Supplement To The AM2020/AFP1010 Voice Alarm Multiplex Manual Number 15889, Revision F1, Dated 12/11/97
Supplement To The AM2020/AFP1010 Voice Alarm Multiplex Manual Number 15889, Revision F1, Dated 12/11/97
Supplement To The AM2020/AFP1010 Voice Alarm Multiplex Manual Number 15889, Revision F1, Dated 12/11/97
AM2020/AFP1010
Voice Alarm Multiplex Manual Number 15889,
Revision F1, dated 12/11/97
Replace the following pages dated 12/11/97, with the same numbered pages dated 10/01/01:
• Cover page/Precautions and Limitations p.1
• Page 19/20
• Page 21/22
• Page 51/52
• Limited Warranty/Rear Cover
Replace Page 3/4 with Precautions and Limitations p.2/Page 4
Document 15889SUP
10/01/01 Revision
ECN 01-537
F2
Tab Set 50022, Bank 2 for Document 15889
The three-ring binder tab set shown above is shipped with every AM2020/AFP1010 system.
If you cannot locate the set in your shipment or if it has been misplaced, you may order
another tab set, Part Number 50022, from your Notifier Customer Service Representative.
AM2020/AFP1010
Voice Alarm
Multiplex
Operation and Installation Manual
Document 15889
10/01/01 Rev: F2
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of Heat detectors do not sense particles of combustion and
smoke detectors, heat detectors, manual pull stations, audible alarm only when heat on their sensors increases at a predeter-
warning devices, and a fire alarm control with remote notifica- mined rate or reaches a predetermined level. Rate-of-rise
tion capability—can provide early warning of a developing fire. heat detectors may be subject to reduced sensitivity over time.
Such a system, however, does not assure protection against For this reason, the rate-of-rise feature of each detector
property damage or loss of life resulting from a fire. should be tested at least once per year by a qualified fire pro-
The Manufacturer recommends that smoke and/or heat detec- tection specialist. Heat detectors are designed to protect
tors be located throughout a protected premise following the property, not life.
recommendations of the current edition of the National Fire IMPORTANT! Smoke detectors must be installed in the
Protection Association Standard 72 (NFPA 72), manufacturer's same room as the control panel and in rooms used by the sys-
recommendations, State and local codes, and the recommen- tem for the connection of alarm transmission wiring, communi-
dations contained in the Guide for Proper Use of System cations, signaling, and/or power. If detectors are not so
Smoke Detectors, which is made available at no charge to all located, a developing fire may damage the alarm system, crip-
installing dealers. A study by the Federal Emergency Man- pling its ability to report a fire.
agement Agency (an agency of the United States government) Audible warning devices such as bells may not alert people
indicated that smoke detectors may not go off in as many as if these devices are located on the other side of closed or
35% of all fires. While fire alarm systems are designed to pro- partly open doors or are located on another floor of a building.
vide early warning against fire, they do not guarantee warning Any warning device may fail to alert people with a disability or
or protection against fire. A fire alarm system may not provide those who have recently consumed drugs, alcohol or medica-
timely or adequate warning, or simply may not function, for a tion. Please note that:
variety of reasons:
• Strobes can, under certain circumstances, cause seizures
Smoke detectors may not sense fire where smoke cannot in people with conditions such as epilepsy.
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors • Studies have shown that certain people, even when they
also may not sense a fire on another level or floor of a building. hear a fire alarm signal, do not respond or comprehend the
A second-floor detector, for example, may not sense a first- meaning of the signal. It is the property owner's responsi-
floor or basement fire. bility to conduct fire drills and other training exercise to
make people aware of fire alarm signals and instruct them
Particles of combustion or “smoke” from a developing fire on the proper reaction to alarm signals.
may not reach the sensing chambers of smoke detectors
because: • In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow. A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
• Smoke particles may become “cold,” stratify, and not reach batteries only for a specified time and only if the batteries have
the ceiling or upper walls where detectors are located. been properly maintained and replaced regularly.
• Smoke particles may be blown away from detectors by air Equipment used in the system may not be technically com-
outlets. patible with the control. It is essential to use only equipment
• Smoke particles may be drawn into air returns before listed for service with your control panel.
reaching the detector. Telephone lines needed to transmit alarm signals from a
The amount of “smoke” present may be insufficient to alarm premise to a central monitoring station may be out of service
smoke detectors. Smoke detectors are designed to alarm at or temporarily disabled. For added protection against tele-
various levels of smoke density. If such density levels are not phone line failure, backup radio transmission systems are rec-
created by a developing fire at the location of detectors, the ommended.
detectors will not go into alarm. The most common cause of fire alarm malfunction is inade-
Smoke detectors, even when working properly, have sensing quate maintenance. To keep the entire fire alarm system in
limitations. Detectors that have photoelectronic sensing excellent working order, ongoing maintenance is required per
chambers tend to detect smoldering fires better than flaming the manufacturer's recommendations, and UL and NFPA stan-
fires, which have little visible smoke. Detectors that have ion- dards. At a minimum, the requirements of Chapter 7 of NFPA
izing-type sensing chambers tend to detect fast-flaming fires 72 shall be followed. Environments with large amounts of
better than smoldering fires. Because fires develop in different dust, dirt or high air velocity require more frequent mainte-
ways and are often unpredictable in their growth, neither type nance. A maintenance agreement should be arranged
of detector is necessarily best and a given type of detector through the local manufacturer's representative. Maintenance
may not provide adequate warning of a fire. should be scheduled monthly or as required by National and/
Smoke detectors cannot be expected to provide adequate or local fire codes and should be performed by authorized pro-
warning of fires caused by arson, children playing with fessional fire alarm installers only. Adequate written records of
matches (especially in bedrooms), smoking in bed, and violent all inspections should be kept.
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).
Precau-L-2001-9.fm 8/31/2001
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be Like all solid state electronic devices, this system may
connected to the fire alarm control panel. Disconnect all operate erratically or can be damaged when subjected to light-
sources of power before servicing. Control unit and associ- ning-induced transients. Although no system is completely
ated equipment may be damaged by removing and/or insert- immune from lightning transients and interferences, proper
ing cards, modules, or interconnecting cables while the unit is grounding will reduce susceptibility. Overhead or outside
energized. Do not attempt to install, service, or operate this aerial wiring is not recommended, due to an increased sus-
unit until this manual is read and understood. ceptibility to nearby lightning strikes. Consult with the Techni-
CAUTION - System Reacceptance Test after Software cal Services Department if any problems are anticipated or
Changes. To ensure proper system operation, this product encountered.
must be tested in accordance with NFPA 72 Chapter 7 after Disconnect AC power and batteries prior to removing or
any programming operation or change in site-specific soft- inserting circuit boards. Failure to do so can damage circuits.
ware. Reacceptance testing is required after any change, Remove all electronic assemblies prior to any drilling, filing,
addition or deletion of system components, or after any modifi- reaming, or punching of the enclosure. When possible, make
cation, repair or adjustment to system hardware or wiring. all cable entries from the sides or rear. Before making modifi-
All components, circuits, system operations, or software func- cations, verify that they will not interfere with battery, trans-
tions known to be affected by a change must be 100% tested. former, and printed circuit board location.
In addition, to ensure that other operations are not inadvert- Do not tighten screw terminals more than 9 in-lbs.
ently affected, at least 10% of initiating devices that are not Over-tightening may damage threads, resulting in reduced ter-
directly affected by the change, up to a maximum of 50 minal contact pressure and difficulty with screw terminal
devices, must also be tested and proper system operation ver- removal.
ified.
Though designed to last many years, system components
This system meets NFPA requirements for operation at 0-49° can fail at any time. This system contains static-sensitive
C/32-120° F and at a relative humidity of 85% RH (non-con- components. Always ground yourself with a proper wrist strap
densing) at 30° C/86° F. However, the useful life of the sys- before handling any circuits so that static charges are
tem's standby batteries and the electronic components may be removed from the body. Use static-suppressive packaging to
adversely affected by extreme temperature ranges and humid- protect electronic assemblies removed from the unit.
ity. Therefore, it is recommended that this system and all
peripherals be installed in an environment with a nominal room Follow the instructions in the installation, operating, and pro-
temperature of 15-27° C/60-80° F. gramming manuals. These instructions must be followed to
avoid damage to the control panel and associated equipment.
Verify that wire sizes are adequate for all initiating and indi- FACP operation and reliability depend upon proper installation
cating device loops. Most devices cannot tolerate more than a by authorized personnel.
10% I.R. drop from the specified device voltage.
FCC Warning
WARNING: This equipment generates, uses, and can Canadian Requirements
radiate radio frequency energy and if not installed and This digital apparatus does not exceed the Class A limits
used in accordance with the instruction manual, may for radiation noise emissions from digital apparatus set
cause interference to radio communications. It has been out in the Radio Interference Regulations of the Canadian
tested and found to comply with the limits for class A Department of Communications.
computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable pro- Le present appareil numerique n'emet pas de bruits radi-
tection against such interference when operated in a oelectriques depassant les limites applicables aux appar-
commercial environment. Operation of this equipment in eils numeriques de la classe A prescrites dans le
a residential area is likely to cause interference, in which Reglement sur le brouillage radioelectrique edicte par le
case the user will be required to correct the interference ministere des Communications du Canada.
at his own expense.
Precau-L-2001-9.fm 8/31/2001
Table of Contents
Section One: Voice Alarm Equipment.................................................................................. 5
Section 1.0 Introduction ................................................................................................................................... 5
Figure 1.0-1 Dress Panel, Single Well (DPSW-1) ............................................................................................. 5
Figure 1.0-2 Fire Fighter's Telephone System Components .............................................................................. 6
Figure 1.0-3 Dress Panel, Double Well (DPDW-1) ............................................................................................ 6
Section 1.1 Related Documentation .................................................................................................................. 8
Table 1-1 Voice Multiplex System Related Documentation ............................................................................... 8
Section Two: Design Considerations ..................................................................................... 9
Section 2.0 Section Objective ........................................................................................................................... 9
Section 2.1 Executing Audio Functions with an AMG-1 .................................................................................... 9
Figure 2.1-1 AMG-1 Audio Functions ............................................................................................................... 9
Section 2.2 Executing Tone Generation with an ATG-2 ..................................................................................... 9
Figure 2.2-2 ATG-2 Audio Functions ................................................................................................................. 9
Section 2.3 Amplifying the Audio Signal .......................................................................................................... 10
Figure 2.3-1 Audio Signal Amplification ........................................................................................................... 10
Figure 2.3-2 ACT-1 Audio Coupling Transformer ............................................................................................. 10
Section 2.4 Driving the Speaker Circuits ........................................................................................................ 10
Figure 2.4-1 Speaker Circuits ......................................................................................................................... 11
Section 2.5 Cascading AMG's for Multi-channel Audio ................................................................................... 14
Section Three: Audio Message/Tone Generators ............................................................... 15
Section 3.1 Operating the AMG-1 Audio Message Generator ....................................................................... 16
Figure 3-1 AMG-1 and ATG-2 Installation ...................................................................................................... 17
Figure 3-2 AMG-1 Terminal Connections ....................................................................................................... 18
Table 3-1 AMG-1 Tone/Message Functions ................................................................................................... 21
Table 3-2 AMG-1 Tone/Message Functions ................................................................................................... 22
Section 3.2 Zone-Coded Voice for the AM2020/AFP1010 ............................................................................. 23
Section 3.3 ATG-2 Audio Tone Generator ...................................................................................................... 26
Figure 3-3A ATG-2 Terminal Connections ...................................................................................................... 27
Figure 3-3B ATG-2 Activation Circuit ............................................................................................................. 28
Section Four: Fire Fighter's Telephone ............................................................................... 30
Figure 4-1 FFT-7 and FFT-7S Installation ....................................................................................................... 30
Figure 4-2 FFT-7 Terminals and Connections ................................................................................................ 32
Figure 4-3 FFT-7S Terminal and Connections ................................................................................................ 33
Section Five: Audio Amplifiers ............................................................................................ 34
Figure 5-1 Installing the AA-30 or AA-30E ..................................................................................................... 34
Figure 5-2 AA-30/AA-30E Terminals and Connectors .................................................................................... 35
Figure 5-3 AA-30/AA-30E Audio Amplifier Status LEDs ................................................................................ 36
Figure 5-4 Speaker Switching Configuration, AA-30/AA-30E (Class A) with CMX-2 (Style Z) ...................... 38
Figure 5-5 Speaker Switching Configuration, AA-30/AA-30E (Class B) with CMX-2 (Style Y) ...................... 38
Figure 5-6 Speaker Switching Configuration, AA-100/AA-100E (Class B) with CMX-2 (Style Y) .................. 39
Figure 5-7 Speaker Switching Configuration, AA-100/AA-100E (ClassB) with CMX-2 (Style Z) ................... 39
Figure 5-8 Speaker Switching Configuration, AA-120/AA-120E (Class B) with CMX-2 (Style Y) .................. 40
Figure 5-9 Speaker Switching Configuration, AA-120/AA-120E (Class B) with CMX-2 (Style Z) .................. 40
Table 5-1 Secondary Current Draw in Standby .............................................................................................. 41
Table 5-2 Secondary Current Draw in Alarm ................................................................................................. 41
Table 5-3 Total Amplifier Secondary Current Draw ......................................................................................... 41
Figure 5-10 Installing the AA-100/AA-100E and AA-120/AA-120E ................................................................ 42
Figure 5-11 AA-100/AA-100E and AA-120/AA-120E Terminals and Connectors ........................................... 43
Figure 5-12 AA-100/AA-100E and AA-120/AA-120E Audio Amplifier Status LEDs ....................................... 44
Section Six: Voice Alarm Peripherals .................................................................................. 46
Section 6.1 The RPJ-1 Remote Paging Jack ................................................................................................. 47
Appendix A: Voice Message Options .................................................................................. 48
Section A.1 VROM/VRAM Installation ........................................................................................................... 48
Appendix B: ACT-1 Audio Coupling Transformer ................................................................. 49
4 Voice Alarm Multiplex 15889:F2 10/01/01
Set ON for 4-Wire audio loop supervision.
Configuration DIP Switches
Address Switch
The AMG-1's configuration DIP switches are defined at right. Address Switch
VRAM Enable A (VRAM "A" installed)
VRAM Enable B (VRAM "B" installed)
Group Function Selection switch
Group Function Selection switch
Group Function Selection switch
*Italics denote setting the address for an AMG-1 with an AMG-X4 EPROM installed.
Factory Messages *
With VROM-(n) chips installed, a factory-programmed message can be selected. For example, VROM-101
provides the following message in a male voice.
"MAY I HAVE YOUR ATTENTION PLEASE! MAY I HAVE YOUR ATTENTION PLEASE! THERE HAS BEEN A
FIRE REPORTED ON YOUR FLOOR. THERE HAS BEEN A FIRE REPORTED ON YOUR FLOOR. PLEASE
PROCEED TO THE STAIRWAYS AND EXIT THE BUILDING. DO NOT USE THE ELEVATORS."
For AMG-1s set in the address range 25-28 (AMG-X4 EPROM required):
AEM-16AT
(the first expander of the ACM-16AT at address 1 (see above)
Off Off On P01 P05 P09 P13 3 Fast Whoops, Pause, VROM A
Off Off On P02 P06 P10 P14 3 Hi/Low Tones, Pause, VROM B
Off Off On P03 P07 P11 P15 3 Yeows, Pause, VRAM A
Off Off On P04 P08 P12 P16 3 Slow Whoops, Pause, VRAM B
Off On Off P01 P05 P09 P13 3 Fast Whoops, Pause, VROM A, VROM B
Off On Off P02 P06 P10 P14 3 Hi/Low Tones, Pause, VRAM A
Off On Off P03 P07 P11 P15 3 Yeows, Pause, VRAM B
Off On Off P04 P08 P12 P16 Wail
On Off Off P01 P05 P09 P13 3 Slow Whoops, Pause, VRAM A
On Off Off P02 P06 P10 P14 3 Hi/Low Tones, Pause, VRAM B
On Off Off P03 P07 P11 P15 Yelp
On Off Off P04 P08 P12 P16 Wail
On On Off P01 P05 P09 P13 California Uniform Fire Code (10s Yelp, Pause)
On On Off P02 P06 P10 P14 California Uniform Fire Code (10s Fast Whoops, Pause)
On On Off P03 P07 P11 P15 3 Hi/Low Tones, Pause, VROM A, Pause
On On Off P04 P08 P12 P16 3 Slow Whoops, Pause, VRAM A, Pause
Off Off On P17 P21 P25 P29 3 Fast Whoops, Pause, VROM A
Off Off On P18 P22 P26 P30 3 Hi/Low Tones, Pause, VROM B
Off Off On P19 P23 P27 P31 3 Yeows, Pause, VRAM A
Off Off On P20 P24 P28 P32 3 Slow Whoops, Pause, VRAM B
Off On Off P17 P21 P25 P29 3 Fast Whoops, Pause, VROM A, VROM B
Off On Off P18 P22 P26 P30 3 Hi/Low Tones, Pause, VRAM A
Off On Off P19 P23 P27 P31 3 Yeows, Pause, VRAM B
Off On Off P20 P24 P28 P32 Wail
On Off Off P17 P21 P25 P29 3 Slow Whoops, Pause, VRAM A
On Off Off P18 P22 P26 P30 3 Hi/Low Tones, Pause, VRAM B
On Off Off P19 P23 P27 P31 Yelp
On Off Off P20 P24 P28 P32 Wail
On On Off P17 P21 P25 P29 California Uniform Fire Code (10s Yelp, Pause)
On On Off P18 P22 P26 P30 California Uniform Fire Code (10s Fast Whoops, Pause)
On On Off P19 P23 P27 P31 3 Hi/Low Tones, Pause, VROM A, Pause
On On Off P20 P24 P28 P32 3 Slow Whoops, Pause, VRAM A, Pause
11
regardless of the number of amplifiers connected to the secondary side of each ACT-1
51
Notes
12
52 Voice Alarm Multiplex 15889:F2 10/01/01
Limited Warranty
This writing constitutes the only warranty made by NOTIFIER® with respect to its
products. NOTIFIER® does not represent that its products will prevent any loss by fire
or otherwise, or that its products will in all cases provide the protection for which they
are installed or intended. Buyer acknowledges that NOTIFIER® is not an insurer and
assumes no risk for loss or damages or the cost of any inconvenience, transportation,
damage, misuse, abuse, accident or similar incident.
This warranty replaces all previous warranties and is the only warranty made by
NOTIFIER®. No increase or alteration, written or verbal, of the obligation of this warranty
is authorized.