Vacon NX Service Manual Vacon NX Service Manual
Vacon NX Service Manual Vacon NX Service Manual
Vacon NX Service Manual Vacon NX Service Manual
Overview
Table of contents 1
1. SERVICE
SERVICE MANUAL
MANUAL REVISION HISTORY ................................................. 3
2. AFTER MARKET SERVICE INFORMATION ...............................................4
2.1. FOREWORD ...............................................................................4
2.2. Overview manual information ........................................
................... ...................................
.............. 5
2.3. Appendix manual information ................................
............ .......................................
.....................
.. 5
2.4. Important
Important instructions
instructions for service
service situations ..................................
................ .................. 5
2.4.1. Personal requirements ......................................
.................. ................................
............ 6
2.4.2. Personal safety notice .....................................
................... ................................
.............. 6
2.4.3. Material requirements ...........................
....... ........................................
........................
.... 6
2.4.4. Tool safety notice ....................................
................ ......................................
.....................
... 7
2.5. SERVICE POLICY ........................................................................7
2.6. WARRANTY TERMS. ....................................................................7
2.7. REPLACEMENT
REPLACEMENT UNITS & SPARE PARTS .......................................
................... .......................
... 7
2.8. MAINTENANCE .............................. ......................................
.................... ........................
...... 8
2.8.1. RECOMMENDED MAINTENANCE ACTIONS ........................
.................... .... 8
2.8.2. RECHARGING
RECHARGING CAPACITORS
CAPACITORS IN STORED UNITS ................. 9
2.8.3. RECHARGING STAND-ALONE CAPACITORS STORED .......... 9
3. SERVICE TOOLS .................................................................................. 11
3.1. INFORMATION ........................................
.................... ........................................
.................................
............. 11
3.2. NC LOAD 1.0.15 .......................................
.................... ......................................
...............................
............ 11
3.3. NC DRIVE 2.0.7 ...........................
....... .......................................
.......................................
.........................
..... 11
3.4. NC SERVICE ...................................
................. ......................................
.......................................
.....................
.. 12
3.4.1. Version 1.09 ................... ......................................
................... ........................
..... 12
3.4.2. Version 1.10 ................... ......................................
................... ........................
..... 12
3.5. DEVICE PROPERTIES SERVICE ............................................
........................ ...........................
....... 12
3.5.1. Version 2.0.2 ....................................
................ ......................................
.........................
....... 12
3.5.2. Version 2.0.3 ....................................
................ ......................................
.........................
....... 12
4. FAULTCODES AND SOFTWARE .............................................................13
4.1. GENERAL ....................................
................. ......................................
.......................................
.........................
..... 13
4.2. FAULT CODES, POSSIBLE
POSSIBLE REASONS AND CHECKING TO TO BE DONE .. . . 13
4.3. SOFTWARE REVISION INFORMATION ........................................
.................... ...................... 13
4.3.1. NXL software information ........................................
................... .........................
.... 13
4.3.1.1.NXL00005V146 .....................................
.................. ............................
......... 13
4.3.1.2.NXL00005V247 .....................................
.................. ............................
......... 14
4.3.1.3.NXL00005V242 .....................................
.................. ............................
......... 14
4.3.2. NXS software ................................. ............................
.................. .......... 14
4.3.2.1.NXS00
4.3.2.1.NXS00001V16 001V160 0 ..................
..........................
.................
..................
........... 14
4.3.2.2.NXS00
4.3.2.2.NXS00001V16 001V161 1 ..................
..........................
.................
..................
........... 14
4.3.2.3.NXS00
4.3.2.3.NXS00001V16 001V162 2 ..................
..........................
.................
..................
........... 14
4.3.3. NXP software .....................................
................. .......................................
........................
..... 14
4.3.3.1.NXP00002V156 .....................................
.................. ............................
......... 14
4.3.3.2.NXP00002V158 .....................................
.................. ............................
......... 14
4.3.3.3.NXP00002V159 .....................................
.................. ............................
......... 15
4.3.3.4.NXP00002V160 .....................................
.................. ............................
......... 15
4.3.3.5.NXP00002V161 .....................................
.................. ............................
......... 15
4.4. INFORMATION REGARDING FAULT TRACING ...............................
................... ............ 15
4.5. FAULT CODES .....................................
................... ......................................
....................................
................ 15
4.5.1. Flowcharts
Flowcharts until NXSV151 and NXPV145 ........................
................... ..... 15
4.5.2. Flowcharts from NXSV152 and NXPV146 ........................
................... ..... 15
service@vacon.com
service@vacon.com Tel +358
+358 (0)201 212 575 Fax +358 (0)204 335 091
2 Table of contents
service@vacon.com Tel +358 (0)201 212 575 Fax +358 (0)204 335 091
1
4 After market service information
2.1. FOREWORD
Service to Vacon AC-drive owners is a high priority of the Vacon Plc as well as contin-
ues development and introduction of new service material. In the line with this purpose
Vacon Plc has implemented the following Vacon Service Manual for Service Centers.
Other service information is also released by Vacon Plc. Service bulletins (SBU´s) con-
tains more specific information about updates of a product.
Vacon Plc will continue to issue updated service manuals aft er the first release of the
manual. Version of documents can be identified from the document number and date
2
After market service information 5
on the back cover. The letter at the end of the SM-number identifies the version, i.e.
SM00002A. The material is available on Vacon service web pages, which requires a
user name and password. Vacon After Market Service department gives the user name
and password to users.
service@vacon.com Tel +358 (0)201 212 575 Fax +358 (0)204 335 091
2
6 After market service information
• All plastic covers must be mounted before switching on voltage from supply source.
WARNING! ONLY QUALIFIED SERVICE TRAINED PERSONS ARE ALLOWED TO USE THIS
MATERIAL AND PERFORM ANY OF THE SERVICE ACTIONS MENTIONED. THE PERSON PERFORM-
ING LOCAL SERVICE WORK ON THE DRIVES MUST HAVE QUALIFICATIONS IN ACCORDANCE
WITH THEIR NATIONAL LAW.
Mechanical surfaces which are equipped with a hot surface sticker must not be
touched. Make sure working environment is safe and won't cause risk for personal
injury.
WARNING! DRIVE TO BE REPAIRED MUST NOT POWERED UP FROM ITS SUPPLY VOLTAGE
SOURCE DURING SERVICE WORK, UNLESS IT IS SPECIALLY MENTIONED.
The following voltages are extremely dangerous and may cause death or severe per-
sonal injury if you come in contact with it. Do not touch any electrical part, dc-bus bars
included when unit supplied from its supply voltage source.
• DC-bus voltage: After switching of the supply voltage, wait until dc-bus voltage has
been discharged. It must be verified to be 0V DC before any service action is
allowed. This voltage sources is life threatening.
• Relay outputs on I/O boards: They may contain dangerous voltage entering from
external devices, even if unit itself is not powered up. Their voltage must be verified
and necessary precautions must be taken to isolate them properly before any ser-
vice action is allowed. This voltage sources is life threatening.
• All power terminals carry voltages, including output terminals when the unit is con-
nected to its supply voltage source and the dc-bus capacitors are charged.
• Internal components and circuit boards are at mains potential when drive is con-
nected to its supply and dc-bus capacitors are charged.
2
After market service information 7
Defective products above FR8: They should be repaired by nearest Service Center at
customer location, unless manufacturer declares otherwise.
RAN-number: Any shipment of defective products and warranty claims to Vacon Plc
must both be identified with a RAN-number issued (Return Authorization Number).
Local Service Center sends a RAN-number request with necessary information via a
PC-program (Vacon RAN) or fax to Vacon Plc. Vacon Plc responds to the request by giv-
ing instructions how to proceed. All shipments in a service case to and from Vacon Plc
uses issued RAN-number. RAN-number issued must be used on all documents concern-
ing the warranty claim. The shipment to Vacon Plc and shipment documents must be
labeled with the RAN-number issued. The missing RAN-number in a shipment and ship-
ment documents, might result in rejection of shipment and warranty claim.
All Service Centers around the world are part of Vacon global service network and the
local Service Center must have measures to reach customer satisfaction.
Only spare parts, specified and approved by Vacon Plc must be used to replace defect
ones. Boards will be repaired only at Vacon Plc. Service actions defined in a released
SBU (Service Bulletin) authorizes repair or modification of the board mentioned.
Warranty will be revoked from the unit, if repair actions have been done without proper
authorization from Vacon Plc.
Vacon Service Center or Partner will store replacement units needed for service pur-
poses for fast response of service cases. The stock of the replacement units should
service@vacon.com Tel +358 (0)201 212 575 Fax +358 (0)204 335 091
2
8 After market service information
contain at least one unit of the biggest power size of every mechanical size up to FR8.
Vacon Plc will compensate stock of spare units in case of unit under manufacturer's
warranty has been delivered to replace of the defective unit.
Service Center will store spare parts based on units sold and needed for service in their
market / service area. If needed the Vacon Plc helps to select needed spares. The
spare parts must be stored properly to prevent material loss due to mishandling.
Always protect components and boards from ESD in all phases of the process by follow-
ing general ESD instructions.
2.8. MAINTENANCE
All technical equipment, as well as drives needs some amount of care taking and failure
preventive maintenance. To maintain trouble free operation of the drive, environmen-
tal conditions, as well as load, line power, process control, etc. have to be within spec-
ifications, determined by manufacturer.
If all conditions are as specified by manufacturer, there is no other concerns, but pro-
vide high enough cooling capacity for the power- and control circuits. This requirement
can be met by making sure, that cooling system works properly. Operation of cooling
fans and cleanness of the heat sink should be verified once in a while.
Regular maintenance is recommended to insure trouble free operation and long lifetime
of the drive. The following things should at least be included in the regular mainte-
nance.
2
After market service information 9
Recommended is also to record all actions and counter values with dates and time for
follow up of maintenance.
When complete units are stored without voltage being applied, the recharging of the
capacitors should be done at least every 12 month by connecting the voltage into unit
and keep unit powered minimum 1 h.
If the storing time is much longer than one year, the recharging of the capacitors has
to be done in a way that the possible high leakage current through the capacitors is
limited. Best alternative is to use DC-power supply with adjustable current limit. Cur-
rent limit has to be set for example to 300…500mA and DC-power supply has to be
connected to the B+/B- terminals (DC+ to B+, DC- to B-) of the DC-link or straight to
the capacitor terminals.
DC-voltage has to be adjusted up to nominal DC-voltage level of the unit (1.35*Un ac)
and has to be supplied at least 1h.
If DC-voltage is not available and unit has been stored much longer than 1 year de-
energized, consult factory before connecting the power.
When using spare part capacitors from stock and it is known that they have been there
over one year as voltage-free, the recharging of capacitors is easiest to perform before
capacitors are installed inside a unit.
DC-supply current limit is set to value 50…100mA and voltage is set up to rated value
of capacitors. The recharging process can be then followed by monitoring the current
meter of the DC-power supply. It is recommended to keep voltage supplied at least 1 h
even that leakage current has already stabilized earlier.
service@vacon.com Tel +358 (0)201 212 575 Fax +358 (0)204 335 091
2
10 After market service information
Due high leakage resistance the dangerous voltage can remain in capacitors long time.
Remember to discharge capacitors by using a proper resistors after recharging is fin-
ished.
+ -
V I
+ -
R
2
Service tools 11
3. SERVICE TOOLS
3.1. INFORMATION
In addition to information about, list of tools needed, contains a list of tools needed in
a service case.
For information how to use the program, please refer to “Contents”, in the “Help”-
menu. Nice to know information as follows.
• When a problem with an eeprom on control-, power- or option board is suspected,
“F40” or “?” displayed.
-> Obtain “Info”. “Info” is located under the “Drive”-menu. A new window opens,
which content can be copied to the clipboard with the “Copy To Clipboard”-push but-
ton.
For information how to use the program, please refer to “Contents”, in the “Help”-
menu. Nice to know information as follows.
• When a problem with an eeprom on control-, power- or option board is suspected,
“F40” or “?” displayed.
-> Obtain “Info”. “Info” is located under the “Drive”-menu. A new window opens,
which content can be copied to the clipboard with the “Copy To Clipboard”-push but-
ton.
• For most complete troubleshooting of parameters, eeprom settings or faultcodes
when a customer contacts you.
-> Obtain “Print Service Info To File”. “Print Service Info To File” is located under
“File”-menu. A txt-file, is generated containing parameter settings, eeprom data and
faultcodes, if listed.
service@vacon.com Tel +358 (0)201 212 575 Fax +358 (0)204 335 091
3
12 Service tools
3.4. NC SERVICE
Program is required for programming the control unit, power unit and star adapter
unit in service cases. Previously installed NCLoad or NCDrive needed before program
is operational. Password protected file intended only for authorized persons. Ask for
the password from your contact in After Market Service.
3
Faultcodes and software 13
4.1. GENERAL
Testing and troubleshooting are one of the first steps in service / repair procedures to
locate and identify defective part from the device. Troubleshooting gives good figure
for further measures, what have to be done to recover unit back in decent condition
and in an operation. Careful troubleshooting and testing in prior to repair saves total
time and surely prevents additional consequential damages if done correctly.
Troubleshooting in general level for the complete drive is described in this section.
This section refers to checking instructions for respective frame size in its "NX-Appen-
dix Manual".
Vacon NX-drive has a capacity to save last 30 faults codes and show them on display
of control panel, if desired. There is always a reason or another for the tripping of the
drive and it should be solved before to proceed in an operation and to avoid damages
in equipment.
Used fault codes are also described in "section 9.Fault tracing" of the Vacon NX fre-
quency converter user manual. On flow charts below all numeric fault codes are
described with an explanations and with measures to be done in different cases for
solving the problem.
Fault codes from F50 and above are generated from the application. They are not sys-
tem software fault codes. Some fault codes in special system-software or applications
do not have troubleshooting instruction. Instructions for such codes are available in
respective software manual.
This troubleshooting section cover drives with Vacon standard software. Instructions
in “FAULT CODES” on page 15 covers fault codes in software versions until "NXSV151"
(11.55.6639) and "NXPV145" (12.26.7284).
4. 3. 1. 1. NXL00005V146
• Hardware compatible with all NXL-power boards from A-version but with two exep-
tions. Requires VB00352B, VB00353B or newer versions.
• Fault code F8_1 no longer appears in MF2, MF3 and MF4, when charging switch is
open less then 300ms.
service@vacon.com Tel +358 (0)201 212 575 Fax +358 (0)204 335 091
4
14 Faultcodes and software
4. 3. 1. 2. NXL00005V247
• Processor changed. Older software does not work on boards listed in table
below.This software supports both processor versions. M30624FGAGP is used today
and will be replaced by M30624FGPGP#D5 (or #U5 lead free).
4. 3. 1. 3. NXL00005V242
• Equal to NXL00005V142, except for new loader inside VCN-file, which supports both
NXL processor versions. This version to be used if customer is requiring old system
software version. See service bulletin SBU00024 0524 for more information.
4. 3. 2. 1. NXS00001V160
• Fixed “Identification run” bug.
4. 3. 2. 2. NXS00001V161
• Known feature: option board parameters are not shown on the display if the option
board data is old (EEPROM data is wrong). Board data has to be updated.
4. 3. 2. 3. NXS00001V162
• Fixed problem for F32. It does not appear, even if the FAN feedback is missing.
• Known feature: option board parameters are not shown on the display if the option
board data is old (EEPROM data is wrong). Board data has to be updated.
4. 3. 3. 1. NXP00002V156
• Hardware compatible with VB00251G, VB00561F or newer versions.
4. 3. 3. 2. NXP00002V158
• Hardware compatible with VB00251G, VB00561F or newer versions.
• Fixed F25_31 fault from CAN-module.
4
Faultcodes and software 15
4. 3. 3. 3. NXP00002V159
• Hardware compatible with VB00251G, VB00561F or newer versions.
• Fixed F43_7-fault, which appeared with some NXOPTBB boards when using absolut
encoder.
4. 3. 3. 4. NXP00002V160
• Hardware compatible with VB00251G, VB00561F or newer versions.
• "Prevention of start up" fault sub code changed to 30.
• Fixed reversing problem when in current limit at zero speed.
• Fixed malfunction for F1, F2 and F7 when control unit first powered up and then
power unit powered up later.
• F25 -> S31, S32, S34 and S39. Power PC specific "crash place" information to
EEPROM, overwriting the fault history. (Only NXP).
4. 3. 3. 5. NXP00002V161
• Fixed problem for F32. It did not appear, even if the FAN feedback is missing.
• Hardware compatible with VB00251G, VB00561F or newer versions.
• Known feature: option board parameters are not shown on the display if the option
board data is old (EEPROM data is wrong). Board data has to be updated.
The control unit must be checked separately in fault situations. Instructions how to
test the control unit using NC Service is in another section.
Most of the procedures for the different fault codes only explain how to proceed with
the power unit section.
These following flow charts cover fault codes in software versions until "NXSV151"
(11.55.6639) and "NXPV145" (12.26.7284).
Fault codes in the newer system softwares are available in the table in this section.
service@vacon.com Tel +358 (0)201 212 575 Fax +358 (0)204 335 091
4
16 Faultcodes and software
F1 C h e c k if p a r a m e te r s
D id f a u l t c o r re s p o n d to t h e lo a d .
displayed.
o c c u r e s e v e r a l tim e s C h a n g e a c c e l e r a t i o n t im e ,
C h e c k lo g g e d YES
w h e n m o to r w a s U /f c u r v e , c u r r e n t s e ttin g s ,
d a t a in
r u n n in g w ith lo a d ? e t c . S t a r t a g a in w ith
faulthistory.
c h e c k e d / c o r r e c t e d s e t ti n g s .
NO
R e m o v e m o to r c a b le s
D id F 1
and
a p p e a r a g a in ?
p o w e r u p d r iv e t o
s ta n d b y - m o d e . NO
YES
M e a s u r e a ll
G iv e s ta r t c o m m a n d
D id F 1 o u t p u t p h a s e c u r re n t s
a n d in c r e a s e o u tp u t NO
a p p e a r a g a in ? a n d c o m p a r e to
f re q u e n c y t o
m o n i to r in g p a g e .
m a x iu m v a lu e .
YES
W as
m e a s u re m e n ts
D id F 1 NO same as
YES
a p p e a r a g a in ? displayed
value?
NO YES
I n t e r n a l f a u lt :
C h e c k c u rre n t m e a s u r e m e n t
circuit.
E x t e r n a l f a u l t:
C u r r e n t c u t te r t i m e t o o l o n g .
C h e c k m o t o r , m o t o r c a b l e , m o t o r lo a d .
I n s t a l l o u t p u t f il t e r s .
W ro n g
p a r a m e t e r s e t ti n g .
4
Faultcodes and software 17
C h e c k if p a r a m e t e r s
F 2 d is p la y e d . D i d f a u lt o c c u r e c o r re s p o n d to t h e lo a d .
C h e c k lo g g e d s e v e r a l tim e s w h e n C h a n g e d e c e l e r a t io n t i m e ,
d a ta in YES
m o to r w a s u s e o f b r a k e c h o p p e r e t c .. .
faulthistory. running? S t a r t a g a i n w it h
c h e c k e d / c o r r e c t e d s e t ti n g s .
NO
D id f a u l t o c c u r e i n
NO D id F 2 o c c u r e
s ta n d b y - m o d e ?
again?
NO
YES YES
M e a s u r e v o l ta g e
in D C - b u s a n d
c o m p a r e i t to
m o n ito r e d v a lu e .
W a s m e a s u re m e n t
s a m e a s d i sp la y e d YES
value?
NO
Internal fault:
C h e c k th e v o lta g e
m e a s u r e m e n t c i r c u it .
NOTE: T r i p l i m i ts E x t e r n a l f a u lt :
NX2 = 437V DC F a u lt w a s g e n e ra t e d fo r a re a s o n .
NX5 = 911V DC S u d d e n c h a n g e s in m a i n s v o l t a g e ,
NX6 = 1200V DC v o l ta g e s p i k e s i n t h e m a i n s ,
t e m p o r a r y f e a t u r e o f lo a d , b r e a k
r e s i s t o r t o o s m a l l.
service@vacon.com Tel +358 (0)201 212 575 Fax +358 (0)204 335 091
4
18 Faultcodes and software
F 3 d is p la y e d .
C h e c k lo g g e d D id f a u l t o c c u r e
d a ta i n s e v e r a l tim e s w h e n NO
faulthistory. m o to r w a s r u n n in g ?
YES
D i d f a u l t o c c u r e in
YES NO
Disconnect s ta n d b y -m o d e ?
m otor cable
f r o m d r iv e a n d
give start
command. M e a s u re o u tp u t
c u r r e n t s in a l l
phases.
D id F 3
appear YES
again?
A r e a ll p h a s e s
NO YES
equal?
NO
I n t e r n a l f a u lt .
C h e c k c u r re n t
m e a s u r e m e n t c ir c u it .
E x t e r n a l f a u l t.
S o f t w a r e t r ig g e d - t h e s u m o f
m o t o rp h a s e c u r re n t is n o t ze r o .
D a m a g e d m o to r o r m o t o r
cable.
4
Faultcodes and software 19
F 4 d is p l a y e d .
C h e c k lo g g e d S e r v i c e a c t io n s a r e
d a t a in b a s e d o n u n i t s iz e .
faulthistory.
F a u lt o c c u r e d d u e to D r iv e r v o l ta g e i s t o o
in t e r fe r e n c e , b e c a u s e lo w o n t h e a s i c b o a r d .
s i g n a l is n o t u s e d .
F a u lt a c tiv a t e d b e c a u s e
p o w e r b o a r d is to o h o t
o r f a u lty p o w e r b o a r d .
NOTE !
< F R 7 - fa u l t is n o t u s e d .
F r 7 - F R 8 - " P o w e r C a r d o v e r te m p e r a t u r e " w ill in d ic a t e F 4 .
F r 1 0 - " D r iv e r p o w e r t o o l o w " w i l l i n d i c a t e F 4 .
service@vacon.com Tel +358 (0)201 212 575 Fax +358 (0)204 335 091
4
20 Faultcodes and software
F 5 d is p l a y e d . C h e c k
I f fa u l t T e s t th e c o n t r o l
lo g g e d d a t a i n
board.
faulthistory.
R e p l a c e c o n t ro lb o a r d a n d
D id i t p a s s t h e l o a d s o f t w a r e i n t o i t.
NO
test? R e m e m b e r p a r a m e te r
settings.
YES
P o s s i b le f a u l t i n c a b l e
c o n n e c t i o n b e t w e e n c o n t r o l- N o i n s t r u c t io n s
a n d p o w e r b o a r d . R e p l a c e it. available!
4
Faultcodes and software 21
FIGURE
FIGURE 7. Fault
Fault code
code F6
F 6 E m e rg e n c y s t o p f au lt
F 6 d is p la y e d .
D id F 6 o c c u r e
C h e c k lo g g e d
s e v e r a l tim e s d u r in g NO
d a ta in
n o r m a l o p e r a t io n ?
faulthistory.
YES
Test
controlunit.
D id i t p a s s t h e
NO
test?
R e p l a c e c o n t r o lb
lb o a r d . YES
L o a d s o f tw a r e a n d a ls o
p a r a m e t e r s e t tit i n g s .
I n e r n a l in
i n t e r f e r e n c e t r igi g g e d
t h e f a u l t.t . C h e c k
c o n n e c t io n s b e tw e e n
c o n t ro l b o a r d a n d
I/O - b o a r d s .
E x t e r n a l r e a s o n t r igi g g e d t h e
f a u lt.C h e c k c a b le
connections.
NOTE!
F a u l t is t rig g e d f ro m p i n - 6 i n
e a c h I /O
/ O - s lo
lo t . S ig n a l n o t
u s e d in s t a n d a r d I /O - b o a r d s .
service@vacon.com
service@vacon.com Tel +358
+358 (0)201 212 575 Fax +358 (0)204 335 091
4
22 Faultcodes and software
FIGURE
FIGURE 8. Fault
Fault code
code F7
F 7 S a t u r a tio n fa u lt
M e a s u re
F 7 d is p la y e d . isolation
C h e c k lo g g e d Is b r a k e re s is ta n c e a n d
YES
d a ta i n chopper used? r e s is ta n c e o n
faulthistory. th e b r a k e
resistor
NO
W e re
m e a s u re m e n ts YES
O K?
FR9-FR13 FR4-FR8 NO
F a u l t c a u s e d b y f a u l tyt y
b r a k e r e s is t o r .
M e a s u re C h a n g e it.
N o i n s t r u c t io
io n s p o w e rm o d u le
available! d ir e c tly f r o m it s
te r m in a ls .
M e a s u re b r a k e
chopper.
R e p la c e b r o k e n W e r e a ll
p o w e r m o d u le a n d NO m e a su re m e n t
pow er board. s OK?
W e r e a ll
YES YES m e a s u re m e n t
s OK?
NO
G iv e s t a r t C h e c k c a p a c ito r s .
c o m m a n d a nd ru n R e p la c e t h e
n o m in a l b ro k e n o n e s . R e p la c e b r o k e n
frequency.
p o w e r m o d u le a n d
powerboard.
I n t e r fe
fe r e n c e c a u s e d t h e
p r o b le m . P o s s ib le c a u s e s ,
p o w e r b o a rd , p o w e r m o d u le
o r in t e r n a l c a b l e s .
4
Faultcodes and software 23
FIGURE
FIGURE 9. Fault
Fault code
code F8
F 8 S Y S T E M F A U L T
F 8 d is p la y e d .
C h e c k lo g g e d
C h e c k w itc h s u b fa u ltc o d e o c c u r e d .
d a ta in
faulthistory.
P r o c e e d w i t h f ini n d i n g t h e r e a s o n
b a s e d o n th e fa u lt c o d e .
N O T E !
S ub faultcodes:
1 = O u t p u t p h a s e c o n tr o l fa u lt.
2 = u P w a t c h d o g w i t h o u t ini n i tit i a l izi z a t ioi o n .
3 = V a c o n B u s w a tc h d o g p r o b le m .
4 = S o f t w a r e t r igi g g e d ( a p p l ici c a t i o n ) .
5 = T o o m u c h n o i s e in V a c o n B u s .
6 = Im p o s s i b le t o r e s e t a s ic - c o n tr o lle r .
7 = A s ic - c o n tr o lle r d o e s n o t c lo s e c h a r g e s w itc h .
service@vacon.com
service@vacon.com Tel +358
+358 (0)201 212 575 Fax +358 (0)204 335 091
4
24 Faultcodes and software
C h e c k i f p a r a m e te r s
F 9 d is p la y e d . D id f a u lt o c c u r e c o r r e s p o n d to th e l o a d .
C h e c k lo g g e d s e v e r a l tim e s w h e n C h a n g e d e c e l e ra t io n tim e ,
d a t a in YES
m o to r w a s u s e o f b r a k e c h o p p e r e tc . . .
faulthistory. running? S ta r t a g a in w ith
c h e c k e d / c o r re c t e d s e t ti n g s .
NO
D id F 9 o c c u r e
again?
D id f a u lt o c c u r e in NO
NO YES
s ta n d b y - m o d e ?
YES
M e a s u re v o lta g e
in D C - b u s a n d
c o m p a r e it t o
m o n i to r e d v a l u e .
W a s m e a s ure m e n t
NO s a m e a s d is p la y e d
value?
YES
I n t e r n a l fa u l t :
C h e c k th e v o lta g e
m e a s u r e m e n t c ir c u i t a n d
capacitors.
NOTE: T r i p l i m i ts E x t e r n a l f a u lt:
NX2 = 183V DC
F a u lt w a s g e n e r a te d f o r a r e a s o n .
NX5 = 333V DC
NX6 = 460V DC S u d d e n c h a n g e s in m a in s v o lta g e ,
v o l ta g e d i p s i n t h e m a i n s ,
t e m p o r a r y f e a t u r e o f lo a d .
4
Faultcodes and software 25
F 1 0 d is p la y e d . Measure
C h e c k lo g g e d m a i n s v o l ta g e Voltages,
NO
d a t a in a t m a in s OK?
faulthistory. te r m in a l s
YES
C h e c k if
fuses are
blown.
C h e c k f o r p o s s i b le i n te r n a l D id y o u f in d
YES
f a i lu r e s in t h e i n v e r te r . b lo w n f u s e s ?
NO
I n t e r n a l fa u l t. C h e c k
m a i n s s u p e r v is i o n . W e r e th e r e
NO
b r o k e n p a r ts ?
YES
Replace
broken
parts.
E x te r n a l re a s o n
a c t i v e t e d t h e f a u lt . T o o
lo w v o l ta g e f o r a l o n g e r
t im e .
R o o t c a u s e m ig h t b e
c o m p o n e n t fa ilu r e o r c a u s e d
b y v o l ta g e d i p s in t h e m a i n s .
service@vacon.com Tel +358 (0)201 212 575 Fax +358 (0)204 335 091
4
26 Faultcodes and software
F 1 1 d is p la y e d . M e a s u re A re
C h e c k lo g g e d m o to r c a b le connections NO
d a ta i n connection a n d m o to r O K ?
faulthistory a n d m o to r .
YES
In t e r n a l fa u lt :
C h e c k c u r re n t
m e a s u r e m e n t c i r c u it .
F 1 1 o c c u re d d u e to a n
e x te r n a l f a u lt .
NOTE!
T h is f a u lt m a y o c c u r w ith s m a ll m o t o r
o r w i t h o u t m o t o r in d r iv e w i t h s o f tw a r e
v e r s io n s o ld e r th a n
N X S 0 0 0 0 1 V 1 0 4 = 1 1 . 1 9 .4 8 8 6
N X P 0 0 0 0 2 V 1 0 5 = 1 2 . 0 7 .5 1 0 0
4
Faultcodes and software 27
F 1 2 d i s p la y e d . M e a s u r e re s i s ta n c e a n d
A r e a ll
C h e c k lo g g e d i s o l a t io n r e s i s ta n c e o n
m e a s u re m e n ts NO
d a ta in b r a k e r e s i s to r a n d i t s
O K?
faulthistory. connections.
YES
Replace
M e a s u re b ra k e c h o p p e r brakeresistor
m a i n c i rc u it. and/or
cables.
I n t e r n a l fa u l t : R e p l a c e
Is b r a k e c h o p p e r
NO brakechopper and
m a i n c ir c u it, O K ?
powerboard.
YES
N o i n s t r u c t io n s
M e a s u re available.
brakechopper
g a t e c i rc u it.
Is b r a k e c h o p p e r
NO
g a t e c i r c u i t, O K ?
YES
I n t e r n a l fa u l t:
C h e c k / c o r re c t c a b le s
b e fo r e r e p la c i n g
powerboard.
service@vacon.com Tel +358 (0)201 212 575 Fax +358 (0)204 335 091
4
28 Faultcodes and software
F 1 3 d is p la y e d .
C h e c k lo g g e d R e a d o p e r a t io n t e m p e r a t u r e o f
d a ta in th e u n it f r o m m o n ito r in g p a g e . .
faulthistory.
D id v a lu e c o r re s p o n d to
a m b ie n t te m p e r a t u r e
NO YES
a n d te m p e r a tu r e lo w e r
th a n - 1 0 C .
I n t e r n a l f a u l t: C h e c k t h e
E x t e r n a l f a u lt : T e m p e r a t u r e is
te m p e r a tu r e m e a s u rm e n t
to o lo w .
circuit.
NOTE!
F R 9 : P o w e rb o a rd h a s its o w n
te m p e r a tu r e m e a s u r e m e n t , w h i c h
c a n a c tiv a t e F 1 3 .
4
Faultcodes and software 29
F 1 4 d i s p la y e d .
C h e c k lo g g e d R e a d o p e r a t io n t e m p e r a t u r e o f
d a t a in t h e u n i t f ro m m o n i t o r in g p a g e . .
faulthistory.
D id v a l u e c o r re s p o n d E x t e r n a l fa u l t :
NO to a m b ie n t YES T e m p e r a t u re is to o
te m p e r a t u re . high.
Check
o p e r a ti o n o f
th e f a n
C h e c k c o n d itio n
D i d f a n o p e r a te
YES o f t h e c o o l in g
properly?
e le m e n t .
NO
I n t e r n a l f a u l t: C h e c k W a s t h e c o o l in g
YES NO
c i rc u i t ry f o r t h e f a n a n d e l e m e n t c le a n ?
t h e f a n i ts e lf .
In t e r n a l f a u l t: C h e c k t h e
te m p e r a t u re E x te r n a l f a u lt: M a k e s u r e
m e a s u r m e n t c i r c u it . th a t u n i t g e ts c l e a n a ir .
NOTE!
F R 9 : P o w e rb o a r d h a s its o w n
t e m p e r a tu r e m e a s u r e m e n t , w h i c h
c a n a c t iv a t e F 1 4 .
service@vacon.com Tel +358 (0)201 212 575 Fax +358 (0)204 335 091
4
30 Faultcodes and software
F 1 5 d is p l a y e d .
C h e c k lo g g e d C h e c k i f m o to r Is m o to r
d a t a in YES
rotating. rotating?
faulthistory.
M e a s u re
NO m o t o r c u r r e n t in
all pha ses .
C o m p a re v a lu e s
t o m o n it o r in g
page.
C h e c k / c o r r e c t p a r a m e t e r s e t ti n g . K e e p i n
m i n d t h e m e c h a n i c a l r a t i n g s o f th e
e q u i p m e n t.
- S t a l l c u r r e n t li m i t
- S t a ll f re q u e n c y W as
- S t a ll f re q u e n c y g a p measurement
YES
S ta ll tim e s am e a s
d i s p la y e d v a l u e ?
NO
P o s s i b l e t o c o r re c t P r o t e c t i o n a c t iv a t e d
p a r a m e te r NO fo r a r e a s o n .
settings?
YES
Is u n i t
functioning
NO
b e t t e r w it h n e w
settings?
I n t e r n a l f a u l t: C h e c k
YES c u r re n t m e a s u r e m e n t
circuit.
T e m p o r a r y lo a d a c t iv a t e d
t h e p r o t e c t io n .
4
Faultcodes and software 31
F 1 6 d is p la y e d .
S o f tw a r e b a s e d t e m p e r a t u r e m o d e l
C h e c k lo g g e d
t ri g g e d t h i s f a u l t .
d a ta i n
M e a s u re t e m p e r a tu r e o f m o to r .
faulthistory.
Is t h e te m p e ra t u re
h i g h e r th a n th e r m a l
NO YES
c a p a b i li t y o f th e
m o to r .
C h e c k t h e p a r a m e t e r s f o r th e r m a l
protection.
E x t e r n a l re a s o n f o r th e f a u l t:
Can M o t o r i s o v e r lo a d e d .
p a r a m e te r s b e NO -D e c re a s e lo a d .
adjusted? - A d d i to n a l c o o l in g o f m o t o r is
needed.
YES
A d j u s t p a r a m e t e r s a n d t ry a g a i n .
E x t e r n a l f a u lt: W ro n g
F 1 6 a g a in ? NO p a r a m e t e r s e t ti n g
t ri g g e d t h e f a u l t .
M e a s u re
o u tp u t c u r r e n t .
D i d m e a s u re d =
YES
M o n ito r e d v a lu e ?
NO I n t e r n a l fa u l t : C h e c k
c u r re n t m e a s u r e m e n t
circuit.
service@vacon.com Tel +358 (0)201 212 575 Fax +358 (0)204 335 091
4
32 Faultcodes and software
F 1 7 d is p l a y e d .
C h e c k lo g g e d S o f tw a r e h a s t r i g g e d t h i s f a u l t .
C h e c k / c o r r e c t u n d e r lo a d
d a t a in
p r o t e c t io n p a r a m e t e r s .
faulthistory.
Can
p a r a m e te r s b e NO
corrected?
D id F 1 7 Adjust YES
YES occure p a r a m e te r s a n d
again? t ry a g a in .
NO
W ro n g
p a r a m e t e r s e t tin g .
E x t e r n a l f a u l t t r ig g e d
t h is p r o t e c t io n .
M e a s u r e m o t o r c u r re n t a n d c o m p a r e
v a l u e o n m o n i to r in g p a g e .
Is m e a s u r e d c u r r e n t
YES = m o n ito r e d
current?
NO
I n t e r n a l f a u l t: C h e c k t h e
c u r r e n t m e a s u r e m e n t c ir c u it
4
Faultcodes and software 33
F 2 2 d i s p la y e d .
C h e c k lo g g e d
d a t a in C h e c k s u b f a u lt c o d e
faulthistory.
2 - > C r it ic a l 1 0 - > C r it ic a l
O th e r
fault fault
A n y p a r a m e t e r in s o f tw a r e A n y p a r a m e t e r in
D a t a w h i c h p o s s ib l y is
o r a p p l i c a t io n c o u l d b e l o s t . s y s te m m e n u c o u l d b e
c r i ti c a l f o r o p e r t i o n i s
C h e c k / c o r re c t a ll lo s t . C h e c k / c o r r e c t
lost.
p a r a m e te r s . p a r a m e te r s .
D i s c o n n e c t in p u t p o w e r f r o m d r iv e a n d
w a i t u n t i l in t e r n a l p o w e r s u p p l y s h u t s
d o w n a g a in . P o w e r u p a g a i n .
YES F 2 2 a g a in ? NO
E x te r n a l f a u l t s u c h a s
I n t e r n a l f a u l t in c a b l e
in t e r fe r e n c e o r p o o r
c o n n e c t io n o r G N D - c o n n e c t io n
c o n tr o lb o a r d p o s s ib l e .
possible.
NOTE !
P a r a m e t e r f a u lt o c c u r e s w h e n t h e t w o la s t c h e c k s u m s a r e n o t e q u a l. C h e c k s u m c a l c u la t e d o n
powerdown.
NOTE !
Subfaultcode:
1 = F ir m w a r e in t e rf a c e p o w e r d o w n v a r ia b l e c h e c k s u m e r r o r , s u c h a s c o u n te r e t c .
2 = F i r m w a r e i n t e r f a c e v a r ia b l e c h e c k s u m e r r o r .
3 = S y s t e m p o w e r d o w n v a r ia b l e c h e c k s u m e r r o r . D a t a p o i n t e r l o s t .
4 = S y s t e m p a r a m e t e r c h e c k s u m e r r o r fo r d e f a u l t p a g e a n d m u l t i m o n i to r in g .
5 = A p p l i c a t io n d e f in e d p o w e r d o w n v a r ia b l e c h e c k s u m e r r o r f o r c o u n t e r o r r e f e r e n c e .
6 = A p p l i c a t io n d e f i n e d p a r a m e t e r v a r i a b l e c h e c k s u m e r r o r f o r c o u n t e r o r r e f e r e n c e .
1 0 = S y s t e m p a r a m e t e r c h e c k s u m e r r o r f o r f a u l t h i s t o r y e n t r ie s o r s y s t e m m e n u p a r a m e t e r .
service@vacon.com Tel +358 (0)201 212 575 Fax +358 (0)204 335 091
4
34 Faultcodes and software
4
Faultcodes and software 35
F 2 5 d is p la y e d .
C h e c k lo g g e d C h e c k s u b f a u lt
d a ta i n code.
faulthistory.
C h e c k th e p a r a m e te r s a n d s ta r t u p t h e
u n i t a g a i n . R e p e a t th e p r o c e s s w i t c h
c a u s e d t h e d r i v e t o t r ip .
YES F 2 5 a g a in ? NO
In t e r n a l f a u l t d u e t o c o n t r o l
N o f a u lt. O n c e o c c i n g
b o a r d f a i lu r e o r s o f t w a r e
trip.
fault.
NOTE:
1 = C pu w a t c h d o g t im e r .
2 = A s ic reset.
11-14 = N X S s p e c ia l c o d e s .
31-51 = N X P s p e c ia l c o d e s .
NOTE:
I f th i s f a u l t o c c u r e s i n p a r t ic u l a r s i t u a t i o n .
- > S t o r e p a r a m e t e r s e t t i n g a n d c o n t a c t s o f tw a r e
vendor.
- > U p d a t e s o f tw a r e .
service@vacon.com Tel +358 (0)201 212 575 Fax +358 (0)204 335 091
4
36 Faultcodes and software
F 2 6 d i s p la y e d .
C h e c k lo g g e d
d a ta in
faulthistory.
F a u lt is t o b e
c o n s id e re d a s
i n f o r m a t io n o n l y .
NOTE!
S o f t w a r e t r ig g e d f a u l t . F a u l t c a n
o c c u r e i n o v e r v o l t a g e s i tu a t i o n .
I f a v a r i a b l e c h a n g e s d u r in g
o v e r v o l ta g e t h e n F 2 i s r e p l a c e d
by F26.
4
Faultcodes and software 37
F 2 9 d is p l y e d .
T h e r m i s t o r in p u t o n
C h e c k e d lo g g e d
o p tio n b o a r d
d a ta in
d e te c te d th i s f a u lt.
faulthistory.
Check
th e r m is to r
c o n n e c tio n a n d
m o to r
te m p e ra tu r e .
E x t e r n a l fa u lt. C o r re c t
th e th e r m is to r o r
c o o l i n g o f th e m o t o r .
NOTE!
T h e r m is t o r in p u t h a s to b e
s h o r tc i rc u it e d i f t h e r m is t o r
not used.
service@vacon.com Tel +358 (0)201 212 575 Fax +358 (0)204 335 091
4
38 Faultcodes and software
F 3 1 d i s p la y e d . C h e c k / c o r r e c t p a r a m e t e r s e ttin g . D id F 3 1
C h e c k lo g g e d A c c e l e r a t io n , c u r r e n t s e t t in g s , a n d appear NO
d a ta i n U / f- s e t ti n g s , s w i t c h i n g f re q u e n c y e t c . again?
faulthistory.
Correct YES
p a r a m e t e r s a g a in .
C h a n g e s e v e ra l
tim e s i f n e e d e d .
D id F 3 1 P a r a m e t e r s e t ti n g
appear NO g e n e r a t e d t h i s f a u l t.
again?
YES
M easure output
c u r r e n t in a l l p h a s e s
a n d c o m p a re t o
m o n i to r in g p a g e .
M e a s u re d E x t e r n a l r e a s o n g e n e r a te d
c u r re n t = t h is f a u lt. P r o b le m w ith
NO
m o n i to r e d m o t o r o r o u t p u t fi l t e r s
current needed.
YES
I n t e r n a l fa u l t : C h e c k
te m p e r a tu r e m e a s u re m e n t
c i r c u i t o r d r i v e i s t o o s m a l l.
NOTE!
F 3 1 o c c u rs o n ly fro m F R 9 a n d b i g g e r fra m e
s iz e s / C H 6 1 a n d b ig g e r c h a s s is .
NOTE!
I f F 3 1 a n d F 4 1 o c c u r s a t th e s a m e t im e .
U s e F 4 1 t r o u b l e s h o o t in g .
4
Faultcodes and software 39
F a n d o e s n o t s t a r t,
F 3 2 d is p la y e d .
w h e n "O N " A r e b o th
C h e c k lo g g e d NO
- c o m m a n d i s g iv e n . le d s "o n "
d a t a in
C h e c k fa n - in v e r te r c o n tin u e s l y ?
faulthistory.
f o r v is i b l e d a m a g e .
YES
D is c o n n e c t a n d c h e c k fa n . P o w e r s u p p l y fa u l t o r
M e a s u r e w i n d i n g r e s is t a n c e " O N " - c o m m a n d m i s s in g .
a n d i n s u l a tio n r e s is t a n c e . S e e " N O T E " w in d o w .
W e r e a ll
m e a s u re m e n ts P o w e r d r iv e , w i th
NO YES
O K? fa n d is c o n n e c t e d .
R e p l a c e f a u lty f a n .
C h e c k a t le a s t f a n
c a p a c i to r a n d f a n - in v e r te r .
M e a s u re o u t p u t I s "g r e e n " l e d
YES
f ro m i n v e r te r . blinking?
NO
Foun d appr. 260V
NO
on all ou tputs?
F a n - i n v e r te r fa u l t .
Also check fan
YES capacitor.
C a p a c i to r f a u l t .
NOTE:
T h i s f a u l t e x i s t i n F R 8 o r b ig g e r d r i v e s .
F R 8 p o w e r c a b le b e t w e e n p o w e r b o a r d a n d
f a n - i n v e r te r c o n t a i n 0 - o h m r e s i s t o r .
P r o b l e m c a n b e i n f a n , f u s e s , f a n - c a p a c i to r , f a n - i n v e r te r , p o w e r - ,
c o n t ro l b o a r d o r c a b le s b e tw e e n th e s e .
C h e c k i s o l a t io n t r a n s f o r m e r a n d o u t p u t - c o m m o n - m o d e f i l t e r ,
i f d r iv e i s e q u i p p e d w i t h s u c h .
service@vacon.com Tel +358 (0)201 212 575 Fax +358 (0)204 335 091
4
40 Faultcodes and software
F 3 4 C A N c o m m u n i c a t io n f a u lt
F 3 4 d is p la y e d .
C h e c k lo g g e d
d a ta i n
faulthistory.
Sent m essage
is n o t
acknowledged.
R e c o n fig u r e o n e o f th e
d r iv e s w itc h h a s g o t C h e c k c a b l e c o n d itio n
l i a n d c o n n e c tio n s .
4
Faultcodes and software 41
F 3 5 d is p la y e d .
C h e c k lo g g e d
d a ta i n
faulthistory.
Application
s c h e d u le r is
overloaded.
C h e c k s u b fa u lt c o d e a n d c o n ta c t
a p p lic a tio n d e v e lo p e r if p r o b le m
o c c u r e s s e v e r a l tim e s .
NOTE:
S u b f a u l t c o d e 8 9 : O v e r lo a d o n 1 m s le v e l .
S u b f a u l t c o d e 9 0 : O v e r lo a d o n 5 m s le v e l .
S u b f a u lt c o d e 9 1 : O v e r lo a d o n 1 0 m s le v e l .
S u b f a u l t c o d e 9 2 : O v e r lo a d o n 1 0 0 m s le v e l.
S u b f a u l t c o d e 9 3 : O v e r lo a d o n 1 0 0 0 m s le v e l .
S u b f a u l t c o d e 9 5 : A p p l ic a t i o n i s n o t s t a r t e d . .
service@vacon.com Tel +358 (0)201 212 575 Fax +358 (0)204 335 091
4
42 Faultcodes and software
F 3 6 d is p l a y e d .
C h e c k lo g g e d
d a t a in
faulthistory.
D id f a u l t o c c u r e a t
f ir s t p o w e r u p a f te r
NO s e r v ic e b e e n p e r f o r m e d ? YES
W a s a n e e p ro m
re p ro g r a m e d ?
E n te r e d e e p r o m d a t a
Eeprom i n c o m p a t i b l e w i t h e x i s ti n g
corrupted. s y s t e m s o f tw a r e .
R e p l a c e t h e b o a r d w i th c o r r u p t e d
C h e c k p r o g r a m e d p o w e r u n it
e e p r o m , if it c a n n o t b e
d a t a a n d c o r r e c t w r o n g s e t ti n g .
r e p r o g ra m e d .
NOTE:
S o f tw a r e i s i n c o m p a t ib l e
w i t h e x i s ti n g p o w e r u n i t .
4
Faultcodes and software 43
F 3 7 d is p la y e d .
C h e c k
subfaultcode..
In d ic a t o n s h o u l d a p p e a r
w h e n s a m e ty p e o f
d e v i c e w ith d if f e r e n t
s e r ia ln u m b e r h a s b e e n
c h a n g e d .
In d ic a tio n o n ly , n o f a u lt.
N O T E :
S u b f a u ltc o d e d is p la y e d :
1 = C o n tr o lc a r d
2 = C o n tr o l u n it
3 = P o w e rc a rd
4 = P o w e ru n it
5 = A d a p te r c a r d
A = S lo t A
B = S lo t B
C = S lo t C
D = S lo t D
E = S lo t E
service@vacon.com Tel +358 (0)201 212 575 Fax +358 (0)204 335 091
4
44 Faultcodes and software
F 3 8 d is p la y e d .
C h e c k
subfaultcode..
In d ic a t o n s h o u l d a p p e a r
w h e n o p t io n b o a r d o r
a d a p te r h a s b e e n
a d d e d .
In d ic a tio n o n ly , n o f a u lt.
N O T E :
S u b f a u ltc o d e d is p la y e d :
1 = C o n tr o lc a r d
2 = C o n tr o l u n it
5 = A d a p te r c a r d
A = S lo t A
B = S lo t B
C = S lo t C
D = S lo t D
E = S lo t E
4
Faultcodes and software 45
F 3 9 d is p la y e d .
C h e c k
subfaultcode..
In d ic a t o n s h o u l d a p p e a r
w h e n o p t io n b o a r d o r
a d a p te r h a s b e e n
re m o v e d .
In d ic a tio n o n ly , n o f a u lt.
N O T E :
S u b f a u ltc o d e d is p la y e d :
5 = A d a p te r c a r d
A = S lo t A
B = S lo t B
C = S lo t C
D = S lo t D
E = S lo t E
service@vacon.com Tel +358 (0)201 212 575 Fax +358 (0)204 335 091
4
46 Faultcodes and software
F 4 0 d is p la y e d . D id f a u l t o c c u r e a t
E e p r o m d a ta o n a
Check f ir s t p o w e r u p a f t e r NO
b o a r d i s i n v a l id .
subfaultcode. a b o a r d re p l a c e m e n t ?
YES
Eeprom
corrupted.
D id y o u p r o g r a m th e
E n t e re d e e p r o m d a t a
YES e e p r o m o r is it f a c t o r y
is n o t v a li d .
p r e -p r o g ra m e d ?
NO
C h e c k p r o g ra m e d E e p r o m is n o t p ro g r a m e d .
p ro g r a m e d d a ta P r o g r a m it a c c o r d in g to v a lid
a n d c o r r e c t it . instructions.
R e p l a c e t h e b o a r d w i th
c o r r u p te d e e p r o m , if it c a n
n o t b e r e p ro g r a m e d .
NOTE:
S u b f a u l tc o d e d i s p l a y e d :
1 = C o n t r o lc a r d
2 = C o n t ro l u n it
3 = P o w e rc a rd
4 = P o w e r u n it
5 = A d a p te r c a rd
A = Slot A
B = Slot B
C = S lo t C
D = S lo t D
E = Slot E
4
Faultcodes and software 47
F 4 1 d is p l a y e d . Software C h e c k s ta t u s o f , a t
C h e c k lo g g e d h a s d e t e c te d to o Status
reference.
d a ta in h i g h s h o r t te r m = "1"
Is it "0" o r "1"?
faulthistory. overload.
O v e r lo a d o r
in t e r n a l f a u lt
Status
c a u s e d t h e t r ip .
= "0"
D r iv e c a n n o t r e a c h
NO F 4 1 a g a in ? r e fe r e n c e . C h a n g e
p a r a m e t e r s e t t i n g , if
possible.
D r iv e i s t o o s m a l l i f
s o ftw a r e u p d a te a n d
p a r a m e te r c h a n g e s d i d
not help.
W a s m e a s u re d
NO v a l u e s = m o n i to r e d
value?
YES
I n te r n a l fa u lt in c u r r e n t
m e a s u r e m e n t c i r c u it .
M e a s u re
C ir c u i t
NO te m p e r a t u re
is O K ?
circuit.
Intern al fau lt in
te m p e r a t u re
m e a s u r e m e n t c i r c u it . YES
A c t u a l o v e r lo a d
U p d a t e s y s t e m s o f tw a r e , i f c a u s e d t h e t r ip .
p o s s i b le o r p r o v i d e c o ld e r D e c r e a s e lo a d o r
c o o l in g a i r . D r iv e i s t o o m a k e c h a n g e s to
s m a ll. p a r a m e t e r s e t ti n g s .
NOTE:
C a l c u l a te d t e m p e r a t u r e i n t e g r a l b a s e d o n m e a s u r e d c u r r e n t , i s a d d e d t o m e a s u r e d t e m p e r a t u r e
t o d e s c r ib e t e m p e r a t u r e r i s e o f th e I G B T ´ s .
W h e n u n i t t r ip s a n d g o e s i n t o s ta n d b y - m o d e , th e v a l u e s i s s to r e d .
P a r a m e t e r s to c h e c k a r e a c c e l e r a t io n t i m e , U / f - c u r v e , c u r r e n t l i m i t ,
D C - b ra k i n g o r s w itc h in g fr e q u e n c y .
service@vacon.com Tel +358 (0)201 212 575 Fax +358 (0)204 335 091
4
48 Faultcodes and software
Software
F 4 2 d i s p la y e d .
h a s d e t e c te d to o I s it p o s s i b l e t o s l o w
C h e c k lo g g e d NO
h ig h te m p e r a t u re d o w n th e p ro c e s s ?
d a ta i n
o n i n te r n a l
faulthistory.
brakeresistor.
YES
I n c r e a s e d e c c e l e r a t io n
tim e a n d s t a r t a g a i n .
NO F 4 2 a g a in ? YES
YES
F a u lt o c c u r e d d u e to
w r o n g d im e n s io n i n g
o f b r a k e r e s i s to r .
I n s t a l l p r o p e r ly
W r o n g p a ra m e te r
d im e n s i o n e d , e x te r n a l
setting.
e x t e r n a l b r a k e r e s is to r a n d
m a k e p a r a m e te r ch a n g e s .
NOTE:
T h is f a u lt c o d e c a n a p p e a r o n l y w h e n in t e rn a l
b r a k e r e s i s t o r a n d i n t e r n a l b r a k e c h o p p e r is u s e d .
4
Faultcodes and software 49
F 4 3 d i s p la y e d . T a k e c o r r e c t iv e
Check a c t io n s b a s e d o n
subfaultcode. subfault code .
C h e c k s t a te o f V i s ib l e f a u l t o n
NO Is status "run "? NO
optioncard. e n c o d e r c a b le ?
YES
YES
M e a s u re
encoder
pulses.
P u ls e s O K ? NO
YES
O p t io n c a r d f a u l t y E n c o d e r o r - c a b l in g f a u l t .
NOTE:
1 : C h a n n e l A m i s s in g
2 : C h a n n e l B m i s s in g
3 : B o t h c h a n n e ls m is s in g .
4 : E n c o d e r r e v e r se d .
5 : C a r d is m i s s i n g
service@vacon.com Tel +358 (0)201 212 575 Fax +358 (0)204 335 091
4
50 Faultcodes and software
F 4 4 d is p la y e d . S t o re p a r a m e te r s to
Check U s e o ld p a ra m e te r s ? YES pan el or PC . Press
subfaultcode. reset.
NO
Download
P r e s s r e s e t. p a r a m e t e r s e t to
drive.
D r iv e w i l l n o w h a v e d e f a u l t
p a r a m e te r s . S e t n e e d e d
p a r a m e te r s .
D r iv e w i l l n o w h a v e
d o w n lo a d e d p a r a m e te r s .
C h e c k th e m o s t c r itic a l
p a r a m e t e r s b e f o r e e n t e r in g
" R U N " -m o d e .
NOTE:
R e a d S e r v ic e B u l l e t i n 0 3 0 3 . A v a i l a b l e i n N X S V 1 2 8 / N X P V 1 2 2 o r n e w e r . C o p y
p a r a m e t e r s to p a n e l o r P C b e f o r e p r e s s i n g r e s e t . A f t e r p r e s s i n g r e s e t , d r i v e w i l l u s e
d e f a u l t p a r a m e t e r s . F 4 4 a p p e a r s w h e n p o w e r u n i t o f d i f f e r e n t s i z e o r v o l ta g e i s
c o n n e c t e d t o s a m e c o n t r o l u n i t . F 4 4 a p p e a r s if n e w o p t i o n c a r d i s o f d i ff e r e n t t y p e .
1 : C o n tr o lc a r d
2 : C o n tr o lu n it
3 : P o w e r c a rd
4 : P o w e r u n it
5 : A d a p t e r c a rd
A : S lo t A
B : S lo t B
C : S lo t C
D : S lo t D
E : S lo t E
4
Faultcodes and software 51
F 4 5 d is p la y e d .
Check
subfaultcode.
P r e s s r e s e t.
S e t o p tio n b o a r d p r a m e t e r s
as needed.
N O T E :
R e a d S e r v ic e B u l l e t i n 0 3 0 3 .
A v a ila b l e in s o f tw a r e N X S V 1 2 8 / N X P V 1 2 2 o r n e w e r .
F 4 5 a p p e a r s if n e w o p tio n c a r d o f d i ffe r e n t ty p e is i n s e r te d in s a m e s lo t .
O p t io n b o a r d p a r a m e t e r s a r e s e t to d e fa u lt.
1 : C o n t ro l c a r d
2 : C o n tr o lu n it
3 : P o w e r c a rd
4 : P o w e r u n it
5: A da pter card
A : S lo t A
B : S lo t B
C : S lo t C
D : S lo t D
E : S lo t E
service@vacon.com Tel +358 (0)201 212 575 Fax +358 (0)204 335 091
4
52 Faultcodes and software
Value
NO YES
> 4mA?
Value
NO YES
OK?
4
Faultcodes and software 53
F 5 2 d is p l a y e d . Empty
C h e c k d a ta in YES
panel?
fau lt history.
M e a s u re + 9 V
NO b e t w e e n p in s 1 a n d
2 o n c o n n e c t o r.
C o m m u n i c a tio n f a u lty
in p a n e l o r
controlboard.
NO 9 V p r e s e n t?
YES
C o n t r o lb o a r d f a u lt y.
P o s s ib l e f a u l t lo c a t io n s a r e
a t c a b l e b e tw e e n p a n e l
a n d c o n t ro l b o a r d o r
NOTE:
controlboard.
F a u l t c a n o c c u r e w h e n p a n e l is
t h e a c t iv e c o n t r o l p l a c e .
service@vacon.com Tel +358 (0)201 212 575 Fax +358 (0)204 335 091
4
54 Faultcodes and software
F 5 3 d is p la y e d . C h e c k c a b le s a n d
C h e c k d a ta in earth-
f a u lt h is t o r y . connections.
C h e c k f ie ld b u s
Cables c o m m u n i c a tio n s ta t u s
NO YES f ro m o p t io n b o a r d
OK?
h a r d w a r e o r s o f tw a r e .
C o m m u n ic a tio n
NO
OK?
Non-shielded
fieldbus-cables,
d is tu r b a n c e , o r p o o r
YES
earth-connection
C h e c k i f d r iv e
r e c o g n iz e s th e
optionboard.
Board
F i e ld b u s o p t io n b o a r d NO recognizesed
faulty. ?
YES
F a u l t in f ie l d b u s - m a s t e r .
R e s e t o f m a s te r n e e d e d .
4
Faultcodes and software 55
F 5 4 d i s p la y e d .
S ta r t- u p o f n e w
C h e c k d a ta i n
optionboard
f a u l t h i s to r y .
I n i t ia l is a t io n s t a t e i s
a c t iv e o n D id f a u lt o c c u r e
o p t io n b o a r d , b u t when a new
YES
doe s not reach o p t io n b o a rd w a s
"run"-state. p lu g g e d i n ?
NO
C h e c k fo r
W r o n g d a ta in " R U N " -s t a t u s f o r
o p t io n b o a r d e e p r o m e a c h o p tio n b o a r d .
Status
NO YES
"RUN"?
H a r d w a r e f a u l t in A p p l ic a t io n m i g h t
c o n t r o l b o a r d o r o p t io n b o a r d c o m m u n i c a t e w i th o p t io n b o a r d
S P I- c o m m u n i c a t io n . t o o m a n y t i m e s / ti m e s l o t .
A p p l i c a t io n i s t o o h e a v y .
NOTE:
F a u l t o c c u r e s w h e n in t e rn a l
S P I - b u s i s o v e r lo a d e d o r b r o k e n . .
S P I -b u s c o m m u n i c a te s w ith s lo t s
B-E.
service@vacon.com Tel +358 (0)201 212 575 Fax +358 (0)204 335 091
4
56 Faultcodes and software
Temperature limit
F56 displayed. have exeeded the
Check data in board parameters.
fault history. Check PT-100
temperature.
Temperature
Hardware fault on YES within
optionboard limits?
NO
4
Faultcodes and software 57
service@vacon.com Tel +358 (0)201 212 575 Fax +358 (0)204 335 091
4
58 Faultcodes and software
4
Faultcodes and software 59
service@vacon.com Tel +358 (0)201 212 575 Fax +358 (0)204 335 091
4
60 Faultcodes and software
4
Faultcodes and software 61
service@vacon.com Tel +358 (0)201 212 575 Fax +358 (0)204 335 091
4
62 Faultcodes and software
4
Faultcodes and software 63
service@vacon.com Tel +358 (0)201 212 575 Fax +358 (0)204 335 091
4
64 Faultcodes and software
4
Option boards 65
5.1. NXOPT A1
To be updated later.
5.2. NXOPT C3
To be updated later.
5.3. NXOPT XX
To be updated later.
service@vacon.com Tel +358 (0)201 212 575 Fax +358 (0)204 335 091
5
66 Procedures after repair
Before preceding to test, check visually that all parts, wirings and connections are cor-
rect. There will be dangerous voltages present during this test.
Connect power supply's DC+ to unit's B+ main terminal. Locate an internal place for
DC+ connection if drive is without DC+ terminal.
Connect power supply's DC- to unit's B- main terminal. Locate an internal place for
DC- connection if drive is without DC- terminal.
Set power supply voltage setting to zero and switch on DC -power supply.
Set parameter 2.7.4 (id 730) to 0 in standard application. This disables the input line
supervision.
Increase the DC voltage to tripping limit. Check for over-voltage fault (F2) indication
on display.
Switch off DC power supply and wait until DC-link has discharged!
6
Procedures after repair 67
Before preceding to testing check visually all parts, wirings and motor connections are
correct.
Switch on AC supply.
Select application and set correct parameters (e.g. motor). Don't set a too high value
for current limit P2.1.5, too short time for acceleration time P2.1.3 or too short time
for deceleration time P2.1.4.
Run motor without load between from minimum to maximum frequency and measure
output current with a current clamp. Compare current clamp values to unit's monitor-
ing value V1.4.
Load motor to nominal value, if possible, and compare current clamp value to unit's
monitoring value V1.4.
Check that fan operates normally and follow unit temperature from monitoring page
V1.9.
service@vacon.com Tel +358 (0)201 212 575 Fax +358 (0)204 335 091