Protection Features: Relay Design Features:: Local Keys As Well As Remote Setting by Communication Port
Protection Features: Relay Design Features:: Local Keys As Well As Remote Setting by Communication Port
Protection Features: Relay Design Features:: Local Keys As Well As Remote Setting by Communication Port
( AD I T Y A– V 2 S e r i e s )
(Preliminary)
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
9 8 Optically isolated digital status input for values are also displayed on large 20 x 4 LCD
monitoring of status to avoid use of external display for metering purpose. The DSC also
relay logic. monitors different digital input through optical
9 100 nos of event memory, event such CB isolator and perform some monitoring function
close, Trip, digital status change, relay pkp such trip circuit supervision, and control potential
etc. All events are with date and time stamped free contact for control CB and generate ALARM
up to 1ms. and Tele-signalling.
9 10 nos of Fault data stored with keypad The power supply module is basically DC – DC
interface and time stamping.
converted designed using modern PWM based
Switching mode technique to convert 110Vdc
Description :
station battery supply to the 12V and 24Vdc low
ADR241B is second generation of Numerical
voltage supply for relay electronics and control
Over current IDMT/DMT Relay. It consist all the
circuit. It also provides necessary isolation from
necessary protection and monitoring functions
station battery. There are two types of power
required for Normal feeder, it consist of
supply modules available 1) having range of
1. High Speed Digital DSP Controller
77Vdc – 250Vdc. Covering requirement of 110Vdc
2. Analog Measuring Module
and 220Vdc station battery system 2) Wide range
3. Power supply Module
setting 18 Vdc – 250 Vdc.
4. Digital Input output module.
The High speed Digital Signal Controller The relay is having total 8 nos of dual LED of high
continuously monitors line phase current and E/F intensity for easy identification of type of fault for
current. Along with different status input, through easy user interface. LEDs L5, L6 and L7 and
CTs, and optical isolated status connections. The Relay R1 to R6, digital status input and controlled
high-speed micro-controller samples these current output are fully programmable via key pad
signals through a A/D converter. The Digital interface.
Signal performs powerful Numerical Algorithms
Main Functions :
to find out RMS of fundamental & harmonic
The ADR241B are having following protection
contents of the current. All measurement is tuned
functions.
to fundamental frequency i.e 50Hz or 60Hz
1. 4 stages of Phase Over Current element.
depending upon setting, thus relay remain stable
(Ip1>, Ip2>, Ip>> and Ip>>>).
during distorted waveform by various industrial
2. 3 stages of 3Io (Internally derived EF) (3Io>,
load. All these measure values are then used for
3Io>> and 3Io>>>).
different protection function such as IDMT Over
3. 3 stages of Ie (Externally EF or REF) (Ie>,
current protection, Instantaneous Over current
Ie>> and Ie>>>).
protection, E/F protection etc. These measured
4. Trip Circuit Supervision.
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
Negative sequence over current (46) PKP, Relay Reset, CB Trip, CB Close, Change of
The ADR241B relay will be provided with any digital status input, Relay setting changed etc.
programmable function to detect Unbalanced Fault Up to 100 such events can be stored and can be
conditions. When Earth Fault elements do not download for detailed analysis. Apart from Event
operated or not sufficiently sensitive. The ADR241B record Relay also record actual waveform of
relay is included with Negative Phase Sequence current along with all digital and logical status
Over Current element it can be programmed as during fault condition. Up to 10 such waveforms
IDMT or Definite Time. can be recorded; the duration of disturbance
record is 3 sec. The disturbance record can be
Programmable DI/DO and LED:-
trigger from physical status input as well as
The ADR241B Relay is provided with 6 digital
from pick, trip operation of relay. This waveform
outputs, 8 opto-isolated input and 6 general
can be downloaded through communication port
purpose LEDs. These can be programmed by local
for further analysis.
key board. Any logical of physical status can be
assigned to any relay contact The logic of digital Relay Talk Software:
status input as well as logical status can be formed The general communication software is provided
and assigned to any of the relay output. The to communicate with relay, known as Relay Talk.
disturbance record can be trigger from external By using this software data such as event log,
logical input. disturbance records etc can be down loaded for
Setting Group: further analysis. The disturbance record data can
The ADR241B Relay is provided with two setting be saved in standard COMTRADE Format which
groups i.e. G1 and G2. Any One group is active at is understandable by numbers of relay testing
a time. The setting group can be changed from units for play back.
digital input, this allow user to change relay setting
dynamically as per the outgoing CB load condition.
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
The waveform and logical and physical status latched by relay can be view and analysed
Data can be viewed as raw sine wave
or RMS value
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
W h i l e O r d e r i n g S p e c i f y t h e f o l l o w i n g I n f o r m a t i o n f o r ADR241B R e l a y
Definition of Model No of Aditya Series of Relays
AM XXX–XX – X – X – XX – X
Auxiliary Supply
PT Secondary
0 = NO PT 01 = 18 – 52 V dc 04 = 30 V dc
1 = 63.5 PT sec 02 = 77 – 250 V dc 05 = 48 V dc
03 = 24 V dc 06 = 18 – 250 Vdc
CT Secondary
1 = 1 Amp.
2 = 5 Amp.
3 = 1 Amp. / 5 Amp. Selectable
AM XXX XX X
Over current Earth Fault Relay
For Adity-V2 series start from 201. For V1 series refer respective document
201 01 Obsolete Version CSE – H - 150 3
201 02 Relay with Standard Back Connections CSE – H - 130 3
Ordering information:
A D R 2 4 1 B - A M - X X X - X X - X - X - X X - X
Example
AD R 2 4 1 B – AM - 2 0 1 - 0 2 - 3 - 0 - 0 2 - 0
T y p e : A D R 2 4 1 B wi t h s t a n d a r d o u t p u t C o n t a c t s
St. Back terminal layout
Cabinet Type: CSE - H - 130
Auxiliary Supply: 77-250Vdc
C T s e c : 1 Amp. / 5 Amp. selectable.
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
Technical Specifications:
General specifications
Sr. No. Specification Particulars
I. Current Input : Suitable for CT secondary 5 Amp. or 1 Amp site selectable
II. Aux. Supply : 77 – 250VDC. Or 18 – 250VDC to be specified.
III. VA burden on CT : Less than 0.2VA
IV. VA burden on Aux. : Less than 10 Watts
V. Operating Temp. range : -10 deg. To + 65 deg.
VI. Continuous Current carrying : 2 x of rated
capacity
VII. Pick up : Within 1.1 times of set value
VIII. Reset Value : 95% to 90% of pick up.
IX. Output Contact : 2 for Trip
: 1 for Reclose
: 1 for PROTH.
: 1 for RLock
: 6 for General Programmable
X. Contact Rating : Continuous: 5A
: Make & carry for 0.5 sec : 30A
: Make carry for 3 sec : 15A
XI. Opto Isolated input : 1 for CB NO
: 1 for CB NC
: 8 as general programmable
XII. Thermal With stand for CT : 20 x of rated for 3.0 sec.
XIII. Setting Group : Two (G1 and G2)
General Settings
1. : Unit ID 1 – 250 in step of 1
: Baud Rate 1200 - 57600
: Com Port RS232 / RS485
: Set Parity None / Even / Odd
: Group Selection G1 / G2
: BF Enable YES / NO
: BF Delay 100 – 1000 msec in step of 50msec
: CT Sec 1A / 5A
: CT Primary 10 – 2000 in step of 1
: Local Control YES / NO
: Trip Ckt Test YES / NO
: Trip Cont SR / HR
: Trip Led SR / HR
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
PICK-UP / FAULT : Green LED indicate Start of timer Self Reset (SR) Type
: Red LED indicates FAULT Hand Reset (HR) Type.
DT / REC : Green LED indicate Dead Time
: Red LED indicate Reclaim time
LOCK / BF : Green LED indicate ARR lock-out (HR) Type
: Red LED indicate Breaker Fail (HR) Type
L5 / L6 / L7 : Spare LEDs Programmable
CLOSE / TRIP : Green LED indicate output close relay contact closer (SR) Type
: Red LED indicates Output trip relay contact closer (SR) Type
Drawing References
XX. : For Back Connections - ADV02402
: For Typical External connection - ADV02303
: For Typical External connection - ADV02304
: For Cabinet Type - MAC01301
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.