Alpha 12
Alpha 12
Alpha 12
High-speed train traction power supply system causes serious negative current problem.
Railway power conditioner (RPC) is efficient in negative sequence compensation. A
novel power quality collaboration compensation system and strategy based on RPC is
proposed in this paper. The minimum capacity conducted is 1/3 smaller than traditional
single station compensation. Simulation results have confirmed that the collaboration
compensation system proposed can achieve a good performance at the negative
sequence compensation with capacity and cost efficient.
Contents
LIST OF FIGURES..............................................................................................................................i
LIST OF TABLES..............................................................................................................................ii
LIST OF ABBREVIATIONS............................................................................................................iii
1. INTRODUCTION...........................................................................................................................1
2. RAILWAY ELECTRIFICATION SYSTEM................................................................................3
2.1 Characteristics of Electric Traction..............................................................................................4
2.2.1 Summary..............................................................................................................................6
2.3 Energy efficiency.........................................................................................................................7
3. HARMONICS..................................................................................................................................9
3.1 HARMONICS.............................................................................................................................9
3.8.1 Definition............................................................................................................................20
3.9 Power Measurement..................................................................................................................21
5.5 INVERTER...............................................................................................................................34
7.3 CONCLUSION.........................................................................................................................54
BIBLIOGRAPHY..............................................................................................................................55
LIST OF FIGURES
LIST OF TABLES
i
Table 1: Harmonic Sequencing Values in Balanced Systems 12
Table 2: Sample of Harmonic Values for Fluorescent lighting 15
Table 3: Typical Harmonics Found for Different Converters 18
Table 4: Current Harmonic Limits as per IEEE 519-1992 19
Table 5: Voltage Harmonic Limits as per IEEE 519-1992 19
Table 6: Comparison of Two Compensation Method 47
LIST OF ABBREVIATIONS
ii
RPC – RAILWAY POWER CONDITIONER
DC – DIRECT CURRENT
AC – ALTERNATING CURRENT
iii
CHAPTER-1
INTRODUCTION
iv
1. INTRODUCTION
With the rapid development of high-speed railway in China, power quality has become
a major concern for traction supply system. Compared with normal electrification
railway locomotive load, high-speed locomotive load has some characteristics, such as
big instantaneous power, high power factor, low harmonic components and high
negative sequence component. A large amount of negative current is injected into grid,
which causes serious adverse impact on power system, such as increasing motor
vibration and additional loss, reducing output ability of transformers and causing relay
protection misoperation. These adverse impacts threaten the safety of high-speed
railway traction supply system and power system. Therefore, it’s necessary to take
measures to suppress negative current.
Many methods and power quality compensators are studied in order to solve the issue
of power quality. The traditional methods adopted to suppress negative current are as
follows: (1) Connect unbalanced load to different supply terminals;(2) Adopt phase
sequence rotation to make unbalanced load distributed to each sequence reasonably;(3)
Connect unbalanced load to higher voltage level supply terminals; (4) Use balanced
transformers such as Scott transformer and impedance balance transformer. These
methods have some effects on reducing unbalance degree, but they are lack of
flexibility and can't adjust dynamically.
To reduce the high compensator capacity, this paper puts forward a new railway
negative unbalance compensation system based on the thought of multiple RPC
collaboration compensation. This method realizes a minimum compensation capacity
which is strictly proved, which reduces 1/3 capacity compared with traditional single
station RPC compensation method. The simulation results have verified the correctness
of the method proposed in this project.
Fig 2(b) Overhead wire and centenary in Bridgeport, Connecticut, United states
Other advantages include the lack of exhaust fumes at point of use, less noise and lower
maintenance requirements of the traction units. Given sufficient traffic density, electric
trains produce fewer carbon emissions than diesel trains, especially in countries where
electricity comes primarily from non-fossil sources.
A fully electrified railway has no need to switch between methods of traction thereby
making operations more efficient. Two countries that approach this ideal are
Switzerland and Hong Kong, but both use more than one system, so unless multi-
system locomotives or other rolling stock is used, a switch of traction method may still
be required.
The main disadvantages are the capital cost of the electrification equipment, most
significantly for long distance lines which do not generate heavy traffic. Suburban
railways with closely-spaced stations and high traffic density are the most likely to be
electrified and main lines carrying heavy and frequent traffic are also electrified in
many countries. Also, if the overhead wiring breaks down in some way, all trains can
be brought to a standstill.
Voltage
Current
Direct current (DC)
Alternating current (AC)
Frequency
Contact System
Third rail overhead line (catenary)
2.2.1 Summary
Summary of advantages and disadvantages:
Lines with low frequency of traffic may not be feasible for electrification
(especially using regenerative braking), because lower running cost of trains
may be overcome by the higher costs of maintenance. Therefore most long-
distance lines in North America and many developing countries are not
electrified due to relatively low frequency of trains.
Electric locomotives may easily be constructed with greater power output than
most diesel locomotives. For passenger operation it is possible to provide
enough power with diesel engines (see e.g. 'ICE TD') but, at higher speeds, this
proves costly and impractical. Therefore, almost all high speed trains are
electric.
The high power of electric locomotives gives them the ability to pull freight at
higher speed over gradients; in mixed traffic conditions this increases capacity
3.1 HARMONICS
The typical definition for a harmonic is “a sinusoidal component of a periodic wave
or\ quantity having a frequency that is an integral multiple of the fundamental
frequency.” Some references refer to “clean” or “pure” power as those without any
harmonics. But such clean waveforms typically only exist in a laboratory. Harmonics
have been around for a long time and will continue to do so. In fact, musicians have
been aware of such since the invention of the first string or woodwind instrument.
Harmonics (called “overtones” in music) are responsible for what makes a trumpet
sound like a trumpet, and a clarinet like a clarinet.
Electrical generators try to produce electric power where the voltage waveform has
only one frequency associated with it, the fundamental frequency. In the North
America, this frequency is 60 Hz, or cycles per second. In European countries and other
parts of the world, this frequency is usually 50 Hz. Aircraft often uses 400 Hz as the
fundamental frequency. At 60 Hz, this means that sixty times a second, the voltage
waveform increases to a maximum positive value, then decreases to zero, further
decreasing to a maximum negative value, and then back to zero. The rate at which these
changes occur is the trigometric function called a sine wave, as shown in figure 1. This
function occurs in many natural phenomena, such as the speed of a pendulum as it
swings back and forth, or the way a string on a voilin vibrates when plucked.
These methods only work properly if the signal is composed of only the fundamental
and harmonic frequencies in a certain frequency range (called the Nyquist frequency,
which is one-half of the sampling frequency). The frequency values must not change
during the measurement period. Failure of these rules to be maintained can result in
mis-information. For example, if a voltage waveform is comprised of 60 Hz and 200
Hz signals, the FFT cannot directly see the 200 Hz. It only knows 60, 120, 180, 240,...,
which are often called “bins”.
The result would be that the energy of the 200 Hz signal would appear partially in the
180Hz bin, and partially in the 240 Hz bin. An FFT-based processer could show a
voltage value of 115V at 60 Hz, 18 V at the 3rd harmonic, and 12 V at the 4th
harmonic, when it really should have been 30 V at 200 Hz.
These in-between frequencies are called “inter harmonics”. There is also a special
category of inter harmonics, which are frequency values less than the fundamental
frequency value, called sub-harmonics. For example, the process of melting metal in an
The presence of harmonics does not mean that the factory or office cannot run
properly. Like other power quality phenomena, it depends on the “stiffness” of the
power distribution system and the susceptibility of the equipment. As shown below,
there are a number of different types of equipment that can have mis operations or
failures due to high harmonic voltage and/or current levels. In addition, one factory
may be the source of high harmonics but able to run properly. This harmonic pollution
is often carried back onto the electric utility distribution system, and may effect
facilities on the same system which are more susceptible.
Since this article is about harmonics, we will concentrate on those types of sources.
“The main sources of harmonic current are at present the phase angle controlled
rectifiers and inverters.” These are often called static power converters. These devices
take AC power and convert it to another form, sometimes back to AC power at the
same or different frequency, based on the firing scheme. The firing scheme refers to the
controlling mechanism that determines how and when current is conducted. One major
variation is the phase angle at which conduction begins and ends.
A typical such converter is the switching-type power supplies found in most personal
computers and peripheral equipment, such as printers. While they offer many benefits
in size, weight and cost, the large increase of this type of equipment over the past
fifteen years is largely responsible for the increased attention to harmonics.
Figure shows below how a switching-type power supply works. The AC voltage is
converted into a DC voltage, which is further converted into other voltages that the
equipment needs to run. The rectifier consists of semi-conductor devices (such as
diodes) that only conduct current in one direction. In order to do so, the voltage on the
one end must be greater than the other end. These devices feed current into a capacitor,
where the voltage value on the cap at any time depends on how much energy is being
taken out by the rest of the power supply.
When the input voltage value is higher than voltage on the capacitor, the diode will
conduct current through it. This result in a current waveform is as shown in Fig 3.3 (a),
and harmonic spectrum in Fig 3.3(b). Obviously, this is not a pure sinusoidal waveform
with only a 60 Hz frequency component.
If the rectifier had only been a half wave rectifier, the waveform would only have
every other current pulse, and the harmonic spectrum would be different, as shown in
Fig 3.3 (b).
Fluorescent lights can be the source of harmonics, as the ballasts are non-linear
inductors. The third harmonic is the predominate harmonic in this case. (See Table 2)
As previously mentioned, the third harmonic current from each phase in a four-wire
Department of EEE, KMMITS 14 | P a g e
wye or star system will be additive in the neutral, instead of cancelling out Some of the
newer electronic ballasts have very significant harmonic problems, as they operate
somewhat like a switching power supply, but can result in current harmonic distortion
levels over 30%.
Low power, AC voltage regulators for light dimmers and small induction motors
adjust the phase angle or point on the wave where conduction occurs. Medium power
converters are used for motor control in manufacturing and railroad applications, and
include such equipment as ASDs (adjustable speed drives) and VFDs (variable
frequency drives). Metal reduction operations, like electric arc furnaces, and high
voltage DC transmission employ large power converters, in the 2-20MVA rating.
This type of 3-phase equipment may also cause other types of power quality
problems. When the semiconductor device is suppose to turn-off, it does not do so
abruptly. This happens under “naturally” commutated conditions, where the voltage
that was larger on the anode side compared to the cathode is now the opposite. This
occurs each cycle as the voltage waveform goes through the sine waveform. It also
happens under “forced” commutation conditions, where the semi-conductor device has
a “gate”-type control mechanism built in to it. This commutation period is a time when
two semiconductor devices are both conducting current at the same time, effectively
shorting one phase to the other and resulting in large current transients.
Wherever the aforementioned equipment is used, one can suspect that harmonics are
present. The amount of voltage harmonics will often depend on the amount of harmonic
currents being drawn by the load, and the source impedance, which includes all of the
wiring and transformers back to the source of the electricity. Ohm’s Law says that
Voltage equals Current multiplied by Impedance. This is true for harmonic values as
well. If the source harmonic impedance is very low (often referred to as a “stiff”
system) then the harmonic currents will result in lower harmonic voltages than if the
source impedance were high (such as found with some types of isolation transformers).
Like any power quality investigation, the search can begin at the equipment effected
by the problem or at the point-of-common-coupling (PCC), where the utility service
meets the building distribution system. If only one piece of equipment is effected (or
suspected), it is often easier to start the monitoring process there. If the source is
suspected to be from the utility service side (such is the case when there is a
neighbouring factory that is known to generate high harmonics), then monitoring
usually begins at the PCC.
The phase voltages and currents, as well as the neutral-to-ground voltage and neutral
current should be monitored, where possible. This will aid in pinpointing problems, or
detecting marginal systems. Monitoring the neutral will often show a high 3rd harmonic
value, indicating the presence of non-linear loads in the facility.
Hand-held harmonic meters can be useful tools for making spot checks for known
harmonic problems. However, harmonic values will often change during the day, as
different loads are turned on and off within the facility or in other facilities on the same
electric utility distribution system. This requires the use of a harmonic monitor or
power quality monitor with harmonic capabilities (such as shown in Figure 8), which
can record the harmonic values over a period of time.
Typically, monitoring will last for one business cycle. A business cycle is how long it
takes for the normal operation of the plant to repeat itself. For example, if a plant runs
three identical shifts, seven days a week, then a business cycle would be eight hours.
More typically, a business cycle is one week, as different operations take place on a
Monday, when the plant equipment is restarted after being off over the weekend, then
on a Wednesday, or a Saturday, when only a Skelton crew may be working.
For voltage harmonics, the voltage level of the system is used to determine the limits,
as shown in Table 5. At the higher voltages, more customers will be effective, hence,
the lower limits.
The European Community has also developed susceptibility and emission limits for\
harmonics. Formerly known as the 555-2 standard for appliances of less than 16 A, a
more encompassing set of standards under IEC 1000-4-7 are now in effect.
Isolating harmonic pollution devices on separate circuits with or without the use of
harmonic filters are typical ways of mitigating the effects of such. Loads can be
relocated to try to balance the system better. Neutral conductors should be properly
sized according to the latest NEC-1996 requirements covering such. Whereas the
neutral may have been undersized in the past, it may now be necessary to run a second
neutral wire that is the same size as the phase conductors. This is particularly important
with some modular office partition-type walls, which can exhibit high impedance
values. The operating limits of transformers and motors should be derated, in
accordance with industry standards from IEEE, ANSI and NEMA on such. Use of
higher pulse converters, such as 24-pulse rectifiers, can eliminate lower harmonic
values, but at the expense of creating higher harmonic values.
3.8.1 Definition
THD is defined as the RMS value of the waveform remaining when the fundamental
is removed. A perfect sine wave is 100%, the fundamental is the system frequency of
50 or 60Hz. Harmonic distortion is caused by the introduction of waveforms at
frequencies in multiplies of the fundamental ie: 3rd harmonic is 3x the fundamental
frequency / 150Hz. Total harmonic distortion is a measurement of the sum value of the
waveform that is distorted.
4.1 INTRODUCTION
The AC electrified railway systems have the power quality problems such as the
reactive power consumption and the load imbalance due to their inherent electrical
characteristics of single-phase and nonlinear moving loads. Also the power electronics
equipments in the AC electrified railway systems produce the large amount of
harmonic currents. These power quality problems in the AC electrified railway systems
have a bad effect on themselves as well as other electric systems connected together.
Therefore a power quality compensator is required to maintain the proper power quality
in the AC electrified railway systems. There are many researches on the power quality
compensator for improving power quality in the AC electrified railway applications.
Especially, a single-phase active power filter and a single-phase hybrid active power
filter, being composed of a passive power filter and an active power filter, have been
studied. Most of the active power filters are connected in parallel with M-phase and T-
phase secondary outputs of Scott transformer respectively. Although they can
compensate the harmonic currents and the reactive power, the load imbalance cannot be
compensated. A three-phase active power filter for power quality compensation has
been proposed. However, the three-phase active power filter installed at the three-phase
mains requires the high-voltage rating. Another active power quality compensator,
being composed of a three-phase inverter and a Scott transformer. An active power
quality compensator with two single-phase inverters connected back-to-back (that is
called the RPQC in this project). The RPQC requires no additional Scott transformer
and can be operated at lower voltage level than the three-phase active power filter. In
spite of these merits, there are few researches on the control of RPQC. A novel control
algorithm based on SRF for the RPQC is proposed. The proposed RPQC control
algorithm can properly compensate the harmonic currents, the reactive power, and the
load imbalance. The effectiveness and the validity of the proposed control algorithm are
demonstrated through the simulations.
Fig 4.2 shows an AC electrified railway system adopting the RPQC. The RPQC
consists of two single-phase inverters sharing a DC-link capacitor. Each of the single
phase inverters is connected with M-phase and T-phase feeder of the Scott transformer.
The RPQC controller is shown in Fig. 4.2.1 consists of the DC-link voltage for the DC-
link voltage regulation, the inverter currents for the current control, and the load
currents for the harmonic extraction are required as the controller inputs. The RPQC
can compensate not only the harmonic currents and reactive power, but also the load
imbalance by exchanging the active power deviation between M-phase and T-phase
feeders through the DC-link capacitor. Fig 4.2.1 shows an AC electrified railway
system adopting the RPQC. The RPQC consists of two single-phase inverters sharing a
DC-link capacitor. Each of the single phase inverters is connected with M-phase and T-
phase feeder of the Scott transformer.
............... .. (1)
After transforming the load current in equation (1) into the SRF coordinate, the
respective d-q components can be expressed as the following equations (2) and (3).
....................... (3)
where, M Ld I − and M Lq I − are the DC values of the load current on the SRF. The
DC values of the d-q axis are obtained by using the low pass filters. M Ld I − % and M
Lq I − % are the AC values of the load current on the SRF, which means the harmonic
contents of the load current. Therefore, when the d-q DC values are subtracted from the
d-q load currents, the d-q harmonic currents to be compensated are obtained. Fig. 4.3
shows the method to extract the harmonic components from the load current.
.................. (4)
Through substituting equations (2) and (3) into equation (1), equation (5) can be
derived as follows
............. (5)
Therefore, the single-phase instantaneous active power and reactive power can be
described as equations (6) and (7).
.................. (6)
....................... (7)
where, VM−Lrms and IM−Lrms denote the RMS value of vM−L and vM−L, respectively. It is
shown that the single phase instantaneous active power depends on the d-axis current
value, while the instantaneous reactive power depends on the q-axis current value. The
source current, iM− s is made by the load current of M-phase, iM− L and the inverter
current, iM−inv, as in equation (8)
....................................... (8)
If the q-axis value of the source current becomes zero through the compensation of the
q-axis current, the corresponding reactive power can be compensated. Fig 4.3.1 shows
the control blocks of reactive power compensation algorithm.
5.2.2 Working
When collector is made positive with respect to emitter, IGBT gets forward
biased. With no voltage between gate and emitter, two junctions between n- region and
p region (i.e. junction J2) are reversed biased; so no current flows from collector to
emitter
When gate is made positive with respect to emitter by voltage V G, with gate-emitter
voltage more than the threshold voltage VGET of IGBT, an n-channel or inversion layer,
is formed in the upper part of p region just beneath the gate, as in PMOSFET. This n-
channel short circuits the n- region with n+ emitter regions. Electrons from the n+
emitter begin to flow to n- drift region through n-channel. As IGBT is forward biased
with collector positive and emitter negative, p+ collector region injects holes into n-
drift region .In short; n-drift region is flooded with electrons from p-body region and
holes from p+ collector region. With this, the injection carrier density in n- drift region
Holes current Ih due to injected holes flowing from collector , p+ n- p transistor Q1, p-
body region resistance Rby and emitter .
Electronic current Ie due to injected electrons flowing from collector, or load, current
IC=emitter current Ie=Ih+Ie.
Major component of collector current is electronic current Ie, i.e. main current path for
collector, or load, current is through p+, n -, drift resistance Rd and n-channel resistance
Rch. Therefore, the voltage drop in IGBT in its on-state is
Vc e . o n = I c . R c h + I c . Rd + V j i
Here Vji is usually 0.7 to 1v as in a p-n diode. The voltage drop Ic. Rch is due to n-
channel resistance, almost the same as in a PMOSFET. The voltage drop Vdf = Ic.Rd in
UGBT is much less than that in PMOSFET. It is due to substantial increase in the
conductivity caused by injection of electrons and holes in n- drift region. The
conductivity increase is the main reason for the low on-state voltage drop in IGBT than
that it is in PMOSFET.
the plot of collector current Ic versus collector-emitter voltage Vce for various values of
gate-emitter voltages VGE1, VGE2 etc .These characteristics are shown below .In the
forward direction, the shape of the output characteristics is similar to that of BJT . But
here the controlling parameter is gate-emitter voltage VGE because IGBT is a voltage
controlled device. When the device is off, junctionJ2 blocks forward voltage and in
The rise time t r is the time during which collector-emitter falls from
0.9VCE to 0.1VCE. IT is also defined as the time for the collector current to rise from
0.1Ic to its final value Ic. After time ton, the collector current Ic and the collector-emitter
voltage falls to small value called conduction drop=VCES where subscript s denotes
saturated value.
The delay time is the time during which gate voltage falls from VGE to threshold voltage
VGET.As VGE falls to VGET during tdf, the collector current falls from Ic to 0.9 Ic. At the
end of the tdf, collector-emitter voltage begins to rise. The first fall time T f1 is defined as
the time during which collector current falls from 90 to 20 % of its initial value I c, or
the time during which collector-emitter voltage rises from VCES to 0.1 VCE.
The final fall time t f2 is the time during which collector current falls
from 20 to 10% of Ic, or the time during which collector-emitter voltage rises from 0.1
VCE to final value VCE.
5.5 INVERTER
Generally inverters are of Two Types:
Thus, nearly sinusoidal load voltages are generated that justifies the use of these
topologies in medium-voltage industrial applications, where high-quality voltage
waveforms are required.
There are nine valid states in three-phase CSIs. Produce zero ac line currents. In this
case, the dc link current freewheels through either the switches S 1 and S4, switches S3
and S6, or switches S5 and S2.
The remaining states produce nonzero ac output line currents. In order to generate a
given set of ac line current waveforms, the inverter must move from one state to
another. Thus, the resulting line currents consist of discrete values of current, which are
ii , 0, and ÿii . The selection of the states in order to generate the given waveforms is
done by the modulating technique that should ensure the use of only the valid states.
................... (5.1)
And
.................... (5.2)
................. (5.3)
To satisfy the Kirchhoff’s Voltage law (KVL) constraint, the switches on the same leg
are not turned on at the same time, which gives the condition
................... (5.4)
for each leg of the inverter. This enables the output voltage to fluctuate between V d/2
and −Vd/2as shown in Figure 2.4 for a dc voltage of 200 V.
Fig 6.1 Traction power system with a three-phase V/V transformer and a RPC
The right feeder section in Fig.1 is denoted as a-phase power arm, while that the left
side is b-phase power arm. The corresponding phases on the primary side are denoted
as Phase A and Phase B, respectively. Since using four-quadrant pulse rectifiers to feed
electrical locomotives, the power factor of high speed electrical locomotive is close to
1. Set UA as the reference value. Assume that the fundamental current vector of a-phase
power arm isaL and the fundamental current vector of b-phase power arm is IbL . IaL and
IbL are shown as follows :
................. (6.0)
The turns ratio of V/V transformer is K, so the three currents of the high-voltage side
are shown as follows:
Before RPC compensation, a-phase power arm has load current aL and the b-phase
power arm has load current bL. Assume that , the three phase current is shown in
Fig.6.1.1
.................. (6.3)
................. (6.4)
, --the equivalent current of RPC converters of a-phase arm and b-phase arm at the
ca cb
voltage of 27.5 kV
The capacity in phase CA, AB and BC is x,y,z , which has a relationship of x>y>z. The
network of x,y,z can be divided into two parts, the one is a balanced network of z,z,z ,
the other is an unbalanced network of x-z, y-z, 0. Assume that X = x − z, Y = y − z, the
original network is simplified as X,Y,0 . Set X/2 as the reference value, the p.u. value of
the simplified network is 2, Y′, 0. Y′ is varying from 0 to 2. The extreme case is Y′ =0.
The optimize compensation strategy is shown below:
A. Single RPC compensation:
Based on the compensation strategy of RPC, when there is a maximum capacity in one
of the traction feeder arms, RPC transfers active power from one traction feeder arm to
another. And then compensates reactive power to both traction feeder arms based on
Steinmetz theory. So the compensation capacity of single RPC is:
................. (6.1)
B. Three stations collaboration compensation:
The simple model of 3 stations structure is shown in Fig.6.2.1. Since RPC could
transfer a quantity of active power and compensate reactive power, a triangle is applied
to illustrate the principle of collaboration compensation: apexes of the triangle are
regarded as active load in Phase-AC, Phase-BC and Phase- AB, and edges of the
triangle are regarded as three railway power conditioners. The arrows mean the delivery
of active power (real part) and compensation of reactive power (imaginary part). There
are three steps to compensate. Firstly, transfer a quantity of active power. Secondly,
separate the network into two parts: a balanced network and an unbalanced network.
And last, make compensation to the unbalanced network based on the Steinmetz theory.
(a) Active power delivery (b) Three phase power after active power
delivery
capacity when .
1 1
The results can be conducted that a= , b = and the minimum capacity is
3 3√3
................. (6.2.1)
This is 2/3 of the capacity of single RPC compensation. Tab.6 shows the
compensation capacity of the two strategies.
It can be proved that this installed capacity (0.1925X) can satisfy any condition when Y'
varying from 0 to 2.
If there is N stations connect to one 220kV bus, N may be 3n, 3n+1 or 3n+2
(n=0,1,2…). When N=3n, it means there are n sets of 3-stations compensation. When
N=3n+1, it means there are n sets of 3-stations compensation and a single station
compensation. When N=3n+2, it means there are n sets of 3- stations compensation and
2 single station compensation.
MATLAB is a numerical computation and simulation tool that was developed into a
commercial tool with a user friendly interface from the numerical function libraries
LINPACK and EISPACK, which were originally written in the FORTRAN
programming language.
As opposed to the well-known computer algebra programs, such as MAPLE or
MATHEMATICA, which are capable of performing symbolic operations and,
therefore, calculating with mathematical equations as a person would normally do with
paper and pencil, in principle MATLAB does purely numerical calculations.
Nevertheless, computer algebra functionality can be achieved within the MATLAB
environment using the so-called “symbolics” toolbox.
Simulink, developed by MathWorks, is a data flow graphical programming language
tool for modeling, simulating and analyzing multidomain dynamic systems. Its primary
interface is a graphical block diagramming tool and a customizable set of block
libraries. It offers tight integration with the rest of the MATLAB environment and can
either drive MATLAB or be scripted from it. Simulink is widely used in control theory
and digital signal processing for multidomain simulation and Model-Based Design.
7.1 MATLAB Simulink for RPC Compensation
Simulation is done to proof the correctness of the theory by MATLAB/Simulink.
Hence the parameters of Single & Multiple RPC Compensation are taken as follows
Assume the maximum load capacity appears at a-phase power arm, that is PAC = 1 .
The base capacity is Pbase = 20MW , and the short-circuit capacity is 750MVA. The
power of b-phase locomotive load is 0. The a-phase load was switch on at 0s, the
compensation system ran at 0.5s.
The simulation schematic diagram is shown in Fig 7.1.1 and Fig 7.1.2. The simulation
parameters are as follows: three phase voltage of the system is 220kV; the frequency is
50Hz; the ratio of V/V transformer is 8:1; the ratio of step down transformer is 40:1;
the capacitor of RPC at DC side is 100000μF, and the value of L1 and L2 is 3mH and
2mH respectively.
49 | P a g e
Fig 7.1.2 Matlab Simulink of RPC Technique For Three Stations Collabration
Compensation
X. Huang, L. Zhang, M He, X.You, and Q. Zheng, "Power electronics used in Chinese
electrical locomotives", in Proc. IEEE 6th Int. Conf. Power Electron. Motion Control,
pp.1196-1200,May, 2009.
Zhuo Sun, Xinjian Jiang, Dongqi Zhu, et al. “A novel active power quality compensator
topology for electrified railway,” IEEE Trans. On Power Electron., vol.19, pp. 1036-
1042, July,2004.
Lu Fang, An Luo, Xiaoyong Xu, Houhui Fang,"A novel power quality compensator
for negative-sequence and harmonic currents in high-speed electric railway, "Power
and Energy Engineering Conference (APPEEC),pp. 1-5, 2011.