MP-12 MS-5012
Initiating Device Circuit Voltage: 8.6 - 12.2VDC Initiating Device Circuit Voltage: 8.6 - 13.5VDC
Max Detector Circuit Standby Current: 2.0mA/circuit Max Detector Circuit Standby Current: 2.0mA/circuit
Compatibility Identifier: "A" Compatibility Identifier: "A"
NAC Power: Full Wave Rectified NAC Power: Full Wave Rectified
MP-24 and MP242FC MS-5024 and MS-5024UD
Initiating Device Circuit Voltage: 18 - 26.2VDC Initiating Device Circuit Voltage: 17.1 - 25.0 VDC
Max Detector Circuit Standby Current: 2.0mA/circuit Max Detector Circuit Standby Current: 2.0 mA/circuit
Compatibility Identifier: "A" Compatibility Identifier: "A"
NAC Power: Full Waved Rectified NAC Power: Full Wave Rectified
MS-124 MS-5210UD
Initiating Device Circuit Voltage: 18 - 26.4VDC Initiating Device Circuit Voltage: 17.9 - 26.4 VDC
Max Detector Circuit Standby Current: 2.0mA/circuit Max Detector Circuit Standby Current: 2.0 mA/circuit
Compatibility Identifier: "A" Compatibility Identifier: "A"
NAC Power: Full Wave Rectified NAC Power: Full Wave Rectified
MS-2/MS-2E, MS-4/MS-4E MS-9200/AMS-9200 (M302, MMF-302)
Initiating Device Circuit Voltage: 17.3 - 24.6 Initiating loop voltage: 16 - 27.5 VDC
Max Detector Circuit Standby Current: 2.0mA/circuit Compatibility Identifier: "A"
Compatibility Identifier: "A" NAC Power: Full Wave Rectified
NAC Power: Full Wave Rectified (Special Application)
MS-9200UD/MS-9200UDE/MS-9200UDLS/
MS-424A MS-9200UDLSE/MS-9200UDLSC (M302, MMF-302)
Initiating Device Circuit Voltage: 18 - 25.2VDC Initiating loop voltage: 19.05 - 25.18 VDC
Max Detector Circuit Standby Current: 2.5mA/circuit Compatibility Identifier: "A"
Compatibility Identifier: "A" NAC Power: Full Wave Rectified (Special Application)
NAC Power: Full Wave Rectified
MS-9600/MS-9600E (M302, MMF-302)
MS-2410B Initiating loop voltage: 16 - 27.5 VDC
Initiating Device Circuit Voltage: 18.62 - 25.43 VDC Compatibility Identifier: "A"
Max Detector Circuit Standby Current: 2.0 mA/circuit NAC Power: Filtered
Compatibility Identifier: "A"
MS-9050UD, MS-9050UDE (M302, MMF-302)
NAC Power: Full Wave Rectified
Initiating loop voltage: 18.75 - 26.1 VDC
MS-4012 Compatibility Identifier: "A"
Initiating Device Circuit Voltage: 8.62 - 12.7VDC NAC Power: Filtered (Special Application)
Max Detector Circuit Standby Current: 2.0mA/circuit
S200 (IZ-4F / IZ-4AF / IZ-8F)
Compatibility Identifier: "A"
Canada Only
NAC Power: Full Wave Rectified
Initiating Device Circuit Voltage: 17 - 26.5VDC
MS-4024 Max Detector Circuit Standby Current: 2.5mA/circuit
Initiating Device Circuit Voltage: 18 - 26.3VDC Compatibility Identifier: "A"
Max Detector Circuit Standby Current: 2.0mA/circuit NAC Power: Full Wave Rectified
Compatibility Identifier: "A"
S1000
NAC Power: Full Wave Rectified
Initiating Device Circuit Voltage: 18 - 25.7VDC
MS-4424, MRP-4424, and MS-4424B Max Detector Circuit Standby Current: 2.5mA/circuit
Initiating Device Circuit Voltage: 17.5 - 26.5VDC NAC Power: Full Wave Rectified
Max Detector Circuit Standby Current: 2.0mA/circuit
S2000 (IZ-4F / IZ-4AF / IZ-8F)
Compatibility Identifier: "A"
Initiating Device Circuit Voltage: 17 - 26.5VDC
NAC Power: Full Wave Rectified
Max Detector Circuit Standby Current: 2.5mA/circuit
MS-4412B Compatibility Identifier: "A"
Initiating Device Circuit voltage: 8.8V - 13.62VDC NAC Power: MPS-24A Filtered
Max Detector Circuit Standby Current: 2.0mA/circuit
MS-5UD-3(E), MS-10UD-3(E)
Compatibility Identifier: "A"
Initiating Device Circuit Voltage: 15.98 - 21.47
NAC Power: Full Wave Rectified
Max Detector Circuit Standby Current: 2.0mA/circuit
Compatibility Identifier: "A"
NAC Power: Full Wave Rectified (Special Application)
ECC-50/100(E) APS-6RF
Emergency Command Center Auxiliary Power Supply
NAC Power: Filtered (Special Application, Regulated) Use with the S-2000 control panels
Nominal operating voltage: 24 VDC NAC Power: Filtered
Maximum signaling current for special application power:
AVPS-24F
2.0 amps
Audio Visual Power Supply
Maximum signaling current for regulated power: 200 mA
Use with the S-2000 control panels
411-UDAC NAC Power: Full Wave Rectified
Universal Digital Alarm Communicator
FCPS-24F
Compatibility Identifier: "A"
Field Charger Power Supply
PCA Board Revision: All
Input voltage: 9 to 32VDC
Max Detector Circuit Standby Current: 2.0mA/ckt
Notification Circuit output: 19.1 to 26.4VDC
Initiating Device Circuit Voltage: 8.6 - 13.5VDC
NAC Power: Filtered
NAC Power: Full Wave Rectified (Special App)
PCB Board Revision: Revision E FCPS-2404
Max Detector Circuit Standby Current: 1.8mA/ckt Field Charger Power Supply
Initiating Device Circuit Voltage: 8.5 - 13.1VDC Input Voltage 9 to 32 VDC
NAC Power: Filtered (Special Application) NAC Power: Filtered
PCB Board Revision: Revision F or later FCPS-24FS6(E)(C), FCPS-24FS8(E)(C)
Max Detector Circuit Standby Current: 2.0mA/ckt Field Charger Power Supply
Initiating Device Circuit Voltage: 10.3 - 12.6VDC Input Voltage 9 to 32 VDC
NAC Power: Filtered (Special Application) NAC Power: Filtered (Special Application)
Revision level can be found on lower right edge of board
Fire Alarm Equipment – Controls & Systems Tested to ANSI Standards By Factory
Mutual
MS-9050UD, MS-9050UDE(M302, MMF-302) MS-9600LS(E), MS-9600UDLS(E) (M302, MMF-302)
Initiating loop voltage: 18.75-26.1 VDC Compatibility Identifier: "A"
Compatibility Identifier: "A" NAC Power: Filtered (Special Application)
NAC Power: Filtered (Special Application)
Various Manufacturers
System Sensor
System Sensor & Fenwal Detectors can be mixed or matched in any zone, provided maximum detector standby
current per loop is not exceeded.
Detector Base
MP-12 MP-24 MS-124 MS-424A MS-2410B
Model Number Model Number
1100/D N/A 20 20 N/A N/A 20
1151 B401/B110LP/B116LP 16 / 16 / N/A 16 / 16 / 1 N/A N/A 16 / 16 / 1
1400 N/A 16 16 16 20 20
1451 B401B / B406B / 16 / N/A 16 / 1 16 / 1 20 / 1 16 / 1
B110LP / B116LP 16 / N/A 16 / 1 16 / 1 20 / 1 16 / 1
1451DH DH-400 16 16 16 20 16
1851DH DH1851DC 16 16 16 20 16
2100/D/S N/A 16 16 N/A N/A 20
2100T/D/S N/A 16 16 N/A N/A 20
2151 B401 / B110LP / B116LP 16 / 16 / N/A 16 / 16 / 1 N/A N/A 16 / 16 / 1
2300T N/A 16 16 16 20 16
2400 N/A 16 16 16 20 16
2400AIT N/A N/A 1 1 1 1
2400AT N/A N/A 1 1 1 1
2400TH N/A 16 16 16 20 16
2451 B401B / B406B / 16 / N/A 16 / 1 16 / 1 20 / 1 16 / 1
B110LP / B116LP 16 / N/A 16 / 1 16 / 1 20 / 1 16 / 1
2451 DH-400 16 16 16 20 16
2451TH B401B / B406B / 16 / N/A 16 / 1 16 / 1 20 / 1 16 / 1
B110LP / B116LP 16 / N/A 16 / 1 16 / 1 20 / 1 16 / 1
2851DH DH2851DC 16 16 16 20 16
1800 N/A N/A
1851B B101B N/A
1851B B107B N/A
2800 N/A N/A
2800TH N/A N/A
2851B B101B N/A
2851B B107B N/A
2851BTH B101B N/A
2851BTH B107B N/A
Fenwal
Fenwal & System Sensor Detectors can be mixed or matched in any zone, provided maximum detector standby
current per loop is not exceeded.
MS-4424
Detector Base
MP-24 MS-124 MS-424A MS-4024 MS-4424B
Model Number Model Number
MRP-4424
CPD-7021 70-201000-001 33 33 40 30 30
70-201000-002
70-201000-003
70-201000-005
CPD-7021 70-211002-000 1 1 1 1 1
MS-5024
Detector Base M-302 S200
MS-5024UD S1000
Model Number Model Number MMF-302 S2000
MS-5210UD
CPD-7021 70-201000-001 25 40 40 41
70-201000-002
70-201000-003
70-201000-005
CPD-7021 70-211002-000 1 1 1 1
PSD-7125 70-201000-001 20 24 25 25
70-201000-002
70-201000-003
70-201000-005
PSD-7126 70-201000-001 20 24 25 25
70-201000-002
70-201000-003
70-201000-005
PSD-7129 70-211002-000 1 1 1 1
Fire•Lite Detectors
Only those control panels listed allow for the use of these detectors.
MS-5012
Detector Base
MP-12 MS-4012 411-UDAC MS-4412B
Model Number Model Number
(PCA revision)
LPSD-12 BLP-12-R 11 11 11 11
Edwards Detectors
Only those control panels using the monitor modules listed allow for the use of these detectors.
6250B 6251B-001 20
6264B N/A 1
6270B 6251B-001 20
2098-9201 2098-9211 20
2098-9202 2098-9211 20
2098-9576 2098-9211 20
DS200 MB200-2W 10 10 15 10 15
DS200HD MB200-2W 10 10 15 10 15
* *
System Sensor B404B Base
System Sensor DH100ACDC Photoelectric 0.15 0.70
System Sensor DH100ACDCLP Photoelectric 0.15 0.70
System Sensor DH100ACDCLWP Photoelectric 0.15 0.70
System Sensor DH400ACDCI† Ionization Duct 25 95
System Sensor DH400ACDCP† Photoelectric Duct 25 95
System Sensor 1112/24/D Ionization 0.05 50
System Sensor 1424 Ionization 0.10 41
System Sensor 1451 (w/ B402B/B112LP Base) Ionization 0.10 39
System Sensor 2112/24ATR Photoelectric 0.50 60/70
System Sensor 2112/24AITR Photoelectric 0.50 60/70
System Sensor 2112/24/D Photoelectric 0.05 50
System Sensor 2112/24R Photoelectric 0.50 60/70
System Sensor 2112/24TR Photoelectric 0.50 60/70
Module
System Sensor 6424† Projected Beam 10 28.4
System Sensor Beam 1224(S) Projected Beam 17 38.5
System Sensor OSI-R-SS Conventional Beam 50* 54*
System Sensor OSI-RA-SS Conventional Beam 50* 54*
Notification Appliances
Control panels with Notification circuits supplied by Special Application power must use appliances listed in this
table.
• Refer to manufacturer’s installation instructions for more information.
• Contact manufacturer for current draws or additional options
MS-5012
MS-5012
Gentex - 12VDC
Use only 12VDC devices with 12 volt control panels.
MODEL NUMBER & NOMENCLATURE (Gentex)
GX-90-2 Horn
GXS-2-15, GXS-2-1575 Strobe
GX90S-2-15 Horn with Strobe
GX90S-2-1575 Horn with Strobe
HG124 Electronic Horn
SHG12-15, SHG12-1575 Electronic Horn with Strobe
Gentex - 24VDC
Use only 24VDC devices with 24 volt control panels.
MODEL NUMBER & NOMENCLATURE (Gentex)
Cooper-Wheelock - 12VDC
Use only 12VDC devices with 12 volt control panels.
MODEL NUMBER & NOMENCLATURE (Cooper-Wheelock)
Cooper-Wheelock - 24VDC
Use only 24VDC devices with 24 volt control panels.
MODEL NUMBER & NOMENCLATURE (Cooper-Wheelock)
Cooper-Wheelock Speakers
Amseco
Compatible with the following:
MS-5UD-3(E), MS-10UD-3(E), MS-5UD-7(E), MS-10UD-7(E), MS-5UD-7C, MS-10UD-7C, MRP-2001(E),
MRP-2002(E)
SH24W-153075, SAD24-153075, SAD24-75110, SL24W-75110, SL24C-3075110, SLB24-75
RSD24-153075, RSD24-75110, SH24W-75110, SH24W-3075110, SHB24-75,
SCM24W-153075, SCM24W-75110, SCM24C-3075110, SCM24C-177, H24W, H24R
Faraday
Compatible with the following:
MS-5UD-3(E), MS-10UD-3(E), MS-5UD-7(E), MS-10UD-7(E), MS-5UD-7C, MS-10UD-7C, MRP-2001(E),
MRP-2002(E)
Quam-Nichols Speakers
UL22/25, UL22/70
System Sensor
MDLA / MDLWA Sync Modules, H24A, P1224MCA, P2415A, P241575A, P2475A, P24110A, PC2415A, PC241575A,
PC2430A, PC2475A, PC24115A, PC24177AS1224MCA, S2415A, S241575A, S2475A, SC24110A, SC2415A,
SC241575A, SC2430A, SC2475A, SC2495A, SC24115A, SC24177A,
SSM24-6A, SSM24-8A, SSM24-10A - Alarm Bells
CHWA, CHRA, HRA, HWA, SRA, SWA, SCRA, SCWA, SRHA, SWHA, SCRHA, SCWHA, P2RA, P2WA, PC2RA,
PC2WA, P4RA, P4WA, PC4RA, PC4WA, CHSRA, CHSWA
Gentex
Strobe lights, synchronizable type, Models ST24-15, -15/75, -30, -60, -75, -110; Models GES24-15, -15/75, -30,
-60, -75, -110, -177. Models may be followed by suffix -P (plain), followed by W (wall), followed by W or R (white
or red color). Intended for indoor use on a wall.
Strobe light, synchronizable type, Model GES3-24, may be followed by suffix -P (plain), followed by W (wall),
followed by W or R (white or red color). Selectable candela (15cd, 30cd, 60cd, 75cd and 110cd). Intended for indoor
use on a wall only.
Strobe light, synchronizable type, Model GES3-12, may be followed by suffix -P (plain), followed by W (wall),
followed by W or R (white or red color). Selectable candela (15cd, 30cd, 60cd, 75cd). Intended for indoor use on a
wall only.
Cooper-Wheelock
Automatic Water Control Valves (FM-Approved) For Preaction and Deluge Sprinkler
Releasing Applications
Solenoid Group A
Solenoid Group C
Star Sprinkler Corp. p/n 5550 24 VDC part of Model D Deluge Valve
Solenoid Group D
Solenoid Group E
Solenoid Group F
Solenoid Group G
MRP-2001(E), MRP-2002(E)
Compatible Solenoids
Rated Current Rated Voltage
Manufacturer Model
DC Milliamps DC Volts
Door Holders
Current
MANUFACTURER MODEL TYPE
(mA)
Relays
Ditek 2LVLP-F
Edco SLCP-30
• MS-9600 • MS-9050UD
• S-2000 with MPS-24A/APS-6R • MS-5UD-7(C)(E), MS-10UD-7(C(E))
• FCPS-24FS6(E), FCPS-24FS8(E) • MRP-2001(E),MRP-2002(E)
• FCPS-24 • MS-9600LS, MS-9600UDLS
• FCPS-2404