SECTION 01 91 00 General Commissioning Requirements Part 1 - General 1.1 Commissioning Description
SECTION 01 91 00 General Commissioning Requirements Part 1 - General 1.1 Commissioning Description
SECTION 01 91 00 General Commissioning Requirements Part 1 - General 1.1 Commissioning Description
SECTION 01 91 00
PART 1 - GENERAL
1.1 COMMISSIONING DESCRIPTION
A. This Section 01 91 00 GENERAL COMMISSIONING REQUIREMENTS shall form the
basis of the construction phase commissioning process and procedures.
The Commissioning Agent shall add, modify, and refine the commissioning
procedures, as approved by the Department of Veterans Affairs (VA), to
suit field conditions and actual manufacturer's equipment, incorporate
test data and procedure results, and provide detailed scheduling for all
commissioning tasks.
B. Various sections of the project specifications require equipment
startup, testing, and adjusting services. Requirements for startup,
testing, and adjusting services specified in the Division 7, Division
21, Division 22, Division 23, Division 26, Division 27, Division 28, and
Division 31 series sections of these specifications are intended to be
provided in coordination with the commissioning services and are not
intended to duplicate services. The Contractor shall coordinate the work
required by individual specification sections with the commissioning
services requirements specified herein.
C. Where individual testing, adjusting, or related services are required in
the project specifications and not specifically required by this
commissioning requirements specification, the specified services shall
be provided and copies of documentation, as required by those
specifications shall be submitted to the VA and the Commissioning Agent
to be indexed for future reference.
D. Where training or educational services for VA are required and specified
in other sections of the specifications, including but not limited to
Division 7, Division 8, Division 21, Division 22, Division 23, Division
26, Division 27, Division 28, and Division 31 series sections of the
specification, these services are intended to be provided in addition to
the training and educational services specified herein.
E. Commissioning is a systematic process of verifying that the building
systems perform interactively according to the construction documents
and the VA’s operational needs. The commissioning process shall
encompass and coordinate the system documentation, equipment startup,
control system calibration, testing and balancing, performance testing
01 91 00 - 1
10-01-15
01 91 00 - 2
10-01-15
and cooperation between the Commissioning Agent and all other parties
(Architects, Engineers, Subcontractors, Vendors, third party testing
agencies, etc.) is essential to the success of the Commissioning
effort.
D. With these fundamental practices in mind, the commissioning process
described herein has been developed to recognize that, in the execution
of the Commissioning Process, the Commissioning Agent must develop
effective methods to communicate with every member of the construction
team involved in delivering commissioned systems while simultaneously
respecting the exclusive contract authority of the Contracting Officer
and Resident Engineer. Thus, the procedures outlined in this
specification must be executed within the following limitations:
1. No communications (verbal or written) from the Commissioning Agent
shall be deemed to constitute direction that modifies the terms of
any contract between the Department of Veterans Affairs and the
Contractor.
2. Commissioning Issues identified by the Commissioning Agent will be
delivered to the Resident Engineer and copied to the designated
Commissioning Representatives for the Contractor and subcontractors
on the Commissioning Team for information only in order to expedite
the communication process. These issues must be understood as the
professional opinion of the Commissioning Agent and as suggestions
for resolution.
3. In the event that any Commissioning Issues and suggested resolutions
are deemed by the Resident Engineer to require either an official
interpretation of the construction documents or require a
modification of the contract documents, the Contracting Officer or
Resident Engineer will issue an official directive to this effect.
4. All parties to the Commissioning Process shall be individually
responsible for alerting the Resident Engineer of any issues that
they deem to constitute a potential contract change prior to acting
on these issues.
5. Authority for resolution or modification of design and construction
issues rests solely with the Contracting Officer or Resident
Engineer, with appropriate technical guidance from the
Architect/Engineer and/or Commissioning Agent.
Spec Writer Note: Edit the following
paragraph to include only those related
work sections that are included in the
01 91 00 - 3
10-01-15
01 91 00 - 4
10-01-15
01 91 00 - 5
10-01-15
List of Acronyms
Acronym Meaning
SO Site Observation
TAB Test Adjust and Balance
VA Department of Veterans Affairs
VAMC VA Medical Center
VA CFM VA Office of Construction and Facilities Management
VACO VA Central Office
VA PM VA Project Manager
VA-RE VA Resident Engineer
USGBC United States Green Building Council
1.6 DEFINITIONS
Acceptance Phase Commissioning: Commissioning tasks executed after most
construction has been completed, most Site Observations and Static Tests
have been completed and Pre-Functional Testing has been completed and
accepted. The main commissioning activities performed during this phase
are verification that the installed systems are functional by conducting
Systems Functional Performance tests and Owner Training.
Accuracy: The capability of an instrument to indicate the true value of
a measured quantity.
Back Check: A back check is a verification that an agreed upon solution
to a design comment has been adequately addressed in a subsequent design
review
Basis of Design (BOD): The Engineer’s Basis of Design is comprised of
two components: the Design Criteria and the Design Narrative, these
documents record the concepts, calculations, decisions, and product
selections used to meet the Owner’s Project Requirements (OPR) and to
satisfy applicable regulatory requirements, standards, and guidelines.
Benchmarks: Benchmarks are the comparison of a building’s energy usage
to other similar buildings and to the building itself.. For example,
ENERGY STAR Portfolio Manager is a frequently used and nationally
recognized building energy benchmarking tool.
Building Information Modeling (BIM): Building Information Modeling is
a parametric database which allows a building to be designed and
constructed virtually in 3D, and provides reports both in 2D views and
as schedules. This electronic information can be extracted and reused
for pre-populating facility management CMMS systems. Building Systems
Commissioning (BSC): NEBB acronym used to designate its commissioning
program.
01 91 00 - 6
10-01-15
01 91 00 - 7
10-01-15
01 91 00 - 8
10-01-15
01 91 00 - 9
10-01-15
01 91 00 - 10
10-01-15
01 91 00 - 11
10-01-15
01 91 00 - 12
10-01-15
01 91 00 - 13
10-01-15
Systems To Be Commissioned
System Description
Building Exterior Closure
Foundations (excluding Standard, special, slab-on-grade, vapor
structural) barriers, air barriers
Basements Basement walls, crawl spaces, waterproofing,
drainage
Superstructure Floor construction, roof construction,
sunshades, connections to adjacent structures
Exterior Closure Exterior walls, exterior windows, exterior
doors, louvers, grilles and sunscreens,
Roofing Roof system (including parapet), roof openings
(skylights, pipe chases, ducts, equipment
curbs, etc.)
Note: The emphasis on commissioning the above
building envelope systems is on control of air
flow, heat flow, noise, infrared, ultraviolet,
rain penetration, moisture, durability,
security, reliability, constructability,
maintainability, and sustainability.
Specialties
Patient Bed Service Medical gas certification and cross check,
Walls electrical connections
Equipment
01 91 00 - 14
10-01-15
Systems To Be Commissioned
System Description
Parking Control Barriers
Equipment
Laboratory Fume Hoods Fume Hood Certification
Biological Safety Cabinet Certification
Cabinets
Packaged Incinerators Combustion Testing, Cycle Certification
Conveying Equipment
Electric Dumbwaiters Interface with other systems (Fire Alarm,
etc.) [ASTM testing and certification by
others]
Elevators Interface with other systems (fire alarm,
etc.) [ASTM testing and certification by
others]
Escalators Interface with other systems (fire alarm,
etc.) [ASTM testing and certification by
others]
Material Delivery Interface with other systems (fire alarm,
Systems elevators, etc.)
Pneumatic Tube Systems Interface with other systems (fire alarm,
etc.)
Fire Suppression
Fire Pump Fire Pump, jockey pump, fire pump
controller/ATS
Fire Sprinkler Systems Wet pipe system, dry pipe system, pre-action
system, special agent systems
Plumbing
Domestic Water Booster pumps, backflow preventers, water
Distribution softeners, potable water storage tanks
Domestic Hot Water Water heaters**, heat exchangers, circulation
Systems pumps, point-of-use water heaters*
Sewerage Pump Systems Sewage ejectors
Wastewater Pump Sump pumps
Systems
Sanitary Waste Grease interceptors, acid neutralizers
Interceptors
General Service Air Packaged compressor systems, air dryers,
Systems filtration
Medical Air Systems Packaged medical air compressor units. Outlet
certification, cross-connection verification
Medical Vacuum Systems Packaged medical vacuum units, outlet
certification, cross-connection verification
Dental Air Systems Packaged dental air compressor units, outlet
certification, cross-connect verification
01 91 00 - 15
10-01-15
Systems To Be Commissioned
System Description
Dental Evacuation and Packaged Dental Evacuation units, packaged
Vacuum Systems dental vacuum units, outlet certification,
cross-connection verification
Waste Anesthesia Gas Packaged Waste Anesthesia Gas units, outlet
Systems certification, cross-connection verification
Medical Gas Systems Medical gas (oxygen, nitrogen, nitrous oxide,
(other than Medical etc.) tank/manifold systems, outlet
Air Systems) certification, cross-connection verification
Chemical Waste Systems Chemical storage tanks, neutralization
systems, ventilation, process control
Reverse-Osmosis Packaged Reverse-Osmosis systems
Systems
Water De-Alkalizing Package Water De-Alkalizing systems
Systems
HVAC
Noise and Vibration Noise and vibration levels for critical
Control equipment such as Air Handlers, Chillers,
Cooling Towers, Boilers, Generators, etc. will
be commissioned as part of the system
commissioning
Direct Digital Control Operator Interface Computer, Operator Work
System** Station (including graphics, point mapping,
trends, alarms), Network Communications
Modules and Wiring, Integration Panels. [DDC
Control panels will be commissioned with the
systems controlled by the panel]
Chilled Water System** Chillers (centrifugal, rotary screw, air-
cooled), pumps (primary, secondary, variable
primary), VFDs associated with chilled water
system components, DDC Control Panels
(including integration with Building Control
System)
Condenser Water Cooling Towers, Fluid Coolers, heat
System** exchangers/economizers, pumps, VFDs associated
with condenser water system components, DDC
control panels.
01 91 00 - 16
10-01-15
Systems To Be Commissioned
System Description
Steam/Heating Hot Boilers, boiler feed water system,
Water System** economizers/heat recovery equipment,
condensate recovery, water treatment, boiler
fuel system, controls, interface with facility
DDC system.
HVAC Air Handling Air handling Units, packaged rooftop AHU,
Systems** Outdoor Air conditioning units, humidifiers,
DDC control panels
HVAC General exhaust, toilet exhaust, laboratory
Ventilation/Exhaust exhaust, isolation exhaust, room
Systems pressurization control systems
HVAC Energy Recovery Heat Wheels, Heat Recovery Loops, AHU
Systems** Integrated Heat Recovery
HVAC Terminal Unit VAV Terminal Units, CAV terminal units, fan
Systems** coil units, fin-tube radiation, unit heaters
Decentralized Unitary Split-system HVAC systems, controls, interface
HVAC Systems* with facility DDC
Unitary Heat Pump Water-source heat pumps, controls, interface
Systems** with facility DDC
Humidity Control Humidifiers, de-humidifiers, controls,
Systems interface with facility DDC
Hydronic Distribution Pumps, DDC control panels, heat exchangers,
Systems
Facility Fuel Systems Boiler fuel system, generator fuel system
Geothermal Energy Geothermal well, ground heat exchanger,
Direct Use Heating ** geothermal pumps, heat exchanger, valves,
instrumentation
Solar Energy Heating Solar collectors, heat exchangers, storage
Systems ** tanks, solar-boosted domestic hot water
heater, pumps, valves, instrumentation
Facility Fuel Gas Witness Natural gas piping pressure testing,
Systems natural gas compressors and storage, propane
storage
Smoke Evacuation Atrium smoke evacuation, other smoke
System evacuation and smoke management systems,
controls, interface with other systems (fire
alarm), emergency operation.
Electrical
01 91 00 - 17
10-01-15
Systems To Be Commissioned
System Description
Medium-Voltage Medium-Voltage Switchgear, Medium-Voltage
Electrical Switches, Underground ductbank and
Distribution Systems distribution, Pad-Mount Transformers, Medium-
Voltage Load Interrupter Switches,
Grounding & Bonding Witness 3rd party testing, review reports
Systems
Electric Power Metering, sub-metering, power monitoring
Monitoring Systems systems, PLC control systems
Electrical System Review reports, verify field settings
Protective Device consistent with Study
Study
Secondary Unit Medium-voltage components, transformers, low-
Substations voltage distribution, verify breaker testing
results (injection current, etc)
Low-Voltage Normal power distribution system, Life-safety
Distribution System power distribution system, critical power
distribution system, equipment power
distribution system, switchboards,
distribution panels, panelboards, verify
breaker testing results (injection current,
etc)
Emergency Power Generators, Generator paralleling switchgear,
Generation Systems automatic transfer switches, PLC and other
control systems
Lighting & Lighting Emergency lighting, occupancy sensors,
Control** Systems lighting control systems, architectural
dimming systems, theatrical dimming systems,
exterior lighting and controls
Cathodic Protection Review 3rd party testing results.
Systems
Lightning Protection Witness 3rd party testing, review reports
System
Communications
Grounding & Bonding Witness 3rd party testing, review reports
System
Structured Cabling Witness 3rd party testing, review reports
System
Master Antenna Witness 3rd party testing, review reports
Television System
01 91 00 - 18
10-01-15
Systems To Be Commissioned
System Description
Public Address & Mass Witness 3rd party testing, review reports
Notification Systems
Intercom & Program Witness 3rd party testing, review reports
Systems
Nurse Call & Code Blue Witness 3rd party testing, review reports
Systems
Security Emergency Witness 3rd party testing, review reports
Call Systems
Duress Alarm Systems Witness 3rd party testing, review reports
Electronic Safety and Security
Grounding & Bonding Witness 3rd party testing, review reports
Physical Access Witness 3rd party testing, review reports
Control Systems
Access Control Systems Witness 3rd party testing, review reports
Security Access Witness 3rd party testing, review reports
Detection Systems
Video Surveillance Witness 3rd party testing, review reports
System
Electronic Personal Witness 3rd party testing, review reports
Protection System
Fire Detection and 100% device acceptance testing, battery draw-
Alarm System down test, verify system monitoring, verify
interface with other systems.
Renewable Energy Sources
Geothermal Energy Geothermal well, DC-AC Inverters, storage
Electrical Generation batteries, turbine generator modules,
Systems ** switchgear, combiner boxes, instrumentation,
monitoring and control systems
Solar Energy Solar collector modules, DC-AC inverter,
Electrical Power storage batteries, combiners, Switchgear,
Generation Systems ** instrumentation, monitoring and control
systems
Wind Energy Electrical Wind Turbines, DC-AC inverter, storage
Power Generation batteries, combiners, switchgear,
Systems ** instrumentation, monitoring and control
systems
Site Utilities
Water Utilities City Water Service Entrance, Backflow
Prevention, Pressure Control, Booster Pumps,
Irrigation Systems
01 91 00 - 19
10-01-15
Systems To Be Commissioned
System Description
Sanitary Sewerage City Sanitary Connection, Waste Treatment
Utilities Systems
Storm Drainage City Storm Water Connection, Site Storm Water
Utilities Distribution
Energy Distribution Connection to Third Party Energy (Steam, High
Utilities Temp Hot Water, Chilled Water) Supply Systems,
Metering, Pressure Control
Transportation
Active Traffic Barrier Witness 3rd party testing
Systems
Integrated Systems Tests
Loss of Power Response Loss of power to building, loss of power to
campus, restoration of power to building,
restoration of power to campus.
Fire Alarm Response Integrated System Response to Fire Alarm
Condition and Return to Normal
Table Notes
** Denotes systems that LEED requires to be commissioned to comply
with the LEED Fundamental Commissioning pre-requisite.
01 91 00 - 20
10-01-15
01 91 00 - 21
10-01-15
01 91 00 - 22
10-01-15
01 91 00 - 23
10-01-15
01 91 00 - 24
10-01-15
01 91 00 - 25
10-01-15
01 91 00 - 26
10-01-15
01 91 00 - 27
10-01-15
01 91 00 - 28
10-01-15
01 91 00 - 29
10-01-15
01 91 00 - 30
10-01-15
01 91 00 - 31
10-01-15
the project and the commissioning process. The Contractor shall update
the Master Construction as directed by the VA.
C. Initial Schedule of Commissioning Events: The Commissioning Agent will
provide the initial schedule of primary commissioning events in the
Commissioning Plan and at the commissioning coordination meetings. The
Commissioning Plan will provide a format for this schedule. As
construction progresses, more detailed schedules will be developed by
the Contractor with information from the Commissioning Agent.
D. Commissioning Coordinating Meetings: The Commissioning Agent will
conduct periodic Commissioning Coordination Meetings of the
commissioning team to review status of commissioning activities, to
discuss scheduling conflicts, and to discuss upcoming commissioning
process activities.
E. Pretesting Meetings: The Commissioning Agent will conduct pretest
meetings of the commissioning team to review startup reports, Pre-
Functional Checklist results, Systems Functional Performance Testing
procedures, testing personnel and instrumentation requirements.
F. Systems Functional Performance Testing Coordination: The Contractor
shall coordinate testing activities to accommodate required quality
assurance and control services with a minimum of delay and to avoid
necessity of removing and replacing construction to accommodate testing
and inspecting. The Contractor shall coordinate the schedule times for
tests, inspections, obtaining samples, and similar activities.
PART 2 - PRODUCTS
2.1 TEST EQUIPMENT
A. The Contractor shall provide all standard and specialized testing
equipment required to perform Systems Functional Performance Testing.
Test equipment required for Systems Functional Performance Testing will
be identified in the detailed System Functional Performance Test
Procedure prepared by the Commissioning Agent.
B. Data logging equipment and software required to test equipment shall be
provided by the Contractor.
C. All testing equipment shall be of sufficient quality and accuracy to
test and/or measure system performance with the tolerances specified in
the Specifications. If not otherwise noted, the following minimum
requirements apply: Temperature sensors and digital thermometers shall
have a certified calibration within the past year to an accuracy of 0.5
o
C (1.0 oF) and a resolution of + or - 0.1 oC (0.2 oF). Pressure sensors
01 91 00 - 32
10-01-15
01 91 00 - 33
10-01-15
PART 3 - EXECUTION
3.1 COMMISSIONING PROCESS ROLES AND RESPONSIBILITIES
A. The following table outlines the roles and responsibilities for the Commissioning Team members during
the Construction Phase:
Spec Writer’s Notes: Edit the following tables to describe the roles
and responsibilities for each commissioning team member for each of the
commissioning tasks as appropriate for the project.
01 91 00 - 35
10-01-15
B. The following table outlines the roles and responsibilities for the Commissioning Team members during
the Acceptance Phase:
01 91 00 - 36
10-01-15
01 91 00 - 37
10-01-15
C. The following table outlines the roles and responsibilities for the Commissioning Team members during
the Warranty Phase:
01 91 00 - 38
10-01-15
01 91 00 - 39
10-01-15
01 91 00 - 41
10-01-15
d. The Contractor shall review and evaluate the procedures and the
format for documenting them, noting any procedures that need to be
revised or added.
3. Sensor and Actuator Calibration
a. All field installed temperature, relative humidity, CO2 and
pressure sensors and gages, and all actuators (dampers and valves)
on all equipment shall be calibrated using the methods described
in Division 21, Division 22, Division 23, Division 26, Division
27, and Division 28 specifications.
b. All procedures used shall be fully documented on the Pre-
Functional Checklists or other suitable forms, clearly referencing
the procedures followed and written documentation of initial,
intermediate and final results.
4. Execution of Equipment Startup
Spec Writer Note: Coordinate the number
of week’s lead-time with the Resident
Engineer.
01 91 00 - 42
10-01-15
B. The Commissioning Agent will review the report and submit comments to
the VA. The Commissioning Agent will work with the Contractor to correct
and verify deficiencies or uncompleted items. The Commissioning Agent
will involve the VA and others as necessary. The Contractor shall
correct all areas that are noncompliant or incomplete in the checklists
in a timely manner, and shall notify the VA and Commissioning Agent as
soon as outstanding items have been corrected. The Contractor shall
submit an updated startup report and a Statement of Correction on the
original noncompliance report. When satisfactorily completed, the
Commissioning Agent will recommend approval of the checklists and
startup of each system to the VA.
C. The Contractor shall be responsible for resolution of deficiencies as
directed the VA.
Spec Writer Note: The following paragraph
on Phased Commissioning is for projects
with phased delivery of buildings or parts
of buildings. It is intended to notify
the Contractor that some Commissioning
Activities, such as startup, functional
testing, etc. will be conducted as the
various phases of the project near
completion and will require multiple
mobilizations of the startup and
functional testing teams to support the
phased commissioning. Delete the
following paragraph when phased delivery
is not part of the project.
01 91 00 - 43
10-01-15
01 91 00 - 44
10-01-15
01 91 00 - 45
10-01-15
Operationa Testing
Trend Alarm Alarm Alarm
Point Type l Trend Trend
Interval Type Range Delay
Duration Duration
OA
AI 15 Min 24 hours 3 days N/A
Temperature
RA
AI 15 Min 24 hours 3 days N/A
Temperature
10
RA Humidity AI 15 Min 24 hours 3 days P >60% RH
min
Mixed Air
AI None None None N/A
Temp
±5°F 10
SA Temp AI 15 Min 24 hours 3 days C
from SP min
Supply Fan
AI 15 Min 24 hours 3 days N/A
Speed
Return Fan
AI 15 Min 24 hours 3 days N/A
Speed
RA Pre-Filter
AI None None None N/A
Status
OA Pre-Filter
AI None None None N/A
Status
After Filter
AI None None None N/A
Status
±10% 10
SA Flow AI 15 Min 24 hours 3 days C
from SP min
OA Supply ±5°F 10
AI 15 Min 24 hours 3 days P
Temp from SP min
RA Supply
AI 15 Min 24 hours 3 days N/A
Temp
RA CHW Valve
AI 15 Min 24 hours 3 days N/A
Position
OA CHW Valve
AI 15 Min 24 hours 3 days N/A
Position
01 91 00 - 46
10-01-15
Operationa Testing
Trend Alarm Alarm Alarm
Point Type l Trend Trend
Interval Type Range Delay
Duration Duration
OA HW Valve
AI 15 Min 24 hours 3 days N/A
Position
±10%
OA Flow AI 15 Min 24 hours 3 days P 5 min
from SP
±10%
RA Flow AI 15 Min 24 hours 3 days P 5 min
from SP
Initial UVC
AI None None None N/A
Intensity (%)
±25%
Duct Pressure AI 15 Min 24 hours 3 days C 6 min
from SP
±10% 10
CO2 Level AI 15 Min 24 hours 3 days P
from SP min
Status
Supply Fan 10
DI COV 24 hours 3 days C <>
Status min
Command
Status
Return Fan 10
DI COV 24 hours 3 days C <>
Status Min
Command
High Static
DI COV 24 hours 3 days P True 1 min
Status
Fire Alarm
DI COV 24 hours 3 days C True 5 min
Status
Freeze Stat 10
DI COV 24 hours 3 days C True
Level 1 min
Freeze Stat
DI COV 24 hours 3 days C True 5 min
Level 2
Freeze Stat
DI COV 24 hours 3 days P True 1 min
Level 3
Fire/Smoke
DI COV 24 hours 3 days P Closed 1 min
Damper Status
Emergency AHU
DI COV 24 hours 3 days P True 1 min
Shutdown
Status
Exhaust Fan 10
DI COV 24 hours 3 days C <>
#1 Status min
Command
Status
Exhaust Fan 10
DI COV 24 hours 3 days C <>
#2 Status min
Command
Status
Exhaust Fan 10
DI COV 24 hours 3 days C <>
#3 Status min
Command
10
OA Alarm DI COV 24 hours 3 days C True
min
High Static 10
DI COV 24 hours 3 days C True
Alarm min
UVC Emitter 10
DI COV 24 hours 3 days P True
Alarm min
01 91 00 - 47
10-01-15
Operationa Testing
Trend Alarm Alarm Alarm
Point Type l Trend Trend
Interval Type Range Delay
Duration Duration
10
CO2 Alarm DI COV 24 hours 3 days P True
min
Power Failure DI COV 24 hours 3 days P True 1 min
Supply Fan
AO 15 Min 24 hours 3 days N/A
Speed
Return Fan
AO 15 Min 24 hours 3 days N/A
Speed
RA CHW Valve
AO 15 Min 24 hours 3 days N/A
Position
OA CHW Valve
AO 15 Min 24 hours 3 days N/A
Position
OA HW Valve
AO 15 Min 24 hours 3 days N/A
Position
Supply Fan
DO COV 24 hours 3 days N/A
S/S
Return Fan
DO COV 24 hours 3 days N/A
S/S
Fire/Smoke
DO COV 24 hours 3 days N/A
Dampers
Exhaust Fan
DO COV 24 hours 3 days N/A
S/S
Exhaust Fan
DO COV 24 hours 3 days N/A
S/S
Exhaust Fan
DO COV 24 hours 3 days N/A
S/S
Operationa Testing
Trend Alarm Alarm Alarm
Point Type l Trend Trend
Interval Type Range Delay
Duration Duration
Space ±5°F 10
AI 15 Min 12 hours 3 days P
Temperature from SP min
±5°F 10
Air Flow AI 15 Min 12 hours 3 days P
from SP min
SA ±5°F 10
AI 15 Min 12 hours 3 days P
Temperature from SP min
Local ±10°F 60
AI 15 Min 12 hours 3 days M
Setpoint from SP min
01 91 00 - 48
10-01-15
Operationa Testing
Trend Alarm Alarm Alarm
Point Type l Trend Trend
Interval Type Range Delay
Duration Duration
Space > 60%
AI 15 Min 12 hours 3 days P 5 min
Humidity RH
Unoccupied 12
DI COV 12 hours 3 days M N/A
Override Hours
Refrigerator 10
DI COV 12 hours 3 days C N/A
Alarm min
Damper 15
AO 12 hours 3 days N/A
Position Minutes
Heating coil
15
Valve AO 12 hours 3 days N/A
Minutes
Position
Operationa Testing
Trend Alarm Alarm Alarm
Point Type l Trend Trend
Interval Type Range Delay
Duration Duration
Space 15 ±5°F 10
AI 12 hours 3 days P
Temperature Minutes from SP min
SA 15 ±5°F 10
AI 12 hours 3 days P
Temperature Minutes from SP min
Pre-Filter 1
AI None None None M > SP
Status hour
30
Water Sensor DI COV 12 hours 3 days M N/A
Min
Cooling Coil
15
Valve AO 12 hours 3 days N/A
Minutes
Position
Heating coil
15
Valve AO 12 hours 3 days N/A
Minutes
Position
Status
30
Fan Coil DO COV 12 hours 3 days M <>
min
ON/OFF Command
01 91 00 - 49
10-01-15
Operationa Testing
Trend Alarm Alarm Alarm
Point Type l Trend Trend
Interval Type Range Delay
Duration Duration
Space 15 ±5°F 10
AI 12 hours 3 days P
Temperature Minutes from SP min
SA 15 ±5°F 10
AI 12 hours 3 days P
Temperature Minutes from SP min
Pre-Filter 1
AI None None None M > SP
Status hour
30
Water Sensor DI COV 12 hours 3 days M N/A
Min
Cooling Coil
15
Valve AO 12 hours 3 days N/A
Minutes
Position
Status
30
Fan Coil DO COV 12 hours 3 days M <>
min
ON/OFF Command
Operationa Testing
Trend Alarm Alarm Alarm
Point Type l Trend Trend
Interval Type Range Delay
Duration Duration
Space 15 ±5°F 10
AI 12 hours 3 days P
Temperature Minutes from SP min
Heating Valve 15
AO 12 hours 3 days N/A
Position Minutes
Status
Unit Heater 30
DO COV 12 hours 3 days M <>
ON/OFF min
Command
Operationa Testing
Trend Alarm Alarm Alarm
Point Type l Trend Trend
Interval Type Range Delay
Duration Duration
Steam Flow 15
AI 12 hours 3 days N/A
(LB/HR) Minutes
Condensate
15
Pump Run AI 12 hours 3 days N/A
Minutes
Hours
Water Meter 15
AI 12 hours 3 days N/A
(GPM) Minutes
01 91 00 - 50
10-01-15
Operationa Testing
Trend Alarm Alarm Alarm
Point Type l Trend Trend
Interval Type Range Delay
Duration Duration
Electric 15
AI 12 hours 3 days N/A
Meter (KW/H) Minutes
Irrigation 15
AI 12 hours 3 days N/A
Meter (GPM) Minutes
Chilled Water 15
AI 12 hours 3 days N/A
Flow (TONS) Minutes
Condensate 15
AI 12 hours 3 days N/A
Flow (GPM) Minutes
High Water
DI COV 12 hours 3 days C True 5 Min
Level Alarm
Condensate Status
10
Pump DO COV 12 hours 3 days P <>
min
Start/Stop Command
Operationa Testing
Trend Alarm Alarm Alarm
Point Type l Trend Trend
Interval Type Range Delay
Duration Duration
Domestic HW
AI 15 Minute 12 Hours 3 days N/A
Setpoint WH-1
Domestic HW
AI 15 Minute 12 Hours 3 days N/A
Setpoint WH-2
Domestic HW > 135 10
AI 15 Minute 12 Hours 3 days C
Temperature oF Min
Domestic HW ±5°F 10
AI 15 Minute 12 Hours 3 days P
Temperature from SP Min
Dom. Circ.
Pump #1 DO COV 12 Hours 3 days N/A
Start/Stop
Dom. Circ.
Pump #2 DO COV 12 Hours 3 days N/A
Start/Stop
Domestic HW
DO COV 12 Hours 3 days N/A
Start/Stop
01 91 00 - 51
10-01-15
Operationa Testing
Trend Alarm Alarm Alarm
Point Type l Trend Trend
Interval Type Range Delay
Duration Duration
System HWS ±5°F 10
AI 15 min 12 hours 3 days C
Temperature from SP Min
System HWR ±15°F 300
AI 15 min 12 hours 3 days M
Temperature from SP Min
HX-1 Entering ±5°F 10
AI 15 min 12 hours 3 days P
Temperature from SP Min
HX-2 Entering ±5°F 10
AI 15 min 12 hours 3 days P
Temperature from SP Min
HX-2 Leaving ±5°F 10
AI 15 min 12 hours 3 days P
Temperature from SP Min
System Flow
AI 15 min 12 hours 3 days N/A
(GPM)
System
±10%
Differential AI 15 min 12 hours 3 days P 8 Min
from SP
Pressure
3 days
Status
HW Pump 1 30
DI COV 12 Hours 3 days C <>
Status min
Command
Status
HW Pump 2 30
DI COV 12 Hours 3 days C <>
Status min
Command
HW Pump 1 VFD
AO 15 Min 12 Hours 3 days N/A
Speed
HW Pump 2 VFD
AO 15 Min 12 Hours 3 days N/A
Speed
Steam Station
#1 1/3
AO 15 Min 12 Hours 3 days N/A
Control Valve
Position
Steam Station
#1 2/3
AO 15 Min 12 Hours 3 days N/A
Control Valve
Position
Steam Station
#2 1/3
AO 15 Min 12 Hours 3 days N/A
Control Valve
Position
Steam Station
#2 2/3
AO 15 Min 12 Hours 3 days N/A
Control Valve
Position
Steam Station
Bypass Valve AO 15 Min 12 Hours 3 days N/A
Position
01 91 00 - 52
10-01-15
Operationa Testing
Trend Alarm Alarm Alarm
Point Type l Trend Trend
Interval Type Range Delay
Duration Duration
HW Pump 1
DO COV 12 Hours 3 days N/A
Start/Stop
HW Pump 2
DO COV 12 Hours 3 days N/A
Start/Stop
HWR #1 Valve DO COV 12 Hours 3 days N/A
HWR #2 Valve DO COV 12 Hours 3 days N/A
Operationa Testing
Trend Alarm Alarm Alarm
Point Type l Trend Trend
Interval Type Range Delay
Duration Duration
Chiller 1
15
Entering AI 12 Hours 3 days N/A
Minutes
Temperature
Chiller 1
15 ±5°F 10
Leaving AI 12 Hours 3 days P
Minutes from SP Min
Temperature
Chiller 1 15
AI 12 Hours 3 days N/A
Flow Minutes
Chiller 1 15
AI 12 Hours 3 days N/A
Percent Load Minutes
Chiller 1 KW 15
AI 12 Hours 3 days N/A
Consumption Minutes
Chiller 1 15
AI 12 Hours 3 days N/A
Tonnage Minutes
Chiller 2
15
Entering AI 12 Hours 3 days N/A
Minutes
Temperature
Chiller 2
15 ±5°F 10
Leaving AI 12 Hours 3 days P
Minutes from SP Min
Temperature
Chiller 2 15
AI 12 Hours 3 days N/A
Flow Minutes
Chiller 2 15
AI 12 Hours 3 days N/A
Percent Load Minutes
Chiller 2 KW 15
AI 12 Hours 3 days N/A
Consumption Minutes
Chiller 2 15
AI 12 Hours 3 days N/A
Tonnage Minutes
Primary Loop
15
Decoupler AI 12 Hours 3 days N/A
Minutes
Flow
Primary Loop 15
AI 12 Hours 3 days N/A
Flow Minutes
01 91 00 - 53
10-01-15
Operationa Testing
Trend Alarm Alarm Alarm
Point Type l Trend Trend
Interval Type Range Delay
Duration Duration
Primary Loop
15
Supply AI 12 Hours 3 days N/A
Minutes
Temperature
Secondary
Loop 15 ±5% 10
AI 12 Hours 3 days P
Differential Minutes from SP Min
Pressure
Secondary 15
AI 12 Hours 3 days N/A
Loop Flow Minutes
Secondary
15
Loop Supply AI 12 Hours 3 days N/A
Minutes
Temperature
Secondary
15
Loop Return AI 12 Hours 3 days N/A
Minutes
Temperature
Secondary 15
AI 12 Hours 3 days N/A
Loop Tonnage Minutes
Status
Primary Loop 30
DI COV 12 Hours 3 days C <>
Pump 1 Status min
Command
Status
Primary Loop 30
DI COV 12 Hours 3 days C <>
Pump 2 Status min
Command
Secondary Status
30
Loop Pump 1 DI COV 12 Hours 3 days C <>
min
Status Command
Secondary Status
30
Loop Pump 2 DI COV 12 Hours 3 days C <>
min
Status Command
Status
Chiller 1 30
DI COV 12 Hours 3 days C <>
Status min
Command
Chiller 1
Evaporator DI COV 12 Hours 3 days N/A
Iso-Valve
Chiller 1
Evaporator DI COV 12 Hours 3 days N/A
Flow Switch
Chiller 1 10
DI COV 12 Hours 3 days C True
Unit Alarm Min
Status
Chiller 2 30
DI COV 12 Hours 3 days C <>
Status min
Command
Chiller 2
Evaporator DI COV 12 Hours 3 days N/A
Iso-Valve
01 91 00 - 54
10-01-15
Operationa Testing
Trend Alarm Alarm Alarm
Point Type l Trend Trend
Interval Type Range Delay
Duration Duration
Chiller 2
Evaporator DI COV 12 Hours 3 days N/A
Flow Switch
Chiller 2 10
DI COV 12 Hours 3 days C True
Unit Alarm Min
Refrigerant 10
DI COV 12 Hours 3 days C True
Detector Min
Refrigerant Status
30
Exhaust Fan DI COV 12 Hours 3 days M <>
min
Status Command
Emergency
DI COV 12 Hours 3 days P True 1 Min
Shutdown
Primary Loop
15
Pump 1 VFD AO 12 Hours 3 days N/A
Minutes
Speed
Primary Loop
15
Pump 2 VFD AO 12 Hours 3 days N/A
Minutes
Speed
Secondary
15
Loop Pump 1 AO 12 Hours 3 days N/A
Minutes
VFD Speed
Secondary
15
Loop Pump 2 AO 12 Hours 3 days N/A
Minutes
VFD Speed
Primary Pump
1 Start / DO COV 12 Hours 3 days N/A
Stop
Primary Pump
2 Start / DO COV 12 Hours 3 days N/A
Stop
Secondary
Pump 1 DO COV 12 Hours 3 days N/A
Start / Stop
Secondary
Pump 2 DO COV 12 Hours 3 days N/A
Start / Stop
Chiller 1
DO COV 12 Hours 3 days N/A
Enable
Chiller 1
Iso-Valve DO COV 12 Hours 3 days N/A
Command
Chiller 2
DO COV 12 Hours 3 days N/A
Enable
Chiller 2
Iso-Valve DO COV 12 Hours 3 days N/A
Command
01 91 00 - 55
10-01-15
Operationa Testing
Trend Alarm Alarm Alarm
Point Type l Trend Trend
Interval Type Range Delay
Duration Duration
Refrigerant
Exhaust Fan DO COV 12 Hours 3 days N/A
Start / Stop
Operationa Testing
Trend Alarm Alarm Alarm
Point Type l Trend Trend
Interval Type Range Delay
Duration Duration
Chiller 1
15
Condenser AI 12 Hours 3 days N/A
Minutes
Entering Temp
Chiller 1
15
Condenser AI 12 Hours 3 days N/A
Minutes
Leaving Temp
Chiller 2
15
Condenser AI 12 Hours 3 days N/A
Minutes
Entering Temp
Chiller 2
15
Condenser AI 12 Hours 3 days N/A
Minutes
Leaving Temp
Cooling Tower 15
AI 12 Hours 3 days N/A
1 Supply Temp Minutes
Cooling Tower 15
AI 12 Hours 3 days N/A
1 Return Temp Minutes
Cooling Tower 15 10
AI 12 Hours 3 days P < 45 oF
1 Basin Temp Minutes Min
Cooling Tower 15
AI 12 Hours 3 days N/A
2 Supply Temp Minutes
Cooling Tower 15
AI 12 Hours 3 days N/A
2 Return Temp Minutes
Cooling Tower 15 10
AI 12 Hours 3 days P < 45 oF
2 Basin Temp Minutes Min
Condenser
15
Water Supply AI 12 Hours 3 days N/A
Minutes
Temp
Condenser
15
Water Return AI 12 Hours 3 days N/A
Minutes
Temp
Outdoor Air 15
AI 12 Hours 3 days N/A
Wet Bulb Minutes
Status
Cooling Tower
DI COV 12 Hours 3 days P <> 1 min
1 Fan Status
Command
Cooling Tower
DI COV 12 Hours 3 days N/A
1 Basin Heat
01 91 00 - 56
10-01-15
Operationa Testing
Trend Alarm Alarm Alarm
Point Type l Trend Trend
Interval Type Range Delay
Duration Duration
Cooling Tower
DI COV 12 Hours 3 days N/A
1 Heat Trace
Status
Cooling Tower
DI COV 12 Hours 3 days P <> 1 min
2 Fan Status
Command
Cooling Tower
DI COV 12 Hours 3 days N/A
2 Basin Heat
Cooling Tower
DI COV 12 Hours 3 days N/A
2 Heat Trace
Chiller 1 Status
Isolation DI COV 12 Hours 3 days P <> 1 min
Valve Command
Chiller 2 Status
Isolation DI COV 12 Hours 3 days P <> 1 min
Valve Command
Condenser Status
Water Pump 1 DI COV 12 Hours 3 days P <> 1 min
Status Command
Condenser Status
Water Pump 2 DI COV 12 Hours 3 days P <> 1 min
Status Command
Chiller 1
15
Condenser AO 12 Hours 3 days N/A
Minutes
Bypass Valve
Chiller 2
15
Condenser By- AO 12 Hours 3 days N/A
Minutes
Pass Valve
Cooling Tower
15
1 Bypass AO 12 Hours 3 days N/A
Minutes
Valve
Cooling Tower 15
AO 12 Hours 3 days N/A
1 Fan Speed Minutes
Cooling Tower
15
2 Bypass AO 12 Hours 3 days N/A
Minutes
Valve
Cooling Tower 15
AO 12 Hours 3 days N/A
2 Fan Speed Minutes
Cooling Tower
1 Fan Start / DO COV 12 Hours 3 days N/A
Stop
Cooling Tower
2 Fan Start / DO COV 12 Hours 3 days N/A
Stop
Condenser
Water Pump 1 DO COV 12 Hours 3 days N/A
Start / Stop
01 91 00 - 57
10-01-15
Operationa Testing
Trend Alarm Alarm Alarm
Point Type l Trend Trend
Interval Type Range Delay
Duration Duration
Condenser
Water Pump 2 DO COV 12 Hours 3 days N/A
Start / Stop
Operationa Testing
Trend Alarm Alarm Alarm
Point Type l Trend Trend
Interval Type Range Delay
Duration Duration
Boiler 1
15 ±5% 10
Steam AI 12 Hours 3 days P
Minutes from SP Min
Pressure
Boiler 1
15
Steam AI 12 Hours 3 days N/A
Minutes
Temperature
Boiler 1 Fire 15
AI 12 Hours 3 days N/A
Signal Minutes
Boiler 2
15 ±5% 10
Steam AI 12 Hours 3 days P
Minutes from SP Min
Pressure
Boiler 2
15
Steam AI 12 Hours 3 days N/A
Minutes
Temperature
Boiler 2 Fire 15
AI 12 Hours 3 days N/A
Signal Minutes
System Steam 15 ±5% 10
AI 12 Hours 3 days P
Pressure Minutes from SP Min
Boiler 1
DI COV 12 Hours 3 days N/A
Enable
Status
Boiler 1 10
DI COV 12 Hours 3 days P <>
Status min
Command
Boiler 1
DI COV 12 Hours 3 days C True 1 Min
Alarm
Boiler 1 on
DI COV 12 Hours 3 days N/A
Fuel Oil
Boiler 1 Low
DI COV 12 Hours 3 days C True 5 Min
Water Alarm
Boiler 1 High
DI COV 12 Hours 3 days C True 5 Min
Water Alarm
Boiler 1 Feed
DI COV 12 Hours 3 days N/A
Pump
Boiler 2
DI COV 12 Hours 3 days N/A
Enable
01 91 00 - 58
10-01-15
Operationa Testing
Trend Alarm Alarm Alarm
Point Type l Trend Trend
Interval Type Range Delay
Duration Duration
Status
Boiler 2 10
DI COV 12 Hours 3 days P <>
Status min
Command
Boiler 2
DI COV 12 Hours 3 days C True 1 Min
Alarm
Boiler 2 on
DI COV 12 Hours 3 days N/A
Fuel Oil
Boiler 2 Low
DI COV 12 Hours 3 days C True 5 Min
Water Alarm
Boiler 2 High
DI COV 12 Hours 3 days C True 5 Min
Water Alarm
Boiler 2 Feed
DI COV 12 Hours 3 days N/A
Pump
Status
Combustion
DI COV 12 Hours 3 days P <> 5 min
Damper Status
Command
Condensate Status
Recovery Pump DI COV 12 Hours 3 days P <> 5 min
Status Command
Boiler 1 Feed
Pump Start / DO COV 12 Hours 3 days N/A
Stop
Boiler 2
DO COV 12 Hours 3 days N/A
Start / Stop
Combustion
Damper DO COV 12 Hours 3 days N/A
Command
Condensate
Recovery Pump DO COV 12 Hours 3 days N/A
Start / Stop
Operationa Testing
Trend Alarm Alarm Alarm
Point Type l Trend Trend
Interval Type Range Delay
Duration Duration
Outside Air 15
AI 12 Hours 3 days N/A
Temperature Minutes
Boiler 1 Fire 15
AI 12 Hours 3 days N/A
Signal Minutes
01 91 00 - 59
10-01-15
Operationa Testing
Trend Alarm Alarm Alarm
Point Type l Trend Trend
Interval Type Range Delay
Duration Duration
Boiler 1
Entering 15
AI 12 Hours 3 days N/A
Water Minutes
Temperature
Boiler 1
15
Leaving Water AI 12 Hours 3 days N/A
Minutes
Temperature
Boiler 2 Fire 15
AI 12 Hours 3 days N/A
Signal Minutes
Boiler 2
Entering 15
AI 12 Hours 3 days N/A
Water Minutes
Temperature
Boiler 2
15
Leaving Water AI 12 Hours 3 days N/A
Minutes
Temperature
Hot Water
15 ±5 oF 10
Supply AI 12 Hours 3 days P
Minutes from SP Min
Temperature
Hot Water
15
Return AI 12 Hours 3 days N/A
Minutes
Temperature
Secondary
Loop 15 ±5% 10
AI 12 Hours 3 days C
Differential Minutes from SP Min
Pressure
15
Lead Boiler AI 12 Hours 3 days N/A
Minutes
Boiler 1
DI COV 12 Hours 3 days N/A
Enable
Status
Boiler 1 10
DI COV 12 Hours 3 days P <>
Status min
Command
Boiler 1
Isolation DI COV 12 Hours 3 days N/A
Valve
Boiler 1 on
DI COV 12 Hours 3 days N/A
Fuel Oil
Boiler 1
DI COV 12 Hours 3 days C True 1 Min
Alarm
Boiler 2
DI COV 12 Hours 3 days N/A
Enable
Status
Boiler 2 10
DI COV 12 Hours 3 days P <>
Status min
Command
Boiler 2
Isolation DI COV 12 Hours 3 days N/A
Valve
01 91 00 - 60
10-01-15
Operationa Testing
Trend Alarm Alarm Alarm
Point Type l Trend Trend
Interval Type Range Delay
Duration Duration
Boiler 2 on
DI COV 12 Hours 3 days N/A
Fuel Oil
Boiler 2
DI COV 12 Hours 3 days C True 1 Min
Alarm
Status
Combustion 10
DI COV 12 Hours 3 days P <>
Dampers Open min
Command
Status
Primary Pump 10
DI COV 12 Hours 3 days P <>
1 Status min
Command
Status
Primary Pump 10
DI COV 12 Hours 3 days P <>
2 Status min
Command
Status
Secondary 10
DI COV 12 Hours 3 days P <>
Pump 1 Status min
Command
Status
Secondary 10
DI COV 12 Hours 3 days P <>
Pump 2 Status min
Command
Primary Pump
AO COV 12 Hours 3 days N/A
1 VFD Speed
Primary Pump
AO COV 12 Hours 3 days N/A
2 VFD Speed
Secondary
Pump 1 VFD AO COV 12 Hours 3 days N/A
Speed
Secondary
Pump 2 VFD AO COV 12 Hours 3 days N/A
Speed
Hot Water
DO COV 12 Hours 3 days N/A
System Enable
Combustion
Dampers DO COV 12 Hours 3 days N/A
Command
Primary Pump
1 Start / DO COV 12 Hours 3 days N/A
Stop
Primary Pump
2 Start / DO COV 12 Hours 3 days N/A
Stop
Secondary
Pump 1 DO COV 12 Hours 3 days N/A
Start / Stop
Secondary
Pump 2 DO COV 12 Hours 3 days N/A
Start / Stop
01 91 00 - 61
10-01-15
SYSTEM
Calibration O&M Calibration Procedure
Sensor
Frequency Reference
Discharge air
Once a year Volume I Section D.3.aa
temperature
Discharge static
Every 6 months Volume II Section A.1.c
pressure
4. Loop tuning documentation and constants for each loop of the building
systems. The documentation shall be submitted in outline or table
separated by system, control type (e.g. heating valve temperature
control); proportional, integral and derivative constants, interval
(and bias if used) for each loop. The following table is a sample
that can be used as a template for submission.
01 91 00 - 62
10-01-15
01 91 00 - 63
10-01-15
01 91 00 - 64
10-01-15
01 91 00 - 65
10-01-15
01 91 00 - 66
10-01-15
01 91 00 - 67
10-01-15
01 91 00 - 68
10-01-15
01 91 00 - 69
10-01-15
01 91 00 - 70
10-01-15
01 91 00 - 71
10-01-15
01 91 00 - 72
10-01-15
01 91 00 - 73
10-01-15
g. Limiting conditions.
H, Performance curves.
2. Documentation: Review the following items in detail:
a. Emergency manuals.
b. Operations manuals.
c. Maintenance manuals.
d. Project Record Documents.
e. Identification systems.
f. Warranties and bonds.
g. Maintenance service agreements and similar continuing commitments.
3. Emergencies: Include the following, as applicable:
a. Instructions on meaning of warnings, trouble indications, and
error messages.
b. Instructions on stopping.
c. Shutdown instructions for each type of emergency.
d. Operating instructions for conditions outside of normal operating
limits.
e. Sequences for electric or electronic systems.
f. Special operating instructions and procedures.
4. Operations: Include the following, as applicable:
a. Startup procedures.
b. Equipment or system break-in procedures.
c. Routine and normal operating instructions.
d. Regulation and control procedures.
e. Control sequences.
f. Safety procedures.
g. Instructions on stopping.
h. Normal shutdown instructions.
i. Operating procedures for emergencies.
j. Operating procedures for system, subsystem, or equipment failure.
k. Seasonal and weekend operating instructions.
l. Required sequences for electric or electronic systems.
m. Special operating instructions and procedures.
5. Adjustments: Include the following:
a. Alignments.
b. Checking adjustments.
c. Noise and vibration adjustments.
d. Economy and efficiency adjustments.
01 91 00 - 74
10-01-15
01 91 00 - 75
10-01-15
01 91 00 - 76