Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Supplement To The AM2020/AFP1010 Voice Alarm Multiplex Manual Number 15889, Revision F1, Dated 12/11/97

Download as pdf or txt
Download as pdf or txt
You are on page 1of 14

Supplement to the

AM2020/AFP1010
Voice Alarm Multiplex Manual Number 15889,
Revision F1, dated 12/11/97

This supplement includes the following:


Document Divider Information .................................................................................. page 2

Replace the following pages dated 12/11/97, with the same numbered pages dated 10/01/01:
• Cover page/Precautions and Limitations p.1
• Page 19/20
• Page 21/22
• Page 51/52
• Limited Warranty/Rear Cover
Replace Page 3/4 with Precautions and Limitations p.2/Page 4

Document 15889SUP
10/01/01 Revision
ECN 01-537
F2
Tab Set 50022, Bank 2 for Document 15889

The three-ring binder tab set shown above is shipped with every AM2020/AFP1010 system.
If you cannot locate the set in your shipment or if it has been misplaced, you may order
another tab set, Part Number 50022, from your Notifier Customer Service Representative.

2 Voice Alarm Multiplex 15889SUP:F2


15889:F2 10/01/01
P/N 15889:F2 ECN 01-537

AM2020/AFP1010
Voice Alarm
Multiplex
Operation and Installation Manual

Document 15889
10/01/01 Rev: F2
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!

An automatic fire alarm system—typically made up of Heat detectors do not sense particles of combustion and
smoke detectors, heat detectors, manual pull stations, audible alarm only when heat on their sensors increases at a predeter-
warning devices, and a fire alarm control with remote notifica- mined rate or reaches a predetermined level. Rate-of-rise
tion capability—can provide early warning of a developing fire. heat detectors may be subject to reduced sensitivity over time.
Such a system, however, does not assure protection against For this reason, the rate-of-rise feature of each detector
property damage or loss of life resulting from a fire. should be tested at least once per year by a qualified fire pro-
The Manufacturer recommends that smoke and/or heat detec- tection specialist. Heat detectors are designed to protect
tors be located throughout a protected premise following the property, not life.
recommendations of the current edition of the National Fire IMPORTANT! Smoke detectors must be installed in the
Protection Association Standard 72 (NFPA 72), manufacturer's same room as the control panel and in rooms used by the sys-
recommendations, State and local codes, and the recommen- tem for the connection of alarm transmission wiring, communi-
dations contained in the Guide for Proper Use of System cations, signaling, and/or power. If detectors are not so
Smoke Detectors, which is made available at no charge to all located, a developing fire may damage the alarm system, crip-
installing dealers. A study by the Federal Emergency Man- pling its ability to report a fire.
agement Agency (an agency of the United States government) Audible warning devices such as bells may not alert people
indicated that smoke detectors may not go off in as many as if these devices are located on the other side of closed or
35% of all fires. While fire alarm systems are designed to pro- partly open doors or are located on another floor of a building.
vide early warning against fire, they do not guarantee warning Any warning device may fail to alert people with a disability or
or protection against fire. A fire alarm system may not provide those who have recently consumed drugs, alcohol or medica-
timely or adequate warning, or simply may not function, for a tion. Please note that:
variety of reasons:
• Strobes can, under certain circumstances, cause seizures
Smoke detectors may not sense fire where smoke cannot in people with conditions such as epilepsy.
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors • Studies have shown that certain people, even when they
also may not sense a fire on another level or floor of a building. hear a fire alarm signal, do not respond or comprehend the
A second-floor detector, for example, may not sense a first- meaning of the signal. It is the property owner's responsi-
floor or basement fire. bility to conduct fire drills and other training exercise to
make people aware of fire alarm signals and instruct them
Particles of combustion or “smoke” from a developing fire on the proper reaction to alarm signals.
may not reach the sensing chambers of smoke detectors
because: • In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow. A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
• Smoke particles may become “cold,” stratify, and not reach batteries only for a specified time and only if the batteries have
the ceiling or upper walls where detectors are located. been properly maintained and replaced regularly.
• Smoke particles may be blown away from detectors by air Equipment used in the system may not be technically com-
outlets. patible with the control. It is essential to use only equipment
• Smoke particles may be drawn into air returns before listed for service with your control panel.
reaching the detector. Telephone lines needed to transmit alarm signals from a
The amount of “smoke” present may be insufficient to alarm premise to a central monitoring station may be out of service
smoke detectors. Smoke detectors are designed to alarm at or temporarily disabled. For added protection against tele-
various levels of smoke density. If such density levels are not phone line failure, backup radio transmission systems are rec-
created by a developing fire at the location of detectors, the ommended.
detectors will not go into alarm. The most common cause of fire alarm malfunction is inade-
Smoke detectors, even when working properly, have sensing quate maintenance. To keep the entire fire alarm system in
limitations. Detectors that have photoelectronic sensing excellent working order, ongoing maintenance is required per
chambers tend to detect smoldering fires better than flaming the manufacturer's recommendations, and UL and NFPA stan-
fires, which have little visible smoke. Detectors that have ion- dards. At a minimum, the requirements of Chapter 7 of NFPA
izing-type sensing chambers tend to detect fast-flaming fires 72 shall be followed. Environments with large amounts of
better than smoldering fires. Because fires develop in different dust, dirt or high air velocity require more frequent mainte-
ways and are often unpredictable in their growth, neither type nance. A maintenance agreement should be arranged
of detector is necessarily best and a given type of detector through the local manufacturer's representative. Maintenance
may not provide adequate warning of a fire. should be scheduled monthly or as required by National and/
Smoke detectors cannot be expected to provide adequate or local fire codes and should be performed by authorized pro-
warning of fires caused by arson, children playing with fessional fire alarm installers only. Adequate written records of
matches (especially in bedrooms), smoking in bed, and violent all inspections should be kept.
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).

Precau-L-2001-9.fm 8/31/2001
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:

WARNING - Several different sources of power can be Like all solid state electronic devices, this system may
connected to the fire alarm control panel. Disconnect all operate erratically or can be damaged when subjected to light-
sources of power before servicing. Control unit and associ- ning-induced transients. Although no system is completely
ated equipment may be damaged by removing and/or insert- immune from lightning transients and interferences, proper
ing cards, modules, or interconnecting cables while the unit is grounding will reduce susceptibility. Overhead or outside
energized. Do not attempt to install, service, or operate this aerial wiring is not recommended, due to an increased sus-
unit until this manual is read and understood. ceptibility to nearby lightning strikes. Consult with the Techni-
CAUTION - System Reacceptance Test after Software cal Services Department if any problems are anticipated or
Changes. To ensure proper system operation, this product encountered.
must be tested in accordance with NFPA 72 Chapter 7 after Disconnect AC power and batteries prior to removing or
any programming operation or change in site-specific soft- inserting circuit boards. Failure to do so can damage circuits.
ware. Reacceptance testing is required after any change, Remove all electronic assemblies prior to any drilling, filing,
addition or deletion of system components, or after any modifi- reaming, or punching of the enclosure. When possible, make
cation, repair or adjustment to system hardware or wiring. all cable entries from the sides or rear. Before making modifi-
All components, circuits, system operations, or software func- cations, verify that they will not interfere with battery, trans-
tions known to be affected by a change must be 100% tested. former, and printed circuit board location.
In addition, to ensure that other operations are not inadvert- Do not tighten screw terminals more than 9 in-lbs.
ently affected, at least 10% of initiating devices that are not Over-tightening may damage threads, resulting in reduced ter-
directly affected by the change, up to a maximum of 50 minal contact pressure and difficulty with screw terminal
devices, must also be tested and proper system operation ver- removal.
ified.
Though designed to last many years, system components
This system meets NFPA requirements for operation at 0-49° can fail at any time. This system contains static-sensitive
C/32-120° F and at a relative humidity of 85% RH (non-con- components. Always ground yourself with a proper wrist strap
densing) at 30° C/86° F. However, the useful life of the sys- before handling any circuits so that static charges are
tem's standby batteries and the electronic components may be removed from the body. Use static-suppressive packaging to
adversely affected by extreme temperature ranges and humid- protect electronic assemblies removed from the unit.
ity. Therefore, it is recommended that this system and all
peripherals be installed in an environment with a nominal room Follow the instructions in the installation, operating, and pro-
temperature of 15-27° C/60-80° F. gramming manuals. These instructions must be followed to
avoid damage to the control panel and associated equipment.
Verify that wire sizes are adequate for all initiating and indi- FACP operation and reliability depend upon proper installation
cating device loops. Most devices cannot tolerate more than a by authorized personnel.
10% I.R. drop from the specified device voltage.

FCC Warning
WARNING: This equipment generates, uses, and can Canadian Requirements
radiate radio frequency energy and if not installed and This digital apparatus does not exceed the Class A limits
used in accordance with the instruction manual, may for radiation noise emissions from digital apparatus set
cause interference to radio communications. It has been out in the Radio Interference Regulations of the Canadian
tested and found to comply with the limits for class A Department of Communications.
computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable pro- Le present appareil numerique n'emet pas de bruits radi-
tection against such interference when operated in a oelectriques depassant les limites applicables aux appar-
commercial environment. Operation of this equipment in eils numeriques de la classe A prescrites dans le
a residential area is likely to cause interference, in which Reglement sur le brouillage radioelectrique edicte par le
case the user will be required to correct the interference ministere des Communications du Canada.
at his own expense.

Precau-L-2001-9.fm 8/31/2001
Table of Contents
Section One: Voice Alarm Equipment.................................................................................. 5
Section 1.0 Introduction ................................................................................................................................... 5
Figure 1.0-1 Dress Panel, Single Well (DPSW-1) ............................................................................................. 5
Figure 1.0-2 Fire Fighter's Telephone System Components .............................................................................. 6
Figure 1.0-3 Dress Panel, Double Well (DPDW-1) ............................................................................................ 6
Section 1.1 Related Documentation .................................................................................................................. 8
Table 1-1 Voice Multiplex System Related Documentation ............................................................................... 8
Section Two: Design Considerations ..................................................................................... 9
Section 2.0 Section Objective ........................................................................................................................... 9
Section 2.1 Executing Audio Functions with an AMG-1 .................................................................................... 9
Figure 2.1-1 AMG-1 Audio Functions ............................................................................................................... 9
Section 2.2 Executing Tone Generation with an ATG-2 ..................................................................................... 9
Figure 2.2-2 ATG-2 Audio Functions ................................................................................................................. 9
Section 2.3 Amplifying the Audio Signal .......................................................................................................... 10
Figure 2.3-1 Audio Signal Amplification ........................................................................................................... 10
Figure 2.3-2 ACT-1 Audio Coupling Transformer ............................................................................................. 10
Section 2.4 Driving the Speaker Circuits ........................................................................................................ 10
Figure 2.4-1 Speaker Circuits ......................................................................................................................... 11
Section 2.5 Cascading AMG's for Multi-channel Audio ................................................................................... 14
Section Three: Audio Message/Tone Generators ............................................................... 15
Section 3.1 Operating the AMG-1 Audio Message Generator ....................................................................... 16
Figure 3-1 AMG-1 and ATG-2 Installation ...................................................................................................... 17
Figure 3-2 AMG-1 Terminal Connections ....................................................................................................... 18
Table 3-1 AMG-1 Tone/Message Functions ................................................................................................... 21
Table 3-2 AMG-1 Tone/Message Functions ................................................................................................... 22
Section 3.2 Zone-Coded Voice for the AM2020/AFP1010 ............................................................................. 23
Section 3.3 ATG-2 Audio Tone Generator ...................................................................................................... 26
Figure 3-3A ATG-2 Terminal Connections ...................................................................................................... 27
Figure 3-3B ATG-2 Activation Circuit ............................................................................................................. 28
Section Four: Fire Fighter's Telephone ............................................................................... 30
Figure 4-1 FFT-7 and FFT-7S Installation ....................................................................................................... 30
Figure 4-2 FFT-7 Terminals and Connections ................................................................................................ 32
Figure 4-3 FFT-7S Terminal and Connections ................................................................................................ 33
Section Five: Audio Amplifiers ............................................................................................ 34
Figure 5-1 Installing the AA-30 or AA-30E ..................................................................................................... 34
Figure 5-2 AA-30/AA-30E Terminals and Connectors .................................................................................... 35
Figure 5-3 AA-30/AA-30E Audio Amplifier Status LEDs ................................................................................ 36
Figure 5-4 Speaker Switching Configuration, AA-30/AA-30E (Class A) with CMX-2 (Style Z) ...................... 38
Figure 5-5 Speaker Switching Configuration, AA-30/AA-30E (Class B) with CMX-2 (Style Y) ...................... 38
Figure 5-6 Speaker Switching Configuration, AA-100/AA-100E (Class B) with CMX-2 (Style Y) .................. 39
Figure 5-7 Speaker Switching Configuration, AA-100/AA-100E (ClassB) with CMX-2 (Style Z) ................... 39
Figure 5-8 Speaker Switching Configuration, AA-120/AA-120E (Class B) with CMX-2 (Style Y) .................. 40
Figure 5-9 Speaker Switching Configuration, AA-120/AA-120E (Class B) with CMX-2 (Style Z) .................. 40
Table 5-1 Secondary Current Draw in Standby .............................................................................................. 41
Table 5-2 Secondary Current Draw in Alarm ................................................................................................. 41
Table 5-3 Total Amplifier Secondary Current Draw ......................................................................................... 41
Figure 5-10 Installing the AA-100/AA-100E and AA-120/AA-120E ................................................................ 42
Figure 5-11 AA-100/AA-100E and AA-120/AA-120E Terminals and Connectors ........................................... 43
Figure 5-12 AA-100/AA-100E and AA-120/AA-120E Audio Amplifier Status LEDs ....................................... 44
Section Six: Voice Alarm Peripherals .................................................................................. 46
Section 6.1 The RPJ-1 Remote Paging Jack ................................................................................................. 47
Appendix A: Voice Message Options .................................................................................. 48
Section A.1 VROM/VRAM Installation ........................................................................................................... 48
Appendix B: ACT-1 Audio Coupling Transformer ................................................................. 49
4 Voice Alarm Multiplex 15889:F2 10/01/01
Set ON for 4-Wire audio loop supervision.
Configuration DIP Switches
Address Switch
The AMG-1's configuration DIP switches are defined at right. Address Switch
VRAM Enable A (VRAM "A" installed)
VRAM Enable B (VRAM "B" installed)
Group Function Selection switch
Group Function Selection switch
Group Function Selection switch

Setting the Address


Use the table below to set the desired address on the AMG-1. To set a switch "ON," push the rocker down in
the ON position. When only one AMG is present, use Address 32.

Address 32 Address 31 Address 30 Address 29


or Address 28* or Address 27* or Address 26* or Address 25*

Address Switch ON ON OFF OFF


Address Switch ON OFF ON OFF

*Italics denote setting the address for an AMG-1 with an AMG-X4 EPROM installed.

Selecting Group Functions


Operation of the various tones and messages available in a voice alarm application is dependent upon the type
and number of ROM chips installed and the functional groups selected by DIP switch settings on the AMG-1.
Group selection is accomplished by setting DIP switch positions 6, 7 and 8 on the AMG-1. See the AMG-1 Group
Function Tables (Tables 3-1 and 3-2).

Factory Messages *
With VROM-(n) chips installed, a factory-programmed message can be selected. For example, VROM-101
provides the following message in a male voice.

"MAY I HAVE YOUR ATTENTION PLEASE! MAY I HAVE YOUR ATTENTION PLEASE! THERE HAS BEEN A
FIRE REPORTED ON YOUR FLOOR. THERE HAS BEEN A FIRE REPORTED ON YOUR FLOOR. PLEASE
PROCEED TO THE STAIRWAYS AND EXIT THE BUILDING. DO NOT USE THE ELEVATORS."

Custom Messages * (with VRAM chips installed)


Custom user messages can be recorded either through the microphone on the AMG-1 or by downloading the
message from a standard audio cassette recorder through the low-level input connector on the AMG-1. DIP
switch positions 4 and 5 are used for this purpose.

1) Set the respective VRAM Enable switch "ON."


VRAM Enable A (VRAM "A" installed)
2) Record or download the message, up to 24 seconds.
VRAM Enable B (VRAM "B" installed)
3) Set the respective VRAM Enable switch "OFF."

* Note: If a digitally-stored voice message fails, the AMG-1 will automati-


cally switch to the primary evacuation tone, and will generate a trouble condition.

Selecting ALL CALL


Pressing the ALL CALL switch will activate all speaker circuits programmed with software type "SPKR." In dual-
channel systems, the signal generated by the particular AMG-1 on which the ALL CALL button has been pressed
will immediately go out across both channels.

AM2020 AMG Programming


During programming of the AM2020/AFP1010 (and after the installation of any AMG-1s), each AMG-1 must be
programmed as if they were annunciators. The address is set on the AMG-1 (25-32) and must correspond to
the programmed annunciator address. Note: All speaker circuits must be programmed with software type "SPKR." When
an FFT-7 is used, it must be attached to an AMG at Address 32.

Voice Alarm Multiplex 15889:F2 10/01/01 7


19
AMG-1 and the ACM-16AT
Set the address of the AMG-1 Audio Message Generator via DIP switches 2 and 3. This address can only be
set for 29-32 for a standard AMG-1 or 25-28 for an AMG-1 with an AMG-X4 EPROM installed. The highest
possible address setting is recommended. This allows the AMG-1 functions to assume the first four points on
an ACM-16AT set to address "1." Up to eight AMG-1s may be installed in an AM2020/AFP1010 system.
For AMG-1s set in the address range A29-A32:

Annunciator points P01-P04 Annunciator points P09-P12


Control tone/messages Control tone/messages
selection for AMG-1 selection for AMG-1
Address 32 Address 30

Annunciator points P05-P08 Annunciator points P13-P16


Control tone/messages Control tone/messages
selection for AMG-1 selection for AMG-1
Address 31 Address 29

ACM-16AT Address A01

For AMG-1s set in the address range 25-28 (AMG-X4 EPROM required):

Annunciator points P17-P20 Annunciator points P25-P28


Control tone/messages Control tone/messages
selection for AMG-1 selection for AMG-1
Address 28 Address 26

Annunciator points P21-P24 Annunciator points P29-P32


Control tone/messages Control tone/messages
selection for AMG-1 selection for AMG-1
Address 27 Address 25

AEM-16AT
(the first expander of the ACM-16AT at address 1 (see above)

Boston Code (Note: requires VROM-109 to be installed in VROM-B position)


The special Boston Code, which appears on the following two pages, will function as follows:
1) Pause.
2) All Call is initiated.
3) One round of Code Four (four pulses of a 900 Hz tone followed by a 1 second pause).
4) VROM B (VROM-109) is played three times.
5) All Call is deactivated.
5) Fifteen second pause.
6) Continuous Temporal.

8 20 Voice Alarm Multiplex 15889:F2 10/01/01


Table 3-1: AMG-1 Tone/Message Functions
(for AMG-1 addresses A32 through A29)
Audio Message Annunciator Control Points
Generator DIP on ACM-16AT Address A01
Switch Settings AMG-1 at Address Tone/Voice Message Group Functions

S6 S7 S8 A32 A31 A30 A29


Off Off Off P01 P05 P09 P13 VROM A
Off Off Off P02 P06 P10 P14 VROM B
Off Off Off P03 P07 P11 P15 VRAM A
Off Off Off P04 P08 P12 P16 VRAM B

Off Off On P01 P05 P09 P13 3 Fast Whoops, Pause, VROM A
Off Off On P02 P06 P10 P14 3 Hi/Low Tones, Pause, VROM B
Off Off On P03 P07 P11 P15 3 Yeows, Pause, VRAM A
Off Off On P04 P08 P12 P16 3 Slow Whoops, Pause, VRAM B

Off On Off P01 P05 P09 P13 3 Fast Whoops, Pause, VROM A, VROM B
Off On Off P02 P06 P10 P14 3 Hi/Low Tones, Pause, VRAM A
Off On Off P03 P07 P11 P15 3 Yeows, Pause, VRAM B
Off On Off P04 P08 P12 P16 Wail

Off On On P01 P05 P09 P13 3 Slow Whoops, Pause, VROM A


Off On On P02 P06 P10 P14 3 Hi/Low Tones, Pause, VROM B
Off On On P03 P07 P11 P15 Yelp
Off On On P04 P08 P12 P16 Wail

On Off Off P01 P05 P09 P13 3 Slow Whoops, Pause, VRAM A
On Off Off P02 P06 P10 P14 3 Hi/Low Tones, Pause, VRAM B
On Off Off P03 P07 P11 P15 Yelp
On Off Off P04 P08 P12 P16 Wail

On Off On P01 P05 P09 P13 3 Slow Whoops, Pause, VROM A


On Off On P02 P06 P10 P14 3 Hi/Low Tones, Pause, VRAM A
On Off On P03 P07 P11 P15 Boston Code
On Off On P04 P08 P12 P16 Horn

On On Off P01 P05 P09 P13 California Uniform Fire Code (10s Yelp, Pause)
On On Off P02 P06 P10 P14 California Uniform Fire Code (10s Fast Whoops, Pause)
On On Off P03 P07 P11 P15 3 Hi/Low Tones, Pause, VROM A, Pause
On On Off P04 P08 P12 P16 3 Slow Whoops, Pause, VRAM A, Pause

On On On P01 P05 P09 P13 Yelp


On On On P02 P06 P10 P14 Hi/Low Tones
On On On P03 P07 P11 P15 Slow Whoop
On On On P04 P08 P12 P16 NFPA Code (Three 470 Hz Tones, 1.5s Pause)
Notes:
1) All the above tone/messages sequences will repeat until they have been deselected through the annunciator
control point. Priority within each group of four is from top (highest priority) to bottom (lowest priority).
2) If a digitally-stored voice message fails, the AMG-1 will automatically switch to the primary evacuation tone and
will generate a trouble condition.
3) All pauses are 5 seconds long unless otherwise noted.

Voice Alarm Multiplex 15889:F2 10/01/01 9


21
Table 3-2: AMG-1 Tone/Message Functions
(for AMG-1 addresses A28 through A25, AMG-X4 EPROM required)
Audio Message Annunciator Control Points
Generator DIP on AEM-16AT Address A01
Switch Settings AMG-1 at Address Tone/Voice Message Group Functions

S6 S7 S8 A28 A27 A26 A25


Off Off Off P17 P21 P25 P29 VROM A
Off Off Off P18 P22 P26 P30 VROM B
Off Off Off P19 P23 P27 P31 VRAM A
Off Off Off P20 P24 P28 P32 VRAM B

Off Off On P17 P21 P25 P29 3 Fast Whoops, Pause, VROM A
Off Off On P18 P22 P26 P30 3 Hi/Low Tones, Pause, VROM B
Off Off On P19 P23 P27 P31 3 Yeows, Pause, VRAM A
Off Off On P20 P24 P28 P32 3 Slow Whoops, Pause, VRAM B

Off On Off P17 P21 P25 P29 3 Fast Whoops, Pause, VROM A, VROM B
Off On Off P18 P22 P26 P30 3 Hi/Low Tones, Pause, VRAM A
Off On Off P19 P23 P27 P31 3 Yeows, Pause, VRAM B
Off On Off P20 P24 P28 P32 Wail

Off On On P17 P21 P25 P29 3 Slow Whoops, Pause, VROM A


Off On On P18 P22 P26 P30 3 Hi/Low Tones, Pause, VROM B
Off On On P19 P23 P27 P31 Yelp
Off On On P20 P24 P28 P32 Wail

On Off Off P17 P21 P25 P29 3 Slow Whoops, Pause, VRAM A
On Off Off P18 P22 P26 P30 3 Hi/Low Tones, Pause, VRAM B
On Off Off P19 P23 P27 P31 Yelp
On Off Off P20 P24 P28 P32 Wail

On Off On P17 P21 P25 P29 3 Slow Whoops, Pause, VROM A


On Off On P18 P22 P26 P30 3 Hi/Low Tones, Pause, VRAM A
On Off On P19 P23 P27 P31 Boston Code
On Off On P20 P24 P28 P32 Horn

On On Off P17 P21 P25 P29 California Uniform Fire Code (10s Yelp, Pause)
On On Off P18 P22 P26 P30 California Uniform Fire Code (10s Fast Whoops, Pause)
On On Off P19 P23 P27 P31 3 Hi/Low Tones, Pause, VROM A, Pause
On On Off P20 P24 P28 P32 3 Slow Whoops, Pause, VRAM A, Pause

On On On P17 P21 P25 P29 Yelp


On On On P18 P22 P26 P30 Hi/Low Tones
On On On P19 P23 P27 P31 Slow Whoop
On On On P20 P24 P28 P32 NFPA Code (Three 470 Hz Tones, 1.5s Pause)
Notes:
1) All the above tone/messages sequences will repeat until they have been deselected through the annunciator
control point. Priority within each group of four is from top (highest priority) to bottom (lowest priority). The
AEM-16AT must be the first expander attached to the ACM-16AT.
2) If a digitally-stored voice message fails, the AMG-1 will automatically switch to the primary evacuation tone
and will generate a trouble condition.
3) All pauses are 5 seconds long unless otherwise noted.
10
22 Voice Alarm Multiplex 15889:F2 10/01/01
Voice Alarm Multiplex
15889:F2
10/01/01
Note 1: Using the supplied cable, connect the "EARTH" ground terminal of each ACT-1 to terminal P8-10 on the AA-100/AA-100E or AA-
120/AA-120E or to a screw on the upper left corner of the AA-30/AA-30E. The "COM" terminal is intended for optional shielding
of the secondary side of the ACT-1 (the low level audio from the ACT-1 through each of the amplifiers). If this shield is desired,
connect to the common of the local power supply (do not, at any point connect the shield from the primary side of the ACT-1).
Note 2: The secondary side of the ACT-1 (low-level audio) may be daisy chained to a maximum of eight audio amplifiers.
Note 3: Additional low-level audio risers, isolated from the main riser, may be drawn from this point.
Note 4: 3 This symbol denotes a local common, in this case for supply number three.
Note 5: A maximum of seven ACT-1 Audio Coupling Transformers may be connected to the AMG or VTG (primary side). The number of
amplifiers connected to the primary side of the ACT-1 (AMG/VTG output) must be reduced by eight for each ACT-1 connected,

11
regardless of the number of amplifiers connected to the secondary side of each ACT-1

51
Notes

12
52 Voice Alarm Multiplex 15889:F2 10/01/01
Limited Warranty

NOTIFIER ® warrants its products to be free from defects in materials and


workmanship for eighteen (18) months from the date of manufacture, under normal
use and service. Products are date stamped at time of manufacture. The sole and
exclusive obligation of NOTIFIER® is to repair or replace, at its option, free of
charge for parts and labor, any part which is defective in materials or workmanship
under normal use and service. For products not under NOTIFIER® manufacturing
date-stamp control, the warranty is eighteen (18) months from date of original
purchase by NOTIFIER®'s distributor unless the installation instructions or catalog
sets forth a shorter period, in which case the shorter period shall apply. This
warranty is void if the product is altered, repaired or serviced by anyone other than
NOTIFIER® or its authorized distributors or if there is a failure to maintain the
products and systems in which they operate in a proper and workable manner. In
case of defect, secure a Return Material Authorization form from our customer
service department. Return product, transportation prepaid, to NOTIFIER®, 12
Clintonville Road, Northford, Connecticut 06472-1653.

This writing constitutes the only warranty made by NOTIFIER® with respect to its
products. NOTIFIER® does not represent that its products will prevent any loss by fire
or otherwise, or that its products will in all cases provide the protection for which they
are installed or intended. Buyer acknowledges that NOTIFIER® is not an insurer and
assumes no risk for loss or damages or the cost of any inconvenience, transportation,
damage, misuse, abuse, accident or similar incident.

NOTIFIER ® GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF


MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE
WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER
NO CIRCUMSTANCES SHALL NOTIFIER® BE LIABLE FOR ANY LOSS OF OR
DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR CONSEQUENTIAL, ARISING
OUT OF THE USE OF, OR INABILITY TO USE NOTIFIER ® PRODUCTS.
FURTHERMORE, NOTIFIER® SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY
OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF,
PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF ITS PRODUCTS.

This warranty replaces all previous warranties and is the only warranty made by
NOTIFIER®. No increase or alteration, written or verbal, of the obligation of this warranty
is authorized.

"NOTIFIER" is a registered trademark.


World Headquarters
One Fire-Lite Place, Northford, CT 06472-1653 USA
203-484-7161 • Fax 203-484-7118
www.notifier.com

You might also like