Artcle 1.2.3.
Artcle 1.2.3.
Artcle 1.2.3.
1.2.3 Special
1.2.3.1 Temporary Installation.
For temporary electrical installation, the same procedure as stated above
shall be followed. At the end of the period covered by the certificate of
inspection, the temporary installation shall be removed. Extended use of
the temporary installation shall require an extension or renewal of the
electrical permit from the office of the building official (OBO) signed by
the Office of the Building Official/EE (OBO/EE).
760 mm x 1000 mm
600 mm x 900 mm
500 mm x 760 mm
(B) In case such as projects of large magnitude, exemption in the use of
the standard drawing sheets may be granted by the office of the local
building official.
(C ) For dwelling unit having a floor area of not more than 50 square
meters with a total load not exceeding 3680 VA, a drawing sheet of size
297 mm x 420 mm (A3 size) is permitted.
1.3.1.3 Graphic Scale. Since the size of the drawing sheet can be
changed photographically, graphic scale shall be shown on each drawing
sheet.
(1) Plan for Power. Layout and wiring plans for power on the floor
plans drawn to scale, shall show:
a. Sizes and location of service entrance conductors, raceways, metering
equipment, main switchboard, layout of feeders and distribution panels
or switches and their sizes, types and ratings;
b. Complete circuits of motors and other electrical equipment, their
controlling devices, their locations and ratings;
c. Complete wiring of emergency power system, if any;
d. Nature of processes/activities carried out in each room or area
(2) Plan for Lighting and Receptacle Outlets. Layout and wiring plans
for general lighting and receptacle outlets on floor plans drawn to scale,
shall show;
a. Location, type and rating of lighting fixtures, indicating illumination
in lux in each room or area. In residence, hotels, apartment houses, and
churches, the illumination level in each room or area need not be shown
nor computed;
b. Location of switches for each fixtures or group of fixtures;
c. Location of receptacle outlets and appliances to be served and their
ratings;
d. Complete circuits of the lighting and receptacle outlets;
e. Complete wiring of emergency lighting system, if any;
f. A separate drawing showing layout of receptacle outlets may be made
at the discretion of the design engineer.
(3) Plan for Fire Alarm Circuits. Layout and wiring plans of fire alarm
station, fire alarm bell, fire alarm control panel, and other shall be drawn
to scale and show.