1019-H8 Eight Supervised Outputs Card: Main Features

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

1019-H8 Eight Supervised Outputs Card

Card mod.1019 H3, used in 1019 series control units, can control up to eight supervised outputs.
It is often used where multiple supervised outputs have to be driven. When utilized in conjunction with 1019-
EV8 it can provide both line supervision and 24 Vdc or 110 Vac power to the controlled devices.

MAIN FEATURES OPERATIONAL MODES


§ Microprocessor technology
§ LED’s for alarms/status indication. Open Outputs normally de-energized
JP1-1
§ On board self-checking functions Closed Outputs normally energized
§ Wire to wire short circuit and open line
monitoring. FRONT PANEL
§ Std. 19” 3HE mounting with locking screw.
§ Dip switches address setting. Led’s indication (S= Output status, F= Line
§ Outputs status programmable as normally condition)
energized or de-energized mode by jumpers
OUT 1-8
OPERATION S Output’s status.
The 1019 H8 provides the electrical monitor of the When LED is on the relevant
controlled outputs; any line malfunction will be output is active.
indicated on card front panel through LED’s and in
detail on 1019 Operator Interface display. F Line Condition.
Outputs are fully programmable through the 1019 When LED is on the relevant
system configuration software. It is therefore output line is in Faulty
possible to independently activate each one of the condition.
eight ouptut channels according to the system logic
needings.

Outputs set
The 1019-H8 outputs can be set as normally
enegized (Fail safe mode) or de-energized.

A MEMBER OF KIDDE PLC


FENWAL IS A REGISTERED TRADE MARK OF KIDDE FENWAL INC.
TECHNICAL CHARACTERISTICS
Model 1019 H8
WIRING
The card is equipped with terminal’s
Part Number SCH 1019/H8-XX (*) board connected to the 1019 I/O rack
by means of a flat cable.
Voltage 22-28 Vdc Customized further terminal strip can
Normal: 40 mA also be provided.

Current Consumption + 10mA when Out active


Max 120 mA
Max output current 500 mA
Max total outputs current 1500 mA
Line monitoring current > 2 mA
Working temperature -10°C +50
Storage temperature -30° C + 70° C
Humidity (RH%) 95% non condensata
Color Ral 9002
Weight 90 g
Dimensions (height std. 19” rack
L. 25 mm P. 150 mm
3HE)
(*)NOTE: Indicates revision index

TYPICAL WIRING DIAGRAM