 Test work sheets for air flow rate measurement in round and
rectangular duct, WS 2C-1 and WS 2C-2, are included in the appendix.
6.2 Divide the coil or filter face into at least 16 sub-areas with the
maximum sub -area not more than one square foot.
6.6 Same test work sheets for rectangular ducts may be used for
measuring at coils or at air filters.
Page 32
. . .
2. Reference Standards.
a. ASHRAE Standard 15 - Safety Code for Mechanical Refrigeration.
k. CTI Bulletin ATC-105 - Acceptance Test Code for Water Cooling Towers.
Page 33
.
4.5 Centrifugal Refrigeration Machine Testing. See EXHIBIT 3-C for test
procedures
4.6 Reciprocating Refrigeration Machine Testing. See EXHIBIT 3-D for test
procedures
4.7 Absorption Refrigeration Machine Testing. See EXHIBIT 3-E for test
procedures
4.8 Heat Rejection Equipment Testing. See EXHIBIT 3-F for test
procedures
Page 34
. . .
1. General.
1.1 Review equipment manufacturer's instructions on start-up and operation
procedures
1.4 Check for headrooms and access spaces around the machine. The spaces
required in the design documents must be provided. Pay special attention to the
refrigeration machine heat exchanger tube replacement and cleaning spaces.
1.5 Verify installed pipe fittings and accessary equipment against project
drawings for completeness and proper installation. Fittings and accessories
include but not limit to valves, strainers, vibration elimination units,
thermometer wells, piping supports, etc.
1.9 Check water flow direction marks for check valves and flow switches.
1.10 All moving parts (motors, belts, etc.) should have protection shields
for personnel safety.
1.11 Check alignment for all non-hermetic motor driven equipment (solution
and refrigerant pumps of absorption machines are usually hermetic type),
including motor, compressor, gear boxes, oil pump, purge pump, and water pumps.
Using some simple tools such as straight edges, square edges, plumb lines, and
strings yield good results. Also observe shaft and coupling for misalignment
Page 35
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
1.12 Observe belt tightness of belt driven equipment. Use belt tension
gage if needed. Belt tension should be as recommended by belt manufacturer.
1.16 For motor starter equipped with overcurrent heaters, check heater
sizes against starter manufacturer's recommendations. The recommendations are
usually contained in operator's manual or posted in starter cabinet.
1.17 If pneumatic pressure is used for system controls, check control air
system pressure.
1.18 Be sure the machine is charged with right kind of refrigerant. Check
sight glass for proper level.
1.20 Make certain that the lubrication material used satisfy the
manufacturer's recommendations. Lubrication are required for compressor
bearings, motor bearings, gear trains, and other equipment. Oil level must be
as recommended.
1.22 Check surface paint for damages and omissions. Equipment nameplates
must not be painted over. Required equipment labels must be present and legible.
1.23 No leakage should be noted for water, oil, refrigerant, steam, and
other fluid (such as lithium bromide).
1.25 Note any unusual noise and vibration at varying load conditions.
Page 36
. .
2.2 Be sure that temperature and pressure indicators for oil system are
functioning properly to indicate the oil system operation.
2.3 Regardless of the oil pump arrangement, the oil pressure supplied to
the compressor bearings and gear box must meet the minimum pressure requirement
specified by the manufacturer whenever the compressor is running (including
coastdown) .If a separate oil pump is used for start-up only, observe the
switch-over operation of the start-up pump and the main oil pump to insure proper
oil pressure at all times.
2.4 Check compressor interlocking function with oil pressure to insure the
operation of paragraph 2.2 above.
2.5 Be sure oil pump is wired separately from circuit feeding to the
compressor
2.6 Be sure oil filter is properly installed in oil pumping system and it
is clean.
2.7 Check oil heating system for proper operation. Oil sump temperature
must not be lower than the manufacturer's recommended temperature for proper
separation of refrigerant. Be sure the oil temperature control system is
operating properly.
2.8 Check oil cooling system for proper oil temperature control and
operation. Oil temperature shall not be over the manufacturer's recommended
temperature
2.12 Note unusual noise and vibration of compressor, bearings, gear box,
and motor.
Page 37
.
3.2 Check pump lubricant (usually water or salt solution) system strainer
and magnetic strainer for cleanliness.
3.3 Check strainers and traps for steam and hot water supply lines for
cleanliness, and condensate piping for proper type of steam traps and vacuum
breakers. Check for proper placement and orientation of same.
3.5 At the time of commissioning inspection, the chiller should have been
adjusted and charged properly by manufacturer's representative. The Team shall
obtain charge data sheet (lithium bromide and additives). If solution samples
have not been drawn for concentration tests, samples should be gathered when the
chiller is in operation (see EXHIBIT 3-E).
3.6 Check relief pipe installation for chiller pressure relief device in
accordance to project drawings. If drawings do not indicate, relief pipe from
steam chiller must terminate at outside of building and relief pipe from hot
water chiller must terminate at a floor drain. Pipe size must not be smaller
than relief device opening area.
4.2 Check compressor interlocking function with oil pressure to insure the
operation of paragraph 4.1 above.
4.3 Be sure oil pump is wired separately from circuit feeding to the
compressor
4.5 Check oil heating system for proper operation. Electric wiring should
Page 38
.
4.6 Check oil level before and during operation. Oil should not be
foaming excessively.
4.7 For chillers with remote condensers, check refrigerant pipe pitch and
oil traps for proper oil return.
4.8For air cooled and evaporatively cooled chillers, spaces for air
circulation is important. Be sure that manufacturer's recommendations are
followed and air is not short circulated from discharge to intake.
4.10 For air cooled condensers equipped with damper controls for low
ambient operation, check damper mechanism for proper adjustment and operation.
4.12 Check water level of evaporative condenser. Water float valve shall
not "chatter". Spray nozzles should have correct pattern without blockage.
There shall be no excessive water carry- through
4.14 Check electric interlocks with condenser water pump and chilled water
pump. Check operation of flow switches.
cycle control, manual override, indicating lights for power and diverting valve
positions, diverting valve speed control and indicator, cleaning cycle counter,
flow switch bypass, alarms, and control panel.
5.3 Check the function of manual override for actuating the cleaning
action.
Page 39
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
5.4 Check diverting valve actuation speed to meet the limitations of the
manufacturer's recommendations. Be sure the speed adjustment setting is secured.
5.5 Observe water flow and brush cleaning action for both forward and
reverse travels. Indicating lights and diverting valve action should agree.
5.6 The time between forward and reverse cleaning actions should be as
recommended by manufacturer.
5.13 See EXHIBIT 3-C for leaking test of flow diverting valve.
Page 40
.
1. General.
1.1 Review equipment manufacturer's instructions on start-up, operation
and maintenance procedures.
1.2 Give general inspection of heat rejection equipment and its associated
equipment, including base, vibration eliminating units, starting electrical
equipment, piping, valves, etc. Be sure that no damage occurred during
construction.
1.3 Check equipment name plates to verify equipment model. Cooling tower,
heat exchanger, and their auxiliary equipment must have the same model numbers
as approved submittals.
1.8 Check fluid flow direction marks for check valves and flow control
valves
1.9 All moving parts (motors, belts, etc.) should have protection shields
for personnel safety.
1.10 Check alignment for all motor driven equipment, including motor, gear
boxes, fans and water pumps. Using some simple tools such as straight edges,
square edges, plumb lines, and strings yield good results. Also observe shaft
and coupling for misalignment while machine is running.
1.11 Observe belt tightness. Use belt tension gage if needed. Belt
tension should be as recommended by belt manufacturer.
Page 41
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
1.16 For motor starter equipped with overcurrent heaters, check heater
sizes with starter manufacturer's recommendations. The recommendations are
usually contained in operator's manual or posted in starter cabinet.
1.17 If pneumatic pressure is used for system controls, check control air
system pressure.
1.18 Make certain that the lubrication material used satisfy the
manufacturer's recommendations. Lubrication are required for fan bearings, motor
bearings, gear trains, and other equipment. Oil level must be as recommended.
External extended grease lines must be provided if specified.
1.19 Check thermal insulation for damages and omissions (for cooling tower
winterizing auxiliaries, if required in specifications).
1.20 Check surface paint for damages and omissions. Equipment nameplates
must not be painted over. Required equipment labels must be present and legible.
2.2 Verify overflow and drain pipes (Drains are usually specified to be
piped to sewer) Check for outlet basin screen, if specified.
.
Page 42
. .
2.3 Water should not spill over hot water basins and cold water collection
basin during any time of the operation. There should not be excessive splash
over air inlet or excessive carryover from air discharge.
2.4 Observe makeup valve and float mechanism for proper operation. Water
level of the cold water collection basin should as recommended by the
manufacturer. For equipment specified with constant bleeding, observe the amount
of makeup to be approximately correct.
2.6 For equipment with spray nozzles, turn fan off (condenser water pump
is on) and observe nozzle spray pattern and blockage.
2.7 For cooling towers having more than one cell, observe water
distribution pattern for obvious imbalance of balancing valves or distribution
valves. Water level in hot water basins should be as recommended by the
manufacturer
2.8 For field assembled towers, check material (fill, frame, casing,
baffle, water distributing plate, etc.) and installation against specifications
and approved submittals.
2.10 For tile filled towers, check tile supports against manufacturer's
shop drawings.
2.11 Check that water treatment system is operational and adjusted. Check
interlock of chemical pump with condenser water pump (or other interlock as
specified)
Page 43
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
2 . Purpose
2.1 To verify full capacity of the installed refrigeration machine for
meeting the specified capacity without exceeding the specified power input.
2.2 To verify part load power consumption of the machine not exceeding the
specified part load power limits at the specified part loads.
3. Industry standards.
3.1 ARI Standard 550 (Standard for Centrifugal or Rotary WAter chilling
Packages) prescribes requirements for testing of centrifugal refrigeration
machines. It specifies the basis for testing, rating, and publishing of
capacities and power requirements. Power input is measured for the compressor
only. These machines are tested and rated under the following conditions:
Page 44
.
3.2 Among other requirements, ARI Standard 550 lists the following
required safety and operating controls:
ARI Standard 550 also requires that the water side of the evaporator
3.3
and condenser be suitable for a working pressure of 1034 kPa (150 psig) Verify .
supplied with the machine may be used to take test data after they have been
calibrated and the accuracies satisfy the minimum tolerance requirements of
tests
Page 45
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
4.3 In most cases, a false load is needed for full load performance test.
Depending on individual project circumstances, false load may be introduced at
the equipment room close to the refrigeration machine to be tested or to the
building equipment installed as parts of the building facility (such as air
handling systems). The former approach may require temporary equipment (such as
temporary boiler or heat exchanger) to provide heat source, piping from the heat
source to the refrigeration machine and/or cross-over piping between the
condenser and the evaporator, and accessories such as shut-off Valves and
temperature controlling mixing valves. The Team should review the piping layout
to be sure that water entering both evaporator and condenser may be adjusted
individually to those of the specified values. The disadvantage of the latter
approach is the long lagging time for the temperature at the refrigeration
machine to stabilize (from the time to introducing false load at the air handling
systems to achieve stable and desired conditions at the test machine) . After it
is determined the approach to take based on cost comparisons, good coordination
between all involved parties is essential.
4.4 The heat exchanger tubes may not be clean to yield the specified
fouling factors. Oil film needs to be cleaned when tubes are new. If the
refrigeration machine has been running for some time to provide temporary
cooling, the tubes should be cleaned before tests. This is especially important
for condenser tubes, because of the low quality of the condenser water and higher
temperature of the tube surface. It is difficult to measure the actual fouling
factor or scale thickness in the field. Only actual cleaning will assure the
correct performance of the machine. The Team should obtain a written statement
from the contractor or witness the cleaning operation that the tubes are cleaned
according to the manufacturer's recommendations (such as using chemicals). If
the machine has been in operation, physical cleaning with rodded brushes may be
necessary unless the refrigeration machine has automatic brush cleaning equipment
and the frequency of cleaning has been set correctly since the refrigeration
machine was in operation.
5. Recommended tests.
5.1 Full load test. The refrigeration machine must deliver the specified
cooling capacity under the specified conditions. The specified conditions may
be different from the basis of the manufacturer's published and selected
conditions. The project specification usually also specifies the entering
condenser water temperature, the leaving chilled water temperature, the condenser
water and the chilled water flow rates, the maximum power consumption rate at
these conditions, and the maximum water friction loss of the two heat exchangers.
Each of these ratings or limitations must be verified by testing directly or
verified by deducing from test data (see paragraph 7.3 for test procedures).
5.2 Part load test. Depending on the refrigeration machine's part load
performance curve, the energy performance of a machine may vary considerably.
In order to have optimum energy performance for the entire cooling season,
several points of the performance curve may be specified to define a skeleton
Page 46
. .
performance curve. The commonly specified points are at 75%, 50%, 25% of the
full load, and/or the lowest desirable stable load. The test conditions for the
part load may be different from those of the full capacity test conditions,
depending on the specifications (see paragraph 7.4 for test procedures).
5.3 Capacity control test. With reduced load the machine should respond
by reducing its capacity and vice versa. The test should verify the automatic
capacity change following load changes without running into unstable conditions
for the entire range of capacity from full load to minimum load as specified.
Project specifications usually do not allow hot gas bypass above 10% of full
load. Therefore, the test should also show the hot gas bypass operation to be
compared with the specifications and the equipment manufacturer's claims (see
paragraph 7.5 for test procedures).
Temperature.
Page 47
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
6.2.1 Chilled water pipe. The total error of combined sensing and
readout devices shall not exceed +/- 3% of measured quantity.
6.2.2 Condenser water pipe. The total error of combined sensing and
readout devices shall not exceed +/- 3% of measured quantity.
Page 48
CHAPTER 3 REFRIGERATION PLANT
(orifice plate or venturi, etc.) is used, the primary element with the largest
throat diameter that still satisfies the required accuracy should be selected to
minimize the friction loss associated with the measuring element.
7.1 Safety control test. This test should be performed before other tests
after an inspection. Some situations requiring pressure and temperature to
trigger control actions are not appropriate to test on line. Therefore these
tests are limited to checking safety control circuits with simulated controlled
Page 49
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
variables. In some cases (refrigerant pressure, oil pressure, etc.), they are
tested indirectly without creating simulated controlled variables (pressure)
Indicating lights, relays, actuators, and controlled components of the machine
are used to confirm the control action.
(A, B, or C) - (A + B + C) / 3
% voltage imbalance -
(A + B + C) / 3
7.1.5 Test all pilot lights and alarms by pressing the appropriate
buttons
temperature switches to be tested shall include, but not limited to, the
following:
Page 50
. . . —
7.1.10 Test flow actuated safety controls. Bypass the flow switches
of evaporator and condenser water at the switches by using jumper wires and
observe pilot lights. This does not indicate the functioning of the flow sensing
mechanism which will be verified later in full load test.
7.1.12 Data to be recorded (Not all items are required for the same
machine. See project specification and submittals for items required and
installed) :
i
1
—
rH CM »
) Mechanical equipment room temperature.
Page 51
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
7.2.2 Check condenser water flow rate. This should be done after
cooling tower is readied for operation. The installed condenser water pump
(permanent or temporary) may not give the correct flow rate. If the flow rate
differs from that of the specified rate, adjust flow balancing device on
condenser water line to the required rate.
7.2.4 Start chilled water pump. Check pump amperage for possible
overload.
7.2.5 Check chilled water flow rate. Adjust flow balancing device
if necessary.
7.2.6 Although the following items may have been checked during
inspection at the beginning of the functional performance testing, they shall be
checked again for running tests as routine startup procedure.
Page 52
. 4
5
3 .
during inspection)
Page 53
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
Full load test. This test follows auxiliary equipment tests with
chilled water and condenser water pumps in operation.
7.3.4 The running of compressor proves that the evaporator water and
condenser water flow switches are functioning (see previous description on safety
tests)
Page 54
.
7.3.10 After water flow rates and temperature of both condenser and
evaporator have achieved the specified values, the refrigeration machine shall
run for a minimum of one (1) hour. Data shall be recorded at 10 minute
intervals. Minor adjustment of water flow rates and temperature may be needed
during this period. The test setup is considered stabilized and test data for
full load performance may be taken, if 3 sets of data (30 minutes total time),
after any adjustment, are within the tolerances as listed below:
7.3.12.7
7.3.12.9 Chilled water flow primary element differential
pressure or other flow instrument output.
Wattmeter output.
7.4 Part load tests. Part load tests should follow immediately after the
full load test. Unless the part load conditions are specified in the project
specification (in cooling capacity or percentage of full load), part load tests
Page 55
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
shall be performed at 75%, 50%, and 25% of the full load cooling capacity. The
chilled water leaving, condenser water leaving and condenser water entering
temperature shall be the same as for full load test, except for 25% capacity test
where the entering condenser water temperature shall be 19.1 °C (66.3 °F) The
.
7.4.4 Repeat the same procedures for all other part load tests. If
unstable conditions of compressor occur (surge), abort the test. Follow
manufacturer's recommended procedures to stop the compressor operation. See
capacity control test later for detecting compressor surge.
7.4.5 Cut off all false load and restore all valves to their normal
operation modes
7.4.6 When the compressor is coasting down, observe and record the
oil pressure gage. The oil pressure shall not be lower than the recommended
pressure as long as the compressor shaft is turning.
7.5 Capacity control test. This test is performed concurrently with the
full load and part load tests. The purpose of this test is to verify the correct
sequencing of the operation when the load changes.
7.5.1 After the full load test, set the chilled water leaving
thermostat up slowly till the start of compressor coastdown. Then set the
thermostat lower to make the circuit again by observing indicating light. A
timer prevents rapid cycling of the compressor. Count the time from the start
of compressor coastdown to the restart of the compressor. This time must be not
less than the manufacturer's recommended time. Observe the prerotation vane's
position during the period the compressor is off and restart. The vanes should
be fully closed when the compressor is off. They should stay closed before the
compressor reaches full speed, then open to their preset fully opened position.
7.5.2 While the building load is reduced for various stages of part
load tests, observe the running of the compressor. There shall be no excessive
noise and vibration. Special attention should be paid to very low load tests to
Page 56
] :
detect surge. Among other operating parameters, surge depends on the amount of
flowing refrigerant, prerotation vane position, and water temperature. Therefore
observations should be made for all part load conditions specified, since
condenser water temperature specified for part loads may be different. A current
meter shall be used to monitor the current draw of the compressor during load
changes. Marked fluctuation of current draw indicates compressor surge.
7.6 Cooling plant system tests. These tests are basically for
interlocking of cooling plant equipment rather than refrigeration machine itself.
Therefore, these tests much depend on the design of the plant. Project drawings
and specifications must be thoroughly studied.
Qm = W (For SI)
Page 57
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
8.2 Part load test. Use the same equations as for full load test. All
sets of specified conditions or percent of part load conditions of 7.4 shall be
calculated
8.3.1 The full load capacity of the machine must be not less than
the specified full load capacity.
8.3.2 The full load power rate shall not be more than the specified
full load power rate.
8.3.3 The part load power rates must not be more than the specified
rates
Page 58
. .
2. Purpose.
2.1 To verify full capacity of the installed refrigeration machine for
meeting the specified capacity without exceeding the specified power input.
2.2 To verify part load power consumption of the machine not exceeding the
specified part load power limits at the specified part loads.
3. Industry standards.
3.1 ARI Standard 590 (Standard for Reciprocating Water- chilling Packages)
prescribes requirements for testing of packaged reciprocating water chillers.
It specifies the basis for testing, rating, and publishing of capacities and
power requirements. These machines are tested and rated at full load under the
following conditions:
Page 59
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
Part load test. A minimum of two part load tests are required. Depending on the
unloading steps of the compressor, the part loads and test condition requirements
vary (see paragraph 5.2). The conditions of entering condenser water, air, or
refrigerant are given as:
A C
Water flow rate for water cooled units is the same as full load test (i.e.
0.538 L/s per kW (3 gpm/full load ton)). The liquid refrigerant temperature of
remote condensers is 5.6 °C (10 °F) below saturated discharge temperature
calculated above.
Page 60
.
3.2 Among other requirements, ARI Standard 590 requires the following
safety controls:
4.3 In most cases a false load is needed for full load performance test.
Depending on individual project circumstances, false load may be introduced at
the equipment room close to the refrigeration machine to be tested or to the
building equipment installed as parts of the building facility (such as air
handling systems). The former approach may require temporary equipment to
provide heat source, piping from the heat source to the refrigeration machine or
cross-over between the condenser and the evaporator (for water cooled condenser
units only) and accessories such as shut-off valves and temperature controlling
,
mixing valves. If cross-over of chilled water and condenser water is used, the
Page 61
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
Team should review the piping layout to be sure that water entering both
evaporator and condenser may be adjusted individually to those of the specified
values. The disadvantage of the latter approach is the long lagging time for the
temperature at the refrigeration machine to stabilize (from the time to
introducing false load at the air handling systems to achieve stable and desired
conditions at the test machine). After it is determined the approach to take
based on cost comparisons, good coordination between all involved parties is
essential.
4.4 The heat exchanger tubes may need to be cleaned to yield the specified
fouling factors. Oil film needs to be cleaned when tubes are new. If the
refrigeration machine has been running for some time to provide temporary
cooling, excessive scale inside the water tubes may have accumulated. This is
especially important for condenser tubes, because of the low quality of the
condenser water and higher temperature of the tube surface. It is difficult to
measure the actual fouling factor or scale thickness in the field. Only actual
cleaning will assure the correct performance of the machine. The Team should
obtain written statement from the contractor or witness the cleaning operation
that the tubes are cleaned according to the manufacturer's recommendations (such
as using chemicals). If the machine has been in operation, the contractor or
manufacturer's representative must make the decision of cleaning tubes, since
chillers with scaled tubes may not pass the power consumption criteria of the
contract specification and the commissioning tests.
5. Recommended tests.
5.1 Full load test. The refrigeration machine must deliver the specified
cooling capacity under the specified conditions. The specified conditions may
be different from the basis of the manufacturer's published and selected
conditions. Project specification usually specifies the entering and the leaving
chilled water temperature, and/or the water flow rates, the maximum water
friction of the heat exchanger (s) the operating conditions of the condenser, and
,
the maximum power consumption rate at these specified conditions. The maximum
water velocity in the heat exchanger tubes may also be specified. Each of these
ratings or limitations must be verified by testing directly or verified by
deducing from test data. Since the capacities of air cooled condensers and
evaporative condensers depend on the conditions of the ambient air, the full load
test may not verify the capacities of the condensers. If the conditions of the
ambient air is not as specified during this test, the full capacity test is for
the packaged units excluding the condensers. The capacities of these condenses
(air cooled or evaporatively cooled) must be tested separately as described in
EXHIBIT 3-F, HEAT REJECTION EQUIPMENT TEST PROCEDURES.
5.2 Part load test. Depending on the refrigeration machine’s part load
performance curve, the energy performance of a machine may vary considerably. In
order to have optimum energy performance for the entire cooling season, more than
one part load conditions may be specified. The chiller performance at these
specified part load shall be tested.
Page 62
.
5.3 Capacity control test. With reduced load the machine should respond
to reduce its capacity and vice versa. The test should verify the automatic
capacity change following load changes without running into unstable conditions
for the entire range of capacity from full load to minimum load as specified.
Capacity control involves step control of cylinder unloading and/or compressor
sequencing.
5.5
6.1 Cooling plant system test. This test involves interlocking of
condenser pump, chilled water pump, cooling tower operation, and other cooling
plant components, such as sequencing of chillers.
Temperature.
6.1.5 For air cooled units, measure the dry bulb temperature of air
entering condensing coil. The measurement error shall not exceed +/- 0.3 °C
(0.5 °F) .
Page 63
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
6.1.7 For units with remote condensing units, measure the saturated
discharge temperature of the refrigerant at the refrigeration machine (not at the
condenser end). The measurement error shall not exceed +/- 0.3 °C (0.5 °F)
6.1.8 For units with remote condensing units, measure the liquid
refrigerant temperature of the refrigerant at the refrigeration machine (not at
the condenser end). The measurement error shall not exceed +/- 0.3 °C (0.5 °F) .
6.2.1 Chilled water pipe. The total error of combined sensing and
readout devices shall not exceed +/- 3% of measured quantity.
6.2.2 Condenser water pipe. The total error of combined sensing and
readout devices shall not exceed +/- 3% of measured quantity.
Page 64
CHAPTER 3 REFRIGERATION PLANT
6.3.3 For large chillers where maximum pressure drops of water heat
exchangers are specified, pressure gages are usually required and installed at
inlet and outlet of evaporators and condensers. These instruments may be used
to verify the heat exchanger water pressure drops.
6.4.3 Check and record electric voltage between feeders and the
frequency at the power supply.
Page 65
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
7.1
(A, B, or C) - (A + B + C) / 3
% voltage imbalance =
(A + B + C) / 3
7.1.3 Make sure the crankcase heater has been on and is working by
feeling the warmth of the compressor. The heater should be on for at least 24
hours with all valves in the refrigerant lines in open positions.
7.1.5 With control circuit power connected, test all pilot lights
and alarms by pressing the appropriate buttons (if provided).
Page 66
.
7.1.15 (For air cooled and evaporately cooled machines) Make sure
rotation direction of fan is correct.
Page 67
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
7.1.19 Check oil level again after machine has been running for at
least 1/2 hour. Oil should have no foam and at correct level. If oil pressure
gage is specified or installed, record pressure.
7.1.21 Load the machine gradually. With constant water flow rate
through the evaporator, the temperature differential of the chilled water
entering and leaving the evaporator and the numbers of active cylinders and
compressors indicates the loading condition of the machine. In most cases false
load will be required.
Page 68
. .
7.1.24
(For air cooled and condenserless machines) Test head
pressure control. Head pressure control must maintain minimum head pressure
during low ambient operation. When machine unloads, head pressure tends to drop
presenting opportunity to observe head pressure control. Depending on
manufacturer's preference (air cooled type) and system design (condenserless
type),
there are various ways to control head pressure during low ambient
applications. The Team should be familiar with the submittals for the chiller
installed. The following examples are for machines with simple ambient
temperature and head pressure controls.
Full load test. This test shall be performed immediately after safety
control and general operational control tests. Test procedures depend on
condenser arrangement. Note that before recording full load data, verify that
hot gas by-pass is off. The manual valve on the hot gas bypass may be turned off
during full load test.
7. 2. 1.1 Add false load until the chiller is fully loaded (all
steps of all compressors are loaded)
Page 69
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
Page 70
. . 4
6 .
7. 2. 2.1 Add false load until the chiller is fully loaded (all
steps of all compressors are loaded)
Page 71
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
7. 2. 3.1 Add false load until the chiller is fully loaded (all
steps of all compressors are loaded)
Page 72
. . 5 . .
7. 2. 3. 7 Data to be recorded:
7.3 Part load tests. Part load tests shall be performed immediately after
the full load test. Unless the part load conditions are specified in the project
specification (in cooling tonnage or percentage of full load), part load tests
shall be performed at two load steps - a step closest to 60% of full load and the
lowest step. If the chiller has only one step of unloading or no capability of
unloading, it shall be tested at 60% and 40% of full capacity. The chilled water
leaving temperature shall be as for full load. The condenser entering conditions
are the same as those of ARI Standard 590 (see paragraph 3.1). They are listed
below for 60%, 50%, and 40% of full load.
Page 73
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
Part load
60% 50% 40%
(water cooled) 81 80 79
Saturated disch. temp. °C (°F)
(air cooled, evap. cooled) 104 100 96
7.3.3 Repeat the same procedures for the lower part load tests.
7.3.4 After tests, cut off all false load and restore all valves to
their normal operation modes.
Q in = W (For SI)
Page 74
.
8.2 Part load test. Use the same equations as for full load test. Both
part load conditions of paragraph 7.3 shall be calculated.
8.3.1 The full load capacity of the machine must be not less than
the specified full load capacity.
8.3.2 The full load power rate shall not be more than the specified
full load power rate.
8.3.4 The part load power rate must not be more than the specified
rates
Page 75
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
2. Purpose.
2.1 To verify full capacity of the machine for meeting the project
specified capacity without exceeding the specified energy input.
2.2 To verify part load energy input of the machine not exceeding the
specified part load energy limits at the specified part loads.
3. Industry standards.
3 1 . ARI Standard 560 (Standard for Absorption Water- chilling Packages)
prescribes requirements for testing of absorption water chillers. It specifies
the basis for testing, rating, and publishing of capacities and energy
requirements. These machines are tested and rated at full load under the
following conditions:
For part load performance, the chilled water temperature, chilled water flow
rate, and condenser water flow rate remain the same as for full load. The
entering condenser water temperature varies linearly with load, decreasing from
29.4 °C (85 °F) for full load to 15.6 °C (60 °F) for no load.
The standard requires that the published capacity be not less than 95% of test
capacity and that the published energy consumption rate and condenser water flow
Page 76
CHAPTER 3 REFRIGERATION PLANT
3.2
The required safety controls include low temperature cutout and provisions for
interlocking to stop operation of the chiller if chilled water flow fails.
4.3 In most cases a false load is needed for full load performance test.
Depending on individual project circumstances, false load may be introduced at
the equipment room close to the refrigeration machine to be tested or to the
building equipment installed as parts of the building facility (such as air
handling systems) The former approach may require temporary equipment to
.
provide heat source, piping from the heat source to the refrigeration machine or
cross-over between the condenser and the evaporator, and accessories such as
shut-off valves and temperature controlling mixing valves. If cross-over of
chilled water and condenser water is used, the Team should review the piping
layout to be sure that water entering both evaporator and condenser may be
adjusted individually to those of the specified values. The disadvantage of the
latter approach is the long lagging time for the temperature at the refrigeration
machine to stabilize (from the time to introducing false load at the air handling
systems to achieve stable and desired conditions at the test machine) After it
.
4.4 The heat exchanger tubes may need to be cleaned to yield the specified
fouling factors. Oil film needs to be cleaned when tubes are new. If the
refrigeration machine has been running for some time to provide temporary
cooling, excessive scale inside the water tubes may have accumulated. This is
especially important for condenser and absorber tubes, because of the low quality
of the condenser water and high temperature of the tube surface. It is difficult
to measure the actual fouling factor or scale thickness in the field. Only
Page 77
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
actual cleaning will assure the correct performance of the machine. The Team
should obtain written statement from the contractor or witness the cleaning
operation that the tubes are cleaned according to the manufacturer's
recommendations (such as using chemicals). If the machine has been in operation,
the contractor or manufacturer's representative must make the decision of
cleaning tubes, since chillers with scaled tubes may not pass the thermal
performance
5.1 criteria of the contract specification and the commissioning tests.
5. Recommended tests.
Full load test. The refrigeration machine must deliver the specified
cooling capacity under the specified conditions. The specified conditions may
be different from the basis of the manufacturer's published and selected
conditions. Project specification usually specifies the entering and the leaving
chilled water and condenser temperatures, and/or the water flow rates, the
maximum water friction of the heat exchanger(s) ,
and the maximum energy
consumption rate at these specified conditions. The maximum water velocity in
the heat exchanger tubes may also be specified. Each of these ratings or
limitations must be proven by testing directly or proven by deducing from test
data
5.2 Part load test. Some project specifications may also specify part
load performance (capacities vs. energy consumption rates) for optimum energy
performance. The operating conditions of the condenser water temperature are
usually different from that of the full load. The chiller performance at part
load shall be tested at the specified part load conditions.
5.3 Capacity control test. With reduced load the machine should respond
by reducing its capacity and vice versa. The test should verify the automatic
capacity change following load changes without running into undesirable
conditions for the entire range of capacity from full load to minimum load as
specified
Page 78
.
6. Instrumentation.
6.1 The required measurement, minimum accuracies, and
measurement precautions are given below:
Temperature.
measurement error for chilled water entering evaporator shall not exceed 0.1 °C
(0.2 °F)
condenser water leaving condenser is measured, the measurement error shall not
exceed +/- 0-1 °C (0.2 °F) .
6.1.5 Hot water measurement (for hot water operated chiller). Same
as for chilled water measurement.
measurement is for checking the state of steam. The temperature sensing location
should be close to the steam control valves. The condensate temperature sensing
location should be in the condensate drop leg before steam traps.
part load tests unless they are verified to meet the minimum accuracy
requirements as stated previously.
Page 79
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
6.2.1 The flow rates of chilled water, condenser water, hot water
and steam shall all be measured. The total error of combined sensing and readout
devices shall not exceed +/- 3% of measured quantity.
Page 80
. !
6.4.2 Check and record electric voltage between feeders and the
frequency at the power supply.
7.1 General operational test. This test should be performed before full
and part load tests. Certain simulated inputs may be needed to trigger control
actions. Therefore some tests are limited to checking safety control circuits
instead of creating true cutout situations. Indicating lights and responses of
relays, actuators, and other equipment are used to confirm the control action.
Details of control sequence may differ between manufacturers and design setup.
The Team should be familiar with the wiring diagrams and manufacturer's
instructions. The following tests are general procedures for confirming control
sequencing function.
7.1.2 Make sure all temperature sensors and controllers have been
calibrated and functioning properly. These include chilled water supply
controller for controlling steam or hot water valves and condenser water
temperature controller for cooling tower and/or condenser water by-pass valve.
Be sure controllers are set at the project specified temperatures.
Page 81
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
7.1.4
Make sure chilled water pump, condenser water pump, and
cooling tower interlocking is functioning properly. Cooling tower should be
readied for operation.
7.1.5 Test flow actuated safety controls. When flow switches in the
chilled water (required by ARI Standard 560) and the condenser water lines are
specified to stop the chiller operation when low or no flow conditions exist,
test these switches by disengaging interlocking between water pump starters and
switching off the respective water pumps or by turning off valves in the chilled
and the condenser water pipes (providing the pipe arrangement permit turning
valves off) to the chiller. Their operation may be verified by observing pilot
lights, measuring electric potential at appropriate wiring junctions or operation
of chiller pumps.
7.1.7 Check chilled water and condenser water flow rates. They
shall agree with project specified rates. Adjust flow balancing devices if
necessary 7.1.9
until it is fully loaded. With constant water flow rate through the evaporator,
the temperature differential of the chilled water entering and leaving the
evaporator indicates the loading condition of the machine. In most cases false
load will be required.
Page 82
. . ,
Page 83
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
1 2 1 .5 Chilled water
. . flow primary element differential
pressure or other flow instrument output.
Page 84
CHAPTER 3 REFRIGERATION PLANT
7.3
7.2.7.19 Steam flow primary element differential pressure or
other flow instrument output.
Part load tests. If part load thermal performance tests are required
in the project specification, part load tests shall be performed immediately
after the full load test. The amount of chiller loads, chilled water
temperature, and condenser water temperature shall be adjusted in accordance to
those specified.
7.3.3 Repeat the same procedures for the next larger part load
specified until all specified part loads have been tested.
7.3.4 After tests, remove all false load and restore all valves to
their normal operation modes.
Page 85
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
8.1
8. Calculations and rate performance.
8.1.1load test.
Full
Qinh “ w2 ( c p2 ) (T e 2 * T 12 )
Qinh = w2 ( H2 * c p2 x T 12 )
where
c pi = specific heat of chilled water, J/(kg °C) [Btu/(lb °F) ]
8.2 Part load test. Use the same equations as for full load test.
The full load capacity of the machine must be not less than
the specified full load capacity.
Page 86
CHAPTER 3 REFRIGERATION PLANT
8.3.2 The heating energy consumption rate at full and part loads
shall not be more than those specified.
Qout
cop
Qine + Qinh
8.3.6 The pressure drop of hot water in generator shall not be more
than that specified.
Page 87
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
1.3 For air cooled condensing coils, the condensing coil capacity is
closely proportional to the temperature difference of condensing temperature and
air dry bulb temperature. Therefore, the coil capacity tested at a certain
outdoor temperature may be converted to design conditions if the condensing
temperature and outside air temperature are known. The test procedures in this
EXHIBIT is based on this assumption.
2. Purpose.
Page 88
2
3.1
3. Industry standards.
3.1.1 tower.
Cooling
3. 1.1. 2 Circulating water flow not more than +/- 10% of design
circulating water flow.
3. 1.2.1 Wet -bulb temperature of air not more than +/- 5.6 °C
3.2.1 Air temperature is measured at tower air intake.
(10 °F) of design.
Page 89
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
Page 90
.
4.4.5 Water is free from debris. Check and clean sump and screen
(or strainer) for debris.
4.5.1 The outdoor temperature during the test must be above 26.7 °C
(80 °F)
Page 91
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
5. Instrumentation.
5.1 Cooling tower.
5.1.2 Condenser water entering (hot water) and leaving (cold water)
temperature differential measurement. Direct measurement of temperature
differential is preferred than measuring both entering and leaving temperatures
and deducing the difference. The measurement error shall not exceed +/- 0,1 °C
(0.2 °F) If differential temperature measurement is difficult to obtain, the
.
leaving condenser water temperature should be measured and the measurement error
of this measurement shall not exceed +/- 0.1 °C (0.2 °F) For multi-tower or
.
5.1.3 Condenser water flow rate. The measurement system error shall
not exceed +/- 3% of measured quantity. Pitot traverse shall be used for
determining water velocity. The instruments for condenser flow rate measurement
in chiller tests may be used for cooling tower tests.
taken in inlet air stream, at 1.2 m (4 ft) from the tower and 1.5 m (5 ft) above
water basin. A minimum of three wet-bulb temperature measurements at different
locations (same level) shall be averaged for thermal performance comparisons.
5.1.5 Fan power. Watt meter of watthour meter. Error shall not
exceed +/- 0.5% of reading.
are provided, attach temperature sensors on the outside of refrigerant pipe and
cover sensor and pipe with 0.025 m (1 in.) thick mineral wool thermal insulation
at least 0.3 m (1 ft) long.
Page 92
. 2 .
6.1
5. 2. 6. Water circulating pump power rate. Watt meter or
watthour meter. Error shall not exceed +/- 0.5% of reading.
6. Test procedures.
Cooling tower.
Page 93
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
1.1
6. 1.7. Entering air wet bulb temperature variation rate +/-
°C/h (2 °F/h)
6.2
6. 1.7. Tower heat load +/- 5%.
6.2.5
6.2.4 The refrigeration machine shall be fully loaded. For loading
procedures and system stabilization requirements, see paragraph 7.2 of EXHIBIT
3-D.
Page 94
CHAPTER 3 REFRIGERATION PLANT
7.1.4 the tested approach shall be not less than the approach of the
manufacturer's curve; and
7.1.5 The measured fan power rating shall not be more than the
specified rating.
7.2.4 Adjust refrigerant flow rate if required (see EXHIBIT 2-B for
flow rate calculations and adjustments).
Page 95
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
Q - M (H in - H out )
J/h (Btu/hr)
(Q)avg = tested coil capacity (see 7.2.6 above), J/h (Btu/h)
(Tcond ) spec = condensing temperature from specifications,
°C (°F)
( CO nd ) test
= saturation temperature corresponding to tested
discharge pressure, °C (°F)
(Tdb) spec = air dry bulb temperature from specifications, °C
(°F)
(o
(Tdb ) test = air dry bulb temperature from test, °C F)
7.2.8 The heat rejection rate (Q) spe c shall not be less than 95% of
the specified heat rejection capacity.
7.2.9 Calculate the average of the 6 measured fan power rates. The
averaged power rate shall not be more than the specified power rate.
Page 96
. 3
2
7.3.4 Adjust refrigerant flow rate if required (see EXHIBIT 2-B for
flow rate calculations and adjustments).
Q = M (H in - H out )
7. 3. 7.1 The total heat rejection rate Q avg shall not be less
than that shown on the manufacturer supplied curve or table at the same entering
air wet bulb and saturated condensing temperature.
Page 97
. . . . .
1. Scope. This chapter provides inspection and testing procedures for heating
equipment and systems. Heating equipment included in this chapter are packaged
air-heating furnaces, hot-water boilers and steam boilers. Boilers may be
cast-iron sectional, fire-box or Scotch-marine fire- tube type, or water-tube
type. Steam boilers may be low pressure (103.4 kPa (15 psig) ASME Boiler and ,
Pressure Vessel section IV) or medium pressure (up to 1034 kPa (150 psig), ASME
Boiler and Pressure Vessel section I). Fuels for furnaces and boilers may be
natural gas, oil, or electric.
2. Reference Standards.
a. ASME Boiler and Pressure Vessel Code - Section I (for power boilers, to
operate over 103.4 kPa (15 psig) steam pressure, or over 121 °C/1103 kPa (250 °F
/160 psig) hot water) Section VI (for heating boilers, to operate not over 103.4
;
kPa (15 psig) steam, or not over 121 °C/1103 kPa (250 °F/160 psig) hot water).
Page 99
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
4.3 Boilers, furnaces, and their components shall be tested for functional
operations. Burners, automatic safety and capacity controls, oil preheat systems
and other components must perform as prescribed in the contract specifications.
4.4 If the building load at the time of testing does not meet the
specified capacity of the contract specification, means to dispose the heat
generated by the test shall be provided. For hot water boilers, temporary pipe
connections to load sources or building equipment cooling sources may be used.
For steam boilers, applying temporary condensers to absorb discharged steam,
using building equipment cooling sources, or wasting steam to the atmosphere may
be used to accommodate the test. However, the test shall not cause excessively
uncomfortable conditions in the building.
Page 100
.
2. Industry standards.
a. ASME Boiler and Pressure Vessel Code specifies the requirements of
construction and inspection of boilers. Section I of the Code is for power
boilers and Section VI is for heating boilers. Heating boiler is defined as low
pressure boiler having a maximum working pressure of 103.4 kPa (15 psig) for
steam operation or a maximum working temperature of 121 °C (250 °F) and/or
maximum working pressure of 1103 kPa (160 psig) for hot water operation. Power
boiler is defined as medium and high pressure boiler having working pressure or
temperature above those defined for low pressure boiler.
c. NFPA Standard 54 (National Fuel Gas Code) is a safety code which applies
to the installation, inspection and testing of fuel gas systems, equipment using
fuel gas and related accessories.
Page 101
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
certain safety requirements to differ from those for single burner boilers. They
are used mostly in field erected large boilers and their application for HVAC use
are not common.
3. General inspection.
3.1 Review equipment manufacturer's instructions on start-up and operation
procedures
3.3 Check equipment name plates to verify equipment model and serial
number. They must have the same model numbers as approved submittals.
3.4 Check for headrooms and access spaces around boiler and furnace for
operation and maintenance. Design specification and manufacturer's recommended
spaces must be provided. For boilers, pay special attention to heat exchanger
tube replacement and cleaning spaces and access spaces to manholes and handholes.
For furnaces, make sure air filter replacement space and burner service space are
adequate
3.5 Inspect heating plant (boiler room and furnace room) for possible fire
hazards. The heating plant should be kept free of combustible fibers and dusts,
flammable liquids, or contents susceptible to smoke or fume contamination.
3.7 Verify installed pipe fittings and accessary equipment against project
drawings and equipment manufacturer's recommendations for completeness and proper
installation. Piping includes blow down piping, steam piping, feed water piping,
gas piping (main fuel and pilot systems), and oil piping (include oil preheat
system for heavy oils). Fittings and accessories include but not limit to
valves, strainers, vibration elimination units, thermometer wells, piping
supports, steam traps, etc.
Page 102
.
3.9 Make sure all gas vent pipes are terminated outdoors.
3.10 All moving parts (motors, belts, etc.) should have protection shields
for personnel safety.
3.11 Check alignment of motor driven equipment. Using some simple tools
such as straight edges, square edges, plumb lines, and strings yield good
results. Also observe shaft and coupling for misalignment while machine is
running.
3.12 Observe belt tightness of belt driven equipment. Use belt tension
gage if needed. Belt tension should be as recommended by belt manufacturer.
3.17 Check safety control wiring connections. All safety control switches
(switches respond to temperature, pressure, flow, level, etc. to break the safety
control circuit) should be connected in the ungrounded conductor.
3.19 Test run motors (fan, pump, air compressor, etc.) to check correct
direction of rotation.
3.20 Check thermal insulation for damages and omissions. All joints
should be sealed. The material, thickness, and finish should be as specified.
3.21 Check surface paint for damages and omissions. Equipment nameplates
must not be painted over. Required equipment labels must be present and legible.
Page 103
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
3.23.1 Check water flow direction marks for check valves and flow
switches
3.23.7 make sure piping system has been cleaned before connections
to boiler are made.
3.23.10 For cast iron sectional boilers during hydrostatic test, pay
special attention to sealed joints, possible cracks, and defective castings which
may develop leaks.
Page 104
.
4.3 Make sure gas and oil line strainers are cleaned. Observe oil line
pressure gage for erratic movement.
4.4 Before operate burners, make sure all valves and switches are in their
operation positions.
4.5 Check pilot flame while draft fan is at maximum and main burner is
off. The pilot should be stable. When burner switch is opened, the pilot flame
should extinguish promptly. Lingering flame require checking of pilot gas valve.
4.6 Verify combustion air interlock with fuel safety valve and electric
ignition. If boiler is equipped with air flow interlock, open air flow switch
to verify control. If boiler is equipped with air pressure (some boilers have
air pump and draft fan from the same motor and is provided with atomizing air
proving switch) and damper sensing interlock, stop fan and manipulate damper
position sensor to verify control. Whenever combustion air control is
interrupted, the fuel safety valve and ignition must deactivate automatically.
Page 105
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
4.9 Verify automatic gas safety shutoff valve (gas fired and gas/oil fired
boilers) tightness by the following procedures:
4.9.2 Trip the automatic shutoff valve by removing its energy source
(electricity or air pressure). The valve indicator should now agree with the
valve status.
4.9.3 Close the gas cock downstream of the automatic shutoff valve.
Open the pipe cock on the leakage test tap.
4.9.5 When the gas pipe is newly installed and is not thoroughly
cleaned, the automatic shutoff valve may indicate leakage. The entire piping and
valves must be cleaned and the test repeated till the valves close tight.
4.10 Test time delays and minimum or maximum time periods of safety
actions by measuring actual time and compare with specified or regulation
required time. Examples are:
Page 106
CHAPTER A HEATING PLANT
4.10.3 Purge timer must prevent safety shutoff valve from opening
before the end of boiler purge cycle.
4.11 While the burner is on, remove the energy source (electricity or air
pressure) of the automatic fuel safety valve. The fire must be out completely
within specified or regulation required time. Also observe valve position
indicator. The indicator must agree with the valve status.
4.12 While the burner is on, close the manual burner valve. The automatic
safety shutoff valve must closed automatically within its specified or regulation
required time.
4.13 Check low fire lighting-off. After pre-ignition purge and before
ignition cycle, the fuel and combustion air control should be interlocked in the
low fire lighting-off position.
4.14 For boilers with automatic cycling controls, check pilot flame
detection controls. The main fuel shut-off valve must be closed when the pilot
flame is not proven.
4.15 For larger sectional boilers with gas burners, there may be multiport
main burners with multi-pilot igniters. Check electronic or thermal supervised
pilot during light-off. Failure of any pilot should cause shut off of fuel to
the pilots and main burners.
4.16 Check indicating lights during the entire inspection and test period
to be sure that they agree with the burner control operation. Indicating lights
are usually provided for:
a. Flame failure
b . Load demand
d. Low water
e. Draft fan.
Page 107
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
5.2 Be sure the oil preheating system is working properly and stable. The
oil temperature supplied to the boiler should be as recommended by the
manufacturer
5.3 After boiler has been operating for a sufficient time to assure warm
conditions, check fuel and air modulating controls for proper settings. The fuel
air ratio at various load conditions should be maintained automatically in
optimum ranges.
5.3.1 The optimum fuel-air ratio may best be checked by flue gas
analysis. An Orsat apparatus may be used for flue gas analysis (see EXHIBIT 2-A
for description of Orsat apparatus) with combustion product drawn from test
opening in stack.
5.3.2 The proper amount of carbon dioxide in the combustion air for
optimum combustion depends on the kind of fuel used. 9.5% to 10.5% for natural
gas and 12.5% to 13% for fuel oil are considered reasonable. There should never
be carbon monoxide measured in the flue gas.
6.2 Check installed pipe sizes against project drawings. If the drawings
do not show relief pipe sizes, make sure the inside diameter of the discharge
pipe is equal to or larger than the safety valve outlet diameter. If manifold
discharge pipes are used, the manifold inside area must be equal to or larger
than the combined areas of individual pipes. Valves should be installed on
boilers directly without other fittings between boilers and safety valves.
6.3 Remove safety valves during boiler cleaning and boiloff operations to
protect from damaging to valve internal parts.
6.4 Note valve settings. These valves are factory set and sealed and
should not be altered in the field.
Page 108
.
6.5 Field testing of safety valves. Although safety valves are tested and
adjusted in factory, they should be tested on boiler to be sure no damage
occurred during storage, installation, or boiler hydrostatic testing. Testing
should be done by the valve manufacturer's representative or by boiler inspector.
Testing may be performed in one of the following two methods:
7. Boiler water level, makeup water control and low water cutoff.
7.1 Make sure water level control and low water cutoff is mounted in a
plumb position.
7.2 Remove electric control box cover and inspect wiring connections,
terminals and mercury switches for looseness and damages.
7.3 Test makeup water control and low water cutoff to be sure the required
control actions are performed at the correct water levels.
7.3.1 The test should be done while burner is in low fire operation.
7.3.2 By observing glass gauge level, the make up water cut-in and
cut-out levels may be tested by draining boiler water through drain valve or
blowdown valves
7.3.3 When makeup water line is valved off or makeup water pump
disabled and the boiler is slowly drained, the point of fuel cutoff may be
observed. At the moment of fuel cutoff alarm should sound and warning light
activated. In no case should the water level drops below the lowest point of the
water level gauge or the lowest permissible water level. For boilers equipped
with dual low-water protection, each device should be tested independently. If
the lowest allowable water level is reached and the burner is not cutoff
automatically, the drain or blowdown valves should be closed immediately and the
normal water level restored to avoid damage to the boiler.
Page 109
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
7.3.5
Caution should be exercised during this test. The boiler
drain and blowdown valves should always be attended so that they may be closed
immediately when needed.
7.4 Inspect water gauge glass for cracks and leakage at gaskets. The
gauge glass should be clean. Operate gauge column isolation valves and drain
valves to make sure they function properly. After test, be sure the isolation
valves are left open.
8.2.1 Perform this test only when the boiler is operating close to
full firing. Soot blowing operation during low firing may produce unfavorable
conditions that could interrupt combustion.
8.2.3 Crack open steam valve to warm pipe up and close drain valve.
Page 110
.
8.3.2 Test electric oil heater thermostat cutin and cutout points
by immerse its sensing element in liquid temperature bath.
8.3.3 Test hot water or steam oil heater thermostat cutin and cutout
points by immerse its sensing element in liquid temperature bath.
8.3.6 The steam trap and condensate pipe of the steam oil heater
must not be unduly hot.
Page 111
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
9.2 Check thermostat for correct leveling, if mercury bulb is used for
electrical contacts.
Page 112
CHAPTER A HEATING PLANT
1. Scope. The test procedures in this EXHIBIT apply to boilers used for HVAC
systems. Included are cast-iron, fire box, scotch marine, electric, and packaged
water tube boilers used for hot water or steam generation. Tests to confirm
capacity and energy conversion efficiency are covered in this EXHIBIT.
Functional tests of boilers and their auxiliaries may be found in EXHIBIT 4-A,
INSPECTION PROCEDURES FOR BOILERS.
2. Industry standards.
b. ANSI Standard Z21.13 (AGA Standard for Gas-Fired Low-Pressure Steam and
Hot-Water Boilers) covers construction and performance requirements of gas-fired
steam or hot water boilers. This standard is applicable to low pressure boilers
as defined in Section VI of ASME Boiler and Pressure Vessel Code and is limited
to boilers of less than 3663 kW (12,500,000 Btu/h) input.
d. The Hydronic Institute Testing and Rating Standard for Heating Boilers
specify methods and procedures for determining performance of cast iron, steel
and copper heating boilers (ASME Section IV boilers) .This Standard gives test
procedures and requirements for overall efficiency and combustion efficiency of
boilers with 87.9 kW (300,000 Btu/h) and larger input. For boilers having less
than 87.9 kW (300 Btu/h) input, the Standard use DOE test requirements.
e. See EXHIBIT 4-A INSPECTION PROCEDURES FOR BOILERS for other standards.
3. General.
3.1 All boilers shall be tested for output at full capacity to verify
capacity requirement, except for small boilers. See contract specifications for
clarification.
3.2 All boilers shall be tested for thermal efficiency at full load. Gas
Page 113
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
and oil fired boilers shall also be tested for combustion efficiencies at part
loads. Two ways are generally used to test boiler thermal efficiencies for gas
and oil fired boilers. They are tested by input/output method or by heat loss
method. Since this guide requires testing of output at full capacity,
input/output method shall be used for full capacity thermal efficiency tests.
3.3 Contract specifications usually specify the amount of energy input (in
terms of fossil fuel amount or electric input amount) and the amount of energy
output and its conditions, all at peak load. It may also specify the required
efficiencies at different loads. Unless the specification requires otherwise,
the following tests and verifications of the boiler performance shall be
performed during commissioning.
3.3.1 For gas and oil fired boilers, test boiler combustion
efficiencies at 25%, 50%, and 75% of specified capacity. At full load, test
thermal efficiency by using input/output method. For boilers having on-off type
burner controls, efficiencies shall be tested for full capacity only.
3.3.2 For gas and oil fired boilers, test and prove that the
limitation of unburned combustibles is met. The amount of unburned combustibles
allowed may be found in the contract specifications.
3.4 The input/output method measures heat in fuel consumed and the heat
output of the boiler. Boiler efficiency is calculated by:
output
Efficiency (per cent) x 100
input
3.5 Flue losses account for the biggest part of gas and oil fired boiler
losses. Combustion efficiency is derived from flue losses. Major effort of
commissioning test should be on measuring flue losses.
3.7 Since many of the steps of the boiler test procedure coincide with
boiler tuneup and startup procedures which are usually performed by a factory
personnel of the boiler manufacturers, the same factory personnel may be the Test
Agent
Page 114
.
4.2 Make sure that the boiler has been cleaned. Oil, grease, and foreign
matter must be chemically cleaned and flushed. Water treatment specialist should
be consulted as to the cleaning compounds and application procedures for cleaning
boiler and treatment of feed water (For requirement of water treatment, consult
contract specification) . In most cases the building piping system is connected
to the boiler to be commissioned. The entire system shall be cleaned. Safety
relief valves must be protected during cleaning.
4.3 Make sure that boiler and auxiliaries (burners, pumps, fans, etc.) are
adjusted for operation.
4.4 Make sure that boiler has been boiled out. Water treatment specialist
should be consulted for selection of chemical compounds and boil-out procedures.
Safety relief valves must be protected.
4.7 For boilers requiring preheating of heavy oil, the oil preheat system
must be in normal operating conditions before tests.
4.8 During capacity and efficiency tests (see Paragraph 6. below), the
heating energy produced by the boiler must be absorbed by building air handling
and/or other equipment such as temporary heat exchangers or steam condensers with
cooling medium provided from building cooling system or temporary cooling
equipment. These building equipment should be prepared and ready for operation
before boiler tests. Steam boilers may be arranged to waste steam to the
atmosphere if the steam produced can be safely piped to outside the heating
plant. The construction contractor should have complete plan and preparation for
this exercise. Overheating of building occupied spaces should be avoided.
Page 115
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
5. Instrumentation.
5.1 Make sure that all instrumentation are in good working orders and are
in calibration. See Chapter 2 BASIC MEASUREMENT for calibration of instruments.
5.3.1 Temperature.
suitable for the temperature range of up to 538 °C (1000 °F) may satisfy this
requirement. The selection of instruments depends mainly on how practical they
can be used in the field for the size of the boiler.
5. 3. 1.4 Hot water (for hot water boiler) inlet and outlet
temperature. The total measurement error shall not exceed +/- 0.3 °C (0.5 °F) .
Page 116
. 4
2
5
3 .
3.3.3 Gas flow rate measurement. Use calibrated gas flow meter.
There may be gas flow meters installed by the gas company. Check if the meter
is dedicated for the boiler to be tested. If not, gas use to other boiler of
appliances need to be turned off during this test. Measurement error shall not
exceed 1% of flow.
5.3.5 Steam flow rate and hot water flow rate. The total
measurement error shall not exceed +/- 3%. It is important to check the primary
element location for good data. If pipe length does not meet those given in
Chapter 2, flow straightener should be used.
5.3.8 Pressure.
Page 117
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
6.1.2 After the boiler has been warmed up, the boiler capacity shall
be adjusted to 25% of the full load capacity as required in the contract
specification and the burner capacity control shall be set to manual. The
measurement of load level is done by measuring fuel input flow rate and the
heating value of the fuel or by measuring the output rate of the boiler
(Measuring output at 25% capacity is for hot water boiler only. Measuring steam
output at this low capacity is generally not advisable) The actual running
.
capacity shall be within +/- 3% of the calculated capacity (full capacity input
or output as specified times 25%).
6.1.3 The building air handling and/or other cooling equipment may
need to be adjusted during the test to provide steady and approximately correct
load.
6.1.4 Test data shall be taken after boiler has been running at
steady state conditions for at least 30 minutes. Steady state conditions of the
boiler operation is defined by measuring the temperature of flue, entering water,
and leaving water (for hot water boiler) or steam pressure (for steam boiler).
All these temperatures shall not vary over 5.6 °C (10 °F) and the pressure shall
not vary over 13.8 kPa (2 psi) during a 30 minute period with three set of
measurements at 15 minute intervals.
6.1.5 Test data required are listed below (See later sections for
detailed measurement requirements). Three sets of test data shall be taken at
15 minute intervals and they shall be arithmetically averaged for capacity and
efficiency calculations.
Page 118
4
9
6
7
8
5 ,
6. 1.5. For hot water boilers, measure and record water inlet
and outlet temperature. If differential temperature measurement is chosen,
measure and record differential temperature.
Page 119
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
Page 120
4
2
3 3
Electric boilers.
6.2.1 Electric boilers shall be tested for full capacity and for
efficiency at full load by input/output method.
6.2.2 The building air handling and/or other equipment may need to
be adjusted during the test to provide steady and approximately correct load.
6.2.3 Test data shall be taken after boiler has been running at
steady state conditions for at least 30 minutes. Steady state conditions of the
boiler operation is defined by measuring the temperature of entering water and
leaving water (for hot water boiler) or entering water and steam pressure (for
steam boiler). All these temperature shall not vary over 5.6 °C (10 °F) during
a 30 minute period with three set of measurements at 15 minute intervals.
Page 121
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
(q)out - M (H s - HJ
7. 1.1. 2 Hot water boiler.
(q)out “ M (H out - H in )
7.2.1 For gas -fired units. Convert measured gas volume flow rate
to standard conditions. Standard conditions for gas is usually at 15 °C (60 °F)
and 101.3 kPa (30 in. of Hg) This standard conditions should be confirmed with
.
Pm + Pb 15 + 273
Qs = Qm (* ) ( (For SI)
101.3 T m + 273
P m + P b x 13.57 60 + 460
Qs - Qm (- ) ( ) (For Customary)
30 x 13.57 Tm + 460
Page 122
CHAPTER A HEATING PLANT
(q) in = Q s x (HHV) g
Q s « Qi x [1 - (T B - 15) x V f ]
(For SI)
Qs = Qn, x [1 - (T m - 60) x V f ]
(For Customary)
( q ) in - Qs X (HHV) 0
Qn,
•= measured volumetric flow rate of oil, m 3 /s (gph)
T m = measured oil temperature at flow meter, °C (°F)
V f = specific volume factor to adjust volume change
due to temperature, if not available from oil
test lab, use 0.00068 per °C (0.00038 per °F)
(q) in = heat input rate, W (Btu/h)
(HHV) C = higher heating value of oil as supplied by
testing lab, J/m 3 (Btu/gal)
7.3
7.2.3 For electric units. Calculate heat input to electric elements
of boiler from measured electric energy:
( q ) in = W (For SI)
( q ) out
7.3.1 eff (in 1) x 100
(q)in
7.3.2 Boiler thermal efficiency at full load shall not be lower than
that required in the contract specification.
Page 123
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
7.4 Combustion efficiency at part loads (for gas and oil fired boilers
only)
7.4.1 Flue losses (q) f Flue losses may be obtained by using charts
.
7.4.3 Boiler combustion efficiencies at 25%, 50%, and 75% shall not
be less than those required in the contract specifications.
Page 124
. .
1. Scope. The test procedures in this EXHIBIT apply to gas, oil, or electric
fired packaged furnaces used for building air heating systems. Tests to confirm
capacity and energy conversion efficiency are covered in this EXHIBIT.
Functional tests of furnaces may be found in EXHIBIT 4-A, INSPECTION PROCEDURES
FOR BOILERS AND FURNACES.
2. Industry standards.
b. ANSI Z21.7 (Standard for Gas-Fired Warm Air Furnaces) gives the minimum
construction, safety, and performance requirements for gas furnaces.
c. See EXHIBIT 4-A INSPECTION PROCEDURES FOR BOILERS AND FURNACES for other
standards
3. General.
3.1 All furnaces shall be tested for output at full capacity to verify
capacity requirements, except certain small furnaces specifically exempt by
contract specifications. Check contract specifications for requirement.
3.2 All fossil -fuel furnaces shall be tested for combustion efficiency at
full load.
3.3 Two ways are generally used in the industry to test furnace
efficiencies. They are tested by input/output method or by heat loss method.
Since air heating furnaces in federal building are relatively small as compared
to other heating equipment (boilers), commissioning tests should be concentrated
on verifying capacity and combustion efficiency.
3.3.1 Gas and oil fired furnaces shall be tested for combustion
efficiency (not thermal efficiency) at full capacity by using heat loss method.
Page 125
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
3.4 The input/output method measures heat in fuel consumed and the heat
output of the furnace. Furnace efficiency is calculated by:
output
Efficiency (percent) = x 100
input
3.6.1 Flue losses account for the biggest part of furnace losses.
Major effort of commissioning test should be on measuring flue losses.
4.2 Make sure that furnace and air filters are cleaned, air circulation
fan (and combustion air fan, if provided) are adjusted correctly and oiled, and
burner are tuned for operation.
4.4 The commissioning team should coordinate with the contractor and
building user to arrange appropriate time for testing so that the building
occupants will not be subjected to overheating conditions.
Page 126
. . 4
2
3 .
5. Instrumentation.
5.1 Make sure that all instrumentation are in good working orders and are
in calibration. See Chapter 2 BASIC MEASUREMENT for calibration of instruments.
Temperature.
suitable for the temperature range of up to 538 °C (1000 °F) may satisfy this
requirement
Page 127
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
5.3.3 Furnace air flow rate. Use pitot traverse and water manometer
to measure either supply or return air flow rate. The measurement error shall
not exceed +/- 5 percent of the quantity measured.
6.1 The test to confirm the furnace capacity and combustion efficiency is
conducted under steady state operation. Turn thermostat up for about 5.6 °C (10
°F) to initiate furnace operation. Measure the supply air temperature at 5
minute intervals. If the variation of 3 measurements are within 1.7 °C (3 °F) ,
6.2 Test data required are listed below (See later sections for detailed
measurement requirements) Three sets of test data shall be taken at 15 minute
.
intervals and they shall be arithmetically averaged for capacity and efficiency
calculations
Page 128
4
2
5
3 .
Page 129
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
6.2. 3.6 Air flow rate. See EXHIBIT 2-C STANDARD TEST
PROCEDURES for details.
Page 130
. . ) : ]
7. 7.1
Calculations and rate performance. (See EXHIBIT 2-B for Standard
Equations of parameter calculations)
Furnace capacity.
Q
(*l)out ^ (^out “
^in)
V
Symbols
(q) out = furnace capacity, W (Btu/h)
Q - volume flow rate of air, m 3/s (ft 3 /m)
v = specific volume of air (average of inlet and
outlet temperature), m 3 /kg (ft 3 /lb)
H out = enthalpy of air at outlet, J/kg (Btu/lb)
H in = enthalpy of air at inlet, J/kg (Btu/lb)
7.2 Furnace capacity shall not be less than specified in the contract
specifications
7.3 Combustion efficiency (required for gas or oil fired furnaces at full
load only)
7.3.1 Sensible flue loss (q) f . Sensible flue losses maybe obtained
by either using equations or charts.
B
R «= A +
X
100
L « ([(1 + AF) (CF(i) + AF (R - 1) (CA(i) )
HHV
x [
(T gas + 460)* - (T air + 460)*])
CA( 3 = 2 7608571x10'® .
Page 131
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
CA(4) «= -7 4253321xl0" 12
.
CA(5) - 6 4307377xl0' 16
.
i — an index, 1 through 5
A, B, AF, CF = constants from following table:
A B AF
CF(4) CF(5)
read. The loss of water vapor of combustion product (also called hydrogen loss)
is 9.55% for natural gas and 6.50 for No. 2 oil. The total combustion loss is
the sum of sensible loss and hydrogen loss.
6.4 Furnace combustion efficiency shall not be less than that specified
in the construction specifications.
Page 132
CHAPTER 4 HEATING PLANT
1%)
XC02,
0R
S
XC02,
r t,s OR r t,f H
Chart 1 Ratio of Total Combustion to Stoichiometric Air
Page 133
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
400 350
(J)
SS‘Jiv
HO
</5 SS‘S
to
1V
r t,s w rt,f H
Page 134
CHAPTER A HEATING PLANT
200 sr
t/i
CO
CO
CO
CO
Page 135
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
|j)
SSJjy
HO
SS‘Sjy
Page 136
. . . .
1. Scope. This chapter provides inspection and testing procedures for air
handling equipment and systems that use chilled water as cooling medium.
Included are central station field erected systems, central station factory
packaged systems, and room terminal units (fan coil units and unit
ventilators). Unitary air handling units that use refrigerant as cooling
media are not included in this chapter. They may be found in chapter 8,
Unitary Air Conditioning Equipment. Certain temperature controls are included
in Chapter 6, Building Automation Systems.
2. Reference Standards.
a ARI Standard 410
.
- Standard for Forced-Circulation Air-Cooling and
Air-Heating Coils
g- ARI Standard 850 - Standard for Commercial and Industrial Air Filter
Equipment
Page 137
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
3.2 See EXHIBIT 5-A for inspection procedures. See Appendix for
inspection check lists.
4.4 See EXHIBIT 5-B for test procedures. See Appendix for test work
sheets
Page 138
CHAPTER 5 AIR HANDLING EQUIPMENT AND SYSTEMS
2. Industry standards.
a. ARI Standard 630 (Standard for Selection, Installation, and Servicing
of Humidifiers) describes humidifier selection procedure, installation
practices, and service practices of humidifiers used in central stations and
self-contained applications.
3.2 Give complete inspection of fan, motor, air filters, cooling coils,
heating coils, dampers, fan and coil bases, vibration isolation units, and
their associated equipment, including associated electrical equipment, piping,
ductwork, etc. Be sure that no apparent damage or rusting occurred.
3.3 Check equipment name plates (air handling unit, fan, motor, air
filter, coils, etc.) to verify equipment model and serial number. They must
have the same model numbers as approved submittals.
3.4 Check for headrooms and access spaces around unit for operation and
maintenance. Manufacturer's recommended spaces must be provided unless the
contract documents specify otherwise. Pay special attention to coil and filter
replacement and cleaning spaces and access spaces.
3.5 Inspect equipment room for possible fire hazards. The room should
be kept free of combustible material and construction debris.
Page 139
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
3.7 Verify service piping, pipe fittings and accessory equipment for
the air handling equipment against project drawings and equipment
manufacturer's recommendations for completeness and proper installation.
Fittings and accessories include but not limit to valves, strainers,
thermometer wells, piping supports, steam traps, etc.
3.8 Check water flow direction marks of check valves and flow switches.
3.10 All moving parts (motors, belts, etc.) should have protective
shields for personnel safety in accordance with job specifications.
3.12 Observe belt tightness of fans. Use belt tension gage if needed.
Belt tension should be as recommended by belt manufacturer. Remove equipment
access panels as necessary.
3.19 For motor starter equipped with overcurrent heaters, check heater
sizes against starter manufacturer's recommendations. The recommendations are
usually contained in operator's manual or posted in starter cabinet.
Page 140
. . .
3.24 Inspect duct connections at air handling unit for excessive air
leakage
4. Fan.
4.1 Inspect fan housing access door and pressure latches for tightness.
Open and close doors to detect interference of door with thermal insulation
and other equipment.
4.2 Check assembly bolts of field assembled fans for any loose bolt.
4.3 Inspect bearing for proper oil or grease application. Grease lines
for bearings should extend to outside of duct connections with grease fittings
if specified. Oiling shall not require dismantling of fans, ducts, or other
equipment if specified.
4.4 Inspect belt guard for access to oiling, speed counting device, and
other maintenance requirements.
4.6 For outlet damper or inlet vane controls inspect control linkage
manually or by manipulating controller for the full range of the stroke. When
a single operator controls inlet vanes of double inlet fans, inlet vanes on
both inlet openings must move in unison. Inspect inlet vane rotation
direction with respect to that of the fan wheel.
4.7 Fans exposed to weather should have protective weather hoods over
motors and drives if specified.
4.8 For fans without duct connections, unless they are housed in
plenums, they must be provided with protective devices for personnel safety
such as wire mesh or expanded metal screens at inlets and outlets if
specified
Page 141
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
4.10 For fans not enclosed in air handling unit casings, make sure
flexible duct connections are installed between fans and ducts if specified.
Check specifications for material and construction of flexible connections.
5.3 Inspect baffles between coils and casing to assure that air is not
bypassing coils.
5.4 Inspect cooling coil drain pans. Coils must have individual pans
with drain pipes for multi-coil assembly to avoid flooding of lower coils if
specified. Similar arrangement is required for sprayed coil dehumidifiers.
5.6 Inspect steam coils for possible coil freezing problem. Good
condensate draining must be provided: adequate slope of tubes, adequate head
between coils and steam traps (minimum 18 in.), and vacuum breakers at high
position of coils. Adequate sizing of steam traps should be checked if the
requirements are not given in the contract specifications. Check for counter
flow, air vents, drains, water trap on cooling coil, piping and water coil.
5.8 Check steam traps and condensate piping of steam coil temperature.
They must not be unduly hot.
6. Air filters.
6.1 Inspect filters for air leakage between filters and holding frames
and between filter assembly and unit casing. Inspect positive sealing devices
for air leakage, if specified.
6.2 For automatic renewable type air filters, inspect medium advancing
Page 142
. . .
and override operation (pressure control, timer setting, media switch, etc.
See specifications for project requirements).
6.3 Inspect filter gage sensing tips for correct static pressure
sensing
6.4 For inclined manometer type filter gages check for correct
installation levels.
6.6 Make sure adequate access spaces are provided for filter media
replacement as per design drawings/specifications.
7 . Dampers
7.1 Verify blade arrangement, bearing material and edge sealing
material
7.4 all dampers in ducts must have access doors if specified. Doors
must be air tight.
8. Air louvers.
9. Casings.
Page 143
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
9.3 Verify access door sizes, gasket tightness, and latch arrangement.
11. Controls.
11.1 Review installed control systems with contract documents and
submittals to assure that the installations are as required.
11.5 Examine valve operation for tight closing. Valve motors and
linkages should be installed securely. Linkages should move through the
entire stroke without binding or interfering with other objects.
11.7 If pneumatic controls are used for system controls, check the
following:
Page 144
. .
11.7.2 Check air filters (both intake air and air line)of air
compressors for cleanliness.
11.7.5 Make sure protective shields are provided for belts and
pulleys
11.7.7 Test open air tank drain for possible water accumulation.
11.7.9 Check for correct air pressure at air tanks and after
pressure reducing valves.
11.8 For electrical and electronic control systems check for loose wire
connections, broken wires, and rust terminals.
11.10 Inspect electronic systems for ground shield cable and possible
interference of magnetic field with signals.
Page 145
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
12.7 Check air filter type for specification compliance. Both outside
air and recirculated air must go through air filters.
12.9 Coil types and valve assembly shall be as specified. Check for
heat transfer fin damages.
12.12 If wall boxes are used for outside air, check box material and
construction. Bird screen shall be provided as specified.
Page 146
CHAPTER 5 AIR HANDLING EQUIPMENT AND SYSTEMS
2. Industry standards.
a. ARI Standard 410 (Standard for Forced-Circulation Air-Cooling and
Air-Heating Coils) describes the method of testing and rating of forced air
cooling and heating coils and the method of establishing coil performance by
extension of test data to operating conditions other than test. It lists a
range of standard rating conditions for important operational parameters such
as air face velocity, fluid velocity in tubes, temperature of air and fluid.
Fluid used in coils tubes are refrigerant, cold and hot water, steam, and
ethylene glycol solution. This standard is used in conjunction with ASHRAE
Standard 33 (Methods of Testing for Rating Forced Circulation Air Cooling and
Air Heating Coils.
Page 147
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
e. ARI Standard 670 (Standard for Fans and Blowers) describes testing and
rating requirements for fans and blowers. This standard is used in
conjunction with ASHRAE Standard 51 (Laboratory Methods of Testing Fans for
Rating Purposes). Test data may be extended by use of fan laws to other fans
with certain restrictions.
f. ARI Standard 850 (Standard for Commercial and Industrial Air Filter
Equipment) describes classification, testing and rating requirements,
performance and safety requirements for factory-made air filter devices and
air filter media. This Standard is used in conjunction with ASHRAE Standard
52 (Methods of Testing Air Cleaning Devices Used in General Ventilation for
Removing Particulate Matter) It states standard rating conditions and values
.
Page 148
CHAPTER 5 AIR HANDLING EQUIPMENT AND SYSTEMS
98%.
3. General.
3.2 Field tests of air handling systems are separated into two groups
in this guide. The air handling unit component tests are based on steady
state operating conditions to verify the peak capacities of the components.
The air handling system operational tests mainly verify the control operations
of the systems.
Page 149
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
3.4 Functional inspection and test process is based on the premise that
the construction contractor has tested, adjusted, and balanced the entire air
and water systems and is ready for normal operation. Certain preparatory
procedures listed in this section are needed before commencing functional
inspection and tests of components and systems.
3.6 All fans (supply, return, exhaust, transfer) which may influence
the air balance in the area should be operating at their normal conditions.
3.8 All safety devices and provisions have been inspected and tested
already
3.9 The space temperature and humidity controls should be set at normal
operating conditions.
3.10 air flow rate measurement of fans and subsystems (if air flow
rates differ from that of the main fan) should be performed before other
tests
3.13 Fan ratings supplied by fan manufacturers and air flow rates of
the design documents are generally in standard air conditions (approximately
dry air at 21.1 °C (70 °F) and 101.3 kPa (29.92 in. of Hg) or 1.20 kg/m 3
,
3
(0.0750 lb/ft ) unless noted otherwise. It is generally adequate to use
volumetric flow rates for commissioning purpose. If the temperature,
humidity, and barometric pressure differ substantially from those of the
standard air, the volumetric flow rates from the test results must be
Page 150
.
adjusted.
3.14 Check if there are dampers installed in main ducts and have no
function in balancing air between duct branches such as fire or smoke
dampers), make sure the blades of these dampers parallel to the air flow.
3.15 The preferred method of measuring air flow rate is the pitot tube
traverse method. It is extremely important in selecting the location in the
ducts for the pitot measurement. If packaged air flow measuring stations are
specified and installed, they should be used after a preliminary check of its
performance. Use SE-9 or -10 for air velocity measurement and SE-12 for
volume air flow rate from EXHIBIT 2B, Chapter 2.
4. Instrumentation.
4.1 Make sure that all instrumentation are in good working orders and
are in calibration. See Chapter 2 BASIC MEASUREMENT for calibration of
instruments
Temperature.
Page 151
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
1.6
Direct measurement of temperature differential of
4. 3. 1.5
entering and leaving air. For calculating energy amount, this measurement is
preferred than deducing the difference from separate temperature measurements
of entering and leaving air in applications of measuring air temperature
differentials. The measurement error shall not exceed +/- 0.28 °C (0.5 °F)
Precautions for measurements described in the previous paragraph must be
observed.
4.3.3 Pressure.
Page 152
.
5.1.2 When fans are tested and rated in the laboratories, they
are tested under ideal inlet and outlet conditions as prescribed in the ASHRAE
(and AMCA) standards. In overwhelming cases of actual installations, the site
conditions of ducts (also called system effect factors) alter the fan
performance, sometimes substantially. The fan manufacturers base their
submittals on matching the performance of the laboratory (or allowed
equivalent) results (fan curves or tables) with estimated air friction (the
specified pressure head) Any mismatch between the laboratory performance and
.
5.1.4 Using Pitot tube to traverse the main ducts of the air
handling unit5.1.6
is the preferred method. Make sure the air flow at the location
of measurement is steady (after minimum length of straight duct run or after
straightening vanes). See EXHIBIT 2-C, STP-5 for measurement procedures.
5.1.5 Measuring air flow rates at coil face or air filter face
with anemometer may be used for supply fan measurement, if good locations for
pitot measurement can not be found. See EXHIBIT 2-C, STP-6 for measurement
procedures
Page 153
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
* Barometric pressure.
Page 154
... 6
5
2
5.1.10.6
5.1.10.4 Perform the required measurements listed in 5.1.7
above
Page 155
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
5.1.10.9 During the maximum and the minimum air flow rate
manipulation, verify the operation sequence of reheat coils (for units with
reheat coils), recirculating fans (for units with recirculating fans), and
other operational controls as required in the contract specifications.
Page 156
. 4
6
9
7
5
2
3
having the same air flow rates through fans and coils, the measured air flow
rates through fans shall be used for coils.
5.2. 3.8 For cooling coil test, measure the entering air
humidity (relative humidity, wet bulb temperature, or dew point temperature).
Usually humidity needs to be added in the air by manipulating humidifier or
false humidity load source. The humidity must be maintained within 3% RH or
equivalent of the contract specified value.
Page 157
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
5.2.4 Separate test work sheets for heating coil and cooling coil
are included in test work sheets for air handling system component tests, WS
5B-2, in the appendix.
5.3 Humidifiers.
Page 158
. . 4
3
5
6
pressure is more than +/- 6.895 kPa (1 psi) from that specified, the steam
line pressure controlling device must be adjusted. Correct the degree of
steam saturation, if the steam is less than saturated, before proceeding
testing. The steam pressure shall be maintained during the test.
6.1.1 The measured total air flow rate of the fan must be within
5% of the specified fan air flow rate. The motor current rate must not be
greater than the full load current shown on the motor mane plate.
Page 159
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
this pressure should be used for reference only, if the other data show that
the fan performance
6.1.3 is satisfied.
6.2.1 For heating coils the entering and the leaving air humidity
are not required to be measured in this guide. The errors of the enthalpy of
air caused by this simplification are not significant if a 50% RH coil
entering air humidity is assumed. This assumption is justified for the
majority of HVAC applications.
kPa (in. of Hg) knowing the measured humidity of entering air for cooling
coil or the assumed humidity (50% RH) of the heating coil, using SE-2.
(Btu/lb) of air), using SE-4. For cooling coil both the dry bulb temperature
and humidity are as measured. For heating coil assume the leaving air has the
same humidity ratio as the entering air (calculated in 6. 2. 3. above).
Page 160
, . . , 6
9
7 ,
3
Calculate specific volume of air, v, m /kg (ft 3 /lb)
6. 2. 3.
of air), using SE-5. The air temperature at the flow measurement location
must be used in this calculation.
in the calculation.
Capacity, W (Btu/h)
- M [
(H) lvg - (H) ent (For SI)
Humidifiers.
6.3.1 Calculate the average entering air and the average leaving
air dry bulb temperature from measured data.
6.3.4
6.3.2 Calculate the average relative humidity, wet bulb
temperature, or dew point temperature of the entering and the leaving air from
measured data.
Page 161
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
SE-5. The air temperature at the flow measurement location must be used in
this calculation.
SE-14. The measured volume air flow rate, Q, m 3 (ft 3 /min), is needed in the
calculation.
Page 162
4
6
5
2
3 8
Page 163
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
side-by-side areas for humidity readings. The mixing temperature and humidity
are the algebraic averages of their respective readings.
Hm - Hr
outside air Q c -= Qs
H0 - Hr
3 3
where Q 0 = minimum outside air quantity, m /s (ft /min)
Q s = supply air quantity measured during component
tests, m 3 /s (ft 3 /min)
Hnj *= average mixed air enthalpy, kJ/kg (Btu/lb) of air
H r *= return air enthalpy, kJ/kg (Btu/lb) of air
H 0 *= outside air enthalpy, kJ/kg (Btu/lb) of air
7.4.3 Test work sheet for checking outside air damper setting is
included in test work sheets for air handling system control operation tests,
WS 5B-3, in the appendix.
Page 164
. . . 4
2
6
8
3
7
5
system admits 100% outside air; and the temperature below which the preheater
valve opens
Page 165
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
7.6.2 At the time of this test the air handling systems are most
likely to be in occupied mode. It is necessary to test the sequence of
controls of shutting- down, outside air damper operation, unoccupied
temperature maintenance, and starting-up.
Page 166
4
6
8
9
53
7
7.7.1
7.6.4 Testing of warm-up/cool-down cycle is included in
test work sheets for air handling system control operation tests, WS 5B-3, in
the appendix.
Examples:
Page 167
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
7.8.1 Examples:
Page 168
. .. 4
2
2
5
3 .
7. 8. 2.1
2. Restore sensors.
7.9.1
7.8.3 Testing the operation of a controller resetting by a second
sensor or by another controller is included in test work sheets for air
handling system control operation tests, WS 5B-3, in the appendix.
7.9 Using multiple zone sensors to reset air temperature for heating or
cooling 7.9.2
Test procedure:
Page 169
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
7. 9. 2. Restore sensors.
Page 170
CHAPTER 6 BUILDING AUTOMATION SYSTEMS
2. Reference Standards.
3. EMCS Inspection.
Page 171
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
4. EMCS Testing.
a. EMCS shall be tested in the field to meet functional performance
requirements of the contract specifications.
f. See EXHIBIT 6-B for test procedures and Appendix for test work
sheets
Page 172
CHAPTER 6 BUILDING AUTOMATION SYSTEMS
2. Industry standards.
a. ANSI Standard C-2 (National Electrical Safety Code) states rules for
practical safeguarding of persons during installation, operation, or
maintenance of electric supply and communication lines and their associated
equipment which are used in buildings as a utility. Included, among others,
are electric supply, telephone, data, fire, and police alarm lines and
equipment
3. Inspection procedures.
3.1 Review contract drawings, specifications, and approved submittals
to become familiar with the requirements.
3.2 If existing equipment and systems are interfaced with the new
system and the specifications require the contractor to test and report the
conditions of the existing equipment and systems, be sure these are performed
before starting commissioning process to minimize future possible disputes.
Page 173
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
3.9 Check equipment and wiring for proper grounding. This includes
equipment in the field, central computer equipment, and building facility such
as raised floor and wire troughs. The requirements of equipment grounding are
usually specified in the equipment manufacturer's installation instructions or
in codes listed in Section 2 above and should be shown on installation shop
drawings. The commissioning team should verify actual installation in the
field. Check grounding wire size, installation manner, and insulation
integrity for safety.
3.11 Check for proper separation of high and low voltage wires, and
discrete vs analog wiring if applicable.
Page 174
CHAPTER 6 BUILDING AUTOMATION SYSTEMS
3.25 Similar to pressure sensing devices, all flow sensing devices are
sensitive to their relative position to fluid flow direction. The sensing
plane of these devices should be inspected in relation to pipe and duct flow
direction.
Page 175
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
3.26 Flow sensing devices must have minimum pipe length upstream and
downstream according to contract specifications, manufacturer' recommended
lengths, or other recommended practices (see Chapter 2 BASIC MEASUREMENT).
Page 176
CHAPTER 6 BUILDING AUTOMATION SYSTEMS
localized automatic temperature controls which may also apply to the EMCS are
described in EXHIBIT 5-B, TEST PROCEDURES FOR AIR HANDLING SYSTEMS. Certain
application precautions of measurement and instrumentation are described in
Chapter 2, BASIC MEASUREMENT. •
2. Industry standards.
a. Military Standard MIL-STD-2202 (EMCS Factory Test Procedures) presents
guidelines for factory test requirements of EMCS using tri-service EMCS guide
specifications, before the equipment is shipped to the field for installation.
Micro systems are not included.
Page 177
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
e . above
3. General.
3.1 The size and configuration of EMCS vary considerably for GSA
managed projects according to the size and complexity of the mechanical
systems, the desire of the owner for system operation, and cost
considerations. Therefore, the commissioning team must review the contract
documents before any attempt to proceed with testing of EMCS.
4. Test procedures.
4.1 Verify calibration of sensors, sensor/transmitters, and
sensor/controllers. This includes temperature, humidity, pressure, flow, and
electricity consumption. See Chapter 2, BASIC MEASUREMENT.
4.2.1 Before the test make sure all EMCS equipment are off.
Page 178
CHAPTER 6 BUILDING AUTOMATION SYSTEMS
4.4 After initial bootup, and prior to any further checkout, verify
backup system operations and switchovers including redundant processors,
backup power supplies, battery backed memories, etc. Review manufacturer's
software and functional test procedures which were performed at the
manufacturer's site. (It is important that in the system specification
process a test procedure be requested and that data from that test be
submitted prior to delivery of system.) Verify EMCS command software used by
building operators from operator's console. This may be checked by issuing
commands at the operator's console and observing display, printer output, or
HVAC equipment responses. The following features are usually specified in the
contract specifications and may be verified as outlined.
Page 179
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
4.5 Test EMCS overall performance. These tests verify the overall
accuracy of the EMCS from sensors, signal conditioning, data transmission,
etc., as well as software used for certain calculations.
Page 180
CHAPTER 6 BUILDING AUTOMATION SYSTEMS
Page 181
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
Page 182
CHAPTER 6 BUILDING AUTOMATION SYSTEMS
Page 183
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
8.1
reports. They should be verified for correctness.
Page 184
1.2 CHAPTER 6 BUILDING AUTOMATION SYSTEMS
1.3
4. 6. Note from operator's console the status of selected
1.4
equipment which is specified to be on scheduled start-stop program.
Page 185
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
becomes lower than a predetermined level. There are many versions of demand
limiting. The commissioning team should be familiar with the demand charge
method and the contract specification requirement of demand limiting.
Page 186
CHAPTER 6 BUILDING AUTOMATION SYSTEMS
4.6.5 5.1
4. 6. 4. See WS6B-8 for sample test work sheets.
Page 187
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
Page 188
CHAPTER 6 BUILDING AUTOMATION SYSTEMS
local loop control. Otherwise, the outdoor damper should be closed so energy
is not wasted to heat the outdoor air. Therefore, the space temperature
setting should be altered during the test so it will be higher and lower than
the outdoor temperature during the course of the test. The damper positions
should be verified during the test to comply with the control logic of the
Page 189
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
software program.
Page 190
CHAPTER 6 BUILDING AUTOMATION SYSTEMS
temperatures
Page 191
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
Page 192
CHAPTER 6 BUILDING AUTOMATION SYSTEMS
Page 193
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
Page 194
CHAPTER 7 FIRE SAFETY AIR MOVING SYSTEMS
1. Scope. This chapter provides inspection and testing procedures for fire
safety functions associated with air moving systems including heating,
ventilating, and air conditioning (HVAC) systems. These systems may be with
or without smoke control capabilities, systems specifically dedicated to zone
smoke control, or systems for stairtower pressurization.
2. Reference Documents.
a. ASHRAE Standard 15 - Safety Code for Mechanical Refrigeration.
Page 195
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
n. UL Standard 181 - Standard for Factory -Made Air Ducts and Connectors.
o.
q. UL Standard 555 - Standard for Fire Dampers and Ceiling Dampers.
UL Standard 555S
p. - Standard for Leakage Rated Dampers for Use in
Smoke Control Systems.
3.1 Air Moving systems shall be inspected to verify that the fire
safety requirements of the contract documents pertaining to materials and
installation have been fulfilled. The fire safety features of air moving
systems must be designed and specified in accordance with GSA Order PBS
P5900.2B, Accident and Fire Protection-General. This order requires that air
conditioning systems be in accordance with NFPA 90A with some specific
exceptions
3.2 See EXHIBIT 7 -A for inspection procedures and Appendix for check
lists for HVAC systems with and without zoned smoke control and for stairtower
pressurization systems.
4.2 See EXHIBIT 7-B for testing requirements for zoned smoke control
systems that are either part of an HVAC system or are dedicated for smoke
control only.
Page 196
CHAPTER 7 FIRE SAFETY AIR MOVING SYSTEMS
2 . Reference standards
a. ASHRAE 15 (Safety Code for Mechanical Refrigeration) is intended to
assure the safe design, construction, installation, operation, and inspection
of refrigeration systems. Among other safety features and precautions, this
standard describes requirements of pressure-limiting devices and pressure-
relief protection, including installation requirements of refrigeration piping
and machinery room housing refrigerating equipment.
e. NFPA 54 (ANSI Z223, National Fuel Gas Code) is a safety code which
applies to the installation of fuel gas piping systems, fuel gas utilization
equipment and related accessories. Among the areas this code addresses are
piping design, piping materials, piping components, piping installation,
Page 197
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
Page 198
CHAPTER 7 FIRE SAFETY AIR MOVING SYSTEMS
spring closing force. Fire dampers are rated at 3/4 hr, 1 hr, 1-1/2 hr, and 3
hr. Ceiling dampers are not assigned hourly ratings, but rather are assembly
components designed for use in specific hourly rated resistive assembles. The
standard requires that manufacturers supply installation instructions for
these dampers.
m. UL 555S (Standard for Leakage Rated Dampers for Use in Smoke Control
Systems) is a test method for leakage rated dampers intended for use in
heating, ventilating, and air conditioning systems. The test method includes
construction requirements and tests for cycling, temperature degradation, duct
loading exposure, salt- spray exposure, and air leakage. These smoke dampers
are classified as 0, I, II, III, or IV leakage rated dampers, and they are
tested at 250 'F or at an elevated temperature selected in increments of 100
'F above 250 'F.
Page 199
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
Systems, may pass through one floor to connect ducts with air terminal units
subject to the limitations of NFPA 90A including firestopping around openings.
Flexible duct connectors must not exceed 14 ft in length. CAUTION: Because
the characteristics of duct connectors and flexible duct connectors are
different, one should not be substituted for the other.
3.4 Check duct coverings and linings to verify that their fire safety
requirements are as specified. Coverings and linings must be in accordance
with the requirements of NFPA 90A. Check that duct coverings do not conceal
any service opening.
3.6 Check plenums between ceilings and floors. Check materials exposed
to air flow in these plenums to verify that these materials have smoke
developed ratings not greater than 50 and are non-combustible or limited
combustible except for electrical wiring, electrical equipment, optical fiber
cable and pneumatic tubing. Check that electrical wiring and equipment in
plenums is installed in accordance with NFPA 70, National Electrical Code.
Check that optical fiber cable in plenums conforms to provisions of NFPA 70,
National Electrical Code, or is listed as having adequate fire-resistant and
low smoke producing characteristics. Check that pneumatic tubing for control
systems is listed as having adequate fire-resistant and low smoke producing
characteristics
The following notes are provided for the convenience of the user of this
inspection method, however, in matters of contract compliance or code
requirements the definitions and wording of NFPA 90A apply:
when tested in accordance with ASTM E136, Standard Method of Test for
Noncombustibility of Elementary Materials, are considered non- combustible
materials
Page 200
CHAPTER 7 FIRE SAFETY AIR MOVING SYSTEMS
3.7 Check air filters. Check air filters to verify that they have the
classification required by the contract documents and that they have been
rated in accordance with UL 900, Standard for Test Performance of Fan Filter
Units
3.8 Check that exposed fan inlets are protected with metal screens in
accordance with contract documents to prevent the entry of paper, trash, and
similar foreign material.
Description Standard
Gas fired heating furnaces combined NFPA 54 (ANSI Z223) National Fuel
with cooling units in the same duct Gas Code
Oil fired heating furnaces combined NFPA 31, Standard for the
with cooling units in the same duct Installation of Oil Burning
Equipment
Page 201
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
dampers to verify that they meet the fire protection rating specified by the
contract documents and that the damper has been tested in accordance with UL
555, Standard for Fire Dampers and Ceiling Dampers. Check that fire dampers
have been installed in accordance with the conditions of their listing and the
manufacturer's installation instructions which are supplied with the damper.
Further check installation by removing fusible link (where applicable) and
operating damper to verify that it closes fully. It is desirable to operate
dampers with normal air flow to assure that they are not held open by the air
stream. Remember to reinstall all fusible links that have been removed during
inspection.
Page 202
. .
contract documents and that the damper has been-^tested in accordance with UL
555S, Standard for Leakage Rated Dampers for Use in Smoke Control Systems.
Check that combination fire and smoke dampers have been installed in
accordance with the conditions of their listing and the manufacturer's
installation instructions. Further check installation by removing fusible
link (where applicable) and operating damper to verify that it fully closes.
It is desirable to operate dampers with normal air flow to assure that they
are not held open by the air stream. Remember to reinstall all fusible links
that have been removed during inspection.
Page 203
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
2. General references.
a. ASHRAE manual "Design of Smoke Control Systems for Buildings" by
Klote and Fothergill consolidates and systematically presents data and
calculation procedures necessary to smoke control systems designers and
discusses design criteria. Included are discussions of the driving forces of
smoke movement, the principles of smoke control, calculation of effective flow
areas, concept of symmetry, and design parameters. A computer program for
analysis of smoke control systems is presented. Concepts of stairwell
pressurization and zoned smoke control are presented.
Page 204
.
6.1 Activate smoke control system operation in the zone. This should
be accomplished by putting one of the detectors into alarm that are intended
to activate the smoke control system in that zone.
6.4 Check to verify that all doors required by the contract documents
to be closed during smoke control system operation are fully closed and that
they operate freely allowing use during evacuation without becoming jammed in
their door frames. This should include doors in the boundary of the smoke
zone being tested.
6.5 Measure and record pressure differences across all closed doors in
the boundary of the smoke zone being tested. Pressure differences resulting
from air flowing to the smoke zone being tested are to be recorded as positive
values, and pressure differences resulting from air flowing from the smoke
zone being tested are to be recorded as negative values.
6.7 Test for smoke feedback into supply air. Place six smoke bombs (3
minute duration size) in a metal container, simultaneously ignite all bombs,
and locate container near exhaust inlet in smoke zone being tested so that all
of the chemical smoke produced by the bombs is drawn directly into the exhaust
Page 205
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
air stream. Check that air supplied to other zones of the building has no
trace of chemical smoke. If chemical smoke is detected in this supply air,
its path should be determined, the path should be blocked, and then the smoke
feedback test should be conducted again. (The two most likely causes of smoke
feedback are a leaky or partly opened return air damper and an outside air
inlet located in the vicinity of the exhaust air outlet.)
6.8 Make sure that this zone has been returned to its normal setting
before continuing to test other zones.
7. Duct mounted smoke detector test. Verify that the smoke detector
is properly selected and properly installed to satisfactorily measure any
products of combustion located in the duct. Smoke is drawn through the
detector sampling chamber by the air flow velocity pressure. Since velocity
pressure is a function of the volume of air flowing (cfm) and the area of the
duct, the test team shall confirm that the velocity pressure is within the
range specified by the equipment manufacturer and the contract specifications.
Test the duct mounted smoke detector operation by setting off a smoke bomb in
the air stream ahead of the detector. Confirm that the detector signals the
alarm properly and that the total post-alarm sequence is proper.
Page 206
CHAPTER 7 FIRE SAFETY AIR MOVING SYSTEMS
2. General references.
a. ASHRAE manual "Design of Smoke Control Systems for Buildings" by
Klote and Fothergill consolidates and systematically presents data and
calculational procedures necessary to smoke control systems designers and
discusses design criteria. Included are discussions of the driving forces of
smoke movement, the principles of smoke control, calculation of effective flow
areas, concept of symmetry, and design parameters. A computer program for
analysis of smoke control systems is presented. Concepts of stairwell
pressurization and zoned smoke control are presented.
Page 207
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
"
following steps.
5.1 With all stairwell doors closed (except for the exterior ground
floor door if it is required to be opened upon system activation) measure and
,
5.2 Open the exterior ground floor stairwell door (except if the
exterior ground floor door is required to be opened upon system activation)
and measure and record pressure differences across each closed stairwell door.
For stairwells without a ground floor exterior door, another highly severe
open door condition must be tested. This can be an exterior door not at the
ground floor or a large flow path to the outside created by opening the
stairwell door and other doors including an exterior building door.
5.4 With the required number of doors opened, check flow direction
through open doorways using a 1.83 m (6 ft) strip of tissue paper secured at
the top of the door frame
Page 208
. . .
1. Scope. This part provides inspection and testing procedures for unitary
air conditioning equipment. A unitary air conditioning unit consists of one
or more factory-made assemblies designed to be used as a matched assembly. It
normally has an evaporator, a compressor, a condenser, and may include a
heating section. Included equipment are packaged rooftop units, computer room
air conditioning units, and packaged terminal air conditioners (PTAC) which
are also known as through- the -wall units. Heat pumps are not included in this
chapter
2. Reference standards.
a. ASHRAE Standard 15 - Safety Code for Mechanical Refrigeration.
Page 209
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
Balance
4.2 If the building load at the time of testing does not meet the
system capacity, introduction of false load may be necessary. Tests shall not
cause excessively uncomfortable conditions in the building.
4.3 See EXHIBIT 8-B for test procedures and Appendix for test work
sheets
Page 210
.
2. Industry standards.
a. ASHRAE Standard 15 (Safety Code for Mechanical Refrigeration) is
intended to assure the safe design, construction, installation, operation, and
inspection of refrigeration systems. Among other safety features and
precautions, this Standard describes requirements of pressure - limiting devices
and pressure - relief protection, including installation requirements of
refrigerant piping and machinery room housing refrigerating machine.
Page 211
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
3.3 Check equipment name plates to verify equipment model and serial
number. They must have the same model numbers as approved submittals.
Check for service access spaces around unit for operation and
3.4
maintenance. Manufacturer's recommended spaces must be provided. Pay special
attention to coil and filter replacement and cleaning spaces and access
spaces
3.5 Inspect equipment space for possible fire hazards. The space
should be kept free of combustible material and construction debris.
Page 212
CHAPTER 8 UNITARY AIR CONDITIONING EQUIPMENT
3.7 Check water flow direction marks of -check valves and flow switches.
3.9 All moving parts (motors, belts, etc.) should have protective
shields for personnel safety.
3.11 Observe belt tightness of fans. Use belt tension gage if needed.
Belt tension should be as recommended by belt manufacturer.
3.13 Be sure the system is charged with the right kind of refrigerant.
Check sight glass for proper level.
3.22 For motor starter equipped with overcurrent heaters, check heater
sizes against starter manufacturer's recommendations. The recommendations are
usually contained in operator's manual or posted in starter cabinet.
Page 213
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
3.28 Be sure that temperature and pressure indicators for oil system
are functioning properly to indicate the oil system operation. Oil pressure
must be as recommended by the manufacturer.
3.30 Be sure oil pump is wired separately from circuit feeding to the
compressor if so specified.
3.32 Check oil heating system for proper operation. Electric wiring
should be verified as per manufacturer's submittals or checked to be sure that
crankcase heater power is on even when the main power is off. The crankcase
heater should be installed snugly in its position. It should be on during
compressor off time.
3.33 Check oil level before and during operation. Oil should not be
foaming excessively.
3.34 For units with remote condensers, check refrigerant pipe pitch and
oil traps for proper oil return.
3.35 For air cooled and evaporatively cooled units, spaces for air
circulation is important. Be sure that manufacturer's recommendations are
followed and air is not short circulated from discharge to intake.
3.27 For air cooled condensers equipped with damper controls for low
ambient operation, check damper mechanism for proper adjustment and operation.
Page 214
.
4.2 Check roof curb and unit installation for correct leveling.
4.3 Noise is often a problem for rooftop units. Inspect to make sure
that the unit and ducts are properly installed. Ducts should have flexible
connections and they should not be in contact with roofing structure above
flexible connections. Spaces between ducts or pipes and roofing structure in
duct/pipe sleeves should be sealed.
4.4 Inspection check list CL 8A-1 for rooftop air conditioning units is
included in the Appendix.
5.4 For units equipped with underfloor water detector, fire detector,
and smoke detector, create conditions (presence of water, high temperature,
Page 215
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
5.6 Check that control deadbands and alarm set points can be easily
changed if so specified.
5.7 Inspection check list CL 8A-2 for computer room air conditioning
units is included in the Appendix.
6.2 Inspect around units to be sure that wall sleeves, unit cabinets,
and wall louvers are installed properly for weatherproofing to seal out wind,
rain, snow, and insects.
7. Fan.
7.1 For large units inspect fan housing access door and pressure
latches for tightness. Open and close doors to detect interference of door
with thermal insulation and other equipment.
7.2 Inspect bearing for proper oil or grease application. Grease lines
for bearings should extend to outside of duct connections with grease
fittings. Oiling shall not require dismantling of fans, ducts, or other
components if so specified in contract documents.
7.3 Inspect belt guard for access to oiling, speed counting device, and
other maintenance requirements.
Page 216
CHAPTER 8 UNITARY AIR CONDITIONING EQUIPMENT
7.5 For outlet damper or inlet vane controls inspect control linkage
manually or by manipulating controller for the full range of the stroke. When
a single operator controls inlet vanes of double inlet fans, inlet vanes on
both inlet openings must move in unison. Inspect inlet vane rotation
direction with respect to that of the fan wheel.
7.6 Fans exposed to weather should have protective weather hoods over
motors and drives.
7.7 For fans without duct connections, unless they are housed in
plenums, they must be provided with protective devices for personnel safety
such as wire mesh or expanded metal screens at inlets and outlets.
8.2 Inspect baffles between coils and casing to assure that air is not
bypassing coils.
8.3 Inspect cooling coil drain pans and drain pipes. For large units
with multi-coil assemblies, each coil must have individual pans with drain
pipes to avoid flooding of lower coils. Cooling coil drain traps must be
adequate for the static pressure imposed.
8.5 Inspect steam coils for possible coil freezing problem. Good
condensate draining must be provided: adequate slope of tubes, adequate
pressure head between coils and steam traps (minimum 18 in.), and vacuum
breakers at high position of coils. Adequate sizing of steam traps should be
checked if the requirements are not given in the contract specifications.
8.7 Check temperature of steam traps and condensate piping for possible
steam leaks. They must not be unduly hot.
Page 217
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
9.
"
Air filters.
9.1 Inspect filters for air leakage between filters and holding frames
and between filter assembly and unit casing. Inspect positive sealing devices
for air leakage, if specified.
9.2 For large units with automatic renewable type air filters, inspect
medium advancing and override operation (pressure control, timer setting,
media switch, etc. See specifications for project requirements).
9.3 Inspect filter gage sensing tips and lines for correct static
pressure sensing.
9.4 For inclined manometer type filter gages check for correct
installation levels.
9.6 Make sure adequate access spaces are provided for filter media
10.
replacement
Dampers.
11. 10.1 Verify that the blade arrangement, bearing material and edge
sealing material meet the requirement of the specifications.
10.4 all dampers in ducts must have access doors in accordance with
specifications. Doors must be air tight.
Air louvers.
11.1 Verify material, arrangement, and dimensions.
Page 218
CHAPTER 8 UNITARY AIR CONDITIONING EQUIPMENT
12.
Casings.
12.2 Verify access door sizes, gasket tightness, and latch arrangement.
Thermal insulation.
14. 13.1 Check thermal insulation for damages and omissions.
Controls.
14.1 Most unitary units are selected with factory installed controls
to satisfy the requirements of contract specifications. The commissioning
team should be familiar with the specifications and manufacturer's operating
instructions to verify the control operations.
Page 219
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
2. Industry standards.
a. ASHRAE Standard 37 (Method of Testing for Rating Unitary Air
Conditioning and Heat Pump Equipment) provides standard test methods for
determining the cooling capacity of unitary air- conditioning equipment and
the cooling and/or heating capacities of unitary heat pump equipment. Unitary
equipment is limited to electrically driven mechanical compression types. It
does not include testing method for room air-conditioners.
conditioners
Page 220
.
cooling or heating section, for separate use and may be used for systems with
a total external duct static resistance up to 24.9 Pa (0.1 inch of water).
3. General.
Page 221
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
3.3 One of the important measurements in i^ooftop and computer room air
conditioning unit testing is the measurement of supply air flow rates.
Depending on field duct arrangements of the project, temporary alteration of
ducts to accommodate measurement instruments may be necessary. However,
temporarily altering ductwork may be costly and should be done as a last
resort when the system is not meeting performance. Good practices for
measuring air flow should be followed (see Chapter 2 AND BASIC MEASUREMENT).
However, the duct alteration should not unduly change the unit performance.
3.6 All fans (supply, return, exhaust, transfer) which may influence
the air balance in the area should be operating at their normal conditions.
3.8 All safety devices and provisions have been inspected and tested
already.
3.9 The space temperature and humidity controls should be set at normal
operating conditions.
3.10 Air flow rate measurement of fans and subsystems (if air flow
rates differ from that of the main fan) should be performed before other
tests
3.13 Fan ratings supplied by fan manufacturers and air flow rates of
the design documents are generally in standard air conditions, approximately
dry air at 21.1 °C (70 °F) and 101.3 kPa (29.92 in. of Hg) or 1.20 kg/m 3
,
Page 222
CHAPTER 8 UNITARY AIR CONDITIONING EQUIPMENT
3.14 Check for dampers installed in main ducts that have no function in
balancing air between duct branches, set the blades of these dampers parallel
to the air flow, or have the dampers removed.
3.15 The preferred method of measuring air flow rate is the pitot tube
traverse method. It is extremely important in selecting the location in the
ducts for the pitot measurement. If packaged air flow measuring stations are
specified and installed, they should be used after a preliminary check of its
performance. Use SE-9 to 11 for air velocity measurement and SE-12 for volume
air flow rate.
4. Instrumentation.
4.1 Make sure that all instrumentation is in good working order and is
in calibration. See Chapter 2 AND BASIC MEASUREMENT for calibration of
instruments. Instrumentation calibration work sheet WS 8B-1 is included in
the Appendix.
Temperature.
Page 223
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
4.3.3 Pressure.
Page 224
3
5.1.3 When fans are tested and rated in the laboratories, they
are tested under ideal inlet and outlet conditions as prescribed in the ASHRAE
(and AMCA) standards. In overwhelming cases of actual installations, the site
conditions of ducts (also called system effect factors) alter the fan
performance, sometimes substantially. The fan manufacturers base their
submittals on matching the performance of the laboratory (or allowed
equivalent) results (fan curves or tables) with estimated air friction (the
specified pressure head) Any mismatch between the laboratory performance and
.
5.1.5 Using Pitot tube to traverse the main ducts of the air
conditioning unit is the preferred method. Make sure the air flow at the
location of measurement is steady (after the recommended minimum length of
Page 225
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
straight duct run or after straightening vanes). ^ See EXHIBIT 2-C, STP-5 for
measurement procedures.
5.1.6 For very large units, measuring air flow rates at coil face
or air filter face with anemometer may be used for supply fan measurement, if
good locations for pitot measurement can not be found. See EXHIBIT 2-C, STP-6
for measurement procedures
* Barometric pressure.
Page 226
..
commissioning testing the commissioning team shtmld make sure that the system
stability is achieved by measuring the fan speed. Use a tachometer or
stroboscope (see EXHIBIT 2-A COMMONLY USED FIELD TEST INSTRUMENTS) to measure
the fan speed continuously for at least 3 minutes. The speed variation shall
not exceed 3%.
Page 227
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
specified fan duty point (volume flow rate and pressure ) may be obtained
during test. Repeated adjustment and measurement may be needed.
5.1.11.4
Perform the required measurements listed in 5.1.8
above
5.1.11.9 During the maximum and the minimum air flow rate
manipulation, verify the operation sequence of reheat coils (for units with
reheat coils), recirculating fans (for units with recirculating fans), and
other operational controls as required in the contract specifications.
pressure retested. The selection the these 25% branches should be estimated
and judged by the Team that these branches may encounter extreme (high or low)
pressure during building load changes.
Page 228
. . 2
3
Cooling/heating measurement. --
5. 2. 4.1 For air cooled units measure outside air dry bulb
temperature. If the temperature is not within 1.1 °C (2 °F) of the contract
specified temperature the test shall be postponed unless the temperature is
within 5.6 °C (10 °F) of the contract specified temperature AND manufacturer's
capacity versus ambient temperature data are available for extrapolation.
Page 229
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
Page 230
.
5.2.13.6 For gas heated units, make sure gas heaters are in
operation.
Page 231
{TV AC FUNCTIONAL INSPECTION AND TESTING GUIDE
Test work sheet WS 8B-2 included in the Appendix may be used for
5.5
rooftop and computer room units.
Page 232
. .
6. PTAC tests.
Test procedures described in this guide for PTAC are basically for
6.1
operational tests.
The cooling coil should show condensation if the space dew point is over 10 °C
(50 °F)
6.4 Test work sheet WS 8B-3 included in the Appendix may be used for
PTAC units.
7.1.1 The measured total air flow rate of the unit must not be
less than the specified fan air flow rate. The motor current rate must not be
greater than the full load current shown on the motor mane plate.
Page 233
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
7.2.1 For heating capacities, the entering and the leaving air
humidity are not required to be measured in this guide. The errors of the
enthalpies of air caused by this simplification are not significant if a 50%
RH entering air humidity is assumed. This assumption is justified for the
majority of HVAC
7.2.3 applications.
Calculation procedure.
Pa (in. of Hg) knowing the measured humidity of entering air for cooling coil
,
or the assumed humidity (50% RH) of the heating coil, using SE-2.
Page 234
. , , 8
9 5 ,
(Btu/lb) of air, using SE-4. For cooling coil both the dry bulb temperature
and humidity are as measured. For heating coil assume the leaving air has the
same humidity ratio as the entering air (calculated in step 7. 2. 3. above).
in the calculation.
7.2.4 The tested unit capacity shall not be less than 95% of the
contract specified capacity.
7.2.5 The test air friction of coil shall not be greater than
110% of the contract specified air friction.
Humidifying capacities.
7.3.1 Calculate the average entering air and the average leaving
air dry bulb temperature from measured data.
Page 235
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
7.3.6
Calculate the saturated water 'pressure of the leaving air,
( ^sw) Ivg >
Pa (in. of Hg) ,
knowing the leaving air dry bulb temperature, using
SE-1.
Page 236
APPENDIX
APPENDIX
Al
3 6
APPENDIX
2.1 TEST WORK SHEET WS 2C-1 -- AIR FLOW RATE IN ROUND DUCTS ... A5
2.2 TEST WORK SHEET WS 2C-2 -- AIR FLOW RATE IN RECTANGLE DUCTS . A6
3.1 INSPECTION CHECK LIST CL 3A-1 -- CHILLER • • • A8
3.2 INSPECTION CHECK LIST CL 3B-1 -- HEAT REJECTION EQUIPMENT
(COOLING TOWER, EVAPORATIVE CONDENSER, AND AIR COOLED
CONDENSER) A12
3.3 TEST WORK SHEET WS 3C-1 -- INSTRUMENT CALIBRATION FOR COOLING
PLANT A14
3.4 TEST WORK SHEET WS 3C-2 -- CENTRIFUGAL CHILLER (SAFETY
CONTROL TEST) A16
3.5 TEST WORK SHEET WS 3C-3 -- CENTRIFUGAL CHILLER (AUXILIARY
EQUIPMENT TEST) A17
3.6 TEST WORK SHEET WS 3C-4 -- CENTRIFUGAL CHILLER (FULL LOAD
TEST) A19
3.7 TEST WORK SHEET WS 3C-5 -- CENTRIFUGAL CHILLER (* % PART
LOAD AND CAPACITY CONTROL TEST) A23
3.8 TEST WORK SHEET WS 3C-6 -- CENTRIFUGAL CHILLER ( COOLING
PLANT SYSTEM TEST) A27
3.9 TEST WORK SHEET WS 3D-1 -- RECIPROCATING CHILLER (SAFETY
CONTROL AND GENERAL OPERATIONAL TESTS) A28
3.10 TEST WORK SHEET WS 3D-2 -- RECIPROCATING CHILLER (FULL LOAD
TEST) A31
3.11 TEST WORK SHEET WS 3D- -- RECIPROCATING CHILLER (* %
PART LOAD TEST) A3
3.12 TEST WORK SHEET WS 3E-1 -- ABSORPTION CHILLER (GENERAL
OPERATIONAL TESTS) A40
3.13 TEST WORK SHEET WS 3E-2 -- ABSORPTION CHILLER (FULL OR PART
LOAD TEST) A42
3.14 TEST WORK SHEET WS 3F-1 -- COOLING TOWER A48
3.15 TEST WORK SHEET WS 3F-2 -- REFRIGERANT CONDENSER (AIR COOLED
OR EVAPORATIVELY COOLED) . A51
4.1 INSPECTION CHECK LIST CL 4A-1 -- BOILER A55
4.2 INSPECTION CHECK LIST CL 4A-2 -- FURNACE A61
4.3 TEST WORK SHEET WS 4B-1 -- INSTRUMENT CALIBRATION FOR BOILER
AND FURNACE A63
4.4 TEST WORK SHEET WS 4B-2 -- GAS AND OIL FIRED BOILER A65
4.5 TEST WORK SHEET WS 4B-3 -- ELECTRIC BOILER A75
4.6 TEST WORK SHEET WS 4C-1 -- GAS AND OIL FIRED AIR FURNACE . . . A79
4.7 TEST WORK SHEET WS 4C-2 -- ELECTRIC AIR FURNACE A81
5.1 INSPECTION CHECK LIST WS 5A-1 -- AIR HANDLING UNIT A83
5.2 TEST WORK SHEET WS 5B-1 -- INSTRUMENT CALIBRATION FOR AIR
HANDLING SYSTEMS A89
5.3 TEST WORK SHEET WS 5B-2 -- AIR HANDLING SYSTEM (COMPONENT
TEST),
FAN A91
A3
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
A4
:
APPENDIX
2.1 TEST WORK SHEET WS 2C-1 -- AIR FLOW RATE IN ROUND DUCTS
Air handling system no. Date
Duct designation no, Test agent
Size
Specified flow rate* cfm Commissioning team
Duct location
No. Steps
Vertical diameter:
Ring 1 "w.c. fpm
Ring 2 "w.c. fpm
Ring 3 "w.c. fpm
Ring 4 "w.c. fpm
Ring 5 "w.c. fpm
Ring 5 "w.c. fpm
Ring 4 "w.c. fpm
Ring 3 "w.c. fpm
Ring 2 "w.c. fpm
Ring 1 "w.c. fpm
COMMENTS
A5
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
2.2 TEST WORK SHEET WS 2C-2 — AIR FLOW "RATE IN RECTANGLE DUCTS
Page 1
No. Steps
COMMENTS
A6
: ...
APPENDIX
TEST WORK SHEET WS 2C-2 -- AIR FLOW RATE IN REGTANGLE DUCTS (continued)
Page 2
No. Steps
COMMENTS
A7
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
COMMENTS
A8
:
APPENDIX
COMMENTS
A9
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
COMMENTS
A10
:
APPENDIX
COMMENTS
All
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
General
COMMENTS
A12
: .
APPENDIX
Equipment no Date
COMMENTS
A13
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
Temperature
Humidity
Pressure
Power
Others
Temperature, F:
1 Water (for chilled, 32 200 1
condenser, steam
condensate, and hot)
2 Low pressure steam 200 300 2
3 Hot water for 200 300 3
absorption machine
4 Refrigerant for 100 200 4
remote condenser
A14
.. ::
APPENDIX
Air humidity:
5 Wet bulb temp, F 35//1 75#1 5
Flow:
7 Flow sensing devices #3 #4 7
for water, steam, and refrigerant, gpm
a
b.
c ._
8 Pressure sensing devices, see Below 8
Pressure
9 Water static #5 #6 9
pressure, ft w.c. or psi
a
b.
c
10 Refrigerant static #7 #8 10
pressure, psi
a.
b.
c
11 Water pressure for 0 20 11
velocity sensing, in. w.c.
Other devices:
a
b.
A15
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
A16
: ,
APPENDIX
OIL SYSTEM:
7 Check oil level 7
8 Turn on oil pump 8
9 Check oil sump temp (* F) 9
Actual temp ( F)
10 Check oil temp at bearing (* F) 10
Actual temp ( F)
11 Check oil press at bearing (* psi) 11
Actual pressure ( psi)
PURGE SYSTEM:
12 Turn purge system to manual control 12
13 Test by following mfg recommendations 13
COMMENTS
A17
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
PUMPOUT SYSTEM:
Test by following mfg recommendations 14
If reciprocating compressor is provided:
14a Turn pumpout system condenser water 14a
valves on
14b Run pumpout compressor for 1/2 hour 14b
14c Record and compare running conditions 14c
with recommendations:
Discharge pressure (* psi/ psi)
Suction pressure (* psi/ psi)
Oil pressure (* psi/ psi)
Ent water temp (* F/ F)
Lvg water temp (* F/ F)
COMMENTS
A18
APPENDIX
A19
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
TEST WORK SHEET WS 3C-4 -- CENTRIFUGAL CHILLER (FULL LOAD TEST) - (continued)
Page 2
1 2 3
9a Chilled water: 9a
Lvg ch w temp ( ,
F) ,
Ent ch w temp ( ,
F) or ,
Ch w temp diff ( F)
Ch w flow rate ( gpm)
,
9b Condenser water: 9b
Lvg cond w temp ( F)
Ent cond w temp ( F) or
Cond w temp diff ( F) , ,
1 2 3
11a Chilled water: 11a
Lvg ch w temp ( F)
Ent ch w temp ( F) or
Ch w temp diff ( F)
Ch w flow rate ( , ,
gpm)
Ent ch w press ( psi)
Lvg ch w press ( psi)
Evaporator lvg refrigerant
temperature ( F)
lib Condenser water: lib
Lvg cond w temp ( F)
Ent cond w temp ( F) or
Cond w temp diff ( F)
Cond w flow rate ( gpm)
Ent condw press ( psi)
Lvg cond w press ( psi)
Cond lvg refrigerant
temperature ( , , F)
11c Electricity: 11c
Wattmeter output ( Watt)
12 No unusual noise during test 12
A20
:
APPENDIX
TEST WORK SHEET WS 3C-4 -- CENTRIFUGAL CHILLER -/FULL LOAD TEST) - (continued)
Page 3
Test capacity
(CAP) t = (ch w temp diff) x (ch w flow rate) x 500 Btu/h
cooling tons
24
COMMENTS
A21
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
TEST WORK SHEET WS 3C-4 -- CENTRIFUGAL CHILLER (FULL LOAD TEST) continued
Page 4
kW/ton
Specified energy performance kW/ton
COMMENTS
A22
: :
APPENDIX
A23
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
1 2 3
i Chilled water: 5a
Lvg ch w temp ( ,
F)
Ch w temp diff ( ,
F) or
Ent ch w temp ( ,
F)
Ch w flow rate ( RPm)
1 2 3
> Condenser water: 5b
Ent cond w temp ( F)
,
1 2 3
l Chilled water: 7a
Lvg ch w temp ( F)
Ent ch w temp ( ,
F) or ,
Ch w temp diff ( F)
,
i Condenser water: 7b
Lvg cond w temp ( F)
Ent cond w temp ( F) or
Cond w temp diff ( F)
Cond w flow rate ( RPm), ,
: Electricity: 7c
Wattmeter output ( Watt)
, ,
COMMENTS
A24
: )
APPENDIX
COMMENTS
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
TEST WORK SHEET WS 3C-5 -- CENTRIFUGAL CHILLER (* % PART LOAD AND CAPACITY
CONTROL TEST) continued Page 4
Test capacity
(CAP) t - (ch w temp diff) x (ch w flow rate) x 500 Btu/h
(E) t
Test energy performance = kW/ton
(CAP) t in tons
kw/ton
COMMENTS
A26
: ,
APPENDIX
COMMENTS
A27
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
A28
: :
APPENDIX
TEST WORK SHEET WS 3D-1 -- RECIPROCATING CHILLER (SAFETY CONTROL AND GENERAL
OPERATIONAL TESTS) continued Pa S e 2
COMMENTS
A29
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
TEST WORK SHEET WS 3D-1 -- RECIPROCATING CHILLER "( SAFETY CONTROL AND GENERAL
OPERATIONAL TESTS) continued Page 3
COMMENTS
A30
:
APPENDIX
COMMENTS
A31
:
TEST WORK SHEET WS 3D-2 -- RECIPROCATING CHILLER FULL LOAD TEST) continued
Page 2
7a Chilled water:
12 3
7a
Lvg ch w temp (_ ,
F)
Ch w temp diff ( F) or
Ent ch w temp ( F)
Ch w flow rate ( , ,
gpm)
7b For water cooled condenser: 7b
Ent cond w temp ( F)
Cond w temp diff ( F) or
Lvg cond w temp ( F)
Cond w flow rate ( gpm)
7c For air or evap cooled condenser: 7c
Saturated discharge pressure
( psi)
Saturated discharge temperature
( F)
8 Repeat step 7 if necessary until 8
differences between 3 readings are less
than the limits.
COMMENTS
A32
:
APPENDIX
TEST WORK SHEET WS 3D- 2 -- RECIPROCATING CHILLER, (FULL LOAD TEST) continued
Page 3
9a Chilled water:
12 3
9a
Lvg ch w temp ( 9 y
F)
Ch w temp diff ( y y
F) or
Ent ch w temp ( y y
F)
Ch w flow rate ( y y KPm)
Ent ch w press ( 9 y
psi)
Lvg ch w press ( y y
psi)
9b Electricity: 9b
Wattmeter output ( , ,
Watt)
9c Water cooled condenser: 9c
Ent cond w temp ( y y
F)
Cond w temp diff ( y y
F) or
Lvr cond w temp ( y y
F)
Cond w flow rate ( y y gP m )
Ent cond w press ( y y
psi)
Lvg cond w press ( y y
psi)
COMMENTS
A33
: : .
TEST WORK SHEET WS 3D- 2 -- RECIPROCATING CHILLER ^ FULL LOAD TEST) continued
Page 4
Test capacity
(CAP) t = (ch w temp diff) x (ch w flow rate) x 500 Btu/h
cooling tons
24
COMMENTS
A34
:
APPENDIX
TEST WORK SHEET WS 3D-2 -- RECIPROCATING CHILLER (FULL LOAD TEST) continued
Page 5
(E) t
Test energy performance = kW/ton
(CAP) t in tons
kW/ton
COMMENTS
:
COMMENTS
A36
. : 3
APPENDIX
Chiller no Date
3a Lvr ch w temp (
12 3
F) 3a
Ch w temp diff ( ,
F) or
Ent ch w temp ( F)
Ch w flow rate ( gpm)
3b Water cooled Condenser: 3b
Ent cond w temp ( , ,
F)
Cond w temp diff ( F) or
Lve cond w temp ( F)
Cond w flow rate ( gpm)
5a Chilled water:
12 3
5a
Lvg ch w temp ( , ,
F)
Ch w temp diff ( , ,
F) or
Ent ch w temp ( , ,
F)
Ch w flow rate ( , ,
gpm)
COMMENTS
: :
5b Electricity: 5b
Wattmeter output ( , ,
Watt)
5c Water cooled condenser: 5c
Ent cond w temp ( , ,
F)
Cond w temp diff ( , ,
F) or
Lvg cond w temp ( , ,
F)
Cond w flow rate ( gP m )
5d Air or evap cooled condenser: 5d
Saturated discharge temperature
( psi)
Saturated discharge temperature
( F)
Ambient air dry bulb temperature
( F)
Ambient air wet bulb temperature
( F)
6 Calculate average test data 6
6a Chilled water: 6a
Lvg ch w temp ( F)
Ch w temp diff ( F) or
Ent ch w temp ( F)
Ch w flow rate ( gpm)
6b Electricity: 6b
Wattmeter output ( Watt)
6c Water cooled condenser l 6c
Ent cond w temp ( F)
Cond w temp diff ( F) or
Lvg cond w temp ( F)
Cond w flow rate ( gpm)
6d Air or evap cooled condenser: 6d
Saturated discharge temp ( F)
Ambient air dry bulb temp ( F)
Ambient air wet bulb temp ( _F)
COMMENTS
A38
: ) ) .
APPENDIX
8a Calculations: 8a
Test capacity
(CAP) t = (ch w temp diff) x (ch w flow rate) x 500 Btu/h
cooling tons
24
(E) t
Test energy performance = kW/ton
(CAP) t in tons
kW/ton
8b Acceptance criteria: 8b
COMMENTS
:
COMMENTS
A40
:
APPENDIX
COMMENTS
A41
: ,
Chiller no .
Date
Make & model_ Test agent
Serial no. Commissioning team
Energy source: Steam psi
Hot water F
Load: Full load % part load
,
A42
: : : .
APPENDIX
TEST WORK SHEET WS 3E-2 -- ABSORPTION CHILLER (-PULL OR PART LOAD TEST)
continued
Page 2
Specified values:
Lvg ch w temp (* F)
Ent ch w temp (* F)
Ch w flow rate (* gpm)
Ent cond w temp (* F)
Lvg cond w temp (* F)
Cond w flow rate (* gpm)
Ent hot w temp (* F)
Lvg hot w temp (* F)
Steam pressure (* psi)
8a Chilled water:
12 3
8a
Lvg ch w temp ( , ,
F)
Ent ch w temp (_ , ,
F) or
Ch w temp diff ( , ,
F)
Ch w flow rate ( , ,
gpm)
8b Condenser water: 8b
Lvg cond w temp ( , ,
F)
Ent cond w temp ( , ,
F) or
Cond w temp diff ( F)
Cond w flow rate ( , ,
gpm)
Hot water: 8c
Lvg hot w temp ( F)
Ent hot w temp ( ,
F) or
Hot w temp diff ( ,
F)
Steam 8d
Steam pressure ( ,
psi)
COMMENTS
A43
: :
TEST WORK SHEET WS 3E-2 -- ABSORPTION CHILLER (FULL OR PART LOAD TEST)
continued
Page 3
A44
:
APPENDIX
TEST WORK SHEET WS 3E- 2 -- ABSORPTION CHILLER (-EULL OR PART LOAD TEST)
continued
Page 4
Chiller no. Date
Steam temperature( ,
F) ,
Condensate temp ( ,
F) ,
COMMENTS
A45
: :
TEST WORK SHEET WS 3E-2 -- ABSORPTION CHILLER (FULL OR PART LOAD TEST)
continued
Page 5
Chiller no. Date
Test capacity
(CAP) t -= (ch w temp diff) x (ch w flow rate) x 500 Btu/h
cooling tons
24
- (
- 32)] x Btu/h
COMMENTS
A46
: ) ) . .
APPENDIX
TEST WORK SHEET WS 3E-2 -- ABSORPTION CHILLER (-FULL OR PART LOAD TEST)
continued
Page 6
Chiller no. Date
COP of chiller:
(CAP) t
Test performance (COP) t =
(Qin)t
A47
:
COMMENTS
A48
.
:
APPENDIX
Tower no Date
Test tower load = (water temp diff) x (water flow rate) x 500 Btu/h
Set 1 - X X 500 Btu/h
Set 2 - X X 500 = Btu/h
Set 3 - X X 500 = Btu/h
Set 4 - X X 500 = Btu/h
Set 5 = X X 500 = Btu/h
Set 6 = X X 500 = Btu/h
The difference of maximum and
minimum calculated tower load
not to exceed 5% of minimum.
(max - min) = - =
5% x min = 5% x
Repeat test if limit is exceeded.
COMMENTS
A49
:
COMMENTS
A50
:
APPENDIX
A51
:
4 5 6
Ref inlet temp ( ,
F)
ref inlet press ( ,
F),
Air DB temp if ( ,
F) or
,
Wattmeter ififif ( ,
W),
COMMENTS
A52
:
APPENDIX
x = Btu/h
COMMENTS
A53
:
15 Acceptance criteria: 15
15a Air cooled condenser: 15a
Qts > Qs
15b Evapratively cooled condenser: 15b
Qt > Q s
COMMENTS
A54
:
APPENDIX
COMMENTS
A55
:
COMMENTS
A56
:
APPENDIX
A57
:
COMMENTS
APPENDIX
correctly
3 Test actual operation:
3a Set burner in low fire 3
A59
: :
COMMENTS
A60
: .
APPENDIX
COMMENTS
A61
:
COMMENTS
A62
:
APPENDIX
Date
Test agent
Commissioning team
Temperature
Humidity
Pressure
Power
Flow rate
Gas concentration
Others
Temperature, F:
1 Water (for feed 32 200 1
water, condensate,
and hot water)
A63
: : .. ::
TEST WORK SHEET WS 8B-1 -- INSTRUMENT CALIBRATION' FOR BOILER AND FURNACE
continued Page 2
Date
Humidity:
2 Relative humidity, % 30#1 90//1 2
3 Dew point temp, F 35 75 3
4 Wet bulb temp, F 3 5# 2 75#2 4
5 Low pressure steam 200 300 5
6 Air 32 150 6
7 Flue 300 2000 7
Flow
8 Water and steam, gpm #3 #4 8
a
b.
c
9 Fuel (gas/oil) #5 9
Pressure
10 Gas, in. w.c. 0 20 10
11 Steam, psia 0 50 11
(for low pressure steam)
Flue gas concentration
12 C02 % ,
0 20 12
13 02, % 0 20 13
14 CO, % 0 3 14
Other devices:
a
b.
c
Notes
#1 Within a dry bulb range of 10 - 100 F
#2 Within a dry bulb range of 35 - 100 F
#3 25% below specified values
#4 25% above specified values
#5 Check against a calibrated flow instrument
Comments
A64
:
APPENDIX
4.4 TEST WORK SHEET WS 4B-2 -- GAS AND -OIL FIRED BOILER
Page 1
COMMENTS
A65
:
TEST WORK SHEET WS 4B-2 -- GAS AND OIL FIRED BOILER continued
Page 2
Boiler no .
Date
Flue temp
12 3
F
,
C0 2 or 0 2 level
12 3
%
,
COMMENTS
A66
:
APPENDIX
TEST WORK SHEET WS 4B-2 -- GAS AND OIL FIRED BOILER continued
Page 3
TEST WORK SHEET WS 4B-2 -- GAS AND OIL FIRED BOILER continued
Page 4
Boiler no. Date
C0 2 or 0 2 level
12 3
%
,
For H W boiler:
COMMENTS
A68
:
APPENDIX
TEST WORK SHEET WS 4B-2 -- GAS AND OIL FIRED BOTLER continued
Page 5
capacity
3a Set capacity to approx. 75% and on 3a
manual control; adjust building
load to match boiler capacity
Flue temp
12 3
COMMENTS :
A69
: .
TEST WORK SHEET WS 4B-2 -- GAS AND OIL FIRED BOILER continued
Page 6
C0 2 or 0 2 level
12 ,
3
%
,
COMMENTS
A70
: .
APPENDIX
TEST WORK SHEET WS 4B-2 -- GAS AND OIL FIRED BOILER continued
Page 7
Boiler no .
Date
Flue temp
12 3
F
,
meter reading
ft 3 /h or gph
time
COMMENTS
A71
:
TEST WORK SHEET WS 4B-2 -- GAS AND OIL FIRED BOILER continued
Page 8
For H W boiler:
ent water temp , ,
F
lvg water temp ,
F or
water temp diff , ,
F
water flow rate , ,
gpm
location of flow measurement:
(check one) ent lvg ,
A72
:
APPENDIX
TEST WORK SHEET WS 4B-2 -- GAS AND OIL FIRED BO-ILER continued
Page 9
Boiler no .
Date
COMMENTS
A73
:
TEST WORK SHEET WS 4B-2 -- GAS AND OIL FIRED BOILER continued
Page 10
Boiler no. Date
(q)out
eff - x 100 - x 100 - %
(q)in
6. Acceptance criteria: 6
Capacity: (CAP) t > (CAP) S
Combustion efficiency at part load:
at 25% capacity not less than * %
at 50% capacity not less than * %
at 75% capacity not less than * %
Thermal efficiency at full load no less than * %
COMMENTS
A74
: ,
APPENDIX
COMMENTS
A75
: t
For H W boiler:
ent water temp , ,
F
lvg water temp ,
F or
water temp diff ,
F
water flow rate , ,
gpm
location of flow measurement:
(check one) ent lvg ,
COMMENTS
:
APPENDIX
(
kwh) -
(
kwh)
= x 3413 = Btu/h
( h) - ( h)
COMMENTS
A77
: q .
( ) out _
eff - x 100 -- x 100 - ___ %
<q)in
3. Acceptance criteria: 3
COMMENTS
A78
APPENDIX
4.6 TEST WORK SHEET WS 4C-1 — GAS AND— OIL FIRED AIR FURNACE
Page 1
C0 2 or 0 2 level
12 %
3
, ,
A79
:
TEST WORK SHEET WS 4C-1 -- GAS AND OIL FIRED AIR-FURNACE continued
Page 2
combustion efficiency = __ %
4 Acceptance criteria: 4
Capacity: (CAP) t > (CAP) S
Combustion efficiency at full
load not less than * %
COMMENTS
A80
APPENDIX
1. Follow the steps outlined in the form and place check marks or
fill data as required. Initial under "pass" or "fail" colums
supply remarks if necessary.
2. and subscript "s" denote data required from specification,
drawings, manufacturer's manuals or by calculations. Copy in blanks.
COMMENTS
:
x ( ) - Btu/h
combustion efficiency = 1
5 Acceptance criteria: 5
Capacity: (CAP) t > (CAP) S
Combustion efficiency at full
load not less than * %
COMMENTS
A82
APPENDIX
General
1 Operation and maintenance manuals complete 1
2 General appearances,
no apparent damage 2
3 Verify unit model with submittals 3
4 Tube pulling space adequate 4
5 Air filter replacement space adequate 5
6 Other access space adequate (headroom, 6
access doors, etc)
7 Equipement room cleaned, no fire hazards 7
8 Equipment room ventilation opening proper 8
9 Ventilation opening automatic damper 9
10 Proper vibration unit installation 10
11 Pipe fittings and accessories complete 11
12 Check valves and flow switches flow 12
direction correct
13 Pipes supported properly 13
14 Protection shields for motor and belts 14
15 Alignment of motor driven components 15
16 Belt tightness 16
17 Lubrication complete and proper 17
18 Thermometers complete 18
19 Pressure gages complete 19
20 Flow meters meet installation requirements 20
21 Electric wiring installation proper 21
22 Elec motors & components grounded properly 22
23 All electric connections tight 23
24 Size of overcurrent heater in motor starter 24
25 Test run motors for direction of rotation 25
26 Thermal insulation complete and no damage 26
27 Surface paint complete, equipment labels 27
complete and legible
COMMENTS
A83
. :
ACU no Date
Fan:
Housing access doors and latchs tight
1 1
Assembly bolts tight (field assembled fan)
2 2
COMMENTS
A84
APPENDIX
Coils
1 No damage to heat transfer fins 1
la Preheat coil la
lb Main heating coil
lc Precooling coil lc
Id Main cooling coil Id
le Reheat coil le
2 Coil tubes pitch correctly 2
2a Preheat coil 2a
2b Main heating coil 2b
2c Precooling coil 2c
2d Main cooling coil 2d
2e Reheat coil 2e
3 No air bypass between coil and casing 3
3a Preheat coil 3a
3b Main heating coil 3b
3c Precooling coil 3c
3d Main cooling coil 3d
3e Reheat coil 3e
4 Cooilin coil drain pans and pipes 4
5 Coil pipe fittings and accessories 5
5a Shut-off valves 5a
5b Strainers 5b
5c Air vents 5c
5d Thermometer wells 5d
5e Balancing devices 5e
5f Drain 5f
5g Others 5g
6 Flow measuring device 6
6a Upstream pipe length or flow straightener 6a
6b Downstream pipe length 6b
6c Meter connection and valves complete 6c
6d Tag with flow rate information 6d
7 Condensate pipe at steam trap - check that 7
steam trap is not passing steam when
control valve is open
(for low pressure steam only)
COMMENTS :
A85
: .
Air filters:
1 Filter frame anchored to casing securely 1
2 No air leakage around filter frame 2
3 No air leakage between filter bank 3
and unit casing
4 New filter media 4
5 Filter gage pressure sensing tip proper 5
6 Inclined manometer gage installation 6
7 Check auto renewable filter advancing 7
mechanism
7a Motor 7a
7b Drivingtrain 7b
7c Timer 7c
7d Pressure sensing 7d
7e Overriding operation 7e
8 Filter replacement spece adequate 8
9 Spare filters 9
Air dampers:
1 Blade arrangement: parallel 1
opposed
2 Blade edge sealing 2
3 Bearings as specified 3
4 Actuator linkage and blade movement 4
5 Access door for dampers in duct 5
Air louvers:
1 Material 1
2 Construction 2
3 Dimensions 3
4 Screen 4
COMMENTS
A86
APPENDIX
Casings
1 Rigidity 1
2 Integraty 2
3 Access doors: 3
3a Size 3a
3b Gasket 3b
3c latches 3c
4 Flexible connections between unit 4
and ducts
5 Outdoor unit roof curb flashing 5
Thermal insulation:
1 No damages and omissions 1
2 Material 2
3 Thickness 3
4 Method of application 4
5 Vapor barrier material and sealing 5
6 Surface finishing 6
COMMENTS
A87
: j
AHU no . Date
Automatic controls:
1 Give general check on control installations 1
against contract documemts and submittals,
control diagrams complete, framed and mounted
2 Observe general operation. Any obvious 2
malfunction, incorrect calibrations, or
incorrct settings and ranges? Hunting observed?
3 Are mercury switches leveled correctly? 3
4 Check valves for correct closing 4
5 Valves and linkages installed securely 5
6 Valve linkages travel freely 6
7 Check dampers for correct closing 7
8 Dampers and linkages installed securely 8
9 Damper linkages travel freely 9
10 Safety features (coil freeze trotection, 10
etc.) installed correctly
11 Interlocking installed correctly 11
12 For pneumatic systems: 12
12a Compressor intake filter clean 12a
12b Compressor discharge filter clean 12b
12c Compressor motor alignment 12c
12d Compressor belt tightness 12d
12e Belt protective shield 12e
12f Compressor oil level 12f
12g Compressor oil filter clean 12g
12h Air tank drain 12h
12i Air pressure at air tank 12i
12 j Air pressure after pressure 12
reducing valves
12k Air tubing connections tight 12k
121 Air pressure gages
13 For electrcal and electronic systems: 13
13a Wire connections tight 13a
13b No broken wires 13b
13c No rust on wire terminals 13c
13d Correct voltage of power supply 13d
13e Signal wires shielded correctly 13e
14 Control panels: wires and tubes labeled,
settings marked, notes attached
COMMENTS
A88
APPENDIX
Date
Test agent
Commissioning team
Temperature
Humidity
Pressure
Power
Others
Temperature, F:
1 Water (for chilled, 32 200 1
condenser, steam
condensate, and hot)
2 Low pressure steam 200 300 2
3 Air 32 150 3
A89
: .. ::
TEST WORK SHEET WS 5B-1 -- INSTRUMENT CALIBRATION- FOR AIR HANDLING SYSTEMS
continued Page 2
Date
Flow:
7 Water and steam, gpm #3 #4 7
a.
b.
c
Pressure
Water, ft w.c. or psi 0 //6 9
10 Air, in. w.c. 0 #7 10
Other devices:
a
b.
c
Notes
n Within a dry bulb temperature range of 10 - 100 F
#2 Within a dry bulb temperature range of 35 - 100 F
#3 25% below specified values
y/4 25% above specified values
#5 This is for velocity type instrumsnts, see pressure calibration
for pressure sensing devices (pitot)
#6 Expected highest pressure
#7 Expected highest pressure or 5 in. w.c. whicherever is higher
Comments
A90
APPENDIX
COMMENTS
A91
: : . .
TEST WORK SHEET WS 5B-2 -- AIR HANDLING SYSTEM (COMPONENT TEST), FAN continued
Page 2
7a Room ,
measured cfm (* cfm) 7a
Room ,
measured cfm (* cfm)
Room ,
measured cfm (* cfm)
Room ,
measured cfm (* cfm)
Room ,
measured cfm (* cfm)
7b Calculate error 7b
(1 - measured/specified supply) x 100%
Room ,
Error = %
Room ,
Error = %
Room ,
Error = %
Room ,
Error = %
Room ,
Error *= %
COMMENTS
A92
APPENDIX
TEST WORK SHEET WS 5B-2 -- AIR HANDLING SYSTEM ^COMPONENT TEST), FAN continued
Page 3
7d Room measured
,
cfm (* cfm) 7d
Room measured
,
cfm (* cfm)
Room measured
,
cfm (* cfm)
Room measured
,
cfm (* cfm)
Room measured
,
cfm (* cfm)
7e Calculate error 7e
(1 - measured/specified supply) x 100%
Room Error =
,
%
Room Error =
,
%
Room Error =
,
%
Room Error =
,
%
Room Error =
,
%
9 Total air flow rate of measured outlets cfm (7a & 7d) 9
11 Calculate error 11
(1 - measured/specified supply) x 100% = %
COMMENTS
A93
:
TEST WORK SHEET WS 5B-2 -- AIR HANDLING SYSTEM ( 6OMP0NENT TEST), FAN continued
Page 4
20a Room ,
measured cfm (* cfm) 20a
Room ,
measured cfm (* cfm)
Room ,
measured cfm (* cfm)
Room ,
measured cfm (* cfm)
Room ,
measured cfm (* cfm)
COMMENTS
A94
APPENDIX
TEST WORK SHEET WS 5B-2 -- AIR HANDLING SYSTEM -(.COMPONENT TEST), FAN continued
Page 5
22 Total air flow rate of measured outlets cfm (7a & 7d) 22
24 Calculate error 24
(1 - measured/specified supply) x 100% = %
COMMENTS
A95
:
TEST WORK SHEET WS 5B-2 -- AIR HANDLING SYSTEM (COMPONENT TEST), FAN continued
Page 6
AH (or fan) no .
Date
COMMENTS
A96
APPENDIX
TEST WORK SHEET WS 5B-2 -- AIR HANDLING SYSTEM -(-COMPONENT TEST), FAN continued
Page 7
6c Calculate error: 6c
(1 - measured/specified supply) x 100%
Box # ,
Error = % (max) Error = % (min)
Box # ,
Error = % (max) Error = % (min)
Box # ,
Error - % (max) Error = % (min)
Box # ,
Error *= % (max) Error - % (min)
Box # ,
Error = % (max) Error = % (min)
Calculate error: 7c
(1 - measured/specified supply) x 100%
Box # Error =
, % ( max ) Error = %(min)
Box # Error =
, % (max) Error = %(min)
Box # Error =
, % (max) Error = %(min)
Box # Error =
, % (max) Error = %(min)
Box # Error =
, % (max) Error =
;
%(min)
COMMENTS
:
TEST WORK SHEET WS 5B-2 -- AIR HANDLING SYSTEM (COMPONENT TEST), FAN continued
Page 8
13 Calculate error: 13
(1 - measured/specified supply) x 100% - % (max)
(1 - measured/specified supply) x 100% = % (min)
COMMENTS
A98
APPENDIX
TEST WORK SHEET WS 5B-2 -- AIR HANDLING SYSTEM ^COMPONENT TEST), FAN continued
Page 9
COMMENTS
A99
:
TEST WORK SHEET WS 5B-2 -- AIR HANDLING SYSTEM (COMPONENT TEST), HEATING COIL
continued Page 10
AH no .
Date
Preheat coil no. Inspection agent
Heating coil:
1 Measure coil air flow rate, see 1
Test Work Sheet WS 2C-2 cfm
2 Measure entering air temp 2
apply false load if needed
(* F)
average temp F
3 Measure & adjust ent w temp to within 3
1 F of specified (water coil)
(* F) F
4 Measure & adjust steam temp & 4
pressure (steam coil) to
within 1 psi of specified
(* psi) psi _____ F
Is steam saturated?
5 Measure and adjust water or steam 5
flow rate to within 3% of specified
6 Disable control of test coil 6
7 Run unit for at least 10 minutes 7
8 Test for steady state at 5 minute 8
intervals: (max diff 2 F)
average lvg air temp:
A100
APPENDIX
TEST WORK SHEET WS 5B-2 -- AIR HANDLING SYSTEM ^COMPONENT TEST), HEATING COIL
continued Page 11
AH no. Date
Preheat coil no.
Reheat coil no.
P w = RH x P sw
COMMENTS
:
TEST WORK SHEET WS 5B-2 -- AIR HANDLING SYSTEM (COMPONENT TEST), HEATING COIL
continued Page 12
AH no. Date
Preheat coil no.
Reheat coil no.
W 0.622 x
0.754 x (_ + 460)
- ---- -
(1 + 1.6078 x W) - cu ft/lb
Pb
COMMENTS
A102
APPENDIX
TEST WORK SHEET WS 5B-2 -- AIR HANDLING SYSTEM ^(COMPONENT TEST), HEATING COIL
continued Page 13
AH no. Date
Preheat coil no.
Reheat coil no.
cfm cfm
M «= lb/min
v
llg Coil heating capacity, C: llg
C = 60 M x [
( H ) lvg - (H) ent ]
-= 60 x x ( - ) = Btu/h
( + + )/3 = Btu/h
P = ( P) ent - (P)lvg = - = ft w c - -
14 Acceptance criteria: 14
COMMENTS
A103
: .
TEST WORK SHEET WS 5B-2 -- AIR HANDLING SYSTEM (COMPONENT TEST), COOLING COIL
continued Page 14
AH no. Date
Precooling coil no. Inspection agent
Water coil:
1 Measure coil air flow rate, see 1
Test Work Sheet WS 2C-2 cfm
2 Measure entering air temp & 2
humidity; apply false load if needed
(* F, * % RH)
average temp F, % RH
3 Measure & adjust ent w temp to within 3
1 F of specified (water coil)
(*_ F) F
4 Measure and adjust water flow rate 4
to within 3% of specified
5 Disable control of test coil 5
6 Run unit for at least 10 minutes 6
7 Test for steady state at 5 minute 7
intervals: (max diff 2 F)
Average lvg air temp:
COMMENTS
A104
APPENDIX
TEST WORK SHEET WS 5B-2 -- AIR HANDLING SYSTEM -(-COMPONENT TEST), COOLING COIL
continued Page 15
AH no. Date
Precooling coil no.
Cooling coil no.
air temp
Ent
12
F , ,
3
Lvg
air temp F , ,
air humidity
Ent % , ,
air humidity
Lvg % , ,
w pressure
Ent ft w.c. (coil or condenser)
, ,
w pressure
Lvg ft w.c. (coil or condenser)
, ,
(Psw)ent - e<
15 -“ 38 - V™' + 392 ” = in. Hg
(Pswhvg = e
(15 * 638 - t 7284/ + 392 » = in. Hg
COMMENTS
A105
:
TEST WORK SHEET WS 5B-2 -- AIR HANDLING SYSTEM (COMPONENT TEST), COOLING COIL
continued Page 16
AH no. Date
Precooling coil no.
Cooling coil no. _____
P w - RH x P sw
Pw
W - 0.622 x
Pb ‘ Pw
COMMENTS
A106
APPENDIX
TEST WORK SHEET WS 5B-2 -- AIR HANDLING SYSTEM -{.COMPONENT TEST), COOLING COIL
continued Page 17
AH no Date
Precooling coil no.
Cooling coil no.
Check Fail &
No. Steps mark Pass Remarks No.
0.754 x ( + 460)
(1 + 1.6078 x W) - cu ft/lb
Pb
cfm cfm
M = lb/min
V
= 60 x x ( )
- Btu/h
( + + ) /3 = Btu/h
14 Acceptance criteria: 14
A107
: :
TEST WORK SHEET WS 5B-2 -- AIR HANDLING SYSTEM (60MP0NENT TEST), HUMIDIFIER
Page 18
AH no. Date
Humidifier no. ___________ Inspection agent
COMMENTS
A108
APPENDIX
TEST WORK SHEET WS 5B-2 -- AIR HANDLING SYSTEM ^COMPONENT TEST), HUMIDIFIER
continued Page 19
AH no. Date
Humidifier no.
= e ( 15 4638
. - [ 7284/ (Td-392 )
p
P w - RH x P sw
Humidity ratio, W: 8c
W = 0.622 x
pb - pw
COMMENTS
A109
:
TEST WORK SHEET WS 5B-2 -- AIR HANDLING SYSTEM (COMPONENT TEST), HUMIDIFIER
continued Page 20
AH no. Date_
Hum i d i f i e r no.
0.754 x ( + 460)
-
(1 + 1.6078 x W) = cu ft/lb
Pb
cfm cfm
M = - - lb/min
v
8f Humidifier capacity, C: 8f
C = 60 M x [
(W) lvg - (W) ent ]
*= 60 x x ( - _) = Btu/n
( + + _)/3 - Btu/h
10 Acceptance criteria 10
COMMENTS
A110
APPENDIX
Supplier Date
System model Inspection agent
CPU make, model Commissioning team
CPU serial no.
NO.
5 DESCRIPTION YES NO N/A REMARKS NO
General
1 Control diagrams, 0 & M manuals complete 1
2 Specified test equipment complete:
2a PROM programmer 2a
2b FID/MUX tester 2b
6
2c Data environment simulator 2c
2d Others 2d
Alll
:
Date
6g Temperature transmitter 6g
6h Humidity transmitter 6h
6i Pressure transmitter 6i
6j Flow transmitter 6j
6k Others 6k
All 2
APPENDIX
Supplier Date
EMCS system model Inspection agent
CPU make .model Commissioning team
CPU serial no.
Software version
A113
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
Supplier Date
EMCS system model
Software version
Check Fail &
No. Steps mark Pass Remarks No.
A114
APPENDIX
Supplier Date
EMCS system model
Software version
Check Fail &
No. Steps mark Pass Remarks No.
A115
:
Supplier Date
EMCS system model Inspection agent_
Software version Commissioning team
COMMENTS
A116
APPENDIX
Supplier Date
EMCS system model
Software version
COMMENTS
A117
:
Flow points:
Enter point no.
sensor kind
service
A118
APPENDIX
TEST WORK SHEET WS 6B-3 -- EMCS OVERALL PERFORMANCE TEST, FLOW continued
Page 2
Supplier Date__
EMCS system model
HVAC system
Check Fail &
No. Steps mark Pass Remarks No.
hw
(1/2)
Flow rate = 44.75 (K Y d 2 F a ) ( )
= 44.75 x x 2 x (-~.)U/2)
( )
= gpm
Flow rate = 60 (f / k)
= 60 x (-77..)
gpm
COMMENTS
A119
:
Supplier Date
EMCS system model Inspection agent
HVAC systm Commissioning team
Software version
System
COMMENTS
A120
APPENDIX
TEST WORK SHEET WS 6B-4 -- EMCS OVERALL PERFORMANCE TEST, FOR ENERGY
CALCULATIONS
continued Page 2
Supplier Date
EMCS system model
HVAC system_
Software version
Check Fail &
No. Steps mark Pass Remarks No.
System
= _____ Btu/lb
COMMENTS
A121
: :
TEST WORK SHEET WS 6B-4 -- EMCS OVERALL PERFORMANCE TEST, FOR ENERGY
CALCULATIONS
continued Page 3
Supplier Date
EMCS system model_
HVAC system
Software version
Check Fail &
No. Steps mark Pass Remarks No.
System
7 Percentage difference 7
«= [1 - ( _(from 6) / ( from 4) ]
x 100
%
COMMENTS
A122
APPENDIX
TEST WORK SHEET WS 6B-4 -- EMCS OVERALL PERFORMANCE TEST, FOR ENERGY
CALCULATIONS
continued Page 4
Supplier D ate
EMCS system model
HVAC system
Software version
Check Fail &
No. Steps mark Pass Remarks No.
System
7 Percentage difference 7
= [1 - ( (from 6) / (from 4) ]
x 100
%
COMMENTS
A123
:
Supplier Date
EMCS system model Inspection agent
HVAC system Commissioning team
Software version
1 System input: 1
Start time set
Stop time set
Days set: weekday
weekend
holiday
Season: heating
cooling
Time delay required? Delay time
2 Record current equipmant operation mode 2
on
off
3 Enter command to put equipment under 3
program
4 Observe equipment operation when set 4
time is reached and record equipment
operation mode
on
off
time delay time ____
5 Manually start or stop equipment 5
6 EMCS issues alarm 6
7 Test conclusion 7
COMMENTS
A124
APPENDIX
Supplier Date
EMCS system model
HVAC system
Software version
1 System input: 1
Days set: weekday
weekend
holiday
Season: heating
cooling
Time delay required? Delay time
2 Record current equipmant operation mode 2
on
off
3 Enter command to put equipment under 3
program
COMMENTS
A125
:
TEST WORK SHEET WS 6B-6 -- EMCS APPLICATION SOFTWARE TEST, OPTIMUM START/STOP
continued Page 2
Supplier_ Date
EMCS system model
HVAC system
Optimum Start - :
Optimum stop - :
COMMENTS
A126
APPENDIX
1 System input: 1
Specified maximum space temp
Specified minimum space temp
Specified minimun cycling time min
2 Enter command to put equipment under 2
duty cycling schedule program
3 Display space temperature (at 5 minute 3
intervals) and equipment operation
status
4 Verify that the equipment is cycling and 4
the space temp does not go beyond the
max. or min. specified temp
5 Enter command or reset temp controller 5
to raise or lower space set temp
6 Verify that the equipment is cycling and 6
the space temp does not go beyond the
max-min specified temp band
7 Verify that the specified minimum on 7
time is not violated during the entire
test period
8 Restore setting of temp controller 8
9 Test conclusion 9
COMMENTS
A127
:
Supplier Date
EMCS system model
HVAC system
Software version
1 System input: 1
Time applicable: start
end
Days applicable: weekday
weekend
holiday
Meter reset interval min
Average power kw
Equipment under control:
Equipment
12 3 4
name
Priority
level
Delay time
(min)
Min off
(min)
Min on
(min)
Max off
(min)
COMMENTS
A128
APPENDIX
TEST WORK SHEET WS 6B-8 -- EMCS APPLICATION SOFTWARE TEST, ELECTRICAL DEMAND
LIMITING continued Page 2
Supplier Date
EMCS system model
HVAC system_
Software version
Check Fail &
No. Steps mark Pass Remarks No.
5 6 7 8
Equipment
name
Priority
level
Delay time
(min)
Min off
(min)
Min on
(min)
Max off
(min)
2 Enter command to put program in operation 2
3 Turn on HVAC equipment and/or increase 3
electric load
4 Verify equipment shut-down and record 4
equipment on/off time
Equipment
12 3 4
Time shed
Time restored
Off time (min)
On time (min)
5 6 7 8
Equipment
Time shed
Time restored
Off time (min)
On time (min)
5 Confirm that equipment shedding sequence 5
agrees with priority list
6 Confirm that equipment on/off times do not 6
exceed specified max and min limits
7 Confirm equipment rotation within 7
the same priority level, if specified
8 Test conclusion 8
COMMENTS :
A129
:
Supplier Date
EMCS system model __
HVAC system
Software version
1 System input: 1
Days applicable: weekday
weekend
holiday
Season: heating cooling
Setback time: start end ,
COMMENTS
A130
:
APPENDIX
TEST WORK SHEET WS 6B-9 -- EMCS APPLICATION SOEIWARE TEST, DAY-NIGHT SETBACK
continued Page 2
Supplier Date
EMCS system model
HVAC system
16 Test conclusion 16
COMMENTS
A131
:
1 System input: 1
Change-over temp F
2 Enter command to put program in operation 2
3 Obtain a current report of system: 3
Outdoor air temp F
Return air temp F
Outdoor sir damper position
Return air damper position _____
Mixed air temp F
4 Compare outdoor air and change-over 4
temp .
if
,
T 0 a > T co go to steps 5 to 9
,
T oa < T co go to steps 8 to 12
,
A132
: ,
APPENDIX
Supplier Date
EMCS system model
HVAC system
Software version
F d.p.
Outdoor air enthalpy Btu/lb
Return air temp F
Return air humidity 1 RH or
F w.b. and
F d.p.
Return air enthalpy Btu/lb
COMMENTS
A133
: 3 .
TEST WORK SHEET WS 6B-11 -- EMCS APPLICATION SOFTWARE TEST, ENTHALPY ECONOMY
CYCLE continued Page 2
Supplier Date
EMCS system model_
HVAC system
Software version
Region OA RA
1
2
3
11 Test conclusion 11
COMMENTS
A134
: ,
APPENDIX
Supplier Date
EMCS system model
HVAC system
Software version
1 System input: 1
Days applicable: weekday
weekend
holiday
Season: heating cooling
,
Space temp: F
Occupied time: start
end
AH unit: start time
s t op time
2 Time of test 2
3 Enter command to put program in 3
operation
4 Verify that OA damper is open 4
COMMENTS
A135
:
TEST WORK SHEET WS 6B-12 -- EMCS APPLICATION SOFTWARE TEST, VENTILATION AIR
CONTROL continued Page 2
Supplier Date
EMCS system model
HVAC system
19 Test conclusion 19
COMMENTS
A136
: .
APPENDIX
Supplier_ Date
EMCS system model
HVAC system
Software version
A137
:
1 System input: 1
Reset schedule:
Outdoor temp HW temp
High F F
Low F F
2 Enter command to put program in 2
operation
3a Substitute outdoor temp sensor with 3a
temp simulator, or
3b Place outdoor temp sensor in temp bath 3b
4 Increase simulated temp or bath temp 4
to below the high limit
5 Observe hot water temp, it should 5
move lower
6 Increase simulated temp or bath temp 6
to 5 F beyond high limit
7 Verify that hot water temp does not go 7
below specified limit
8 Decrease simulated temp or bath temp 8
to above low limit
9 Observe hot water temp, it should 9
move higher
10 Decrease simulated temp or bath temp 10
to 5 F beyond low limit
11 Verify that hot water temp does not go 11
above specified limit
12 Restore temp sensors 12
13 Test conclusion 13
COMMENTS
A138
: ,
APPENDIX
Supplier Date
EMCS system model
HVAC system
Software version
1 System input:
Reset schedule:
Space Valve
temp position CHW temp
High F % F
Low F % F
Space high humidity limit:
% RH
F wb
F dp
2 Enter command to put program in 2
operation
3a Substitute space temp sensor with 3a
temp simulator, or
3b Place space temp sensor in temp bath, 3b
or
3c Be ready to change valve position sensor 3c
(or control signal feedback sensor)
4a Change temp simulator to raise temp 4a
(not over the limit) or
,
COMMENTS
A139
:
TEST WORK SHEET WS 6B-15 -- EMCS APPLICATION SOFTWARE TEST, CHILLED WATER
TEMPERATURE RESET continued Page 2
Supplier Date
EMCS system model
HVAC system^
COMMENTS
A140
: ,
APPENDIX
Supplier Date
EMCS system model
HVAC system
Software version
1 System input: 1
Reset schedule:
OA wet OA dry Cond water
bulb temp bulb temp temp
High F F F
Low F F F
Condenser water low limit F
2 Enter command to put program in 2
operation
3 Substitute outdoor temp sensor with 3
temp simulator
4 Substitute outdoor humidity sensor 4
with humidity simulator
5 Manipulate temp and humidity sensors 5
to obtain desired successively
lower wet bulb temp (using a
psychromatric chart may be helpful)
and observe condenser water supply
temp
6 Record simulated outdoor conditions: 6
Dry bulb Humidity Wet bulb
temp ,
F temp ,
F
COMMENTS
A141
:
TEST WORK SHEET WS 6B-16 -- EMCS APPLICATION SOFTWARE TEST, CONDENSER WATER
TEMPERATURE RESET continued Page 2
Supplier Date
EMCS system model
HVAC system
12 Test conclusion 12
COMMENTS
A142
: :
APPENDIX
General
1 All materials in plenums appropriate
2 Air filters appropriate
3 Fan inlets protected by screens
4 Heating equipment installation appropriate
5 Cooling equipment installation appropriate
6 Manual controls installed
7 Automatic controls installed
Ductwork:
1 Duct material appropriate
2 Duct installation appropriate
3 Duct connectors appropriate
4 Duct coverings appropriate
5 Duct linings appropriate
Dampers
1 Fire dampers located where required
2 Fire dampers of appropriate rating
3 Fire dampers installed appropriately
4 Ceiling dampers located where required
5 Ceiling dampers of appropriate rating
6 Ceiling dampers installed appropriately
7 Smoke dampers located where required
8 Smoke dampers of appropriate rating
9 Smoke dampers installed appropriately
10 Combination fire and smoke dampers
located where required
11 Combination fire and smoke dampers
of appropriate rating
12 Combination fire and smoke dampers
installed appropriately
COMMENTS
A143
: :
Manual shutdown
COMMENTS
A144
APPENDIX
Date
Test agent
Flow Direction:
Doors in barriers of smoke Pressure Difference From To
control zone (inches water gage) Zone Zone
:
COMMENTS
A146
:
APPENDIX
TEST WORK SHEET WS 7B-1 -- ZONED SMOKE CONTROL .SYSTEM - DUCT MOUNTED DETECTOR
(continued) Page 3
COMMENTS
A147
HVAC FUNCTIONAL INSPECTION AND TESTING GUIDE
Stairwell No.
A148
:
APPENDIX
Date
Test agent
Stairwell No.
Flow Direction:
Doors Open in Pressurized From To
Stairwell Stair Stair
COMMENTS
A149
: :
elec ,
gas (check one) ___
Stage of cooling: 1_ , 2 , 3 ,4 .
General
1 Operation and maintenance manuals complete 1
2 General appearances no apparent damage
,
2
3 Verify unit model with submittals 3
4 Component service space adequate 4
5 Air filter replacement space adequate 5
6 Other access space adequate (headroom, 6
access doors, etc)
7 Equipment space clean, no fire hazards 7
8 Proper vibration unit installation 8
9 Pipe fittings and accessories complete 9
10 Check valves and flow switches, flow 10
direction correct
11 Pipes supported properly 11
12 Protection shields for motor and belts 12
13 Alignment of motor driven components 13
14 Belt tightness satisfactory 14
15 Lubrication complete and proper 15
16 Correct refrigerant kind 16
17 Correct refrigerant level 17
18 Compressor oil filter clean and proper 18
19 Correct compressor oil level: 19
Before operation
During operation
20 Cramkcase heater installed correctly 20
21 Crankcase heater on when unit off 21
22 Thermometers complete 22
23 Pressure gages complete 23
24 Flow meters meet installation requirements 24
25 Electric wiring installation proper 25
26 Elec motors & components grounded properly 26
27 All electric connections tight 27
COMMENTS
A150
APPENDIX
Fan:
1 Housing access doors and latchs tight 1
2 Grease or oil tubes for bearings proper 2
3 No need removing belt guard for oiling 3
or speed check
4 Fan running steadily 4
5 Fans with inlet vanes or outlet dampers: 5
5a Damper linkage no excessive play 5a
5b Damper closes tight 5b
5c Direction of inlet damper blade proper 5c
5d Inlet dampers for double inlet fan proper 5d
6 Protective hood over motor and belt for 6
outdoor installation
7 Inlet and outlet wire protection for fan 7
without duct connection
8 Flexible connections between fan and ducts 8
COMMENTS :
A151
: :
ACU no .
Date
Coils
1 No damage to heat transfer fins 1
la Heating coil la
lb Cooling coil lb
2 Coil tubes pitch correctly 2
2a Heating coil 2a
2b Cooling coil 2b
3 No air bypass between coil and casing 3
3a Heating coil 3a
3b Cooling coil 3b
A Cooling coil drain pans and pipes 4
5 Coil pipe fittings and accessories 5
5a Shut-off valves 5a
5b Strainers 5b
5c Air vents 5c
5d Sensor and thermometer wells 5d
5e Balancing devices 5e
5f Drain 5f
5g Others 5g
6 Flow measuring device 6
6a Upstream pipe length or flow straightener 6a
6b Downstream pipe length 6b
6c Meter connection and valves complete 6c
6d Tag with flow rate information 6d
7 Condensate pipe at steam trap not over 7
200 F when control valve is open
(for low pressure steam only)
Air filters:
1 Filter frame securely anchored to casing 1
2 No air leakage around filter frame 2
3 No air leakage between filter bank 3
and unit casing
4 New (clean) filter media 4
5 Filter gage pressure sensing tip proper 5
6 Inclined manometer gage installation 6
COMMENTS
A152
: :
APPENDIX
7
INSPECTION CHECK LIST CL 8A-1 -- ROOFTOP AIR CONDITIONING UNIT (continued)
Page 4
mechanism
7a Motor 7a
7b Driving train 7b
7c Timer 7c
7d Pressure sensing 7d
7e Overriding operation 7e
7f Control operation 7f
8 Filter replacement space adequate 8
9 Spare filters to meet specifications 9
Air dampers:
1 Blade arrangement: parallel 1
opposed
2 Blade edge sealing 2
3 Bearings as specified 3
4 Actuator linkage and blade movement 4
5 Access door for dampers in duct 5
Air louvers:
1 Material 1
2 Construction 2
3 Dimensions 3
4 Screen 4
Casings
1 Rigidity 1
2 Integraty 2
3 Access doors : 3
3a Size 3a
3b Gasket 3b
3c latches 3c
4 Flexible connections between unit 4
and ducts
COMMENTS
A153
:
Automatic controls:
1 Give general check on control installations 1
against contract documents and submittals
2 Observe general operation. Any obvious 2
malfunction, incorrect calibrations, or
incorrct settings and ranges?
3 Are mercury switches leveled correctly? 3
4 Check valves for correct closing 4
5 Valves and linkages installed securely 5
6 Valve linkages travel freely 6
7 Check dampers for correct closing 7
8 Dampers and linkages installed securely 8
9 Damper linkages travel freely 9
10 Safety features (coil freeze protection, 10
etc.) installed correctly
11 Interlocking installed correctly 11
12 For controls interfacing with pneumatic
building system, check interfacing devices
13 For electrcal and electronic systems: 13
13a Wire connections tight 13a
13b No broken wires 13b
13c No rust, corrosion or film 13c
on wire terminals
13d Correct voltage on power supply 13d
13e Signal wires shielded correctly 13e
13f Shielding terminated at one end only 13f
COMMENTS
A154
: :
APPENDIX
General
1 Operation and maintenance manuals complete 1
2 General appearances, no apparent damage 2
3 Verify unit model with submittals 3
4 Component service space adequate 4
5 Air filter replacement space adequate 5
6 Other access space adequate (headroom, 6
access doors, etc)
7 Equipment space clean, no fire hazards 7
COMMENTS
A155
: . :
A156
. : .
APPENDIX
ACU no Date
Air filters:
1 Filter frame anchored to casing securely 1
2 No air leakage around filter frame 2
3 No air leakage between filter bank 3
and unit casing
4 New (clean) filter media 4
5 Filter gage pressure sensing tip proper 5
6 Inclined manometer gage installation 6
7 Filter replacement spece adequate 7
8 Spare filters 8
Air dampers:
1 Blade arrangement: parallel 1
opposed
2 Blade edge sealing 2
3 Bearings as specified 3
4 Actuator linkage and blade movement 4
5 Access door for dampers in duct 5
Casings
1 Rigidity 1
2 Integraty 2
3 Access doors: 3
3a Size 3a
3b Gasket 3b
3c latches 3c
4 Flexible connections between unit 4
and ducts
A157
:
Automatic controls:
1 Give general check on control installations 1
against contract documemts and submittals
2 Observe general operation. Any obvious
10 2
malfunction, incorrect calibrations, or
incorrct settings and ranges?
3 Are mercury switches leveled correctly? 3
4 Check valves for correct closing 4
5 Valves and linkages installed securely 5
6 Valve linkages travel freely 6
7 Check dampers for correct closing 7
8 Dampers and linkages installed securely 8
9 Damper linkages travel freely 9
Interlocking installed correctly 11
11a Control wire connections tight 11a
11b No broken control wires lib
11c No rust, corrosion or film 11c
on wire terminals
lid Correct voltage on power supply lid
lie Signal wires shielded correctly lie
Ilf Shielding grounded at one end only Ilf
12 Check operation of indicating lights 12
13 Check operation of audible alarms 13
14 Check dehumidifier operation for 14
units with variable air flow rates
when dehumidify is in operation
15 Check operation of underfloor water 15
detection system
16 Check operation of unit fire 16
detection system
17 Check operation of unit smoke 17
system
COMMENTS
A158
:
APPENDIX
(check one)
A159
: .
Date
Test agent
Commissioning team
Temperature
Humidity
Pressure
Power
Others
Temperature, F:
1 Water (for condenser ,
32 200 1
steam, condensate,
and hot water)
2 Low pressure steam 200 300 2
3 Air 32 150 3
A160
: . ::
APPENDIX
TEST WORK SHEET WS 8B-1 -- INSTRUMENT CALIBRATION FOR UNITARY AIR CONDITIONING
UNIT continued Page 2
Date
Humidity:
4 Relative humidity, % 30#1 90#1 4
5 Dew point temp, F 35 75 5
Flow:
7 Water and steam, gpm #3 #4 7
a
b.
c
Pressure
9 Air, in. w.c. 0 #6 9
Other devices:
a
b.
c
Notes
#1 Within a dry bulb temperature range of 10 - 100 F
#2 Within a dry bulb temperature range of 35 - 100 F
#3 25% below specified values
#4 25% above specified values
#5 This is for velocity type instrumsnts, see pressure calibration
for pressure sensing devices (pitot)
#6 Expected highest pressure or 5 in. w.c. whicherever is higher
Comments
A161
:
8.5 TEST WORK SHEET WS 8B-2 UNITARY ROOFTOP AND COMPUTER ROOM
UNIT, AIR FLOW RATE TEST Page 1
COMMENTS
A162
: :
APPENDIX
TEST WORK SHEET WS 8B-2 -- UNITARY ROOFTOP AND .COMPUTER ROOM UNIT, AIR FLOW
RATE TEST continued Page 2
7a Room ,
measured cfm (* cfm) 7a
Room measured cfm (* cfm)
Room ,
measured cfm (* cfm)
Room measured cfm (* cfm)
Room measured cfm (* cfm)
7b Calculate error 7b
(1 - measured/specified supply) x 100%
Room ,
Error = %
Room Error = %
Room Error = %
Room Error = %
Room ,
Error = %
COMMENTS
A163
: . .
TEST WORK SHEET WS 8B-2 -- UNITARY ROOFTOP AND COMPUTER ROOM UNIT, AIR FLOW
RATE TEST continued Page 3
7d Room measured ,
cfm (* cfm) 7d
Room measured ,
cfm (* cfm)
Room measured ,
cfm (* cfm)
Room measured ,
cfm (* cfm)
Room measured ,
cfm (* cfm)
7e Calculate error 7e
(1 - measured/specified supply) x 100%
Room Error - ,
%
Room Error = ,
<y
Room Error = ,
%
Room Error = ,
%
Room Error *= ,
%
9 Total air flow rate of measured outlets cfm (7a & 7d) 9
11 Calculate error 11
(1 - measured/specified supply) x 100% «= %
COMMENTS
A164
: .
APPENDIX
TEST WORK SHEET WS 8B-2 -- UNITARY ROOFTOP AND -COMPUTER ROOM UNIT, AIR FLOW
RATE TEST continued Pa g e 4
Room »
measured cfm (* cfm) 20a
Room »
measured cfm (* cfm)
Room »
measured cfm (* cfm)
Room »
measured cfm (* cfm)
Room »
measured cfm (* cfm)
COMMENTS
A165
: .
TEST WORK SHEET WS 8B-2 -- UNITARY ROOFTOP AND COMPUTER ROOM UNIT, AIR FLOW
RATE TEST continued Page 5
22 Total air flow rate of measured outlets__ cfm (7a & 7d) 22
24 Calculate error 24
(1 - measured/specified supply) x 100% = %
COMMENTS
A166
:
APPENDIX
TEST WORK SHEET WS 8B-2 -- UNITARY ROOFTOP AND -COMPUTER ROOM UNIT, AIR FLOW
RATE TEST continued Page 6
COMMENTS
A167
: : ;
;
TEST WORK SHEET WS 8B-2 -- UNITARY ROOFTOP AND COMPUTER ROOM UNIT, AIR FLOW
RATE TEST continued Page 7
6c Calculate error: 6c
(1 - measured/specified supply) x 100%
Box # ,
Error = % (max) Error «= % (min)
Box # ,
Error = % (max) Error - % (min)
Box # ,
Error = % (max) Error -= % (min)
Box // ,
Error = % (max) Error = % (min)
Box # ,
Error = % (max) Error = % (min)
Calculate error 7c
( 1 - me asured/specif ied supply) x 100%
Box # Error =
,
%(max); Error = %(rain)
Box // Error =
, % (max) Error *= %(min)
Box # Error,
= % ( max ) Error -= %(min)
Box # Error,
= % (max) Error *= %(min)
Box # Error,
= % (max) Error = %(min)
COMMENTS
A168
:
APPENDIX
TEST WORK SHEET WS 8B-2 -- UNITARY ROOFTOP AND XOMPUTER ROOM UNIT, AIR FLOW
RATE TEST continued Page 8
13 Calculate error: 13
(1 - measured/specified supply) x 100% «= % (max)
(1 - measured/specified supply) x 100% = % (min)
COMMENTS
A169
:
TEST WORK SHEET WS 8B-2 -- UNITARY ROOFTOP AND COMPUTER ROOM UNIT, AIR FLOW
RATE TEST continued Page 9
19 Date
AH unit no.
COMMENTS
A170
:
APPENDIX
TEST WORK SHEET WS 8B-2 -- UNITARY ROOFTOP AND .COMPUTER ROOM UNIT, HEATING
CAPACITY TEST continued Page 10
AH unit no .
Date
Heating medium: Steam Inspection agent
Heating capacity:
1 Air flow rate (from air flow rate test, 1
WS-2,page 2) cfm
2 Measure entering air temp 2
apply false load if needed
(* F)
average temp F
3 Measure & adjust ent w temp to within 3
1 F of specified (water coil only)
(* F) F
A Measure & adjust steam temp & 4
pressure (steam coil only) to
within 1 psi of specified
(* psi) psi F
Is steam saturated?
5 Measure and adjust water or steam 5
flow rate to within 3 1 of specified
(water or steam coil only)
6 Disable control of test coil (water 6
or steam coil only)
7 Check electric coil is energized
(electric coil only) 7
8 Check gas burner is on (gas unit only) 8
9 Run unit for at least 10 minutes 9
COMMENTS
A171
: ]
TEST WORK SHEET WS 8B-2 -- UNITARY ROOFTOP AND COMPUTER ROOM UNIT, HEATING
CAPACITY TEST continued Page 11
(Psw)ent - e'
15 * 638 - 728 * /( + 392 ” = in. Hg
Pw - RH x P sw
COMMENTS
A172
:
APPENDIX
TEST WORK SHEET WS 8B-2 -- UNITARY ROOFTOP AND -COMPUTER ROOM UNIT, HEATING
CAPACITY TEST continued Page 12
W -= 0.622 x
Pb " Pw
0.754 x ( + 460)
-
(1 + 1.6078 x W) = cu ft/lb
Pb
COMMENTS
A173
: ,
TEST WORK SHEET WS 8B-2 UNITARY ROOFTOP AND COMPUTER ROOM UNIT, HEATING
CAPACITY TEST continued Page 13
cfm cfm
M Ib/min
” 60 x x ( - )
= Btu/h
( )/3 = Btu/h
14 Acceptance criteria: 14
COMMENTS
A174
: ,
APPENDIX
TEST WORK SHEET WS 8B-2 -- UNITARY ROOFTOP AND -COMPUTER ROOM UNIT, COOLING
CAPACITY TEST continued Page 14
Commissioning team
COMMENTS
A175
: ( ]
TEST WORK SHEET WS 8B-2 -- UNITARY ROOFTOP AND COMPUTER ROOM UNIT, COOLING
CAPACITY TEST continued Page 15
P CW
^ «=
“ -[15.4638
“ - 7284/ (Td+392 )
-
i
\
sw/ent
= c-[15.4638 7284/ + 392)] „ in. Hg
-
'
\ _ e-[15.4638 7284/ + 392)) = in. Hg
sw/ent
P w - RH x P sw
COMMENTS
A176
:
APPENDIX
TEST WORK SHEET WS 8B-2 -- UNITARY ROOFTOP AND -COMPUTER ROOM UNIT, COOLING
CAPACITY TEST continued Pa g e 16
AH no. Date
9c Humidity ratio, W: 9c
W - 0.622 x
9d Enthalpy, H: 9d
0.754 x ( + 460)
= (1 + 1.6078 x W) = cu ft/lb
Pb
COMMENTS
A177
:
TEST WORK SHEET WS 8B-2 -- UNITARY ROOFTOP AND COMPUTER ROOM UNIT, COOLING
CAPACITY TEST continued Page 17
AH no. Date
cfm cfm
M - ----- - lb/min
_
v
= 60 x x ( - ) = Btu/hr
10 Acceptance criteria: 10
COMMENTS
A178
: :
APPENDIX
TEST WORK SHEET WS 8B-2 -- UNITARY ROOFTOP AND -COMPUTER ROOM UNIT, HUMIDIFIER
CAPACITY TEST continued Page 18
Commissioning team
COMMENTS
A179
: ] .
TEST WORK SHEET WS 8B-2 UNITARY ROOFTOP AND COMPUTER ROOM UNIT, HUMIDIFIER
CAPACITY TEST continued Page 19
8b Vapor pressure, Pw : 8b
P„ « RH x P sw
8c Humidity ratio, W: 8c
Pw
W - 0.622 x
Pb ' Pw
COMMENTS
A180
:
APPENDIX
TEST WORK SHEET WS 8B-2 -- UNITARY ROOFTOP AND -COMPUTER ROOM UNIT, HUMIDIFIER
CAPACITY TEST continued Page 20
0.754 x ( + 460)
(1 + 1.6078 x W) cu ft/lb
Pb
cfm cfm
M= - lb/min
v
8f Humidifier capacity, C: 8f
= 60 x x ( - ) = Btu/hr
9 Acceptance criteria: 9
COMMENTS
A181
:
10
fan operation
3 Turn ventilation control to off 3
4 Turn cooling control to on, make sure 4
thermostat setting is at least 10 F
belo room temperature
T
COMMENTS
A182
on hUMDtn
NIST-1 14A U.S.DEPARTMENT OF COMMERCE 1.
S. AUTHOR(S)
James Y. Kao
5. PERFORMING ORGANIZATION (IF JOINT OR OTHER THAN NIST, SEE INSTRUCTIONS) 7. CONTRACT/GRANT NUMBER
DEPARTMENT OF COMMERCE
U.S.
NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY
GAITHERSBURG, MD 20899 8. TYPE OF REPORT AND PERIOD COVERED
9. SPONSORING ORGANIZATION NAME AND COMPLETE ADDRESS (STREET, CITY, STATE, ZIP)
This guide is developed for the Public Building Service (PBS) of the General Services
Administration (GSA) for final inspection and testing of heating, ventilating, and air-
conditioning (HVAC) systems in Federal buildings prior to Government acceptance. The
guide describes in detail the functional inspection and testing procedures and
calculations. It includes eight chapters: General, Instrumentation and Basic
Measurement, Refrigeration Plant, Heating Plant, Air Handling Equipment and systems.
Building Automation Systems, Fire Safety Air Moving Systems, and Unitary Air Handling
Equipment. The appendix contains detailed inspection checklist and test work sheets
designed to be used in the field.
12. KEY WORDS (6 TO 12 ENTRIES; ALPHABETICAL ORDER; CAPITALIZE ONLY PROPER NAMES; AND SEPARATE KEY WORDS BY SEMICOLONS)
air handling system test; building automation system test; commissioning; field test; fire
safety test; functional test; heating plant test; inspection; smoke control test;
refrigeration plant test
13. AVAILABILITY
' — 14. NUMBER OF PRINTED PAGES
JL UNLIMITED
FOR OFFICIAL DISTRIBUTION. DO NOT RELEASE TO NATIONAL TECHNICAL INFORMATION SERVICE
429
(NTIS).
ORDER FROM SUPERINTENDENT OF DOCUMENTS, U.S. GOVERNMENT PRINTING OFFICE 15. PRICE
WASHINGTON, DC 20402.
A19
ORDER FROM NATIONAL TECHNICAL INFORMATION SERVICE (NTIS), SPRINGFIELD, VA 22161.
ELECTRONIC FORM